UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 October 17, 2012 Mr. Joseph H. Plona Senior Vice President and Chief Nuclear Officer Detroit Edison Company Fermi 2 - 210 NOC 6400 North Dixie Highway Newport, MI 48166

SUBJECT:

FERMI 2 - CORRECTION LETTER FOR AMENDMENT RE: TSTF-501, REVISION 1, "RELOCATE STORED FUEL OIL AND LUBE VOLUME VALUES TO LICENSEE CONTROL" (TAC NO. ME6861)

Dear Mr. Plona:

On February 24,2011, the U.S. Nuclear Regulatory Commission (NRC) issued License Amendment No. 188 to Facility Operating License No. NPF-43 for the Fermi 2 facility (Agencywide Documents Access and Management System (ADAMS) Accession No. ML113500433). After issuance of the license amendment, Detroit Edison Company (the licensee) identified an administrative error on page 3.8-4 of the Technical Specifications (TSs).

Specifically, the voltage values in Surveillance Requirements (SRs) 3.8.1.7.a and 3.8.1.7.b were incorrectly shown as 3740 instead of 3950.

In the licensee's August 12, 2011, application (ADAMS Accession No. ML112270114) associated with License Amendment No. 188, the voltage value in SRs 3.8.1.7.a and 3.8.1.7. b was correctly identified as 3950. Prior to issuance of the amendment, the licensee provided a copy of TS page 3.8-4 to the NRC staff for incorporating into the approved license amendment, and this copy contained the erroneous voltage value.

License Amendment No. 188 only revised SR 3.8.1.4. Therefore, the voltage values specified in SRs 3.8.1.7.a and 3.8.1.7.b should reflect the last revision of TS page 3.8-4. Page 3.8-4 was last revised during issuance of License Amendment No. 183 (ADAMS Accession No. ML102770382), and indicated a voltage value of 3950 for SR 3.8.1.7.a and SR 3.8.1.7.b.

J. Plona -2 Please replace existing TS page 3.8-4 with the enclosed corrected replacement page. If you have any questions or concerns regarding this matter, please contact me at (301) 415-8371 or Mahesh.chawla@nrc.gov.

';;r Mahesh L. Chawla, Project Manager Plant Licensing Branch 111-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-341

Enclosure:

TS Page 3.8-4 cc w/encl: Distribution via ListServ

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEI LLANCE FREQUENCY SR 3.8.1.4 Veri fy each day tank contai ns ~ one hour 31 days supply of fuel oil.

SR 3.8.1. 5 Check for and remove accumulated water from 31 days each day tank.

SR 3.8.1.6 Verify each fuel oil transfer system 31 days operates to automatically transfer fuel oil from storage tanks to the day tanks.

SR 3.8.1.7 -. -..... --. --. -... -NOTE - ........ -. - -----

All EDG starts may be preceded by an eng-j ne prelube period and followed by a warmup period prior to loading.

Verify each EDG starts from standby 184 days condition and achieves:

a. In S 10 seconds. voltage ~ 3950 V and frequency ~ 58.8 Hz; and
b. Steady state voltage ~ 3950 V and s 4580 V and frequency ~ 58.8 Hz and s 61.2 Hz.

SR 3.8.1.8 Verify each EDG rejects a load greater than 18 months or equal to its associated single largest post-accident load. and following load rejection. the frequency is S 66.75 Hz.

(continued)

FERMI . UNIT 2 3.8-4 Amendment No. 134.178.183.188

J. Plona - 2 Please replace existing TS page 3.8-4 with the enclosed corrected replacement page. If you have any questions or concerns regarding this matter, please contact me at (301) 415-8371 or Mahesh.chawla@nrc.gov.

Sincerely, IRAJ Terry Beltz for Mahesh L. Chawla, Project Manager Plant Licensing Branch 111-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-341

Enclosure:

TS Page 3.8-4 cc w/encl: Distribution via ListServ DISTRIBUTION:

PUBLIC LPL3-1 R/F RidsAcrsAcnw_MaiICTR Resource RJones, Rill RidsNrrDssStsb Resource RidsNrrDorlDpr Resource MMorris, Rill RidsNrrDorlLpl3-1 Resource RidsNrrPMFermi2 Resource GWaig, NRR RidsNrrLABTully Resource RidsNrrDeEptb Resource RidsOgcRp Resource RidsRgn3MailCenter Resource RidsNrrDssSbpb Resource JCameron, Rill MSingletary, NRR RWolfgang, NRR Package Accession Num ber: ML12276A236 OFFICE NRR/LPL3-1/PM NRR/LPL3-1/LA NRR/LPL3-1/BC(A) NRR/LPL3-1/PM NAME MChawla BTuily IFrankl MChawla ITBe/tz for DATE 10/16/12 10/16/12 10/17/12 10/17/12 OFFICIAL RECORD COPY