05000275/FIN-2010005-02
From kanterella
Revision as of 16:49, 8 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Inadequate Transient Combustibles Procedure |
Description | The inspectors identified a noncited violation of Diablo Canyon Unit 2 Facility Operating License Condition 2.C.(5), Fire Protection, after Pacific Gas and Electric failed to ensure procedures for controlling flammable and combustible materials adequately incorporated requirements of the fire hazard analysis. On October 18, 2010, the inspectors identified that transient combustible materials staged in the Unit 1 12 kilovolt switchgear room did not have an approved transient combustibles permit. The licensee stated that the combustibles permit procedure did not require a permit for the room while Unit 1 was shutdown. However, the plant fire hazards design basis described safe shutdown equipment in the room that would be needed to support a safe shutdown of the operating unit, specifically the Unit 2 startup bus located in the room. The inspectors determined that the licensees transient combustibles permit procedure was inadequate because the procedure did not require a permit for the Unit1 12 kilovolt switchgear room when Unit 2 was operating. The licensee entered the issue into the corrective action program as Notification 50366302 and performed an evaluation of the transient combustibles stored in the area.
The inspectors concluded that this finding was more than minor because it affected the Mitigating Systems Cornerstone external factors attribute objective to limit the likelihood of those events that upset plant stability and challenge critical safety functions. The inspectors determined that the finding was within the fire prevention and administrative controls category and represented a low degradation level due to the minimal impact on the effectiveness and reliability of the affected systems. The inspectors concluded that the finding was of very low safety significance (Green) based on a qualitative screening, the low degradation rating, and only equipment needed to reach and maintain cold shutdown conditions was affected. This finding had a crosscutting aspect in the area of human performance associated with the resources component because the licensee failed to ensure that the design documentation adequately identified the Unit 2 startup bus as equipment required for safe shutdown for Unit 2 H.2(c). |
Site: | Diablo Canyon |
---|---|
Report | IR 05000275/2010005 Section 1R05 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | E Wong P Goldberg L Ricketson M Brown M Peck C Graves R Kopriva D Allen C Osterholtz I Anchondo D Reinert C Alldredge B Latta |
CCA | H.7, Documentation |
INPO aspect | WP.3 |
' | |
Finding - Diablo Canyon - IR 05000275/2010005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Diablo Canyon) @ 2010Q4
Self-Identified List (Diablo Canyon)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||