{{#Wiki_filter:_      .        .      . _ - _ - - _ _ _  _ - . _ _ . ~ - _ _ _ _ - . . - _        __        _ _ . . - .
i NOTICE OF VIOLATION                                                !
i Toledo Edison Company                                                              Docket No. 50-346 Toledo, Ohio                                                                      License No. NPF-3 l                                                                                                                          l i
As a result of the inspection conducted on September 12-16 and October 11,                                  ;
1988, and in accordance with the "General Policy and Procedures for NRC                                    i l            Enforcement violation wasActions}"
ident fied:  10 CFR Part 2, Appendix C (1988), the following l
Technical Specification Section 3.7.10.a Action Statement requires that with                                !
oneormoreoftherequIredfirebarrierpenetrationsnon-functional,within.
one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the operability of fire detectors on at least                              ;
;              one side of the non-functional fire barrier and establish an hourly fire watch                              !
patrol.                                                                                                    !
i e
Contrary to the above requirements, it was determined that on four occasions                                (
persons performing continuous fire watch duties were found inattentive                                    i (sleeping or dozing). On three occasions fire watch personnel had either                                    !
left their areas of responsibility prior to being relieved or were relieved                                j incorrectly; or hourly fire watch patrols had missed patrolling their required                              '
.              areas. Further, on four additional occisions, due to personnel error,                                      ;
1              continuous fire watches had nct been established within one hour as required.
This is a Severity Level IV violation (Supplement I).                                                      l t
!            .With respect to this item, the inspection showed that actions had been taken                              [
i to correct the identified violation and to prevent recurrence. Consequently,                              [
no reply to this violation is required and we have no further questions                                    .
;              regarding this matter.                                                                                    ;
I l                                                                                                                        i l
Dated
                      /*/n/v                                                              ,
HubertvJ. Miller, Director ll
  ;                                                                                Division of Reactor Safety            l t
i i
f i                8910250094 881019                                                                                      l gon Aoocn 0 9 3            J' i
:                                                                                                                        I e                                                                                                                          i
                                                                                                                          )
1
[
:                                                                                                                      \}}

Latest revision as of 13:20, 30 December 2020

Notice of Violation from Insp on 880912-16 & 1011.Violation Noted:Determined That on Four Occasions,Persons Performing Continuous Fire Watch Duties Found Sleeping or Dozing & Continous Fire Watches Not Established within 1 H
ML20204J299
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 10/19/1988
From: Miller H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20204J297 List:
References
50-346-88-28, NUDOCS 8810250084
Download: ML20204J299 (1)


Text

_ . . . _ - _ - - _ _ _ _ - . _ _ . ~ - _ _ _ _ - . . - _ __ _ _ . . - .

i NOTICE OF VIOLATION  !

i Toledo Edison Company Docket No. 50-346 Toledo, Ohio License No. NPF-3 l l i

As a result of the inspection conducted on September 12-16 and October 11,  ;

1988, and in accordance with the "General Policy and Procedures for NRC i l Enforcement violation wasActions}"

ident fied: 10 CFR Part 2, Appendix C (1988), the following l

Technical Specification Section 3.7.10.a Action Statement requires that with  !

oneormoreoftherequIredfirebarrierpenetrationsnon-functional,within.

one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the operability of fire detectors on at least  ;

one side of the non-functional fire barrier and establish an hourly fire watch  !

patrol.  !

i e

Contrary to the above requirements, it was determined that on four occasions (

persons performing continuous fire watch duties were found inattentive i (sleeping or dozing). On three occasions fire watch personnel had either  !

left their areas of responsibility prior to being relieved or were relieved j incorrectly; or hourly fire watch patrols had missed patrolling their required '

. areas. Further, on four additional occisions, due to personnel error,  ;

1 continuous fire watches had nct been established within one hour as required.

This is a Severity Level IV violation (Supplement I). l t

! .With respect to this item, the inspection showed that actions had been taken [

i to correct the identified violation and to prevent recurrence. Consequently, [

no reply to this violation is required and we have no further questions .

regarding this matter.  ;