Finding | |
---|---|
Title | Failure to Maintain a Fire Barrier |
Description | The inspectors identified a noncited violation of Diablo Canyon Facility Operating License Condition 2.C (5), Fire Protection, after Pacific Gas and Electric failed to maintain the integrity of Door 155 in the rated condition. On December 9, 2010, the inspectors identified that the fire door was inoperable. Equipment Control Guideline 18.7, Fire Rated Assemblies, required the licensee to maintain Door 155 in a configuration that would provide at least a 112-hour rated fire barrier. The inspectors previously identified that Door 155 was degraded as a fire barrier in 2009. The licensee entered the violation into the corrective action program as Notification 50367381 and took immediate corrective actions to restore the fire barrier to the rated condition and to implement weekly plant fire door walkdowns
The inspectors concluded that the finding was more than minor because the degraded fire barrier affected the Mitigating Systems Cornerstone external factors attribute and objective to prevent undesirable consequences due to fire. The inspectors determined that the finding was within the fire confinement category and that the fire barrier was moderately degraded. The inspectors concluded that the finding was of very low safety significance (Green) because there was a non-degraded automatic full area water-based suppression system in the exposed fire area. This finding had a crosscutting aspect in the area of problem identification and resolution associated with the corrective action program component because the licensee did not take effective corrective actions to following the previous occurrence of the violation P.1(d). |
Site: | Diablo Canyon |
---|---|
Report | IR 05000275/2010005 Section 1R05 |
Date counted | Dec 31, 2010 (2010Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | E Wong P Goldberg L Ricketson M Brown M Peck C Graves R Kopriva D Allen C Osterholtz I Anchondo D Reinert C Alldredge B Latta |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |