ATTACHMENT 2 CONSUMERS POWER COMPANY PALISADES PLANT DOCKET 50-255 TECHNICAL SPECIFICATIONS CHANGE REQUEST LICENSE DPR-20 PRIMARY COOLANT PUMP FLYWHEEL INSPECTIONS Proposed Pages 2 Pages

(~ -9601250076 960118 ________ ______

PDR ADOCK 05000255 P

PDR

4.3 SYSTEMS SURVEILLANCE APPLICABILITY Applies to preoperational and inservice structural surveillance of the reactor vessel and othet Class 1, Class 2 and Class 3 system components.

OBJECTIVE To insure t'he integrity,of the C,lass 1, Class 2 and Class 3 piping systems andcomponents.

SPECIFICATIONS a,b,c,d - Deleted

e., The lnservice Inspection program shall be reevaluated as required by 10 CFR 50, Section 50.55a(g)(5) to consider incorporation of new inspection techniques that have been proven practical, and the conclusions of the evaluation shall be used as appropriate to update the inspection.program.
f.

Surveillance of the regenerative heat exchanger shall be performed as indicated tn Table 4.3.2.

g.

A survefllance program to.monitor radiation induced changes in the mechanical and impact properties of the.reactor vessel materials sha 11 be ma-i nta i ned as des.cri bed in Section. 4. 5. 3 of the FSAR.

4-16 Amendment N'o...Y., i-3-G, -142-

TABLE 4.3.2 Miscellaneous Surveillance Items Equipment Regenerative Heat Exchanger

a.

Primary Side Shell to Tube Sheet Welds

b.

Primary Head Method Volumetric Volumetric 4-23 Frequency 5-Year Maximum lnterval(l00%}

5-Year Maximum Interv.al ( 100%}

Amendment No. -34, ::/-9, -142-

ATTACHMENT 3 CONSUMERS POWER COMPANY PALISADES PLANT DOCKET 50-255 TECHNICAL SPECIFICATIONS CHANGE REQUEST LICENSE DPR-20 PRIMARY COOLANT PUMP FLYWHEEL INSPECTIONS Current Pages Marked to Show Changes 2 Pages

4.3 SYSTEMS SURVEILLANCE APPLICABILITY Applies to preoperational and tnservice structural surveillance of the reactor vessel and other Class 1, Class 2 and Class 3 system components.

OBJECTIVE To insure the integrity of the Class 1, Class 2 and Class 3 piping syst~ms and components.

SPECIFICATIONS a,b,c,d - Deleted

.e.

The lnservice Inspection program shall be reevaluated as required by 10 CFR 50, Section 50.55a(g)(5) to consider incorporation of new inspection techniques that have been proven practical, and the conclusions of the evaluation shall be used as appropriate to update the inspection program.

f.

Surveillance of the regenerative heat exchanger aAe primary eeelaAt pttmp fly~lheels shall be performed as indicated in Table 4.3.2.

g.

A surveillance program to monitor radiation induced changes in the mechanical and impact properties of the reactor vessel materials shall be maintained as described in Section 4.5.3 of the FSAR.

4-16 Amendment No..§3.,.J-3.G, -142-

TABLE 4.3.2 Miscellaneous Surveillance Items Equipment

1.

Regenerative Heat Exchanger

2.
a.

Primary Side Shell to Tube Sheet Welds

b.

Primary Head Primary GeelaAt Pump Method Volumetric Volumetric

'*'el umctri e 4-23 Frequency 5-Year Maximum Interval(100%)

5-Year Maximum Interval (100%)

100% Upper Flywheel Each RefueliAg Amendment No. a-4, 19, 42-

ATTACHMENT 4 CONSUMERS POWER COMPANY PALISADES PLANT DOCKET 50-255 LICENSE DPR-20 "RELAXATION OF PRIMARY COOLANT PUMP FLYWHEEL INSPECTION REQUIREMENTS"