- _ _ _ _

l e

1

' NOTICE OF VIOLATION i

Docket No. 50-346 q

Toledo Edison Company e

l As a result of the inspection conducted on August 10-14 and 19-21, 1987, and in accordance with 10 CFR Part 2, Appendix C - General Statement of Policy and j

Procedure for NRC Enforcement Actions (1985), the following violation was identified:

Technical Specification 4.11.1.1.1 requires that radioactive liquid wastes be sampled and analyzed according to the sample and analysis program of Table 4.11-1.

Table 4.11-1 requires that certain named principal gamma emitters, including Cs-134, be detected at a concentration greater than 5 x 10-7 uCi/ml (Lower Limit of Detection).

Contrary to.the above, on July 22, August 4 and 9, 1987 the licensee spectroscopy system failed to identify and quantify Cs-134, present in liquid waste samples, at concentrations greater than 5'x 10-7 uCi/ml.

l This is a Severity Level IV violation (Supplement IV).

j Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this l

office within thirty days of the date of this Notice a written statement or explanation in reply, including for each violation:

(1) corrective action taken and the results achieved; (2) corrective action to be taken to avoid i

further violations; and (3) the date when full compliance will be achieved.

i Consideration may be given to extending your response time for good cause shown.

l

/

D y

SEP 11 1987 f

Dated

b. D. Shafer Ehief j

EmergencyPrdparednessand Radiological Protection Branch i

8709180264 870911 PDR ADOCK 05000346 G