ML18052A892

From kanterella
Jump to navigation Jump to search
Application for Amend to License DPR-20,revising Tech Spec Table 3.22.1 Re Fire Detection Instrumentation,Per 851121 & 22 Submittals Concerning Proposed Changes to Control Room Habitability.Rev Includes Removal of Water Flow Switches
ML18052A892
Person / Time
Site: Palisades 
Issue date: 03/09/1987
From: Berry K
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML18052A893 List:
References
NUDOCS 8703120440
Download: ML18052A892 (3)


Text

consumers Power Pll'WERINli llllCHlliAN'S PRDliRESS General Offices:

1945 West Parnell Road, Jackson, Ml 49201 * (517) 788-1636 March 9, 1987 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

TECHNICAL SPECIFICATIONS CHANGE REQUEST REVISION -

FIRE DETECTION INSTRUMENTS Kenneth W Berry Director Nuclear Licensing Attached is a revision to a previously proposed Technical Specifications Change Request.. Consumers Power submittal of November 21, 1985, corrected November 22, 1985, provided revised proposed changes which superceded a portion of our November 19, 1.984, proposed change on Control Room Habitability and the entire proposed change of February 5, 1985, Inspection and Testing of Fire Protection Devices and Assemblies.

This submittal revises Table 3.22.1 Fire Detection Instrumentation from the November 21 and 22, 1985, submittals.

The revisions include removal of several water flow switches from the table and adds ultraviolet detectors in the intake structure.

A check in the amount of $150 was enclosed with our February 5, 1985, Technical Specifications Change Request, thus, no check is attached.

~1~~-t!J~

?J Kenneth W Berry Director, Nuclear Licensing CC Administrator, Region III, NRC NRC Resident Inspector - Palisades Attachment

( 8703120440 870309 I PDR ADOCK 05000255 P

PDR OCOZ87-0209A-NL04/NL02

"\\

I J

--1

Request for CONSUMERS POWER COMPANY Docket 50-255 Change to the Technical Specifications License DPR-20 For the reasons hereinafter set forth, it is requested that the Technical Specifications contained in the Provisional Operating License DPR-20, Docket 50-255, issued to Consumers Power Company on October 16, 1972, for the Palisades Plant be changed as described in Section I below:

I.

CHANGE Replace Table 3.22.1, Fire Detection Instrumentation with the revised table*provided as an attachment to this letter.

II.

DISCUSSION Consumers Power Company submitted proposed Technical Specifications related to fire protection requirements in letters dated. November 21 and 22, 1985.

Included within the proposal was a revised Table 3.22.1 for fire detection instrumentation.

Since that letter, certain changes have been identified as necessary for Table 3.22.1 *. These changes are provided herein and supersede any prior vers~ons of Table 3.22.1.

This change eliminates all but two water flow switches from Table 3.22.1.

The Palisades Fire Hazard Analysis takes credit for water flow switches located in the diesel generate~ rooms only.

Therefore, since no safety related function is provided by the other switches, a Technical Specification for them is not considered to be necessary or appropriate.

With the exception of water flow switches, this proposal includes all other additions provided in the November 22, 1985 letter.

These items were added to reflect physical additions to the *Auxiliary Building which were completed to facilitate the Control Room Emergency Air Cleanup System.

In addition to the earlier changes, new fire detection instruments have been added to Table 3.22.1 for the intake structure.

These instruments were added as a result of concerns identified during the NRC Fire Protection Inspection Analysis of No Significant Hazards Consideration This change revision removes all water flow switches from Technical Specification fire detec,tion instrumentation except those mentioned in

  • the Fire Hazards Analysis.

In addition, this revision adds the ultraviolet detection system to the Technical Specifications.

This system was installed in the intake structure as a result of issues identified in the NRC Appendix R inspection.

. TSP0287-0209A-NL04/NL02

This change does not result in an increase in the probability or consequences of an analyzed accident.

The Fire Hazards Analysis does not require the use of the deleted fire flow switches.

The addition of the ultraviolet detection results in improved detection and, therefore, enhances safety.

This change does not create the possibility of a different accident or malfunction.

The flow switches were not used in the Fire Haz~rds Analysis.

Therefore, flow detection by the switches should not affect safety.

The addition of the ultraviolet detection system results in additional controls and, therefore, only improves plant safety.

2 The margin of safety defined in Technical Specifications is not reduced by this change.

Since the water flow switches are not utilized in the Fire Hazards analysis, their availability is not considered an enhance-"

ment of the margin of safety.

The ultra violet detection system is an additional method of fire detection and improves the margin of safety.

III.

CONCLUSION The Palisades Plant Review Committee has reviewed this Technical Specification Change Request and has determined that this change. does not involve an unreviewed safety question and therefore involves no significant hazards consideration.

This change has also been reviewed under the cognizance of the Nuclear Safety Board.

A copy of this Technical Specification Change Request has been sent to the State of Michigan official designated to receive such Amendments to the Operating License.

CONSUMERS POWER COMPANY By~~.nt'-

Nuclear Operations Sworn and subscribed to before me this 9th day of March 1987.

TSP0287-0209A-NL04/NL02