to EOP FR-H.5, Response to SG Low Level.
ML17265A549
Person / Time
Site: Ginna Constellation icon.png
Issue date: 02/12/1999
From: Sidelinger R
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17265A547 List:
References
FR-H.5, NUDOCS 9902250304
Download: ML17265A549 (6)


Text

EOP: TITLE:

REV: 5 FR-H.5 RESPONSE TO STEAM GENERATOR LOW LEVEL PAGE 1 of 5 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER RESPONSI MANAGER EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:

9902250304 9'P02i2 05000244' PDR ADOCK PDR

EOP: TITLE:

REV: 5 FR-H.5 RESPONSE TO STEAM GENERATOR LOW LEVEL PAGE 2 of 5 A. PURPOSE This procedure provides actions to respond to a S/G low level condition.

B. ENTRY CONDITIONS/SYMPTOMS

l. ENTRY CONDITIONS This procedure is entered from:
a. F-0.3, HEAT SINK Critical Safety. Function Status Tree, on a YELLOW condition.

EOP: TITLE:

REV: 5 FR-H.5 ~ RESPONSE TO STEAM GENERATOR LOW LEVEL PAGE 3 of 5 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~ I ~ ~ ~ ~ ~ ~ 0 ~ ~ 1 0 1 0 1 ~ ~ ~ ~ ~ 1 ~ ~ 1 ~ P 0 0 1 I I ~ I ~ ~ 4 0 ~ 0 ~

CAUTION STEAM RELEASES FROM AFFECTED S/G(S) SHOULD BE MINIMIZED.

~ ~ ~ ~ ~ ~ ~ 0 1 ~ ~ 4 0 P 4 0 0 ~ ~ 0 ~ 0 ~ 4 1 1 1 ~ 0 i ~ ~ 1 1 1 ~ ~ 1 ~ I NOTE: o Throughout this procedure "affected" refers to any S/G in which narrow range level is less than 5'/ [25/i adverse CNMT].

o Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10+05 R/hr.

1 Identify Affected S/G(s):

a. Narrow range level - LESS THAN a. Return to procedure and step in 5'/i [25'/o adverse CNMT] effect.

2 Verify S/G Blowdown Isolation Place S/G blowdown valves master Valves From Affected S/G(s) switch to CLOSE.

CLOSED-IF valves can ~NO be closed

~ AOV-5738 for S/G A manually, THEN dispatch AO to

~ AOV-5737 for S/G B locally isolate blowdown.

o S/G A, close V-5701 o S/G B, close V-5702

EOP: TITLE:

REV 5 FR-H.$ RESPONSE TO STEAM GENERATOR LOW LEVEL PAGE 4 of 5 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED

~ ~ ~ ~ ~ ~ 0 ~ 0 ~ 1 ~ ~ ~ 1

  • 0 ~ ~ 0 4 1 i 4 0 ~
  • I i 0 ~ 0 ~ ~ ~ 0 0 ~ f ~

CAUTION AFW FLOW SHOULD NOT ESTABLISHED TO ANY FAULTED S/G THAT HAS BEEN ISOLATED UNLESS NEEDED FOR RCS COOLDOWN.

~ ~ ~ 0 0 0 4 ~ 1 ~ ~ I ~ 0 ~ 0 ~ 1 ~ ~ ~ ~ 1 ~ 1 ~ ~ ~ ~ ~ ~ I I ~ 1 ~ ~ ~ ~ ~ ~

3 Check If Affected Secondary Side Is S/G(s)

Intact:

IF affected S/G(s) previously identified as faulted. THEN return to procedure and step in effect.

o Pressure in affected S/G(s)

STABLE OR INCREASING IF affected S/G pressure decreasing in an uncontrolled manner or o Pressure in affected S/G(s) completely depressurized and has GREATER THAN 110 PSIG not been previously isolated, THEN go to E-2, FAULTED STEAM GENERATOR ISOLATION, Step 1.

4 Check AFW Flow To Affected IF affected S/G(s) wide range level S/G(s) GREATER THAN 50 GPM greater than 35 inches [100 inches adverse CNMT], THEN establish AFW flow as necessary to refill affected S/G(s).

IF affected S/G(s) wide range level less than 35 inches [100 inches adverse CNMT] . THEN do not establish AFW flow to affected S/G(s). Consult the plant engineering staff to evaluate refilling the affected S/G(s) as part of long-term plant recovery and go to 6.

EOP: TITLE:

REV: 5 FR-H.S ~ 'ESPONSE TO STEAM GENERATOR LOW LEVEL

\ PAGE 5 .of 5 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 5 Continue Filling Affected S/G(s) Until Narrow Range Level Greater Than 5% [25%

adverse CNMT]

.6 Return To Procedure And Step In Effect

-END-