Technical Specification (TS) 5.5.10.c, "Ventilation Filter Testing Program." A sample of the charcoal was sent to NUCON for methyl iodide penetration testing. On May 30, 2006, at 0923 the Control Room Emergency Filtration System ( CREFS) was declared inoperable based on failure of the charcoal to meet the methyl iodide penetration acceptance criterion of Filtration System ( CREFS)," Condition A, " CREFS Inoperable," with a Required Action of "Restore CREFS to OPERABLE status.
The F-16 charcoal filter trays were replaced and retested. A second failure occurred due to penetration and system bypass test exceeding allowable limits. The filters were replaced again and the degraded Sealant (RTV) repaired.
Subsequent testing on June 3, 2006, demonstrated compliance with TS 5.5.10.b, TS 5.5.10.c, and TS 5.5.10.d. Operations exited the CREFS TSAC June 4, 2006, at 2030.
CREFS is a single train system. Based on the guidance in NUREG-1022 fora single train system that performs a safety function, this condition was determined to be reportable per 10 CFR 50.73(a)(2)(v), "Event or Condition That Could Have Prevented Fulfillment of a Safety Function." Technical Specifications allow for this system to be inoperable for a period of seven days. |
FACILITY NAME (1) DOCKET NUMBER (2) LER NUMBER (6 PAGE (3)
Event Description:
On May 2, 2006, testing was conducted on the F-16, Control Room Charcoal/HEPA/Roughing Filter [FLT], in accordance with Technical Specification (TS) 5.5.10.c, "Ventilation Filter Testing Program." A sample of charcoal was sent to NUCON for methyl iodide penetration testing. On May 30, 2006, at 0923 the Control Room Emergency Filtration System (CREFS) [VI] was declared inoperable based on failure of the charcoal to meet the methyl iodide penetration acceptance criterion of "Control Room Emergency Filtration System (CREFS)," Condition A, "CREFS Inoperable" with a Required Action of "Restore CREFS to OPERABLE status" in a completion time of seven (7) days. Both units were in Mode 1 at 100% rated thermal power.
Operations replaced the F-16 charcoal filter trays on May 30, 2006. On May 31, 2006, freon leak testing of the F-16 control room charcoal adsorber [ADV] failed based on 98.6% filtration efficiency results. The acceptance criterion is z 99.00%. An inspection of the F-16 filter frame, housing and trays was performed.
This inspection identified degraded Sealant (RTV) on the north and south vertical seams of the downstream side of the charcoal adsorber (CAP 01033448). This degradation allowed upstream air to bypass the could lead to bypass air flow.
The charcoal filter trays were replaced again on June 3, 2006 (Work Order 286726). The trays were verified to be full prior to installation. The charcoal also passed a laboratory methyl iodide penetration test prior to shipment to Point Beach Nuclear Plant (PBNP).
The degraded RTV condition was resolved by applying new RN on the downstream side of the north and south vertical seams. In addition, new RN was applied to the upstream side of the north and south vertical seams (Work Order 286788). GE Silicone RTV 102 was used in accordance with the component instruction manual.
Testing was completed on June 3, 2006, that demonstrated compliance with TS 5.5.10.b, TS 5.5.10.c, and TS 5.5.10.d. Operations exited the CREFS TSAC June 4, 2006, at 2030.
During replacement of filters and repair of RN on the filter frame/housing, the tightness of the control room envelope (CRE) was not affected. The outside/pressurization airflow rate in control room ventilation system Mode 4 remained above the minimum of 4455 cfm. Therefore, the CRE to all adjacent spaces Differential Pressure (DP) measurements remained greater than 1/8" with significant margin to spare.
Component and system Description:
The CREFS provides a protected environment from which operators can control the unit following an uncontrolled release of radioactivity.
FACILITY NAME (1) DOCKET NUMBER (2) LER NUMBER (6 PAGE (3) POINT BEACH NUCLEAR PLANT UNIT 1 05000266 l REVISION The CREFS consists of one emergency makeup air filtration unit, two emergency makeup fans, two recirculation fans, and the required ducts and dampers necessary to establish the required flow paths and isolation boundaries. The CREFS is an emergency system, parts of which operate during normal operations.
The air entering the control room is continuously monitored by a noble gas radiation monitor and the control room itself is continuously monitored by an area radiation monitor. One detector output above its setpoint will actuate the emergency makeup mode of operation for the CREFS.
The limiting design bases accident for the control room dose analysis is the large break Loss of Coolant Accident (LOCA).
The CREFS will pressurize the control and computer rooms to at least 0.125 inches water gauge in the emergency makeup mode of operation. The CREFS role in maintaining control room habitability is discussed in the Final Safety Analysis Report (FSAR), Section 9.8.
The CREFS provides airborne radiological protection for control room personnel, as demonstrated by the limiting control room dose analysis for the design basis LOCA. Control room dose analysis assumptions are presented in the FSAR, Section 14.3.5.
Event Analysis and Safety Significance:
The F-16 filter is part of the control room ventilation system that is used for emergency operation and is used to maintain control room personnel radiation dose within regulatory requirements.
Prior to the test, there were no known significant conditions adverse to quality present. There were no conditions where nuclear safety or personnel safety were significantly threatened or had been compromised.
The condition was identified as part of routine testing that is performed to ensure system operation meets technical specification requirements.
This event was of low safety significance because this event would not have prevented CREFS from performing its safety function since the last successful completion of the Technical Specification surveillance. The methyl iodide penetration test result of the charcoal sample, 98.905% filter efficiency was well above the safety analysis (FSAR Section 14.3.5) stated 95% required filter efficiency for organic (methyl) and elemental material. In addition, a qualitative assessment of the impact of the extra out of service time was performed and concluded that there was no direct effect on Core Damage Assessment due to the CREFS being out of service.
FACILITY NAME (1) _ DOCKET NUMBER (2) _ LER NUMBER (6) _ PAGE (3)
Cause:
The exact cause for failure of the methyl iodide penetration test of the sample of the charcoal adsorber has not yet been determined. However, the subsequent test failure due to excessive bypass flow was attributed to a combination of:
- aging of the RN used to seal the seams between the filter frame and the filter housing, and
- possible bypass airflow due to an underfill condition in 7 of the 14 filter trays.
Corrective Action:
The F-16 charcoal filter trays were replaced with new trays that were verified to be properly filled before installation. The degraded RN condition was repaired by applying new RN over the degraded RN.
Proper gasket crush was verified when installing the new filter trays.
Previous Similar Events:
None.
|
---|
|
|
| | Reporting criterion |
---|
05000305/LER-2006-010 | | | 05000456/LER-2006-001 | Unit 1 Reactor Coolant System Pressure Boundary Leakage Due To Inter-Granular Stress Corrosion Cracking of a Pressurizer Heater Sleeve | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded | 05000454/LER-2006-001 | Technical Specification Required Action Completion Time Exceeded for Inoperable Containment Isolation Valves Due to Untimely Operability Determination | | 05000423/LER-2006-001 | Loss Of Safety Function Of The Control Room Emergency Ventilation System | 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | 05000369/LER-2006-001 | Ice Condenser and Floor Cooling System Containment Isolation Valve inoperable longer than allowed by Technical Specification 3.6.3. | | 05000353/LER-2006-001 | HPCI Ramp Generator Signal Converter Failure | 10 CFR 50.73(a)(2)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident 10 CFR 50.73(a)(2)(v), Loss of Safety Function | 05000352/LER-2006-001 | Loss Of One Offsite Circuit Due To Invalid Actuation Of Fire Suppression System | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000336/LER-2006-001 | | 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor | 05000316/LER-2006-001 | Failure to Comply with Technical Specification 3.6.2, Containment Air Locks | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000315/LER-2006-001 | Plant Shutdown Required by Technical Specification Action 3.6.5.B.1 | | 05000293/LER-2006-001 | | 10 CFR 50.73(a)(2)(iv), System Actuation | 05000289/LER-2006-001 | | | 05000287/LER-2006-001 | Actuation of Emergency Generator due to Spurious Transformer Lockout | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000251/LER-2006-001 | Turkey Point Unit 4 05000251 1 OF 6 | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000247/LER-2006-001 | Manual Reactor Trip Due to Multiple Dropped Control Rods Caused by Loss of Control Rod Power Due to Personnel Error | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000440/LER-2006-001 | Incorrect Wiring in the Remote Shutdown Panel Results in a Fire Protection Program Violation | | 05000413/LER-2006-001 | | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000368/LER-2006-001 | Completion of a Plant Shutdown Required by Technical Specifications Due to Loss of Motive Power to Certain Containment Isolation Valves as a Result of a Phase to Ground Short Circuit in a Motor Control Cubicle | 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown | 05000306/LER-2006-001 | | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown | 05000298/LER-2006-001 | Cooper Nuclear Station 05000298 1 of 4 | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000286/LER-2006-001 | I | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000282/LER-2006-001 | | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(v), Loss of Safety Function | 05000266/LER-2006-001 | | 10 CFR 50.73(a)(2)(v), Loss of Safety Function | 05000261/LER-2006-001 | Manual Reactor Trip Due to Failure of a Turbine Governor Valve Electro-Hydraulic Control Card | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000255/LER-2006-001 | | 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition | 05000461/LER-2006-002 | Turbine Bypass Function Lost Due to Circuit Card Maintenance Frequency | | 05000458/LER-2006-002 | Loss of Safety Function of High Pressure Core Spray Due to Manual Deactivation | | 05000456/LER-2006-002 | Units 1 and 2 Entry into Limiting Condition for Operation 3.0.3 due to Main Control Room Ventilation Envelope Low Pressure | | 05000443/LER-2006-002 | Noncompliance with the Requirements of Technical Specification 6.8.1.2.a | | 05000387/LER-2006-002 | DMissed Technical Specification surveillance requirement | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000362/LER-2006-002 | Unit 3 Shutdown to Inspect Safety Injection Tank Spiral Wound Gaskets | | 05000336/LER-2006-002 | Manual Reactor Trip Due To Trip Of Both Feed Pumps Following A Loss Of Instrument Air | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000316/LER-2006-002 | | 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000315/LER-2006-002 | Failure to Comply with Technical Specification Requirement 3.6.13, Divider Barrier Integrity | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000293/LER-2006-002 | | | 05000289/LER-2006-002 | | | 05000251/LER-2006-002 | Intermediate Range High Flux Trip Setpoint Exceeded Technical Specification Allowable Value | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000440/LER-2006-002 | Scaffold Built in the Containment Pool Swell Region | 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition | 05000413/LER-2006-002 | Safe Shutdown Potentially Challenged by an External Flooding Event and Inadequate Design and Configuration Control | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000388/LER-2006-002 | Missed Technical Specification LCO 3.8.1 Entry for Unit 2 During Unit 1 ESS Bus Testing | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000348/LER-2006-002 | Main Steam Isolation Valve Failure to Close | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000305/LER-2006-002 | | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000301/LER-2006-002 | | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000286/LER-2006-002 | 450 Broadway, GSB P.O. Box 249 Buchanan, N.Y. 10511-0249Entergy Tel (914) 734-6700 Fred Dacimo Site Vice President Administration September 13, 2006 Indian Point Unit No. 3 Docket No. 50-286 N L-06-084 Document Control Desk U.S. Nuclear Regulatory Commission Mail Stop O-P1-17 Washington, DC 20555-0001 Subject:L Licensee Event Report # 2006-002-00, "Manual Reactor Trip as a Result of Arcing Under the Main Generator Between Scaffolding and Phase A&B of the Isophase Bus Housing" Dear Sir: The attached Licensee Event Report (LER) 2006-002-00 is the follow-up written report submitted in accordance with 10 CFR 50.73. This event is of the type defined in 10 CFR 50.73(a)(2)(iv)(A) for an event recorded in the Entergy corrective action process as Condition Report CR-IP3-2006-02255. There are no commitments contained in this letter. Should you or your staff have any questions regarding this matter, please contact Mr. Patric W. Conroy, Manager, Licensing, Indian Point Energy Center at (914) 734-6668. Fred R. Dacimo Site Vice President Indian Point Energy Center Docket No. 50-286 NL-06-084 Page 2 of 2 Attachment: LER-2006-002-00 CC: Mr. Samuel J. Collins Regional Administrator — Region I U.S. Nuclear Regulatory Commission U.S. Nuclear Regulatory Commission Resident Inspector's Office Resident Inspector Indian Point Unit 3 Mr. Paul Eddy State of New York Public Service Commission INPO Record Center NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB NO. 3150-0104 EXPIRES: 06/30/2007
(6-2004)
. Estimated burden per response to comply with this mandatory collection request: 50 hours.DReported lessons learned are incorporated into the licensing process and fed back to industry. Send comments regarding burden estimate to the Records and FOIA/Privacy Service Branch (T-5 F52), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by internetLICENSEE EVENT REPORT (LER) e-mail to infocollects@nrc.gov, and to the Desk Officer, Office of Information and Regulatory Affairs, NEOB-10202, (3150-0104), Office of Management and Budget, Washington, DC 20503. If a means used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection. ■ 1. FACILITY NAME 2. DOCKET NUMBER I 3. PAGE
INDIAN POINT 3 05000-286 1 OF 6
4.TITLE: Manual Reactor Trip as a Result of Arcing Under the Main Generator Between
Scaffolding and Phase A&B of the Iso-phase Bus Housing | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000282/LER-2006-002 | | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000269/LER-2006-002 | High Energy Line Breaks Outside Licensing Basis May Result in Loss of Safety Function | | 05000263/LER-2006-002 | | | 05000255/LER-2006-002 | | 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications | 05000254/LER-2006-002 | Quad Cities Nuclear Power Station Unit 1 05000254 1 of 3 | 10 CFR 50.73(a)(2)(iv)(A), System Actuation | 05000483/LER-2006-003 | Unexpected Inoperability of the Emergency Exhaust System due to Inoperable Pressure Boundary | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
|