| title = Rev 1 to Solid State Protection Sys Function Test-Train B.
| title = Rev 1 to Solid State Protection Sys Function Test-Train B
| author name =  
| author name =  
| author affiliation = PUBLIC SERVICE ELECTRIC & GAS CO. OF NEW JERSEY
| author affiliation = PUBLIC SERVICE ELECTRIC & GAS CO. OF NEW JERSEY
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:NOTE: PRESS HARO YOU ARE MAKING FIVE (S) COPIES                               .
{{#Wiki_filter:*.
ADMINISTRATIVE PROCEDURE 3 ON-THE-SPOT CHANGE CHANGE TYPE:
NOTE: PRESS HARO YOU ARE MAKING FIVE (S) COPIES.
1\71 lC.J PERMANENT (GREEN)
CHANGE TYPE:
D    *TEMPORARY (ORANGE)
ADMINISTRATIVE PROCEDURE 3 ON-THE-SPOT CHANGE 1\\71 PERMANENT D *TEMPORARY lC.J (GREEN)
                                                                                                        *EXPIRES:
(ORANGE)  
*EXPIRES:
ALL ON*THE*SPOT CHANGES TO BE CONSIDERED !="OR APPLICABILITY TO BOTH UNITS.
ALL ON*THE*SPOT CHANGES TO BE CONSIDERED !="OR APPLICABILITY TO BOTH UNITS.
[ZJ   UNIT I PROCECURENO. ___     \~\=>--.....\J...._-_\~B........
[ZJ UNIT I  
                                                                  *~'~*~O~L~~q--*_________      REV. NO. _ _\_ _ _ CHANGE No._\..___ _
~
  ~    UNITZ  PROCECURENO.~~c:9-.---..?n.......~-__.\~B-'_*~\-*___,OQ~-C\_,________            REV. NO._--.._ _ CHANGE NO._.;___ _\
UNITZ PROCECURENO. ___  
PROPOSED CHANGE:
\\~\\=>--.....\\J...._-_\\~B  
                                  <a.'d-,.\.L\,           res.:1-,.s,           e.~,.,1.1_,     ca.~\.\\;i 1   A~~       B.~\,\'1 B. ~'- \         J
*~'~*~O~L~~q--* ______ ___ REV. NO. __ \\ ___ CHANGE No._\\..__ __
                                                                '8. d.. \. C\ )   CC> . d-L \ u REASON FOR CHANGE:
PROCECURENO.~~c:9-.---..?n  
ACTION TAKEN FOR OTHER UNIT:
....... ~-__.\\~B-'_*~\\-*___,OQ~-C\\_,_ ______ _
                  &deg;SP.W'Q..     ~
\\
AUTHORIZATION:       ~**S ERViORIN
REV. NO._--.. __ CHANGE NO._.;__ __
:.;~ CHARGE
PROPOSED CHANGE:  
                                                                                                                            ~ DATE OR SHIFT SUPERVISOR
<a.'d-,.\\.L\\, res.:1-,.s, e.~,.,1.1_,
  -SIGNATURE ALSO VERIFIES THAT APPLICABILITY TO                   ~OTH UNITS HAS BEEN CONSIDERED.
ca.~\\.\\\\;i 1
ACCEPTABLE:                         POST CHANGE-REVIEW/APPROVAL I ~I       D                 ()l!!clratt'-
A~~
      ~         D             .19K~THEAD c:~:I'"t:J"'.3 ~ ~ .                :'           SORC \:HAIRMAN) l?tl             I                     ~r~
B. ~'- \\ J  
'8. d.. \\. C\\ )
CC>. d-L \\ u REASON FOR CHANGE:
ACTION TAKEN FOR OTHER UNIT:  
&deg;SP.W'Q..  
~
AUTHORIZATION: ~
:.;~  
**S ERViORIN CHARGE OR SHIFT SUPERVISOR  
-SIGNATURE ALSO VERIFIES THAT APPLICABILITY TO ~OTH UNITS HAS BEEN CONSIDERED.
ACCEPTABLE:
POST CHANGE-REVIEW/APPROVAL I ~I D
() l!!clratt'-
~
D  
.19K~THEAD c:~:I'"t:J"'.3 ~ ~
:' SORC \\:HAIRMAN) l?tl I  
~r~
MANAGER.* SALEM GENERATING STATION RETURN COMPLETED OR REJECTED FORM TO DEPARTMENT REQUESTING CHANGE.
MANAGER.* SALEM GENERATING STATION RETURN COMPLETED OR REJECTED FORM TO DEPARTMENT REQUESTING CHANGE.
FOLLOW*UP TO REJECTED ON-THE-SPOT CHANGE ACTION TAKEN:
FOLLOW*UP TO REJECTED ON-THE-SPOT CHANGE ACTION TAKEN:  
    ' 8303160573 830314 PDR ADOCK 05000272 S                     PDR.
' 8303160573 830314 PDR ADOCK 05000272 S
PDR.
PERFORMED BY:
PERFORMED BY:
SIGNATURE                                           DATE RETURN TO DEPARTMENT HEAD FOR ROUTING THROUGH POST CHANGE*REVIEW/APPROVAL CYCLE.
SIGNATURE RETURN TO DEPARTMENT HEAD FOR ROUTING THROUGH POST CHANGE*REVIEW/APPROVAL CYCLE.
DATE B.~\\,\\'1
~
DATE


  *\
*\\
SALEM NUCLEAR GENERATING STATION PUBLIC SERVICE ELECTRIC & qAS COMPANY ELECTRIC GENERATION DEPARTMENT PROCEDURE APPROVAL COVER SHEET   SAF~TY     RELATED PROCEDURE:
PROCEDURE:
lPD-18.1.009 - SOLID STATE PROTECTION SYSTEM REMARKS:  FUNCTIONAL TEST - TRAIN B REV. 1 - General Revision to incorporate On-The-Spot-Changes .
REMARKS:
PERF. ENGR. SORC     STA. SUPT.
REV 1
REV                                      APPROVED    REVIEWED  APPROVED 1
SALEM NUCLEAR GENERATING STATION PUBLIC SERVICE ELECTRIC & qAS COMPANY ELECTRIC GENERATION DEPARTMENT PROCEDURE APPROVAL COVER SHEET SAF~TY RELATED lPD-18.1.009 -
SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST -
TRAIN B REV. 1 - General Revision to incorporate On-The-Spot-Changes.
PERF. ENGR.
APPROVED SORC REVIEWED STA. SUPT.
APPROVED  


'x SALEM GENERATING STATION                   NUMBER -     lPD-18 .1. 009
'x SALEM GENERATING STATION NUMBER -
* PERFORMANCE DEPARTMENT (I & C)             REV. NO. _l~------
lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)
DATE       _5~/~2~4~/~8~2_______
TEST PROCEDURE REV. NO.
TEST PROCEDURE PAGE 1             50
_l~------
                                                                  --- OF TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE
_5~/~2~4~/~8~2 ______ _
PAGE 1 OF 50 TITLE 1.0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B


==1.0 Purpose==
==Purpose:==
l*.1 The purpose of this procedure is to verify the operability of Solid State Protection System Train B.
l*.1 The purpose of this procedure is to verify the operability of Solid State Protection System Train B.
1.2   To satisfy the train surveillance requirement of the technical specifications *
1.2 To satisfy the train surveillance requirement of the technical specifications
* 2.0  
* 2.0  


==References:==
==References:==
2ol Solid State Protection System Manual.
2.2 Wiring Diagrams:
203688, 2~2885, 224305
: I
\\


2ol  Solid State Protection System Manual.
*' x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
2.2  Wiring Diagrams:    203688, 2~2885,  224305
TEST PROCEDURE NUMBER -
                                              ';
lPD-18.1. 009 REV.NO.
:I
_1_* ------------~
                                              \
DATE 5/24/82 PAGE 2 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  
 
*' x SALEM GENERATING STATION                   NUMBER -    lPD-18 .1. 009
**    PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE REV.NO.
DATE
_1_*------------~
5/24/82 PAGE 2
                                                                  --- OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B


==3.0 Precautions==
==3.0 Precautions==
3.1   Test conditions must be applied to only Train B.       A reactor trip will occur if both trains have a general warning condition. Therefore, it is extremely important that the doors to only one train at a time are open, to preclude the introduction of test conditions into
3.1 Test conditions must be applied to only Train B.
  **          3.2 both trainsc Test conditions may be applied to one train using its*
A reactor trip will occur if both trains have a general warning condition.
                  . built-in testers, while the opposite train is used to ma~ntain the plant protection and provide data to       the demultiplexers. If in the process of testing, mal-functions are detected, they can be isolated by care-fully following the procedures in Section 6 of the Solid State Protection Manual.
Therefore, it is extremely important that the doors to only one train at a time are open, 3.2 to preclude the introduction of test conditions into both trainsc Test conditions may be applied to one train using its*  
3.3   This procedure must be completed in the sequence given to insure successful completion *
. built-in testers, while the opposite train is used to ma~ntain the plant protection and provide data to the demultiplexers.
If in the process of testing, mal-functions are detected, they can be isolated by care-fully following the procedures in Section 6 of the Solid State Protection Manual.
3.3 This procedure must be completed in the sequence given to insure successful completion *  


,x SALEM GENERATING STATION                   NUMBER -     lPD-18 .1. 009 REV.NO. 1~~~~~~~
,x SALEM GENERATING STATION NUMBER -
* PERFORMANCE DEPARTMENT (I & C)
lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)
DATE         5/24/82
*TEST PROCEDURE REV.NO.
                                                            ----~--~-------
1~~~~~~~
            *TEST PROCEDURE                              PAGE 3     OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 4.0   Limitations and Actions:
DATE 5/24/82  
4.1   If, at any time during the performance of this test, there is any reason to suspect that the test equipment being used may not be performing properly, a comparison check shall be performed with a similar device or the device shall be checked for calibration against a standardo This shall be done prior ~o taking any other corrective action.
----~--~-------
                                                                              \.._.
PAGE 3 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 4.0 Limitations and Actions:
4o2   If, during the performance of this test, the "As Found" data does not meet the requirements of the specified accuracy, the Job Supervisor shall be notified immediately
4.1 If, at any time during the performance of this test, there is any reason to suspect that the test equipment being used may not be performing properly, a comparison check shall be performed with a similar device or the device shall be checked for calibration against a standardo This shall be done prior ~o taking any other corrective action.
4o2 If, during the performance of this test, the "As Found" data does not meet the requirements of the specified accuracy, the Job Supervisor shall be notified immediately
_ and PD-14.1.001 shall be performed.
_ and PD-14.1.001 shall be performed.
4o3   If, during the performance of this procedure, the required status indication cannot be obtained, the Job Supervisor shall be notified immediately.     Exceptions*
4o3 If, during the performance of this procedure, the required status indication cannot be obtained, the Job Supervisor shall be notified immediately.
Exceptions*
to the required indication, due to plant conditions at the time of the test, may be made by the Job Supervisor.
to the required indication, due to plant conditions at the time of the test, may be made by the Job Supervisor.
Any exceptions of this nature must be indicated and explained in the Remarks section of this procedure.
Any exceptions of this nature must be indicated and explained in the Remarks section of this procedure.
4o4   An entry will be made in the Remarks section of this
4o4 An entry will be made in the Remarks section of this procedure indicating any deficiency and the corrective action taken.  
* procedure indicating any deficiency and the corrective action taken.
\\.._.
* X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
lPD-18.1. 009 REV. NO.
....;;;..l ______ _
DATE
_S~/...:2;..;;4-'-/..;;.8=2 ___ _
PAGE _4 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 5.0 Test Equipment:
Device Name PD No.
Recal. Date Fluke (2)
Stop Watch


*X SALEM GENERATING STATION                 NUMBER -        lPD-18 .1. 009 REV. NO.    ....;;;..l_ _ _ _ _ __
SALEM GENERATING STATION lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)
* PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
DATE        _S~/...:2;..;;4-'-/..;;.8=2_ _ __
REV. NO.
TEST PROCEDURE PAGE _4_ _ OF                   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 5.0  Test Equipment:
DATE 1
Device Name              PD No.                 Recal. Date Fluke (2)
5/24/82 PAGE _s __ OF 50 TITLE 6.* 0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B Prerequisites:
Stop Watch
6.1 The individual assigned to perform this procedure 6.2 is qualified to do so in accordance with Solid State Protection System Qualification Card 2.6.
Supervisor The Senior Shift Supervisor/Shift Supervisor has granted permission to perform this procedure.
Senior Shift Supervisor/Shift Supervisor Date/Time 603 The Control Operator is aware of all of the alarms and indications that will result from the performance of this procedure.
Control Operator


SALEM GENERATING STATION                   NUMBER -    lPD-18.1.009 REV. NO. 1
SALEM GENERATING STATION lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)
* PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
DATE         5/24/82 TEST PROCEDURE                                PAGE _s__  OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 6.* 0 Prerequisites:
REV. NO.
6.1   The individual assigned to perform this procedure is qualified to do so in accordance with Solid State Protection System Qualification Card 2.6.
1 DATE 5/24/82 PAGE 6
Supervisor 6.2  The Senior Shift Supervisor/Shift Supervisor has granted permission to perform this procedure.
OF so TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 7.0 System Line~up:
Senior Shift Supervisor/Shift Supervisor Date/Time 603  The Control Operator is aware of all of the alarms and indications that will result from the performance of this procedure.
7.1 The following conditions must be established and/or verified by the Control Operator.
Control Operator
7.1.1 Reactor Trip Bypass Breaker A is open and in the Racked Out position.
Safeguard actions which are being blocked by virtue of having been *Reset from the Control Bezel will be re-initiated at the completion of this test if the necessary logic signal is present.
The Safeguard actions involved are:
: 1.
Containment Spray
: 2.
Phase A Isolation
: 3.
Phase B Isolation
: 4.
Feedwater Isolation s:.
Containment Ventilation Isolation from Safety Injection signal Control Operator  


SALEM GENERATING STATION                   NUMBER -     lPD-18.1.009
.x SALEM GENERATING STATION NUMBER -
* PERFORMANCE DEPARTMENT (I & C)
lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)
REV. NO.     1 DATE         5/24/82 TEST PROCEDURE PAGE   6    OF so TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 7.0  System Line~up:
TEST PROCEDURE REV. NO.  
7.1 The following conditions must be established and/or verified by the Control Operator.
---=l=--------
7.1.1     Reactor Trip Bypass Breaker A is open and in the Racked Out position .
DATE 5/24/82 PAGE _7 __ OF 50 TITLE 8.0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B Instructions:
* Safeguard actions which are being blocked by virtue of having been *Reset from the Control Bezel will be re-initiated at the completion of this test if the necessary logic signal is present. The Safeguard actions involved are:
8.1 Measure and record the following instrument Bus Voltages (Required 117 + 10 VAC).
: 1. Containment Spray
8elel Bus #1 TB-110 -
: 2. Phase A Isolation
11 & 12 VAC 8olo2 Bus #2 TB-210 -
: 3. Phase B Isolation
11 & 12 VAC 8.1.3 Bus #3 TB-310 - 11 & 12 VAC 8.; 1. 4 Bus #4 TB-410 -
: 4. Feedwater Isolation s:. Containment Ventilation Isolation from Safety Injection signal Control Operator
11 & 12 VAC 8.1.5 Bus #1 TB--654 -
2 & 12 VAC 8.2 Open the front doors of Train B Logic Bay and Train B Output Relay Bay.
: 8. 3--- On the Logic Tester Panel, verify and record the following Power Supply Voltages 8.3.1
+.4 8VDC #1 Required 4 8. 7 + 0. 2 VDC As Found As Left 8.3.2
+48VDC #2 Required 48.7 + 0.2 VDC As Found.
As Left


.x SALEM GENERATING STATION                       NUMBER -     lPD-18 .1. 009
.x SALEM GENERATING STATION NUMBER -
* PERFORMANCE DEPARTMENT (I & C)                 REV. NO.   ---=l=--------
lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)
DATE         5/24/82 TEST PROCEDURE                                    PAGE _7_ _ OF     50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
TEST PROCEDURE REV. NO.
* l  
~~~~~~~-
DATE 5/24/82 PAGE ---..8 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
8.1    Measure and record the following instrument Bus Voltages (Required 117 + 10 VAC).
(Continued) 8.3.3  
8elel    Bus #1 TB-110 - 11    &  12              VAC 8olo2    Bus #2 TB-210 - 11 & 12                  VAC
+lSVDC #1 Required 15.7 + 0.2 VDC As Found As Left  
* 8.1.3 8.; 1. 4 Bus #3 TB-310 - 11 Bus #4 TB-410 - 11 12 12 VAC VAC 8.1.5    Bus #1 TB--654 - 2  &  12              VAC 8.2    Open the front doors of Train B Logic Bay and Train B Output Relay Bay.
+15VDC #2 Required l5o7 + 0.2 VDC As Found As Left 8.4 Verify the followi.ng Solid State Protection System General Warnings Lamps are Off o 8 0. 4.1 General Warning Lamp - Train A 8.4.2 General Warning Lamp - Train B 8.5 Depress the following General Warning Lamps and verify the Lamp Lights, and then remains OFF.
: 8. 3--- On the Logic Tester Panel, verify and record the following Power Supply Voltages 8.3.1    +.4 8VDC #1 Required 4 8. 7 + 0. 2 VDC
General Warning Lamp -
* 8.3.2 As Found               As Left
Train A 8.5.2 General Warning Lamp -
                          +48VDC #2 Required 48.7 + 0.2 VDC As Found .              As Left
Train B Initial


.x SALEM GENERATING STATION                 NUMBER -     lPD-18 .1. 009 REV. NO.   *l
.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
* PERFORMANCE DEPARTMENT (I & C)                      ~~~~~~~-
TEST PROCEDURE NUMBER -
DATE         5/24/82 TEST PROCEDURE                              PAGE ---..8__ OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
lPD-18.1. 009 REV.NO.  
~l~~~~~~-
DATE
_5~/_2_4~/_8_2 ______ _
PAGE 9
OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                     Initial 8.3.3    +lSVDC #1 Required 15.7 + 0.2 VDC As Found            As Left
(Continued) 8.6 On the Logic Test Panel, following indicators will 8.6.1 Testing 8.6.2 Bad 8.6.3
                        +15VDC #2 Required l5o7 + 0.2 VDC
. Good 8.6.4 Continuity 8.6.5 Memory Set 8.6.6 1/1 8.6.7 1/2 8.6.8 1/3 8.6.9 1/4 8.6.10 2/2 8.6.11 2/3 8.6.12 2/4 verify light that each of the by depressing it.
* As Found            As Left 8.4 Verify the followi.ng Solid State Protection System General Warnings Lamps are Off o 8 4 .1
Initial
: 0.     General Warning Lamp  - Train  A 8.4.2    General Warning Lamp  - Train B 8.5  Depress the following General Warning Lamps and verify the Lamp Lights, and then remains OFF.
General Warning Lamp - Train A
* 8.5.2     General Warning Lamp - Train B
 
.x SALEM GENERATING STATION                  NUMBER -    lPD-18 .1. 009 REV.NO.   ~l~~~~~~-
* PERFORMANCE DEPARTMENT (I & C)
DATE      _5~/_2_4~/_8_2_______
TEST PROCEDURE                              PAGE              OF 50 9
TITLE      SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B


==8.0 Instructions==
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
(Continued)                                        Initial 8.6  On the Logic Test Panel, verify that each of the following indicators will light by depressing it.
8.6.1      Testing 8.6.2      Bad 8.6.3    . Good 8.6.4      Continuity 8.6.5      Memory Set 8.6.6      1/1 8.6.7      1/2 8.6.8      1/3 8.6.9      1/4 8.6.10      2/2
* 8.6.11 8.6.12 2/3 2/4
* SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
TEST PROCEDURE NUMBER -
REV.NO.
. lPD-18.1. 009 REV.NO.
DATE
~l~~~~~~-
                                                                                                              . lPD-18 .1. 009
DATE 5/24/82 PAGE 10 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  
                                                                                                              ~l~~~~~~-
PAGE 5/24/82 10     OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                                                 Initial 8.7 Record UV Coil Voltage Meter Reading.
(Continued) 8.7 Record UV Coil Voltage Meter Reading.
..              Required 43 VDC + 2 VDC
Required 43 VDC + 2 VDC Initial
((w~:n, ~~hh~~~~~~( O\~~.&deg;.~:.~1 ~ ~.~~l~*:; <->.~.:~~*~:ni-\~--:.
((w~:n, ~~hh~~~~~~( O \\~~.&deg;.~:.~1 ~ ~.~~l~*:; <->.~. :~~*~:ni-\\~--:.,
                    \ "'-"" *~ ''~ '.:, t: ..,_. l:"<ffi c. *1-.. \*;:i :H><.'- 1G t..ic ~ , :** 1.-.. L.. *
t'' ~--~ L1<.- i 1~\\
                                                                                                                    ,t'' ~--~ L1<.- i  1~\
\\ "'-"" *~ ''~ '.:, t:..,_.
                                                                                                                                        /
l:"<ffi c. *1-..  
8.8  On the         Outpu~           Relay Test Panel, place the Mode Selector Switch in the Test position.
\\*;:i :H><.'-
8.9 Verify the Operate Lamp is not lighted.
1G t..ic ~, :** 1.-.. L.. *  
8.10 Verify the General Warning Lamp is                                                   lighted~
/
On the Outpu~ Relay Test Panel, place the Mode Selector 8.8 Switch in the Test position.
8.9 Verify the Operate Lamp is not lighted.
8.10 Verify the General Warning Lamp is lighted~
8.11 Verify the operation of the Semi-Automatic Tester.
8.11 Verify the operation of the Semi-Automatic Tester.
Self-check as follows:
Self-check as follows:  
                                                        -NOTE-Steps 8.11.6 through 8.11.11 will result in continuous alarms in the Control Room if there are any tripped inputs to the SSPS.
-NOTE-Steps 8.11.6 through 8.11.11 will result in continuous alarms in the Control Room if there are any tripped inputs to the SSPS.
8.11.1                 Verify that the continuity lamp is lighted .
8.11.1 8.11.2 Verify that the continuity lamp is lighted.
* 8.11.2                On the Tester PC Card (AlOS), verify that the top four LED's (light emitting diodes) are lighted.
On the Tester PC Card (AlOS), verify that the top four LED's (light emitting diodes) are lighted.  


x SALEM GENERATING STATION                 NUMBER -     lPD-18.1.009 REV. NO.      l PERFORMANCE DEPARTMENT (I & C)
x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
DATE          5/24/82 TEST PROCEDURE PAGE   11   OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
TEST PROCEDURE NUMBER -
REV. NO.
DATE lPD-18.1.009 l
5/24/82 PAGE 11 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                   Initial 8.11~3   Depress the test pushbutton. Verify that the continuity lamp and the top four LEDS on Al08 extinguish.
(Continued) 8.11~3 8.11.4 8.11.7 Depress the test pushbutton.
8.11.4    Release the TEST pushbutton. Verify that the continuity lamp and the top four LEDS
Verify that the continuity lamp and the top four LEDS on Al08 extinguish.
* on Al08 light.
Release the TEST pushbutton.
Verify that the continuity lamp and the top four LEDS on Al08 light.
On the Logic Test Panel, place the Input Error Inhibit switch to the Inhibit position.
On the Logic Test Panel, place the Input Error Inhibit switch to the Inhibit position.
Place the MULTIPLEXER TEST switch to the A & B position.
Place the MULTIPLEXER TEST switch to the A & B position.  
                                              *~.
*~.
8.11.7    Place the BLOCKING FUNCTION TEST switch to the BLOCKS NOT INHIBITED position.
Place the BLOCKING FUNCTION TEST switch to the BLOCKS NOT INHIBITED position.
Depress and release the TEST pushbutton.
Depress and release the TEST pushbutton.
8.11.8.l Verify that the amber testing lamp lights.
8.11.8.l Verify that the amber testing lamp lights.
8.11.8.2 In approximately 1.6 seconds, verify that this lamp extinguishes.
8.11.8.2 In approximately 1.6 seconds, verify that this lamp extinguishes.
8.11.8.3 Verify that the GOOD lamp lights.
8.11.8.3 Verify that the GOOD lamp lights.
Initial


x SALEM GENERATING STATION                     NUMBER-     lPD-18.1.009 REV. NO. 1
x SALEM GENERATING STATION NUMBER-lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)
* PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE REV. NO.
DATE       5/24/82 TEST PROCEDURE                                PAGE .;;;1~2__ OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE 1
5/24/82 PAGE  
.;;;1~2 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                       Initial 8.11.8.4   In approximately 1.6 seconds, verify that the good lamp extinguishes and repeatedly blinks on and off for these periods.
(Continued) 8.11.8.4 In approximately 1.6 seconds, verify that the good lamp extinguishes and repeatedly blinks on and off for these periods.
8.11.9     Place the BLOCKING FUNCTION TEST switch to the INHIBIT BLOCKS position.
8.11.9 8.11.10 Place the BLOCKING FUNCTION TEST switch to the INHIBIT BLOCKS position.  
8.11.10    ~epress and release th~ Test pushbutton.
~epress and release th~ Test pushbutton.
8.11.10.1 Verify that the AMBER TESTING lamp LIGHTS.
8.11.10.1 Verify that the AMBER TESTING lamp LIGHTS.
8.11.10.2 Verify that the red BAD lamp lights.
8.11.10.2 Verify that the red BAD lamp lights.
8.11.11   Place the MULTIPLEXER TEST switch to INHIBIT *.
8.11.11 Place the MULTIPLEXER TEST switch to INHIBIT *.
8.12 Verify Reactor Trip Breaker B is CLOSED (if Reactor Trip Breaker is open have the Cont.rel Operator CLOSE Reactor Trip Breaker (B)
8.12 Verify Reactor Trip Breaker B is CLOSED (if Reactor Trip Breaker is open have the Cont.rel Operator CLOSE Reactor Trip Breaker (B) 8.13 Verify the following High Radiation ALARM Lights on panel lRPl are OFF.
* 8.13 Verify the following High Radiation ALARM Lights on panel lRPl are OFF.
8.13.1 lR-llA Containment or Vent Particulate Initial
8.13.1     lR-llA Containment or Vent Particulate


x SALEM GENERATING STATION                     NUMBER -     lPD-18 .1. 009 REV. NO.   -=-1_ _ _ _ _ __
x SALEM GENERATING STATION NUMBER -
* PERFORMANCE DEPARTMENT (I & C)
lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)
DATE        ~5~/~2~4~/~8=2~~~-
TEST PROCEDURE REV. NO.  
TEST PROCEDURE 13         50 PAGE
-=-1 ______ _
                                                                ---    OF TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE
~5~/~2~4~/~8=2~~~-
PAGE 13 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                         Initial 8.13.2     1R-12A Containment or Vent Gas Effluent.
(Continued) 8.13.2 8.13.3 1R-12A Containment or Vent Gas Effluent.
8.13.3    1R-12B Containment or Vent Gas Effluent (Iodine)
1R-12B Containment or Vent Gas Effluent (Iodine)
* 8.14 If any high RADIATION ALARM is present in
* 8.14 If any high RADIATION ALARM is present in Steps 8.13e1 through 8.13. 3 lift the *field lead on terminal TB-506-2.
* Steps 8.13e1 through 8 .13. 3 lift the *field lead on terminal TB-506-2.
8.15 Perform the following for LOGIC and PERMISSIVE testing.
8.15 Perform the following for LOGIC and PERMISSIVE testing. Record results on TABLE I.
Record results on TABLE I.
WARNING:   If a malfunction within the logics is detected, the red BAD LAMP will come on at the instant of detection and
WARNING:
                          -remain on. It is then necessary to refer to Section 6.3 of the Solid State Protection System Manual to troubleshoot and define the cause.
If a malfunction within the logics is detected, the red BAD LAMP will come on at the instant of detection and  
Verify the following switches are in *the positions indicated *
-remain on.
* 8.15.1.1   Logic A 8.15.1.2 _Logic B OFF 24
It is then necessary to refer to Section 6.3 of the Solid State Protection System Manual to troubleshoot and define the cause.
Verify the following switches are in *the positions indicated
* 8.15.1.1 Logic A OFF 8.15.1.2 _Logic B 24 Initial


.x SALEM GENERATING STATION                   NUMBER -        lPD-18.1.009
.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
* PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
TEST PROCEDURE REV. NO.
REV. NO.
DATE 1
DATE lPD-18.1.009 1
5/24/82 PAGE ..;;;;l;..;;..4_ OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
5/24/82 PAGE..;;;;l;..;;..4_ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                 Initial 8.15.1.3   Logic C       24 8.15.1.4   Logic D       24
(Continued)  
* 8.15.l.6 8.15.2 Memories      OFF Place Logic A switch to position "l" and verify that Function Logic! Lamp 2/3 lights.
. I 8.15.1.3 Logic C 24 8.15.1.4 Logic D 24 8.15.l.6 Memories OFF 8.15.2 8.15.3 8.15.5 Place Logic A switch to position "l" and verify that Function Logic! Lamp 2/3 lights.
8.15.3    Depress and. release the TEST pushbutton.
Depress and. release the TEST pushbutton.
The amber testing lamp will LIGHT. After all combinations of logics are tested, the Amber TESTING Lamp should extinguish and
The amber testing lamp will LIGHT.
                                                      .   ~
After all combinations of logics are tested, the Amber TESTING Lamp should extinguish and  
  . I the Green GOOD Lamp should 1light. The I
. ~
GOOD Lamp will extinguish ;*1he next tl.me the TEST pushbutton is dep;ressed ..
the Green GOOD Lamp should 1light.
Place the Blocking Functi~n Test Switch to the opposite position and r~peat Steps 8.15.2 and 8.15.3 *
The I
* 8.15.5    Using Table I, perform Step 8.15.2 through 8.15.4 for the positions of the logic and permissive switches as listed.
GOOD Lamp will extinguish ;*1he next tl.me the TEST pushbutton is dep;ressed..
Place the Blocking Functi~n Test Switch to the opposite position and r~peat Steps 8.15.2 and 8.15.3
* Using Table I, perform Step 8.15.2 through 8.15.4 for the positions of the logic and permissive switches as listed.
Initial


SALEM GENE.ING ST ATION PERFORMANCE DEPARTMENT TEST PROCEOUHE 0& C)
SALEM GENE.ING ST A TION PERFORMANCE DEPARTMENT 0 & C)
* NUMBER_
TEST PROCEOUHE NUMBER_
REV.NO.
lPD-18.1. 009 REV.NO.
DATE lPD-18 .1. 009 l
l  
                                                                            ~~~~------~
~~~~------~
5/24/82 PAGE 15   OF 50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                           FUNCTION LOGIC          BLOCKING FUNCTION.
DATE 5/24/82 PAGE 15 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS PER-LOGI C LOGIC LOGIC LOGIC MIS-A B
TEST SWITCH PER-                                                                     BLOCKS LOGI C   LOGIC   LOGIC LOGIC   MIS-       TEST                                              INHIBIT      NOT A         B     C     D     SIVE     FUNCTION                  REQUIRED    ACTUAL      BLOCKS INHIBITED OFF     24     24     24     OFF  OFF                                                       (GOOD OR BAD) 1     24     24     24     OFF LOSS OF FLOW, LOOP 1              2/3 2    24     24     24     OFF LOSS OF FLOW, LOOP 2              2/3 3    24     24     24   OFF LOSS OF FLOW, LOOP 3              2/3 4     24     24     24   OFF LOSS OF FLOW, LOOP 4              2/3 5    24      24      24    OFF  LOSS OF FLOW, RCP                 2/4 6    24      24      24    OFF  PRESSURIZER, LOW PRESSURE TRIP     2/4
C D
SIVE OFF 24 24 24 OFF 1
24 24 24 OFF 2
24 24 24 OFF 3
24 24 24 OFF 4
24 24 24 OFF 5
24 24 24 OFF 6
24 24 24 OFF TABLE I LOGIC & PERMISSIVES TEST FUNCTION OFF LOSS OF FLOW, LOSS OF FLOW, LOSS OF FLOW, LOSS OF FLOW, LOOP LOOP LOOP LOOP LOSS OF FLOW, RCP 1
2 3
4 PRESSURIZER, LOW PRESSURE FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/3 2/3 2/3 2/4 TRIP 2/4 BLOCKING FUNCTION.
TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED (GOOD OR BAD)


,/\
,/\\
SALEM GE.A TING ST A TION NUMBER -   lPD-18 .1. 009 PEAFOAft.1ANCE DEPARTMENT (I & C)                                  REV. NO. 1 TEST PAOCEDUBE                                              DATE       5/24/82 50 PAGE
SALEM GE.A TING ST A TION PEAFOAft.1ANCE DEPARTMENT (I & C)
                                                                                    - OF TITLE        SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                              FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                    BLOCKS LOGIC    LOGIC  LOGIC  LOGIC    MIS-        TEST                                             INHIBIT     NOT A        B      c      D    SIVE      FUNCTION                   REQUIRED     ACTUAL   BLOCKS INHIBITED .l 7    24      24    24      OFF  PRESSURIZER, HIGH PRESSURE TRIP     2/4 8    24      24    24      OFF  PRESSURIZER, HIGH WATER LEVEL       2/3 TRIP 9    24      24      24    OFF  LOW FEEDWATER FLOW, LOO:P 1         1/2 10      24      24      24    OFF  LOW FEEDWATER FLOW, LOOP 1         1/2 11      24      24      24    OFF  LOW FEEDWATER FLOW, LOOP 2         1/2 12    24      24      24    OFF  LOW FEEDWATER FLOW, LOOP 2         1/2
TEST PAOCEDUBE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
c D
SIVE 7
24 24 24 OFF 8
24 24 24 OFF 9
24 24 24 OFF 10 24 24 24 OFF 11 24 24 24 OFF 12 24 24 24 OFF NUMBER -
lPD-18.1. 009 REV. NO.
1 DATE 5/24/82 PAGE 16 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED  
.l PRESSURIZER, HIGH PRESSURE TRIP 2/4 PRESSURIZER, HIGH WATER LEVEL 2/3 TRIP LOW FEEDWATER FLOW, LOO:P 1 1/2 LOW FEEDWATER FLOW, LOOP 1 1/2 LOW FEEDWATER FLOW, LOOP 2 1/2 LOW FEEDWATER FLOW, LOOP 2 1/2  


SALEM GE.A TING STATION PERFORMANCE DEPARTMENT (I & C)
SALEM GE.A TING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE
TEST PROCEDUHE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
* NUMBER -
c D
REV. NO.
SIVE 13 24 24 24 OFF 14 24 24 24 OFF 15 24 24 24 OFF 16 24 24 24 OFF 17 24 24 24 OFF 18 24 24 24
lPD-18 .1. 009 1
.OFF
5/24/82 DATE PAGE 17   OF   50 TITLE        SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                            FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                  BLOCKS LOGIC    LOGIC  LOGIC  LOGIC  MIS-        TEST                                           INHIBIT     NOT . ;
: 19.
A        B      c      D    SIVE      FUNCTION                   REQUIRED   ACTUAL     BLOCKS INHIBITED 13      24      24    24    OFF  LOW FEEDWATER FLOW, LOOP 3       1/2 14      24      24    24    OFF  LOW FEEDWATER FLOW, LOOP 3       1/2 15      24      24      24    OFF  LOW FEEDWATER FLOW, LOOP 4       1/2 16      24      24      24    OFF  LOW FEEDWATER FLOW, LOOP 4       1/2 17      24      24      24    OFF  OIL PRESSURE SWITCHES REACTOR     2/3 TRIP 18      24      24      24  .OFF  STOP VALVES GENERATOR TRIP       2/2
24 24 24 OFF NUMBER -
: 19. 24      24      24    OFF  STOP VALVES GENERATOR TRIP       2/2
lPD-18.1. 009 REV. NO.
1 DATE 5/24/82 PAGE 17 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED LOW FEEDWATER FLOW, LOOP 3 1/2 LOW FEEDWATER FLOW, LOOP 3 1/2 LOW FEEDWATER FLOW, LOOP 4 1/2 LOW FEEDWATER FLOW, LOOP 4 1/2 OIL PRESSURE SWITCHES REACTOR 2/3 TRIP STOP VALVES GENERATOR TRIP 2/2 STOP VALVES GENERATOR TRIP 2/2  


SA.LEM GE.TING STATION PERFORMANCE DEPARTMENT (I & C)
SA.LEM GE.TING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE
TEST PROCEDUHE  
                                        *~'; .
*~';..
* NUMBER -
NUMBER -
REV. NO.
REV. NO.
lPP-18 .1. 009 1 .*
DATE lPP-18.1. 009 1.*
5/24/82 DATE PAGE     18   OF   50 TITLE           SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS.                                               FUNCTION LOGIC           BLOCKING FUNCTION TEST SWITCH PER-                                                                       BLOCKS LOGIC   LOGIC    LOGIC  LOGIC  'MIS-           TEST                                             INHIBIT      NOT A        B      C    .D     SIVE         FUNCTION                  REQUIRED      ACTUAL    BLOCKS INHIBITED 20      24     24    24    OFF   STOP VALVES REACTOR TRIP           2/2 21      24      24    24     OFF   SOURCE RANGE TR+P                   2/2 22      24      24      24   OFF   SOURCE RANGE TRIP                   2/2 23      24     24      24    OFF   FEED THRU TO LOGIC B 23      1    *24      24   OFF     INTERMEDIATE RANGE TRIP           2/2 23      2      24      24   OFF     INTERMEDIATE RANGE TRIP           2/2 23      3      24      24   OFF     POWER RANGE, LOW SETPOINT TRIP     2/4
5/24/82 PAGE 18 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B LOGIC A
20 21 22 23 23 23 23 TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS.
LOGIC LOGIC B
C 24 24 24 24 24 24 24 24 1
*24 2
24 3
24 PER-LOGIC  
'MIS-TEST FUNCTION
. D SIVE 24 OFF STOP VALVES REACTOR TRIP 24 OFF SOURCE RANGE TR+P 24 OFF SOURCE RANGE TRIP 24 OFF FEED THRU TO LOGIC B 24 OFF INTERMEDIATE RANGE TRIP 24 OFF INTERMEDIATE RANGE TRIP 24 OFF POWER RANGE, LOW SETPOINT TRIP FUNCTION LOGIC REQUIRED ACTUAL 2/2 2/2 2/2 2/2 2/2 2/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM G.ATING ST A TION PERFORMANCE DEPARTMENT (I & C)
SALEM G.ATING ST A TION NUMBER -
* NUMBER -
lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)
REV. NO.
TEST PAOCEDUHE REV. NO.
lPD-18.1.009 1
1 DATE TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS  
TEST PAOCEDUHE                                            DATE           5/24/82 PAGE  19    OF  50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                             FUNCTION LOGIC          BLOCKING FUNCTION TEST SWITCH
*PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
                                *PER-                                                                     BLOCKS LOGIC   LOGIC   LOGIC LOGIC MIS-         TEST.                                            INHIBIT      NOT A       B       C     D     SIVE     FUNCTION                   REQUIRED     ACTUAL   BLOCKS INHIBITED 23       4     24     24     OFF' POWER RANGE, HIGH SETPOINT TRIP     2/4 23       5     24     24   .OFF OVERTEMPERATURE DELTA T TRIP         2/4 23      6      24     24    OFF OVERPOWER DELTA T TRIP               2/4 23      7      24      24   OFF   RCP UNDERVOLTAGE TRIP               2/4 23      8      24     24    OFF RCP UNDERVOLTAGE TRIP               1/2 23      9      24     24    OFF RCP UNDERVOLTAGE, TURB. FEED         1/2 PUMP
C D
SIVE TABLE I LOGIC & PERMISSIVES TEST.
FUNCTION 5/24/82 PAGE 19 OF FUNCTION LOGIC REQUIRED ACTUAL 23 4
24 24 OFF' POWER RANGE, HIGH SETPOINT TRIP 2/4 23 5
24 23 6
24 23 7
24 23 8
24 23 9
24 24
.OFF OVERTEMPERATURE DELTA T TRIP 24 OFF OVERPOWER DELTA T TRIP 24 OFF RCP UNDERVOLTAGE TRIP 24 OFF RCP UNDERVOLTAGE TRIP 24 OFF RCP UNDERVOLTAGE, TURB. FEED PUMP 2/4 2/4 2/4 1/2 1/2 50 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GE.A TING ST A TION PERFORMANCE DEPARTMENT (I & C)
SALEM GE.A TING ST A TION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUBE
TEST PROCEDUBE NUMBER_
                                                      **        NUMBER_
lPD-18.1. 009 REV. NO.
REV. NO.
1.
lPD-18 .1. 009 1 .
DATE 5/24/82 PAGE 20 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST.
5/24/82 DATE PAGE   20   OF 50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                             FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                   BLOCKS LOGIC   LOGIC   LOGIC LOGIC MIS-       TEST.                                           INHIBIT      NOT A       B       c     b   SIVE     FUNCTION                   REQUIRED   ACTUAL     BLOCKS INHIBITED 23     10     24     24   OFF RCP UNDERVOLTAGE, TURB. FEED       2/4 PUMP 23     11       24   24   OFF LOW STEAMLINE PRESSURE             2/4 23     12       24     24   OFF HIGH STEAMLINE FLOW, LOOP 1         1/2 23     13       24     24   OFF HIGH STEAMLINE FLOW, LOOP 2         1/2 23     14       24     24   OFF HIGH STEAMLINE FLOW, LOOP 3         1/2 23     15     *24     24   OFF HIGH STEAMLINE FLOW, LOOP 4         1/2
A B
c b
SIVE FUNCTION REQUIRED ACTUAL 23 10 24 24 OFF RCP UNDERVOLTAGE, TURB. FEED 2/4 PUMP 23 11 24 24 OFF LOW STEAMLINE PRESSURE 2/4 23 12 24 24 OFF HIGH STEAMLINE FLOW, LOOP 1 1/2 23 13 24 24 OFF HIGH STEAMLINE FLOW, LOOP 2 1/2 23 14 24 24 OFF HIGH STEAMLINE FLOW, LOOP 3 1/2 23 15  
*24 24 OFF HIGH STEAMLINE FLOW, LOOP 4 1/2 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


I\
I\\
SALEM G.ATING STATION                                           NUMBER -   lPD-18 .1. 009 PERFORMANCE DEPARTMENT (I & C)                                              1 REV. NO.
SALEM G.ATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDU'HE                                                        5/24/82 DATE PAGE 21   OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST T.RAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                             FUNCTION LOGIC .       BLOCKING FUNCTION TEST SWITCH PER-                                                                     BLOCKS LOGIC   LOGIC   LOGIC LOGIC MIS-         TEST                                             INHIBIT      NOT A       B       c     D   SIVE       FUNCTION                   REQUIRED   ACTUAL     BLOCKS INHIBITED 23     16     ~4     24   OFF STEAMLINE ISOLATION                 2/4
TEST PROCEDU'HE NUMBER -
      ~3     17     24     24   OFF HIGH .CONTAINMENT PRESSURE,         2/3 SAFETY INJECTION 23     18     24     24   OFF HI-HI CONTAINMENT PRESSURE,         2/4.
lPD-18.1. 009 REV. NO.
SPRAY ACTUATION 23     19     24     24   OFF HI-HI CONTAINMENT PRESSURE,         2/4 SPRAY ACTUATION 23     20     24     24   OFF HI-HI CONTAI'NMENT PRESSURE,       2/4 STEAM STOP VALVES
1 DATE 5/24/82 PAGE 21 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST T.RAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC.
PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST A
B c
D SIVE FUNCTION REQUIRED ACTUAL 23 16  
~4 24 OFF STEAMLINE ISOLATION 2/4  
~3 17 24 24 OFF HIGH.CONTAINMENT PRESSURE, 2/3 SAFETY INJECTION 23 18 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4.
SPRAY ACTUATION 23 19 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4 SPRAY ACTUATION 23 20 24 24 OFF HI-HI CONTAI'NMENT PRESSURE, 2/4 STEAM STOP VALVES BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)
SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PAOCEDUHE
TEST PAOCEDUHE NUMBER -
* NUMBER -
lPD-18.1. 009 REV. NO.
REV. NO.
1 DATE 5/24/82 PAGE 22 OF 50 TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC.& PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST A
DATE lPD-18 .1. 009 1
B c
5/24/82 PAGE 22   OF   50 TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC .& PERMISSIVES
D SIVE FUNCTION REQUIRED ACTUAL 23 21 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4 PHASE B ISOLATION 23 22 24 24 OFF SAFETY INJECTION, PHASE A 1/1 ISOLATION 23 23 24 24 OFF SAFETY INJECTION, CONTAINMENT 1/2 VENTILATION ISOLATION 23 24 24 24 OFF FEED THRO TO LOGIC C 23 24 l
                                                                                                                ;
24 OFF STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 1 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED i
FUNCTION SELECTORS                                             FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH LOGIC   LOGIC   LOGIC LOGIC PER-MIS-       TEST                                             INHIBIT BLOCKS NOT
                                                                                                                ;
A        B       c     D   SIVE     FUNCTION                     REQUIRED   ACTUAL     BLOCKS INHIBITED  i 23     21       24     24   OFF HI-HI CONTAINMENT PRESSURE,         2/4 PHASE B ISOLATION 23     22       24     24   OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23     23       24     24   OFF SAFETY INJECTION, CONTAINMENT       1/2 VENTILATION ISOLATION 23     24       24     24   OFF FEED THRO TO LOGIC C 23     24       l     24   OFF STEAMLINE DIFFERENTIAL               2/3 PRESSURE, LOOP 1


I\
I\\
SALEM G.ATING ST A TION                                           NUMBER -     lPD-18 .1. 009 PERFORMANCE DEPARTMENT (I & C)                                    REV. NO.     1 TEST PROCEDUHE                                              DATE         5/24/82 PAGE   23   OF 50 TITLE          SOLID STATE PROTECT.ION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                              FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                      BLOCKS LOGIC    LOGIC    LOGIC  LOGIC  MIS-:-        TEST                                             INHIBIT     NOT A        B      c      D    SIVE        FUNCTION                   REQUIRED     ACTUAL   BLOCKS .INHIBITED 23      24      2    24    OFF    STEAMLINE DIFFERENTIAL             2/3 PRESSURE, LOOP 2 23      24      3    24    OFF    STEAMLINE DIFFERENTIAL             2/3 PRESSURE, LOOP 3 23      24      4    24    OFF    STEAMLINE DIFFERENTIAL             2/3 PRESSURE, LOOP 4 23      24      5    24    OFF      PRESSURIZER PRESSURE             2/3 23      24.      6    24    OFF      PRESSURIZER PRESSURE             2/3 23      24      7    24    OFF      PRESSURIZER PRESSURE             2/3
SALEM G.ATING ST A TION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE TITLE SOLID STATE PROTECT.ION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-:-
A B
c D
SIVE 23 24 2
24 OFF 23 24 3
24 OFF 23 24 4
24 OFF 23 24 5
24 OFF 23
: 24.
6 24 OFF 23 24 7
24 OFF NUMBER -
lPD-18.1. 009 REV. NO.
1 DATE 5/24/82 PAGE 23 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS.INHIBITED STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 2 STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 3 STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 4 PRESSURIZER PRESSURE 2/3 PRESSURIZER PRESSURE 2/3 PRESSURIZER PRESSURE 2/3  


SALEM GE.ATING STATION
SALEM GE.ATING STATION
* PERFORMANCE DEPARTMENT (I & Cl TEST PAOCEDUHE
* PERFORMANCE DEPARTMENT (I & Cl TEST PAOCEDUHE NUMBER:-
                                                                    **      NUMBER:-
REV. NO.
REV. NO.
lPD-18.1.009 1
lPD-18.1.009 1
DATE         5/24/82 PAGE  24    OF  50 TITLE         SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                                       FUNCTION LOGIC        BLOCKING FUNCTION TEST SWITCH    .
DATE TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS PER-LOGI C LOGIC LOGIC LOGIC MIS~
PER-                                                                         . BLOCKS LOGI C   LOGIC     LOGIC   LOGIC MIS~               TEST                                           INHIBIT      NOT A       B       C       D   S.IVE             FUNCTION                    REQUIRED    ACTUAL    BLOCKS INHIBITED 23     24       8     24   OFF   STEAM GENERATOR LO-LO WATER               2/3
TEST FUNCTION A
                                                .LEVEL LOOP 1 23      24      .9      24    OFF   STEAM GENERATOR LO-LO WATER               2/3 LEVEL LOOP. 2 23      24      10      24    OFF   STEAM GENERATOR LO-LO WATER               2/3 LEVEL LOOP 3
B C
                                              ~ ..
D S.IVE 23 24 8
23      24      11      24    OFF   STEAM GENERATOR LO-LO WATER               2/3 LEVEL LOOP 4 23      24      i2      24    OFF   STEAM GENERATOR LO-LO WATER               1/4 LEVEL TRIP
24 23 24
.9 24 23 24 10 24 23 24 11 24 23 24 i2 24 OFF STEAM GENERATOR LO-LO WATER  
.LEVEL LOOP 1 OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP. 2 OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP 3  
~..
OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP 4 OFF STEAM GENERATOR LO-LO WATER LEVEL TRIP 5/24/82 PAGE 24 OF 50 FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/3 2/3 2/3 1/4 BLOCKING FUNCTION TEST SWITCH
. BLOCKS INHIBIT NOT BLOCKS INHIBITED


                                              \, -
S~LEM GaA TING ST A TION PERFORMANCE DEPARTMENT (I & C)
S~LEM G a ATING ST ATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE  
TEST PROCEDUHE
\\, -
* NUMBER-REV. NO.
* NUMBER-lPD-18.1.009 REV. NO.
lPD-18.1.009 1
1 DATE 5/24/82 PAGE 25 OF 50 TITLE SOLID.STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
5/24/82 DATE PAGE   25       50
c b
                                                                                --- OF ---
SIVE 23 24 13 24 OFF 23 24 14 24 OFF 23 24 15 24 OFF 23.
TITLE         SOLID.STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                             FUNCTION LOGIC        BLOCKING FUNCTION TEST SWITCH PER-                                                                     BLOCKS LOGIC   LOGIC   LOGIC LOGIC MIS-         TEST                                            INHIBIT      NOT A       B       c     b   SIVE       FUNCTION                    REQUIRED    ACTUAL    BLOCKS INHIBITED 23     24     13     24   OFF STEAM GENERATOR LO-LO WATER         1/4 LEVEL, MOTOR FEED PUMP 23      24      14    24    OFF .STEAM GENERATOR *LO-LO WATER         2/4 LEVEL, TURBINE FEED PUMP 23      24      15    24    OFF  STEAM GENERATOR HI-HI LEVEL,         2/3 GENERATOR 1 23 . 24      16    24    OFF  STEAM GENERATOR HI-HI LEVEL,         2/3 GENERATOR 2 23      24      17    24    OFF  STEAM GENERATOR HI-HI LEVEL,         2/3 GENERATOR 3
24 16 24 OFF 23 24 17 24 OFF TABLE I LOGIC & PERMISSIVES TEST FUNCTION STEAM GENERATOR LO-LO WATER LEVEL, MOTOR FEED PUMP  
.STEAM GENERATOR *LO-LO WATER LEVEL, TURBINE FEED PUMP STEAM GENERATOR HI-HI LEVEL, GENERATOR 1 STEAM GENERATOR HI-HI LEVEL, GENERATOR 2 STEAM GENERATOR HI-HI LEVEL, GENERATOR 3 FUNCTION LOGIC REQUIRED ACTUAL 1/4 2/4 2/3 2/3 2/3 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GU*
SALEM GU **
* TING STATION PERFORMANCE DEPARTMENT (I & C)
TING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PAOCEDUHE
TEST PAOCEDUHE NUMBEA-AEV. NO.
* NUMBEA-AEV. NO.
lPD-18.1.009 1
lPD-18.1.009 1
DATE         5/24/82 PAGE              50
DATE TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS PER-LOG IC LOGIC LOGIC LOGIC MIS-TEST FUNCTION A
                                                                                -2(?- - OF TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                           FUNCTION LOGIC          BLOCKING FUNCTION TEST SWITCH PER-                                                                     BLOCKS LOG IC   LOGIC   LOGIC LOGIC MIS-       TEST                                             INHIBIT      NOT A       B       C     D   SIVE     FUNCTION                  REQUIRED      ACTUAL    BLOCKS INHIBITED 23     24       18     24   OFF STEAM GENERATOR HI-HI LEVEL,     2/3 GENERATOR 4 23      24      19    24    OFF LOW TAVG                         2/4 23      24      20    24    OFF TAVG AND REACTOR TRIPPED         2/2 23      24      21    24    OFF UV DIODES AND OUTPUT             1/4 23     24       22     24   OFF SAFETY INJECTION DIODES & OUTPUT 1/4 23     24       23     24   OFF UV DIODES AND OUTPUT             1/4
B C
D SIVE 23 24 18 23 24 19 23 24 20 23 24 21 24 24 24 24 OFF STEAM GENERATOR HI-HI LEVEL, GENERATOR 4 OFF LOW TAVG OFF TAVG AND REACTOR TRIPPED OFF UV DIODES AND OUTPUT 5/24/82 PAGE 2(?
OF 50 FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/4 2/2 1/4 23 24 22 24 OFF SAFETY INJECTION DIODES & OUTPUT 1/4 23 24 23 24 OFF UV DIODES AND OUTPUT 1/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GE.ATINGSTATION PERFORMANCE DEPARTMENT TEST PAOCEDUHE 11 & C)
A SALEM GE.ATINGSTATION NUMBER -
* NUMBER -
lPD-18.1.009 PERFORMANCE DEPARTMENT 11 & C)
REV. NO.
REV. NO.
lPD-18.1.009 1
1 TEST PAOCEDUHE DATE 5/24/82 PAGE 27 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH PER-BLOCKS LOGIC LOGIC LOGIC LOGIC MIS-TEST INHIBIT NOT A
DATE         5/24/82 PAGE   27   OF   50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                               FUNCTION LOGIC       BLOCKING FUNCTION TEST SWITCH PER-                                                                   BLOCKS LOGIC   LOGIC   LOGIC LOGIC     MIS-       TEST                                           INHIBIT     NOT A       B       c         D   SIVE     FUNCTION                   REQUIRED   ACTUAL   BLOCKS INHIBITED 23     24     24   _* 24     OFF FEED THRU TO LOGIC D 23     24     24         1   OFF SAFETY INJECTION DIODES & OUTPUT 1/3 23     24     24         2   OFF UV DIODES AND OUTPUT               1/4 23     24     24         3   OFF UV DIODES AND OUTPUT               1/4 23     24     24         4   OFF UV DIODES AND OUTPUT               1/4 23     24     24         5   OFF UV DIODES AND OUTPUT               1/4 23     24     24         6   OFF UV DIODES AND OUTPUT               1/4
B c
D SIVE FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED 23 24 24
_* 24 OFF FEED THRU TO LOGIC D 23 24 24 1
OFF SAFETY INJECTION DIODES & OUTPUT 1/3 23 24 24 2
OFF UV DIODES AND OUTPUT 1/4 23 24 24 3
OFF UV DIODES AND OUTPUT 1/4 23 24 24 4
OFF UV DIODES AND OUTPUT 1/4 23 24 24 5
OFF UV DIODES AND OUTPUT 1/4 23 24 24 6
OFF UV DIODES AND OUTPUT 1/4  


SALEM   GEa     TING STATION PERFORUANCE DEPARTMENT (I & C)
SALEM GEa TING STATION PERFORUANCE DEPARTMENT (I & C)
TEST PAOCEDUHE
TEST PAOCEDUHE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC. LOGIC LOGIC LOGIC MIS-A B
* NUMBER -
c D
REV. NO.
SIVE 23 24 24 7
lPD-18 .1. 009 1
OFF 23 24 24 8
DATE         5/27/82 PAGE   28   OF   50 TITLE          SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC *& PERMISSIVES FUNCTION SELECTORS                                                  FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                      BLOCKS LOGIC . LOGIC    LOGIC  LOGIC    MIS-        TEST                                               INHIBI'I'   NOT A        B        c      D      SIVE      FUNCTION                     REQUIRED   ACTUAL     BLOCKS INHIBITED 23      24      24      7      OFF  FEEDWATER CONTROL                     1/2 23      24      24      8      OFF  FEEDWATER CONTROL                     1/1 23      24      24      9      OFF  RCP UNDERFREQUENCY                   2/4 23    24        24    10      OFF  RCP UNDERFREQUENCY                   1/2 23    24        24    11      OFF  RCP UNDERFREQUENCY                   1/2 23    24        24    12      OFF  RCP UNDERFREQUENCY                   2/4 23    24        24    13      OFF  POWER RANGE, HI FLUX RATE TRIP       2/4
OFF 23 24 24 9
OFF 23 24 24 10 OFF 23 24 24 11 OFF 23 24 24 12 OFF 23 24 24 13 OFF NUMBER -
lPD-18.1. 009 REV. NO.
1 DATE 5/27/82 PAGE 28 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC *& PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBI'I' NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED FEEDWATER CONTROL 1/2 FEEDWATER CONTROL 1/1 RCP UNDERFREQUENCY 2/4 RCP UNDERFREQUENCY 1/2 RCP UNDERFREQUENCY 1/2 RCP UNDERFREQUENCY 2/4 POWER RANGE, HI FLUX RATE TRIP 2/4  


SALE~ GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)
SALE~ GE.A TING ST A TION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE.
TEST PROCEDUHE.
* NUMBER -
NUMBER -
REV. NO.
REV. NO.
lPD-18 .1. 009 1
DATE lPD-18.1. 009 1
DATE          5/24/82 PAGE   29   OF   50
5/24/82 PAGE 29 OF 50  
"'IT(U:         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                             FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                    BLOCKS LOGIC   LOGIC   LOGIC LOGIC  MIS-        TEST                                              INHIBIT      NOT A       B       c     D     SIVE      FUNCTION                    REQUIRED    ACTUAL    BLOCKS INHIBITED 23     24     24     14     OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23      24      24    15    OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23      24      24    16    OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23      24      24    17    OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23      24. 24    18    OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION 23      24      24    19    OFF SAFETY INJECTION, PHASE A           1/1 ISOLATION
"'IT(U:
SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS LOGIC LOGIC LOGIC LOGIC A
B c
D 23 24 24 14 23 24 24 15 23 24 24 16 23 24 24 17 23
: 24.
24 18 23 24 24 19 TABLE I LOGIC & PERMISSIVES PER-MIS-TEST SIVE FUNCTION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION FUNCTION LOGIC REQUIRED ACTUAL 1/1 1/1 1/1 1/1 1/1 1/1 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GEN.TING STATION PERFORMANCE DEPARTMENT (I & C)
SALEM GEN.TING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PAOCEDUHE
TEST PAOCEDUHE TITLE SOI.ID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
* NUMBER -
c D
REV. NO.
SIVE 23 24 24 20 OFF 23 24 24 21 OFF 23 24 24 22 OFF 23 24 24 23 OFF 23 24 24 24 OFF 23 24 24 24 1
lPD-18 .1. 009 1
NUMBER -
DATE          5/24/82 PAGE   30   OF   50 TITLE        SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
lPD-18.1. 009 REV. NO.
                                                    . TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                              FUNCTION LOGIC          BLOCKING FUNCTION TEST SWITCH PER-                                                                      BLOCKS LOGIC   LOGIC    LOGIC  LOGIC  MIS-        TEpT                                             INHIBIT      NOT A      B        c      D    SIVE      FUNCTION                   REQUIRED     ACTUAL     BLOCKS INHIBITED 23    24      24    20    OFF  SAFETY INJECTION, PHASE A           1/1 ISOLATION 23    24      24    21
DATE 1
                                - OFF  SAFETY INJECTION, PHASE A           1/1 ISOLATION 23    24      24    22    OFF  SAFETY INJECTION, PHASE A*           1/1 ISOLATION 23    24      24    23    OFF  SAFETY INJECTION, PHASE A           1/1 ISOLATION 23    24      24    24    OFF  FEED THRU TO PERMISSIVES 23    24      24    24      1  P6                                   1/2
5/24/82 PAGE 30 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B  
. TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC TEpT FUNCTION REQUIRED ACTUAL SAFETY INJECTION, PHASE A 1/1 ISOLATION SAFETY INJECTION, PHASE A 1/1 ISOLATION SAFETY INJECTION, PHASE A*
1/1 ISOLATION SAFETY INJECTION, PHASE A 1/1 ISOLATION FEED THRU TO PERMISSIVES P6 1/2 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)'
SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)'
* NUMBER -
TEST PROCEDUHE
.*4'.:
-~---------------------------
NUMBER -
REV. NO.
REV. NO.
lPD-18 .1. 009 1
DATE PAGE lPD-18.1. 009 1
TEST PROCEDUHE                                                DATE          5/24/82-31         50
5/24/82-31 OF 50 TITLE SOLID STATE PROTECTION.SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS LOGIC LOGIC LOGIC LOGIC A
                                          .*4'.:
B c
PAGE
D 2_3 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 LOGIC PER-MIS-TEST SIVE FUNCTION 2
                                                                                        --- OF ---
P8 3
TITLE           SOLID STATE PROTECTION.SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS
PlO 4
* FUNCTION LOGIC          BLOCKING FUNCTION TEST SWITCH PER-                                                                          BLOCKS LOGIC   LOGIC   LOGIC LOGIC MIS-            TEST                                              INHIBIT      NOT A         B       c     D   SIVE          FUNCTION                    REQUIRED_ ACTUAL        BLOCKS INHIBITED 2_3     24     24     24     2  P8                                      2/4 23       24     24     24     3  PlO                                    2/4 23       24     24     24     4  P7                                    1/3 23       24     24     24     5  pg                                    2/4 !
P7 5
23       24     24     24     6  P12 23       24     24     24     7  P12                                    2/4 23       24     24     24     8   P12                                   2/4
pg 6
P12 7
P12 8
P12 TABLE I
& PERMISSIVES FUNCTION LOGIC REQUIRED_ ACTUAL 2/4 2/4 1/3 2/4 2/4 2/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED


J\
J\\
SALEM GE.ATING STATION PERFORUANCE DEPARTMENT (I & C)
SALEM GE.ATING STATION PERFORUANCE DEPARTMENT (I & C)
* NUMBER -
TEST PROCEDUHE
REV. NO. 1 lPD-18.1.009 TEST PROCEDUHE                                            DATE          5/24/82 PAGE    32   OF 50
'TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B
  'TITLE          SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS                                              FUNCTION LOGIC         BLOCKING FUNCTION TEST SWITCH PER-                                                                    BLOCKS LOGIC  LOGIC    LOGIC  LOGIC  MIS-        TEST                                              INHIBIT      NOT A        B      c      I)    SIVE      FUNCTION                    REQUIRED     ACTUAL   BLOCKS INHIBITED 23      24      24    24      9  Pll                                2/3   I I
c I)
23      24      24    24      10  P8 RCP BREAKERS                    1/4 23      24      24    24      11  P8 RCP BREAKERS                    1/4 OFF     24      24    24    OFF  OFF                                OFF
SIVE 23 24 24 24 9
 
23 24 24 24 10 23 24 24 24 11 OFF 24 24 24 OFF NUMBER -
*X SALEM GENERATING STATION                   NUMBER -   lPD-18 .1. 009 PERFORMANCE DEPARTMENT (I & C)              REV.NO. _l~~~~~~
REV. NO.
DATE     _5/,__24~/~8_2~~~~
DATE PAGE lPD-18.1.009 1
TEST PROCEDURE                                PAGE _3_3__ OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
5/24/82 32 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES TEST FUNCTION Pll P8 RCP BREAKERS P8 RCP BREAKERS OFF FUNCTION LOGIC REQUIRED ACTUAL 2/3 I
I 1/4 1/4 OFF BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED
* X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
lPD-18.1. 009 REV.NO.
_l~~~~~~
DATE
_5/,__24~/~8_2~~~~
PAGE _3_3 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                       Initial 8.16 Perform the following Memories Testing._
(Continued) 8.16 Perform the following Memories Testing._
Record results on TABLE II.
Record results on TABLE II.
8.16.l   Place MEMORIES switch to position "l".
8.16.l 8.16.2 8.16.3 8.16.4 Place MEMORIES switch to position "l".
(The 1/4 function logic lamp will light
(The 1/4 function logic lamp will light whenever the MEMORIES switch is not in the OFF position)..
* 8.16.2 whenever the MEMORIES switch is not in the OFF position) ..
In the MEMORY FUNCTION TEST portion of the LOGIC TEST PANEL, depress and. release the RED pushbutton and verify that the MEMORY SET lamp lights.
In the MEMORY FUNCTION TEST portion of the LOGIC TEST PANEL, depress and. release the RED pushbutton and verify that the MEMORY SET lamp lights.     (If already on, depress and release BLACK pushbutton).
(If already on, depress and release BLACK pushbutton).
8.16.3    After MEMORY SET lamp lights, depress and release BLACK pushbutton.
After MEMORY SET lamp lights, depress and release BLACK pushbutton.
8.16.4    Repeat Steps 8.16.2 and 8.16.3 for the positions of the MEMORIES switch as listed oh TABLE II .
Repeat Steps 8.16.2 and 8.16.3 for the positions of the MEMORIES switch as listed oh TABLE II.
I & C - 001
I & C - 001 Initial


SALEM GENERATING STATION                  NUMBER -     lPD-18 .1. 009 REV. NO. 1 PERFORMANCE DEPARTMENT (I & C)
NUMBER -
DATE        5/24/82 TEST PROCEDURE                               PAGE _3_4__ OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE 2 MEMORIES FUNCTION                                            FUNCTION      MEMORY      FUNCTION SELECTOR                                             LOGIC          TEST    PUSHBUTTON MEMORIES                   TEST FUNCTION                1/4          RED        BLACK OFF         OFF                                                    (ON OR OFF) 1       POWER RANGE BLOCK
REV. NO.
DATE lPD-18.1. 009 1
5/24/82 SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE PAGE _3_4 __ OF 50 TITLE FUNCTION SELECTOR MEMORIES OFF 1
* 2 3
* 2 3
INTERMEDIATE RANGE BLOCK SOURCE RANGE BLOCK 4        SOURCE RANGE BLOCK 5        SAFETY INJECTION BLOCK, PRESSURIZER 6        SAFETY INJECTION BLOCK, PRESSURIZER 7        SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LEVEL ,
4 5
8        SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LOGIC 9        AUTOMATIC SAFETY INJECTION BLOCK 10          FEEDWATER VALVE CONTROL
6 7
**11              FEEDWATER VALVE CONTROL OFF         OFF I & C - 001
8 9
10
**11 OFF I & C - 001 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TEST FUNCTION OFF POWER RANGE BLOCK TABLE 2 MEMORIES INTERMEDIATE RANGE BLOCK SOURCE RANGE BLOCK SOURCE RANGE BLOCK SAFETY INJECTION BLOCK, PRESSURIZER SAFETY INJECTION BLOCK, PRESSURIZER SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LEVEL,
SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LOGIC AUTOMATIC SAFETY INJECTION BLOCK FEEDWATER VALVE CONTROL FEEDWATER VALVE CONTROL OFF FUNCTION LOGIC 1/4 MEMORY TEST RED FUNCTION PUSHBUTTON BLACK (ON OR OFF)


    .~
.~  
SALEM GENERATING STATION                                                                                         NUMBER -                     lPD-18 .1. 009 REV.NO.                   _l_ _ _ _ _ __
".i.
PERFORMANCE DEPARTMENT&deg; (I & C)
1 a. r nn1 SALEM GENERATING STATION PERFORMANCE DEPARTMENT&deg; (I & C)
DATE                         5/24/82
TEST PROCEDURE NUMBER -
                                                                                                                                                              -----'----~---
lPD-18.1. 009 REV.NO.
TEST PROCEDURE 35               50 PAGE
_l ______ _
                                                                                                                                                                      ---          OF TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE 5/24/82  
-----'----~---
PAGE 35 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                                                                                                 Initial 8.17 Perform the following for Output Relay Testing and Record'results on TABLE III.
(Continued)
8.17.1         Place the MASTER RELAY SELECTOR in Position "l".
Initial 8.17 Perform the following for Output Relay Testing and Record'results on TABLE III.
8.17.2        Depress SLAVE TEST A pushbutton and verify that the required "A" lamps lights while pushbutton is depressed.                                                                             Verify the required lamps light by placing an "X" under each on*requirement.
8.17.1 8.17.2 8.17.3 8.17.4 c..*
8.17.3        Repeat Step 8.17.2 for SLAVE TEST B.
~*
8.17.4        Repeat Steps 8.17.2 and 8.17.3 for each MASTER RELAY SELECTOR position listed on TABLE III.
('. \\ \\.
c..*    -
~
( ' . \ \.
Place the MASTER RELAY SELECTOR in Position "l".
                                          ~*
Depress SLAVE TEST A pushbutton and verify that the required "A" lamps lights while pushbutton is depressed.
                                            ~
Verify the required lamps light by placing an "X" under each on*requirement.
                                              \-z:..:.   .......... -1...*.i '--
Repeat Step 8.17.2 for SLAVE TEST B.
                                                                                .      (I
Repeat Steps 8.17.2 and 8.17.3 for each MASTER RELAY SELECTOR position listed on TABLE III.
                                                                                          ~
(I H
H            .
'II
                                                                                                                      \::""l...
\\-z:..:........... -1...*.i '--
                                                                                                                                'II
~  
                                                                                                                                    ** ....      ~ <"
\\::""l...  
i ..
~ <"
                                              \                                                         "'"'"~         ~*J           -  ......"'\_.,.       ,~,.,,,       S:\v:.....* *~
i...  
                                                '~~ \....                       \.:>f'; ,..; ;...\... *     \j"~,...~ \,:''\             \&deg;")*~t:. <!..       C'\~
\\
c     ~               V---~*C.       \   ~       &#xa5;..i.vc i_ ., -~\:!C<'3;                       \I... "-.:*<.*l\ ~ \t. 1<:C 'C. \
"'"'"~  
                                                    \<... lcC:~                     . \.;.. \..:: '.C       -~~-Q..
~*J  
                                                                                      \
...... "'\\_.,.  
                                                  -.,                                        .. ,,                '.'\
,~,.,,,  
".i.                                            ''~\'\""c.c....                             "A         ~(...
'~~ \\....  
                                                  ~~ .;* \-                     (-'1- *" . :. \. ._
\\.:>f';,..; ;...\\... *  
* 1 a. r _ nn1
\\j"~,...~ \\,:''\\
\\&deg;")*~t:. <!..
C'\\~
c ~
V---~*C. \\ ~  
&#xa5;..i.vc i_.,  
-~\\:!C<'3;  
\\I... "-.:*<.*l\\ ~  
\\<... lcC:~.  
\\.;.. \\..:: '.C  
-~~-Q..  
\\  
'.'\\  
''~\\'\\""c.c.... "A  
~(...  
~~.;* \\-
(-'1- *"..:. \\... _
* S:\\v:..... * *~
\\t. 1<:C 'C. \\


SALEM G.ATING STATION PERFORMANCE DEPARTMENT (I & C)
SALEM G.ATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDUHE
TEST PROCEDUHE NUMBER -
* NUMBER -
lPD-18.1. 009 REV. NO.
REV. NO.
1 DATE 5/24/82 PAGE 36 OF 50 TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B MASTER RELAY SELECTOR 1
lPD-18 .1. 009 1
2 3
DATE         5/24/82 PAGE   36   OF 50 TITLE         SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE III LOGIC & PERMISSIVES MASTER RELAY                                                                 SLAVE RELAY CONTINUITY LAMPS SELECTOR              SLAVE RELAY FUNCTION          Al    A2    A3     A4     Bl     B2   B3 B4 1      CONTAINMENT ISOLATION, PHASE A            ON   ON    ON    OFF     ON     ON   ON  OFF 2      CONTAINMENT VENTILATION ISOLATION        ON   OFF   OFF   OFF     ON     *oFF   OFF OFF 3      STEAM STOP VALVES                        ON    OFF   OFF   OFF    ON     O;F'F OFF OFF 4      SPRAY ACTUATION                          ON    OFF   OFF   OFF    ON     ON   OFF OFF 5      CONTAINMENT ISOLATION, PHASE B            ON    ON    OFF   OFF     ON     ON   OFF OFF 6      FEEDWATER VALVES (HI-HI STEAM            ON    OFF   OFF   OFF     OFF    pFF   OFF OFF GENERATOR LEVEL) 7      TRIP TURBINE/MAIN FEEDWATER PUMPS        ON    OFF    OFF   OFF     OFF     OFF   OFF OFF
4 5
6 7
TABLE III LOGIC & PERMISSIVES SLAVE RELAY FUNCTION CONTAINMENT ISOLATION, PHASE A CONTAINMENT VENTILATION ISOLATION STEAM STOP VALVES SPRAY ACTUATION CONTAINMENT ISOLATION, PHASE B FEEDWATER VALVES (HI-HI STEAM GENERATOR LEVEL)
TRIP TURBINE/MAIN FEEDWATER PUMPS Al ON ON ON ON ON ON ON A2 ON OFF OFF OFF ON OFF OFF SLAVE RELAY CONTINUITY LAMPS A3 A4 Bl B2 B3 B4 ON OFF ON ON ON OFF OFF OFF ON  
*oFF OFF OFF OFF OFF ON O;F'F OFF OFF OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF pFF OFF OFF OFF OFF OFF OFF OFF OFF  


SALEM GE.TING STATION PERF0Rf.1ANCE DEPARTMENT (I & C)
SALEM GE.TING STATION PERF0Rf.1ANCE DEPARTMENT (I & C)
TEST PROCEDUHE
TEST PROCEDUHE NUMBER -
* NUMBER -
REV. NO.
REV. NO.
lPD-18 .1. 009 1
DATE lPD-18.1. 009 1
5/24/82 DATE PAGE   37   OF 50 TITLE         SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE III LOGIC & PERMISSIVES MASTER RELAY                                                              SLAVE RELAY CONTINUITY LAMPS SELECTOR          SLAVE RELAY FUNCTION             Al   A2     A3    A4      Bl    B2  B3  B4 8      RCP UNDERFREQUENCY                     ON   OFF   OFF   OFF     OFF   OFF OFF OFF 9      SPARE                                  ON   OFF   OFF   OFF     OFF   OFF OFF OFF 10        (NOT USED)                              OFF   OFF   OFF   OFF     OFF   OFF OFF OFF 11        (NOT USED)                              OFF   OFF   OFF   OFF     OFF   OFF OFF OFF 12        LO-LO TAVG STEAM DUMP INTERLOCK        ON    OFF   OFF   OFF     OFF   OFF OFF OFF 13        LOSS OF POWER/TURBINE AUXILIARY PUMP    ON    OFF   OFF   OFF     OFF   OFF. OFF OFF 14        LOW WATER LEVEL/MOTOR AUXILIARY PUMP    ON    OFF   OFF   OFF     OFF   OFF OFF OFF 15        LOW WATER LEVEL/TURBINE AUXILIARY PUMP  ON    OFF   OFF   OFF     OFF   OFF OFF OFF
5/24/82 PAGE 37 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B MASTER RELAY SELECTOR 8
9 10 11 12 13 14 15 TABLE III LOGIC & PERMISSIVES SLAVE RELAY FUNCTION Al A2 RCP UNDERFREQUENCY ON OFF SPARE ON OFF (NOT USED)
OFF OFF (NOT USED)
OFF OFF LO-LO TAVG STEAM DUMP INTERLOCK ON OFF LOSS OF POWER/TURBINE AUXILIARY PUMP ON OFF LOW WATER LEVEL/MOTOR AUXILIARY PUMP ON OFF LOW WATER LEVEL/TURBINE AUXILIARY PUMP ON OFF SLAVE RELAY CONTINUITY LAMPS A3 A4 Bl B2 B3 B4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF.
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF  


,/\
,/\\
SALEM GE.A TING STATION                                           NUMBER -     lPD-18 .1. 009 PERF0Rf..1ANCE DEPARTMENT (I & C)                                 REV. NO.     1 TEST PAOCEDUUE DATE           5/24/82 PAGE   38   OF   50 TITLE         SOI, ID STATE PROTECTION SYSTEM FUNCTION~L TEST TRAIN B TABLE III LOGIC & PERMISSIVES MASTER RELAY                                                                 SLAVE RELAY CONTINUITY LAMPS SELECTOR           SLAVE RELAY FUNCTION               Al   A2     A3     A4. Bl     B2   B3   B4 16       GENERATOR TRIP & .STEAM DUMP INTERLOCK     ON   OFF   OFF     OFF     OFF   OFF OFF OFF 17       TAVG AND REACTOR TRIPPED                   ON   OFP   OFF     OFF     ON   OFF OFF OFF 18       SAFETY INJECTION .                         ON   ON     ON     ON     ON     ON   ON   ON 19         (NOT USED)                               OFF   OFF   OFF     OFF     OFF   OFF OFF OFF 20         (NOT USED)                               OFF   OFF   OFF     OFF     OFF   OFF OFF OFF 21         (NOT USED)                               OFF   OFF   OFF     OFF     OFF   OFF OFF OFF 22         (NOT USED)                               OFF   OFF   OFF     OFF     OFF   OFF OFF OFF 23         (NOT USED)                               OFF   OFF   OFF     OFF     OFF   OFF OFF OFF OFF       OFF                                       OFF   OFF   OFF     OFF     OFF   OFF OFF OFF
SALEM GE.A TING STATION NUMBER -
lPD-18.1. 009 PERF0Rf..1ANCE DEPARTMENT (I & C)
REV. NO.
1 TEST PAOCEDUUE DATE 5/24/82 PAGE 38 OF 50 TITLE SOI, ID STATE PROTECTION SYSTEM FUNCTION~L TEST TRAIN B TABLE III LOGIC & PERMISSIVES MASTER RELAY SLAVE RELAY CONTINUITY LAMPS SELECTOR SLAVE RELAY FUNCTION Al A2 A3 A4.
Bl B2 B3 B4 16 GENERATOR TRIP &.STEAM DUMP INTERLOCK ON OFF OFF OFF OFF OFF OFF OFF 17 TAVG AND REACTOR TRIPPED ON OFP OFF OFF ON OFF OFF OFF 18 SAFETY INJECTION.
ON ON ON ON ON ON ON ON 19 (NOT USED)
OFF OFF OFF OFF OFF OFF OFF OFF 20 (NOT USED)
OFF OFF OFF OFF OFF OFF OFF OFF 21 (NOT USED)
OFF OFF OFF OFF OFF OFF OFF OFF 22 (NOT USED)
OFF OFF OFF OFF OFF OFF OFF OFF 23 (NOT USED)
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF  


SALEM GENERATING STATION                     NUMBER -       lPD-18 .1. 009 REV. NO.      1 PERFORMANCE DEPARTMENT (I & C)
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
DATE          5/24/82 TEST PROCEDURE                                  PAGE     39 OF SO SOLID STATE PROTECTION SYSTEM FUNCTIONAL T.EST TRAIN B TITLE
TEST PROCEDURE NUMBER -
REV. NO.
DATE lPD-18.1. 009 1
5/24/82 PAGE 39 OF SO TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL T.EST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                         Initial 8.18 Place the MULTIPLEXER TEST switch to Normal.
(Continued) 8.18 Place the MULTIPLEXER TEST switch to Normal.
8.19 Replace (if required) the field lead to TB-506-2 lifted ~n Step 8.14.
8.19 Replace (if required) the field lead to TB-506-2 lifted ~n Step 8.14.
8.20 Inform the Control Operator that a containment ventilation isolation will be initiated if a high radiation alarm is present when this procedure is completed.       Inform him that -he may reset the containment ventilation isolation at this time.
8.20 Inform the Control Operator that a containment ventilation isolation will be initiated if a high radiation alarm is present when this procedure is completed.
8.21 Manual Input Function Test
Inform him that -he may reset the containment ventilation isolation at this time.
                                      -NOTE-   8.~\.\)   8.ai.\.&deg;t Omit steps 8.21.4, 8.21.5, 8.21.14, 8.21.16 6'.,l.\,\0 and &.21.19 if Reactor is Tripped Tripped                      Operational 8.21.1   Have the Control Operator rack in and close Reactor By-pass Breaker B, and verify that the breaker is in Operate position and its light is illuminated .
8.21 Manual Input Function Test  
-NOTE-8.~\\.\\) 8.ai.\\.&deg;t Omit steps 8.21.4, 8.21.5, 8.21.14, 8.21.16 6'.,l.\\,\\0 and &.21.19 if Reactor is Tripped 8.21.1 Tripped Operational Have the Control Operator rack in and close Reactor By-pass Breaker B, and verify that the breaker is in Operate position and its light is illuminated.
I & C
* 001 Initial


**          SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
TEST PROCEDURE NUMBER -
REV. NO.
REV. NO.
DATE PAGE lP D-18 . 1. 0 0 9 5/24/82 40     OF     50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE lP D-18. 1. 0 0 9 5/24/82 PAGE 40 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                           Initial
(Continued)  
                                            *-WARNING-Reactor By-pass Breaker B must remain energized for the duration of the manual testing, otherwise a Reactor Trip will occur *
*-WARNING-Reactor By-pass Breaker B must remain energized for the duration of the manual testing, otherwise a Reactor Trip will occur
* 8.21.2     At the LOGIC TEST Panel place the LOGIC A Test Switch in Position 7.
* 8.21.2 8.21.3
High Pressure Trip).
: 8. 21. 4
(Pressurizer 8.21.3      In the MANUAL INPUT FUNCTION TEST portion of the LOGIC TEST PANEL, depress and hold any TWO pushbuttons.
: 8. 21. 5 8.21.6 At the LOGIC TEST Panel place the LOGIC A Test Switch in Position 7.
: 8. 21. 4    At the Control Board, verify that Reactor Trip Break~r   B is OPEN.
(Pressurizer High Pressure Trip).
: 8. 21. 5    Verify the UV COIL VOLTAGE meter indicates approximately 0 VDC.
In the MANUAL INPUT FUNCTION TEST portion of the LOGIC TEST PANEL, depress and hold any TWO pushbuttons.
8.21.6      Release the pushbuttons depressed in Step 8.21.3 .
At the Control Board, verify that Reactor Trip Break~r B is OPEN.
I & C - 001
Verify the UV COIL VOLTAGE meter indicates approximately 0 VDC.
Release the pushbuttons depressed in Step 8.21.3.
I & C - 001 Initial


'x
'x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
* SALEM GENERATING STATION                   NUMBER -     lPD-18 .1. 009 PERFORMANCE DEPARTMENT (I & C)            REV. NO.   -*--=l=--------
TEST PROCEDURE NUMBER -
DATE         5/24/82 TEST PROCEDURE PAGE   41   OF   50 TITLE     . SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
lPD-18.1. 009 REV. NO.  
-*--=l=--------
DATE 5/24/82 PAGE 41 OF 50 TITLE  
. SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                     Initial
(Continued)
: 8. 21. 7 Place the LOGIC A Test Switch in the OFF position.
: 8. 21. 7
: 8. 21. 8  Have the Control Opeator close the Reactor Trip Breaker B .
: 8. 21. 8 8.21.9 8.21.10 8.21.11 Place the LOGIC A Test Switch in the OFF position.
**                        8.21.9    Have the Control Operator OPEN Reactor By-Pass Breaker B.
Have the Control Opeator close the Reactor Trip Breaker B.
8.21.10  Have the Control Operator rack Out Reactor By-Pass Breaker B.
Have the Control Operator OPEN Reactor By-Pass Breaker B.
8.21.11  Verify that the general warning test LED for SSPS Train B is extinguished in both Train A and Train B .
Have the Control Operator rack Out Reactor By-Pass Breaker B.
* I I & C
Verify that the general warning test LED for SSPS Train B is extinguished in both Train A and Train B.
* 001
I I & C
* 001 Initial


. )<
. )<
* SALEM GENERATING STATION                   NUMBER -   lPD-18 .1. 009 REV.NO. _l_ _ _ _ _ _~
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
DATE       5/24/82 TEST PROCEDURE PAGE
lPD-18.1. 009 REV.NO.
                                                                      - OF 50 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
_l ______ ~
DATE 5/24/82 PAGE 42 OF 50 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                     Initial 8.22 Perform the following for SAFETY INJECTION RESET TIMING TEST.
(Continued) 8.22 Perform the following for SAFETY INJECTION RESET TIMING TEST.
8.22.1     Select position 9 on the MEMORIES switch and if the MEMORY SET lamp is illuminated, depress the BLACK button to extinguish it .
8.22.1 8.22.2 8.22.3 Select position 9 on the MEMORIES switch and if the MEMORY SET lamp is illuminated, depress the BLACK button to extinguish it.
8.22.2    In the OUTPUT TEST cabinet, place test switch 602 in the BLOCK   OUT~UT position.
In the OUTPUT TEST cabinet, place test switch 602 in the BLOCK OUT~UT position.
8.22.3    Connect the Digital Voltmeter as follows:
Connect the Digital Voltmeter as follows:
8.22.3Al
8.22.3Al
* TD-1, Terminal 6 (+)
* TD-1, Terminal 6 (+)
8.22.3.2   Logic Ground (GND) 8.-22.4   The DVM should read approximately +48 VDC.
8.22.3.2 Logic Ground (GND) 8.-22.4 8.22.5 8.22.6 The DVM should read approximately +48 VDC.
8.22.5    Move the positive lead of the DVM from TD-1, Terminal 6 to TD-1, Terminal 2.
Move the positive lead of the DVM from TD-1, Terminal 6 to TD-1, Terminal 2.
8.22.6    The DVM should indicate 0 VDC.
The DVM should indicate 0 VDC.
I & C - 001
I & C - 001 Initial


.x SALEM GENERATING STATION                     NUMBER -     lPD-18 .1. 009 REV.NO. _l_ _ _ _ _ __
.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
DATE         5/24/82 TEST PROCEDURE PAGE   43   OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
lPD-18.1. 009 REV.NO.
_l ______ _
DATE 5/24/82 PAGE 43 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                     Initial 8.22.7     Latch-up Relay K602 by depressing the latch plunger and time the interval from this point until the voltmeter reads approximately *+48 VDC.   (The time should be 60 to 65 sec.)
(Continued) 8.22.7 8.22.8 Latch-up Relay K602 by depressing the latch plunger and time the interval from this point until the voltmeter reads approximately *+48 VDC.
                                    - - - - -sec.
(The time should be 60 to 65 sec.)
* 8.22.8      At the Control Board depress the S.I.
sec.
At the Control Board depress the S.I.
Block/Reset pushbutton and verify the following:
Block/Reset pushbutton and verify the following:
8.22.8.1   DVM indicates 0 VDC 8.22.8.2   MEMORY SET lamp lights 8.22.8.3   Relay K602 Resets 8.22.9     Return the MEMORIES switch to the OFF position.
8.22.8.1 DVM indicates 0 VDC 8.22.8.2 MEMORY SET lamp lights 8.22.8.3 Relay K602 Resets 8.22.9 8.22.10 Return the MEMORIES switch to the OFF position.
8.22.10    Connect the Digital Voltmeter as follows:
Connect the Digital Voltmeter as follows:
8.22.10.l TD-1, Terminal 6 (+)
8.22.10.l TD-1, Terminal 6 (+)  
**                        - 8.22.10.2 IDgic Ground (GND) 8.22.11     The DVM .should read approximately +48 VDC.
- 8.22.10.2 IDgic Ground (GND) 8.22.11 The DVM.should read approximately +48 VDC.
I & C - 001
I & C - 001 Initial
* SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
 
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER_
TEST PROCEDURE NUMBER_
REV.NO.
lPD-18.1. 009 REV.NO.
DATE PAGE lPD-18 .1. 009
~l~~~~~~~
                                                          ~l~~~~~~~
DATE 5/24/82 PAGE 44 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  
5/24/82
                                                              - OF 50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                       Initial 8.22.12     Move the positive lead of the DVM to TD-1 Terminal 2 and measure the resistance to gr_ound (GND) . The DVM should indicate an Open.
(Continued) 8.22.12 8.22.13 Move the positive lead of the DVM to TD-1 Terminal 2 and measure the resistance to gr_ound (GND).
* 8.22.13    Connect the Digital Voltmeter (AC Scale) as follows:
The DVM should indicate an Open.
8.22.13.l TD-1, Terminal 1 8.22.13.2 TD-1, Terminal 5 8.22.14   The.DVM* should read 0 VAC.
Connect the Digital Voltmeter (AC Scale) as follows:
NOTE:      A DVM indication of 25 VAC or less is considered noise.
8.22.13.l TD-1, Terminal 1 8.22.13.2 TD-1, Terminal 5 8.22.14 NOTE:
8.22.15    Measure the resi.stance between* TD-1, Terminal 1 and TD-1, Terminal 5.       The DVM should indicate an OPEN.
8.22.15 The.DVM* should read 0 VAC.
8.22.16   In the output test cabinet, return the test
A DVM indication of 25 VAC or less is considered noise.
**                        switch 602 to the UNBLOCK   outp~t   position and verify the TL/TXC Alarm light extinguishes.
Measure the resi.stance between* TD-1, Terminal 1 and TD-1, Terminal 5.
The DVM should indicate an OPEN.
Initial 8.22.16 In the output test cabinet, return the test switch 602 to the UNBLOCK outp~t position and verify the TL/TXC Alarm light extinguishes.  


. }(
. }(
SALEM GENERATING STATION .                                                   NUMBER -             lPD-18 .1. 009 REV. NO.              1 PERFORMANCE DEPARTMENT (I & C)
SALEM GENERATING STATION.
DATE                  5/24/82 TEST PROCEDURE PAGE       45       OF       50 TITLE *~~-S~O.:..=L~I~D-*~s~TA_..:.TE:::._P~R-O_T_E~C~T.:.:..;_IO~N:..:..._S~Y.:.:..;_S_TE_M~F-U_N_C_T~IO_N_A_L~T~E~S-T~T-RA~I-N_B~
PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
REV. NO.
DATE lPD-18.1. 009 1
5/24/82 PAGE 45 OF 50 TITLE *~~-S~O.:..=L~I~D-*~s~TA_..:.TE:::._P~R-O_T_E~C~T.:.:..;_IO~N:..:..._S~Y.:.:..;_S_TE_M~F-U_N_C_T~IO_N_A_L~T~E~S-T~T-RA~I-N_B~  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                                                 Initial 8.22.17             Have the Control Operator reinstate the FLUX TRIP MANUAL Blocks from the Control
(Continued) 8.22.17 Have the Control Operator reinstate the FLUX TRIP MANUAL Blocks from the Control  
                                                . Board.
. Board.
NOTE:               The pushbutton must be pushed even when BEZEL block light is lit.                               (ND block~ can
NOTE:
* be applied if their permissives are not present, therefore, only those permitted will be set.)
The pushbutton must be pushed even when BEZEL block light is lit.
8.22.17.1 Block Source Range-Train B                                       pu~hed 8.22.17.2 Block Intermediate Range-Train B pushed.
(ND block~ can be applied if their permissives are not present, therefore, only those permitted will be set.)
8.22.17.3 Block Power Range - Train B pushed.
8.22.17.1 Block Source Range-Train B pu~hed 8.22.17.2 Block Intermediate Range-Train B pushed.
WARNING:             The Flux Trip Manual Blocks. must*be reinstated prior to placing the input error inhibit switch in the normal position.
8.22.17.3 Block Power Range -
8.22.18             Place the Input Error Inhibit Switch in the NORMAL position
Train B pushed.
* I & C -001
WARNING:
The Flux Trip Manual Blocks. must*be reinstated prior to placing the input error inhibit switch in the normal position.
8.22.18 Place the Input Error Inhibit Switch in the NORMAL position
* I & C -001 Initial


. 'X SALEM GENERATING STATION                                                                                 NUMBER -     lPD-18.1.009 REV. NO.      1 PERFORMANCE DEPARTMENT (I & C)
. 'X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
DATE          5/24/82 TEST PROCEDURE PAGE   46   OF 50 TITLE                                     SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
TEST PROCEDURE NUMBER -
REV. NO.
DATE lPD-18.1.009 1
5/24/82 PAGE 46 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                 Initial 8.23 Perform the following for Spray Actuation Test.
(Continued) 8.23 Perform the following for Spray Actuation Test.
8.23.1                       Depreas Spray Test pushbutton for each of the individual channels and verify proper indication at the Control Board .
8.23.1 Depreas Spray Test pushbutton for each of the individual channels and verify proper indication at the Control Board.
* 8.23;1.l                   Channel I Containment Pressure Hi-Hi       I
8.23;1.l Channel I Containment Pressure Hi-Hi I
: 8. 23 .1. 2               Channel II Containment Pressure Hi-Hi       II 8.23.1.3                   Channel III Containment Pressure Hi-Hi       III 8.23.1.4                   Channel IV Containment Pressure "Hi-Hi.       IV 8.23.2                        Place input ERROR INHIBIT Switch in the
: 8. 23.1. 2 Channel II Containment Pressure Hi-Hi II 8.23.1.3 Channel III Containment Pressure Hi-Hi III 8.23.1.4 Channel IV Containment Pressure 8.23.2 8.23.3 "Hi-Hi.
* 8.23.3 INHIBIT position.
IV Place input ERROR INHIBIT Switch in the INHIBIT position.
Place the MODE Selector switch in the OPERATE position.
Place the MODE Selector switch in the OPERATE position.
I Iii c j 001
I Iii c j 001  
  * ****- **) *,o**~**-*'<**"*O.-.~: *.-*o*.-, ... ._.,.~-.-.-..*-*,-*.*.-*o*r-Y-~*-- *-~*** --~*--**-*-'*"*'*- * --**** .**
**) *,o**~**-*'<**"*O.-.~: *.-*o*.-,...._.,.~-.-.-..*-*,-*.*.-*o*r-Y-~*-- *-~***  
--~*--**-*-'*"*'*- * --****.**
Initial


  ~
~  
. x' SALEM GENERATING STATION                                                                                                                       NUMBER -      lPD-18 .1. 009 PERFORMANCE DEPARTMENT (I & C)                                                                                                                 REV. NO.     1 DATE          5/24/82 TEST PROCEDURE PAGE   47   OF   50 TITLE                                                 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
. x' I & C -001 SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
REV. NO.
DATE lPD-18.1. 009 1
5/24/82 PAGE 47 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                                                             Initial 8.23.4                       Actuate"the following MANUAL BLOCKS using the pushbuttons on the Control Board.                                               No blocks can be applied if their permissives are not present; therefore, only those per-rni tted will be set.
(Continued) 8.23.4 Actuate"the following MANUAL BLOCKS using the pushbuttons on the Control Board.
8.23.4.1                   Pressurizer Safety Injection .
No blocks can be applied if their permissives are not present; therefore, only those per-rni tted will be set.
* 8.23.4.2                   Steamline Pressure Safety Injection.
8.23.4.1 Pressurizer Safety Injection.
Safeguard actions which are being blocked by
8.23.4.2 Steamline Pressure Safety Injection.  
                                                                                                                                              -NOTE-virtue of having been Reset from the Control Bezels will be re-initiated *at this time if necessary logic signal is present.                                                       The safe-guard actions involved are:
-NOTE-Safeguard actions which are being blocked by virtue of having been Reset from the Control Bezels will be re-initiated *at this time if necessary logic signal is present.
: 1.           Containment Spray
The safe-guard actions involved are:
: 2.           Phase A Isolation
: 1.
: 3.           Phase B Isolation
Containment Spray
: 4.           Feedwater Isolation
: 2.
: 5.           Containment Ventilation Isolation from Safety Injection Signal.
Phase A Isolation
Inform the Control Operator of this condition .
: 3.
* Control Operator I & C -001
Phase B Isolation
  **...* --* ,.. *" ...... - **. - .... :::**._"!'. r-.-.- *-***""!--* ...... _._,._. *****---:-**--*-- -*~ - .........., .. - ,. -..... - -* . *- . . .. . ****- .*...
: 4.
* SALEM GENERATING STATION PERFORMANCE DEPARTMENT {I & C)
Feedwater Isolation
: 5.
Containment Ventilation Isolation from Safety Injection Signal.
Inform the Control Operator of this condition.
Control Operator  
**...* --*,.. *"...... - **. -.... :::**._"!'. r-.-.- *-***""!--*...... _._,._. *****---:-**--*-- -*~ -..........,.. -,. -..... - -*. *-..... ****-.*...
Initial
 
SALEM GENERATING STATION PERFORMANCE DEPARTMENT {I & C)
TEST PROCEDURE NUMBER -
TEST PROCEDURE NUMBER -
REV.NO.
lPD-18.1. 009 REV.NO.
DATE PAGE lPD-18 .1. 009
__;;l;;__~~~~~~
__;;l;;__~~~~~~
5/24/82 48   OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
DATE 5/24/82 PAGE 48 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  


==8.0 Instructions==
==8.0 Instructions==
(Continued)                                      Initial
*8.23.s 8.23.6 (Continued)
                        *8.23.s   Place the Input ERROR Inhibit switch in the NORMAL position.
Place the Input ERROR Inhibit switch in the NORMAL position.
8.23.6    Have the Control Operator reset all unwanted safeguards actions which were re-initiated as a iesult of this test *
Have the Control Operator reset all unwanted safeguards actions which were re-initiated as a iesult of this test
* 8.24 Perform the following for the Multiplexer checks.
* 8.24 Perform the following for the Multiplexer checks.
* WARNING:   It is necessary that SSPS Train A Mul tip],exer .
* WARNING:
Switch be in the normal position and that its general warning lamp be off. If the lamp is already on, it is necessary that it be cleared before the A & B position is selected in the
It is necessary that SSPS Train A Mul tip],exer.
                              *other train.
Switch be in the normal position and that its general warning lamp be off.
8.24.1     Place Train B Multiplexer Test Switch to the A & B position.
If the lamp is already on, it is necessary that it be cleared before the A & B position is selected in the  
8.24.2    Verify no intermittent condition exists.
*other train.
NOTE:      An intermittent (on/off) condition is when the indication appears at the control board and the computer at approximately one repetition per second. This indicates one of the two trains has a malfunction in its data multiplexing.
8.24.1 8.24.2 NOTE:
I & C - 001
Place Train B Multiplexer Test Switch to the A & B position.
Verify no intermittent condition exists.
An intermittent (on/off) condition is when the indication appears at the control board and the computer at approximately one repetition per second.
This indicates one of the two trains has a malfunction in its data multiplexing.
I & C - 001 Initial


                              -~-------
X*
X*
-~-------
SALEM GENERATING STATION                   NUMBER -   lPD-18 .1. 009 REV.NO. _l_ _ _ _ _ __
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE*
DATE.       5/24/82 TEST PROCEDURE*                              PAGE 49   OF   50 TITLE       SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
NUMBER -
                ~.*o Instructions: (Continued)                                     Initial 8.24.3   Place Train B Multiplexer Test Switch to the Normal position.
lPD-18.1. 009 REV.NO.
8.24.4    If the Shift Supervisor wants the Safety Injection block re-initiated for the train, short terminals 2 and 6 on TDl and have the Controls Operator depress S.I. Reset for Train B.
_l ______ _
Remove jumper:
DATE.
Initial Senior Shift Supervisor/Shift Supervisor 9.0 System Return to Normal:
5/24/82 PAGE 49 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B  
9.1 The Senior Shift Supervisor/Shift Supervisor has been notified that this channel has been returned to normal.
~.*o Instructions:
Senior Shift Supervisor/Shift Supervisor
(Continued) 8.24.3 8.24.4 Place Train B Multiplexer Test Switch to the Normal position.
* Date/Time 1 s. c - 001
If the Shift Supervisor wants the Safety Injection block re-initiated for the train, short terminals 2 and 6 on TDl and have the Controls Operator depress S.I. Reset for Train B.
Remove jumper: ----
Initial Senior Shift Supervisor/Shift Supervisor 9.0 System Return to Normal:
9.1 The Senior Shift Supervisor/Shift Supervisor has been notified that this channel has been returned to normal.
Senior Shift Supervisor/Shift Supervisor Date/Time 1 s. c -001 Initial


          ..~
~  
. x ,*
.. x,*
NUMBER -     lPD-18 .1. 009 SALEM GENERATING STATION REV.NO.   --"l~------
SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)
PERFORMANCE DEPARTMENT (I & C)
TEST PROCEDURE NUMBER -
DATE         5/24/82 TEST PROCEDURE                                                                                              PAGE   50   OF   50 TITLE                                 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
lPD-18.1. 009 REV.NO.  
: 10. 0 Remarks:                                                               w.o.                                 I.O .
--"l~------
DATE 5/24/82 PAGE 50 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B
: 10. 0 Remarks:
w.o.
I.O.
11.0 Completion:
11.0 Completion:
11.l Completed by:
11.l Completed by: --------
Technician           Date           Time
Technician Date Time 11.2 Approved by: --------
* 11.2 Approved by:
Supervisor Time Date I & C -001  
Supervisor         Date             Time I & C -001
......................,..-... -*.***-.-:.***-... --..................... --.-**~***... *-,,... -.......}}
                    ..................... .,..- ... -*.***-.-:.***- ... -- ..................... --.-**~*** ... *- ,, ... - ...... .}}

Latest revision as of 04:45, 6 January 2025

Rev 1 to Solid State Protection Sys Function Test-Train B
ML18087A736
Person / Time
Site: Salem  
Issue date: 08/02/1982
From:
Public Service Enterprise Group
To:
Shared Package
ML18087A720 List:
References
1PD-18.1.009, NUDOCS 8303160573
Download: ML18087A736 (52)


Text

  • .

NOTE: PRESS HARO YOU ARE MAKING FIVE (S) COPIES.

CHANGE TYPE:

ADMINISTRATIVE PROCEDURE 3 ON-THE-SPOT CHANGE 1\\71 PERMANENT D *TEMPORARY lC.J (GREEN)

(ORANGE)

  • EXPIRES:

ALL ON*THE*SPOT CHANGES TO BE CONSIDERED !="OR APPLICABILITY TO BOTH UNITS.

[ZJ UNIT I

~

UNITZ PROCECURENO. ___

\\~\\=>--.....\\J...._-_\\~B

  • ~'~*~O~L~~q--* ______ ___ REV. NO. __ \\ ___ CHANGE No._\\..__ __

PROCECURENO.~~c:9-.---..?n

....... ~-__.\\~B-'_*~\\-*___,OQ~-C\\_,_ ______ _

\\

REV. NO._--.. __ CHANGE NO._.;__ __

PROPOSED CHANGE:

<a.'d-,.\\.L\\, res.:1-,.s, e.~,.,1.1_,

ca.~\\.\\\\;i 1

A~~

B. ~'- \\ J

'8. d.. \\. C\\ )

CC>. d-L \\ u REASON FOR CHANGE:

ACTION TAKEN FOR OTHER UNIT:

°SP.W'Q..

~

AUTHORIZATION: ~

.;~
    • S ERViORIN CHARGE OR SHIFT SUPERVISOR

-SIGNATURE ALSO VERIFIES THAT APPLICABILITY TO ~OTH UNITS HAS BEEN CONSIDERED.

ACCEPTABLE:

POST CHANGE-REVIEW/APPROVAL I ~I D

() l!!clratt'-

~

D

.19K~THEAD c:~:I'"t:J"'.3 ~ ~

' SORC \\:HAIRMAN) l?tl I

~r~

MANAGER.* SALEM GENERATING STATION RETURN COMPLETED OR REJECTED FORM TO DEPARTMENT REQUESTING CHANGE.

FOLLOW*UP TO REJECTED ON-THE-SPOT CHANGE ACTION TAKEN:

' 8303160573 830314 PDR ADOCK 05000272 S

PDR.

PERFORMED BY:

SIGNATURE RETURN TO DEPARTMENT HEAD FOR ROUTING THROUGH POST CHANGE*REVIEW/APPROVAL CYCLE.

DATE B.~\\,\\'1

~

DATE

  • \\

PROCEDURE:

REMARKS:

REV 1

SALEM NUCLEAR GENERATING STATION PUBLIC SERVICE ELECTRIC & qAS COMPANY ELECTRIC GENERATION DEPARTMENT PROCEDURE APPROVAL COVER SHEET SAF~TY RELATED lPD-18.1.009 -

SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST -

TRAIN B REV. 1 - General Revision to incorporate On-The-Spot-Changes.

PERF. ENGR.

APPROVED SORC REVIEWED STA. SUPT.

APPROVED

'x SALEM GENERATING STATION NUMBER -

lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE REV. NO.

_l~------

DATE

_5~/~2~4~/~8~2 ______ _

PAGE 1 OF 50 TITLE 1.0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

Purpose:

l*.1 The purpose of this procedure is to verify the operability of Solid State Protection System Train B.

1.2 To satisfy the train surveillance requirement of the technical specifications

  • 2.0

References:

2ol Solid State Protection System Manual.

2.2 Wiring Diagrams:

203688, 2~2885, 224305

I

\\

  • ' x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

_1_* ------------~

DATE 5/24/82 PAGE 2 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

3.0 Precautions

3.1 Test conditions must be applied to only Train B.

A reactor trip will occur if both trains have a general warning condition.

Therefore, it is extremely important that the doors to only one train at a time are open, 3.2 to preclude the introduction of test conditions into both trainsc Test conditions may be applied to one train using its*

. built-in testers, while the opposite train is used to ma~ntain the plant protection and provide data to the demultiplexers.

If in the process of testing, mal-functions are detected, they can be isolated by care-fully following the procedures in Section 6 of the Solid State Protection Manual.

3.3 This procedure must be completed in the sequence given to insure successful completion *

,x SALEM GENERATING STATION NUMBER -

lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)

  • TEST PROCEDURE REV.NO.

1~~~~~~~

DATE 5/24/82


~--~-------

PAGE 3 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 4.0 Limitations and Actions:

4.1 If, at any time during the performance of this test, there is any reason to suspect that the test equipment being used may not be performing properly, a comparison check shall be performed with a similar device or the device shall be checked for calibration against a standardo This shall be done prior ~o taking any other corrective action.

4o2 If, during the performance of this test, the "As Found" data does not meet the requirements of the specified accuracy, the Job Supervisor shall be notified immediately

_ and PD-14.1.001 shall be performed.

4o3 If, during the performance of this procedure, the required status indication cannot be obtained, the Job Supervisor shall be notified immediately.

Exceptions*

to the required indication, due to plant conditions at the time of the test, may be made by the Job Supervisor.

Any exceptions of this nature must be indicated and explained in the Remarks section of this procedure.

4o4 An entry will be made in the Remarks section of this procedure indicating any deficiency and the corrective action taken.

\\.._.

  • X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV. NO.

....;;;..l ______ _

DATE

_S~/...:2;..;;4-'-/..;;.8=2 ___ _

PAGE _4 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 5.0 Test Equipment:

Device Name PD No.

Recal. Date Fluke (2)

Stop Watch

SALEM GENERATING STATION lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE 1

5/24/82 PAGE _s __ OF 50 TITLE 6.* 0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B Prerequisites:

6.1 The individual assigned to perform this procedure 6.2 is qualified to do so in accordance with Solid State Protection System Qualification Card 2.6.

Supervisor The Senior Shift Supervisor/Shift Supervisor has granted permission to perform this procedure.

Senior Shift Supervisor/Shift Supervisor Date/Time 603 The Control Operator is aware of all of the alarms and indications that will result from the performance of this procedure.

Control Operator

SALEM GENERATING STATION lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

1 DATE 5/24/82 PAGE 6

OF so TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B 7.0 System Line~up:

7.1 The following conditions must be established and/or verified by the Control Operator.

7.1.1 Reactor Trip Bypass Breaker A is open and in the Racked Out position.

Safeguard actions which are being blocked by virtue of having been *Reset from the Control Bezel will be re-initiated at the completion of this test if the necessary logic signal is present.

The Safeguard actions involved are:

1.

Containment Spray

2.

Phase A Isolation

3.

Phase B Isolation

4.

Feedwater Isolation s:.

Containment Ventilation Isolation from Safety Injection signal Control Operator

.x SALEM GENERATING STATION NUMBER -

lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE REV. NO.

---=l=--------

DATE 5/24/82 PAGE _7 __ OF 50 TITLE 8.0 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B Instructions:

8.1 Measure and record the following instrument Bus Voltages (Required 117 + 10 VAC).

8elel Bus #1 TB-110 -

11 & 12 VAC 8olo2 Bus #2 TB-210 -

11 & 12 VAC 8.1.3 Bus #3 TB-310 - 11 & 12 VAC 8.; 1. 4 Bus #4 TB-410 -

11 & 12 VAC 8.1.5 Bus #1 TB--654 -

2 & 12 VAC 8.2 Open the front doors of Train B Logic Bay and Train B Output Relay Bay.

8. 3--- On the Logic Tester Panel, verify and record the following Power Supply Voltages 8.3.1

+.4 8VDC #1 Required 4 8. 7 + 0. 2 VDC As Found As Left 8.3.2

+48VDC #2 Required 48.7 + 0.2 VDC As Found.

As Left

.x SALEM GENERATING STATION NUMBER -

lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE REV. NO.

  • l

~~~~~~~-

DATE 5/24/82 PAGE ---..8 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.3.3

+lSVDC #1 Required 15.7 + 0.2 VDC As Found As Left

+15VDC #2 Required l5o7 + 0.2 VDC As Found As Left 8.4 Verify the followi.ng Solid State Protection System General Warnings Lamps are Off o 8 0. 4.1 General Warning Lamp - Train A 8.4.2 General Warning Lamp - Train B 8.5 Depress the following General Warning Lamps and verify the Lamp Lights, and then remains OFF.

General Warning Lamp -

Train A 8.5.2 General Warning Lamp -

Train B Initial

.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

~l~~~~~~-

DATE

_5~/_2_4~/_8_2 ______ _

PAGE 9

OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.6 On the Logic Test Panel, following indicators will 8.6.1 Testing 8.6.2 Bad 8.6.3

. Good 8.6.4 Continuity 8.6.5 Memory Set 8.6.6 1/1 8.6.7 1/2 8.6.8 1/3 8.6.9 1/4 8.6.10 2/2 8.6.11 2/3 8.6.12 2/4 verify light that each of the by depressing it.

Initial

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

. lPD-18.1. 009 REV.NO.

~l~~~~~~-

DATE 5/24/82 PAGE 10 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.7 Record UV Coil Voltage Meter Reading.

Required 43 VDC + 2 VDC Initial

((w~:n, ~~hh~~~~~~( O \\~~.°.~:.~1 ~ ~.~~l~*:; <->.~. :~~*~:ni-\\~--:.,

t ~--~ L1<.- i 1~\\

\\ "'-"" *~ ~ '.:, t:..,_.

l:"<ffi c. *1-..

\\*;:i :H><.'-

1G t..ic ~, :** 1.-.. L.. *

/

On the Outpu~ Relay Test Panel, place the Mode Selector 8.8 Switch in the Test position.

8.9 Verify the Operate Lamp is not lighted.

8.10 Verify the General Warning Lamp is lighted~

8.11 Verify the operation of the Semi-Automatic Tester.

Self-check as follows:

-NOTE-Steps 8.11.6 through 8.11.11 will result in continuous alarms in the Control Room if there are any tripped inputs to the SSPS.

8.11.1 8.11.2 Verify that the continuity lamp is lighted.

On the Tester PC Card (AlOS), verify that the top four LED's (light emitting diodes) are lighted.

x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1.009 l

5/24/82 PAGE 11 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.11~3 8.11.4 8.11.7 Depress the test pushbutton.

Verify that the continuity lamp and the top four LEDS on Al08 extinguish.

Release the TEST pushbutton.

Verify that the continuity lamp and the top four LEDS on Al08 light.

On the Logic Test Panel, place the Input Error Inhibit switch to the Inhibit position.

Place the MULTIPLEXER TEST switch to the A & B position.

  • ~.

Place the BLOCKING FUNCTION TEST switch to the BLOCKS NOT INHIBITED position.

Depress and release the TEST pushbutton.

8.11.8.l Verify that the amber testing lamp lights.

8.11.8.2 In approximately 1.6 seconds, verify that this lamp extinguishes.

8.11.8.3 Verify that the GOOD lamp lights.

Initial

x SALEM GENERATING STATION NUMBER-lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE REV. NO.

DATE 1

5/24/82 PAGE

.;;;1~2 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.11.8.4 In approximately 1.6 seconds, verify that the good lamp extinguishes and repeatedly blinks on and off for these periods.

8.11.9 8.11.10 Place the BLOCKING FUNCTION TEST switch to the INHIBIT BLOCKS position.

~epress and release th~ Test pushbutton.

8.11.10.1 Verify that the AMBER TESTING lamp LIGHTS.

8.11.10.2 Verify that the red BAD lamp lights.

8.11.11 Place the MULTIPLEXER TEST switch to INHIBIT *.

8.12 Verify Reactor Trip Breaker B is CLOSED (if Reactor Trip Breaker is open have the Cont.rel Operator CLOSE Reactor Trip Breaker (B) 8.13 Verify the following High Radiation ALARM Lights on panel lRPl are OFF.

8.13.1 lR-llA Containment or Vent Particulate Initial

x SALEM GENERATING STATION NUMBER -

lPD-18.1. 009 PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE REV. NO.

-=-1 ______ _

DATE

~5~/~2~4~/~8=2~~~-

PAGE 13 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.13.2 8.13.3 1R-12A Containment or Vent Gas Effluent.

1R-12B Containment or Vent Gas Effluent (Iodine)

  • 8.14 If any high RADIATION ALARM is present in Steps 8.13e1 through 8.13. 3 lift the *field lead on terminal TB-506-2.

8.15 Perform the following for LOGIC and PERMISSIVE testing.

Record results on TABLE I.

WARNING:

If a malfunction within the logics is detected, the red BAD LAMP will come on at the instant of detection and

-remain on.

It is then necessary to refer to Section 6.3 of the Solid State Protection System Manual to troubleshoot and define the cause.

Verify the following switches are in *the positions indicated

  • 8.15.1.1 Logic A OFF 8.15.1.2 _Logic B 24 Initial

.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1.009 1

5/24/82 PAGE..;;;;l;..;;..4_ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued)

. I 8.15.1.3 Logic C 24 8.15.1.4 Logic D 24 8.15.l.6 Memories OFF 8.15.2 8.15.3 8.15.5 Place Logic A switch to position "l" and verify that Function Logic! Lamp 2/3 lights.

Depress and. release the TEST pushbutton.

The amber testing lamp will LIGHT.

After all combinations of logics are tested, the Amber TESTING Lamp should extinguish and

. ~

the Green GOOD Lamp should 1light.

The I

GOOD Lamp will extinguish ;*1he next tl.me the TEST pushbutton is dep;ressed..

Place the Blocking Functi~n Test Switch to the opposite position and r~peat Steps 8.15.2 and 8.15.3

  • Using Table I, perform Step 8.15.2 through 8.15.4 for the positions of the logic and permissive switches as listed.

Initial

SALEM GENE.ING ST A TION PERFORMANCE DEPARTMENT 0 & C)

TEST PROCEOUHE NUMBER_

lPD-18.1. 009 REV.NO.

l

~~~~------~

DATE 5/24/82 PAGE 15 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS PER-LOGI C LOGIC LOGIC LOGIC MIS-A B

C D

SIVE OFF 24 24 24 OFF 1

24 24 24 OFF 2

24 24 24 OFF 3

24 24 24 OFF 4

24 24 24 OFF 5

24 24 24 OFF 6

24 24 24 OFF TABLE I LOGIC & PERMISSIVES TEST FUNCTION OFF LOSS OF FLOW, LOSS OF FLOW, LOSS OF FLOW, LOSS OF FLOW, LOOP LOOP LOOP LOOP LOSS OF FLOW, RCP 1

2 3

4 PRESSURIZER, LOW PRESSURE FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/3 2/3 2/3 2/4 TRIP 2/4 BLOCKING FUNCTION.

TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED (GOOD OR BAD)

,/\\

SALEM GE.A TING ST A TION PEAFOAft.1ANCE DEPARTMENT (I & C)

TEST PAOCEDUBE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

c D

SIVE 7

24 24 24 OFF 8

24 24 24 OFF 9

24 24 24 OFF 10 24 24 24 OFF 11 24 24 24 OFF 12 24 24 24 OFF NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 16 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED

.l PRESSURIZER, HIGH PRESSURE TRIP 2/4 PRESSURIZER, HIGH WATER LEVEL 2/3 TRIP LOW FEEDWATER FLOW, LOO:P 1 1/2 LOW FEEDWATER FLOW, LOOP 1 1/2 LOW FEEDWATER FLOW, LOOP 2 1/2 LOW FEEDWATER FLOW, LOOP 2 1/2

SALEM GE.A TING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

c D

SIVE 13 24 24 24 OFF 14 24 24 24 OFF 15 24 24 24 OFF 16 24 24 24 OFF 17 24 24 24 OFF 18 24 24 24

.OFF

19.

24 24 24 OFF NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 17 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED LOW FEEDWATER FLOW, LOOP 3 1/2 LOW FEEDWATER FLOW, LOOP 3 1/2 LOW FEEDWATER FLOW, LOOP 4 1/2 LOW FEEDWATER FLOW, LOOP 4 1/2 OIL PRESSURE SWITCHES REACTOR 2/3 TRIP STOP VALVES GENERATOR TRIP 2/2 STOP VALVES GENERATOR TRIP 2/2

SA.LEM GE.TING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE

  • ~';..

NUMBER -

REV. NO.

DATE lPP-18.1. 009 1.*

5/24/82 PAGE 18 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B LOGIC A

20 21 22 23 23 23 23 TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS.

LOGIC LOGIC B

C 24 24 24 24 24 24 24 24 1

  • 24 2

24 3

24 PER-LOGIC

'MIS-TEST FUNCTION

. D SIVE 24 OFF STOP VALVES REACTOR TRIP 24 OFF SOURCE RANGE TR+P 24 OFF SOURCE RANGE TRIP 24 OFF FEED THRU TO LOGIC B 24 OFF INTERMEDIATE RANGE TRIP 24 OFF INTERMEDIATE RANGE TRIP 24 OFF POWER RANGE, LOW SETPOINT TRIP FUNCTION LOGIC REQUIRED ACTUAL 2/2 2/2 2/2 2/2 2/2 2/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM G.ATING ST A TION NUMBER -

lPD-18.1.009 PERFORMANCE DEPARTMENT (I & C)

TEST PAOCEDUHE REV. NO.

1 DATE TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS

  • PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

C D

SIVE TABLE I LOGIC & PERMISSIVES TEST.

FUNCTION 5/24/82 PAGE 19 OF FUNCTION LOGIC REQUIRED ACTUAL 23 4

24 24 OFF' POWER RANGE, HIGH SETPOINT TRIP 2/4 23 5

24 23 6

24 23 7

24 23 8

24 23 9

24 24

.OFF OVERTEMPERATURE DELTA T TRIP 24 OFF OVERPOWER DELTA T TRIP 24 OFF RCP UNDERVOLTAGE TRIP 24 OFF RCP UNDERVOLTAGE TRIP 24 OFF RCP UNDERVOLTAGE, TURB. FEED PUMP 2/4 2/4 2/4 1/2 1/2 50 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM GE.A TING ST A TION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUBE NUMBER_

lPD-18.1. 009 REV. NO.

1.

DATE 5/24/82 PAGE 20 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST.

A B

c b

SIVE FUNCTION REQUIRED ACTUAL 23 10 24 24 OFF RCP UNDERVOLTAGE, TURB. FEED 2/4 PUMP 23 11 24 24 OFF LOW STEAMLINE PRESSURE 2/4 23 12 24 24 OFF HIGH STEAMLINE FLOW, LOOP 1 1/2 23 13 24 24 OFF HIGH STEAMLINE FLOW, LOOP 2 1/2 23 14 24 24 OFF HIGH STEAMLINE FLOW, LOOP 3 1/2 23 15

  • 24 24 OFF HIGH STEAMLINE FLOW, LOOP 4 1/2 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

I\\

SALEM G.ATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDU'HE NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 21 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST T.RAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC.

PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST A

B c

D SIVE FUNCTION REQUIRED ACTUAL 23 16

~4 24 OFF STEAMLINE ISOLATION 2/4

~3 17 24 24 OFF HIGH.CONTAINMENT PRESSURE, 2/3 SAFETY INJECTION 23 18 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4.

SPRAY ACTUATION 23 19 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4 SPRAY ACTUATION 23 20 24 24 OFF HI-HI CONTAI'NMENT PRESSURE, 2/4 STEAM STOP VALVES BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PAOCEDUHE NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 22 OF 50 TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC.& PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC PER-LOGIC LOGIC LOGIC LOGIC MIS-TEST A

B c

D SIVE FUNCTION REQUIRED ACTUAL 23 21 24 24 OFF HI-HI CONTAINMENT PRESSURE, 2/4 PHASE B ISOLATION 23 22 24 24 OFF SAFETY INJECTION, PHASE A 1/1 ISOLATION 23 23 24 24 OFF SAFETY INJECTION, CONTAINMENT 1/2 VENTILATION ISOLATION 23 24 24 24 OFF FEED THRO TO LOGIC C 23 24 l

24 OFF STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 1 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED i

I\\

SALEM G.ATING ST A TION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE TITLE SOLID STATE PROTECT.ION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-:-

A B

c D

SIVE 23 24 2

24 OFF 23 24 3

24 OFF 23 24 4

24 OFF 23 24 5

24 OFF 23

24.

6 24 OFF 23 24 7

24 OFF NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 23 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBIT NOT FUNCTION REQUIRED ACTUAL BLOCKS.INHIBITED STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 2 STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 3 STEAMLINE DIFFERENTIAL 2/3 PRESSURE, LOOP 4 PRESSURIZER PRESSURE 2/3 PRESSURIZER PRESSURE 2/3 PRESSURIZER PRESSURE 2/3

SALEM GE.ATING STATION

  • PERFORMANCE DEPARTMENT (I & Cl TEST PAOCEDUHE NUMBER:-

REV. NO.

lPD-18.1.009 1

DATE TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS PER-LOGI C LOGIC LOGIC LOGIC MIS~

TEST FUNCTION A

B C

D S.IVE 23 24 8

24 23 24

.9 24 23 24 10 24 23 24 11 24 23 24 i2 24 OFF STEAM GENERATOR LO-LO WATER

.LEVEL LOOP 1 OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP. 2 OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP 3

~..

OFF STEAM GENERATOR LO-LO WATER LEVEL LOOP 4 OFF STEAM GENERATOR LO-LO WATER LEVEL TRIP 5/24/82 PAGE 24 OF 50 FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/3 2/3 2/3 1/4 BLOCKING FUNCTION TEST SWITCH

. BLOCKS INHIBIT NOT BLOCKS INHIBITED

S~LEM GaA TING ST A TION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE

\\, -

  • NUMBER-lPD-18.1.009 REV. NO.

1 DATE 5/24/82 PAGE 25 OF 50 TITLE SOLID.STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

c b

SIVE 23 24 13 24 OFF 23 24 14 24 OFF 23 24 15 24 OFF 23.

24 16 24 OFF 23 24 17 24 OFF TABLE I LOGIC & PERMISSIVES TEST FUNCTION STEAM GENERATOR LO-LO WATER LEVEL, MOTOR FEED PUMP

.STEAM GENERATOR *LO-LO WATER LEVEL, TURBINE FEED PUMP STEAM GENERATOR HI-HI LEVEL, GENERATOR 1 STEAM GENERATOR HI-HI LEVEL, GENERATOR 2 STEAM GENERATOR HI-HI LEVEL, GENERATOR 3 FUNCTION LOGIC REQUIRED ACTUAL 1/4 2/4 2/3 2/3 2/3 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM GU **

TING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PAOCEDUHE NUMBEA-AEV. NO.

lPD-18.1.009 1

DATE TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS PER-LOG IC LOGIC LOGIC LOGIC MIS-TEST FUNCTION A

B C

D SIVE 23 24 18 23 24 19 23 24 20 23 24 21 24 24 24 24 OFF STEAM GENERATOR HI-HI LEVEL, GENERATOR 4 OFF LOW TAVG OFF TAVG AND REACTOR TRIPPED OFF UV DIODES AND OUTPUT 5/24/82 PAGE 2(?

OF 50 FUNCTION LOGIC REQUIRED ACTUAL 2/3 2/4 2/2 1/4 23 24 22 24 OFF SAFETY INJECTION DIODES & OUTPUT 1/4 23 24 23 24 OFF UV DIODES AND OUTPUT 1/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

A SALEM GE.ATINGSTATION NUMBER -

lPD-18.1.009 PERFORMANCE DEPARTMENT 11 & C)

REV. NO.

1 TEST PAOCEDUHE DATE 5/24/82 PAGE 27 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES FUNCTION SELECTORS FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH PER-BLOCKS LOGIC LOGIC LOGIC LOGIC MIS-TEST INHIBIT NOT A

B c

D SIVE FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED 23 24 24

_* 24 OFF FEED THRU TO LOGIC D 23 24 24 1

OFF SAFETY INJECTION DIODES & OUTPUT 1/3 23 24 24 2

OFF UV DIODES AND OUTPUT 1/4 23 24 24 3

OFF UV DIODES AND OUTPUT 1/4 23 24 24 4

OFF UV DIODES AND OUTPUT 1/4 23 24 24 5

OFF UV DIODES AND OUTPUT 1/4 23 24 24 6

OFF UV DIODES AND OUTPUT 1/4

SALEM GEa TING STATION PERFORUANCE DEPARTMENT (I & C)

TEST PAOCEDUHE TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC. LOGIC LOGIC LOGIC MIS-A B

c D

SIVE 23 24 24 7

OFF 23 24 24 8

OFF 23 24 24 9

OFF 23 24 24 10 OFF 23 24 24 11 OFF 23 24 24 12 OFF 23 24 24 13 OFF NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/27/82 PAGE 28 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC *& PERMISSIVES FUNCTION LOGIC BLOCKING FUNCTION TEST SWITCH BLOCKS TEST INHIBI'I' NOT FUNCTION REQUIRED ACTUAL BLOCKS INHIBITED FEEDWATER CONTROL 1/2 FEEDWATER CONTROL 1/1 RCP UNDERFREQUENCY 2/4 RCP UNDERFREQUENCY 1/2 RCP UNDERFREQUENCY 1/2 RCP UNDERFREQUENCY 2/4 POWER RANGE, HI FLUX RATE TRIP 2/4

SALE~ GE.A TING ST A TION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE.

NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 PAGE 29 OF 50

"'IT(U:

SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS LOGIC LOGIC LOGIC LOGIC A

B c

D 23 24 24 14 23 24 24 15 23 24 24 16 23 24 24 17 23

24.

24 18 23 24 24 19 TABLE I LOGIC & PERMISSIVES PER-MIS-TEST SIVE FUNCTION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION OFF SAFETY INJECTION, PHASE A ISOLATION FUNCTION LOGIC REQUIRED ACTUAL 1/1 1/1 1/1 1/1 1/1 1/1 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM GEN.TING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PAOCEDUHE TITLE SOI.ID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

c D

SIVE 23 24 24 20 OFF 23 24 24 21 OFF 23 24 24 22 OFF 23 24 24 23 OFF 23 24 24 24 OFF 23 24 24 24 1

NUMBER -

lPD-18.1. 009 REV. NO.

DATE 1

5/24/82 PAGE 30 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B

. TABLE I LOGIC & PERMISSIVES FUNCTION LOGIC TEpT FUNCTION REQUIRED ACTUAL SAFETY INJECTION, PHASE A 1/1 ISOLATION SAFETY INJECTION, PHASE A 1/1 ISOLATION SAFETY INJECTION, PHASE A*

1/1 ISOLATION SAFETY INJECTION, PHASE A 1/1 ISOLATION FEED THRU TO PERMISSIVES P6 1/2 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

SALEM GE.ATING STATION PERFORMANCE DEPARTMENT (I & C)'

TEST PROCEDUHE

.*4'.:

-~---------------------------

NUMBER -

REV. NO.

DATE PAGE lPD-18.1. 009 1

5/24/82-31 OF 50 TITLE SOLID STATE PROTECTION.SYSTEM FUNCTIONAL TEST TRAIN B FUNCTION SELECTORS LOGIC LOGIC LOGIC LOGIC A

B c

D 2_3 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 23 24 24 24 LOGIC PER-MIS-TEST SIVE FUNCTION 2

P8 3

PlO 4

P7 5

pg 6

P12 7

P12 8

P12 TABLE I

& PERMISSIVES FUNCTION LOGIC REQUIRED_ ACTUAL 2/4 2/4 1/3 2/4 2/4 2/4 BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

J\\

SALEM GE.ATING STATION PERFORUANCE DEPARTMENT (I & C)

TEST PROCEDUHE

'TITLE SOLID STATE PROTECTION FUNCTION SELECTORS PER-LOGIC LOGIC LOGIC LOGIC MIS-A B

c I)

SIVE 23 24 24 24 9

23 24 24 24 10 23 24 24 24 11 OFF 24 24 24 OFF NUMBER -

REV. NO.

DATE PAGE lPD-18.1.009 1

5/24/82 32 OF 50 SYSTEM FUNCTIONAL TEST TRAIN B TABLE I LOGIC & PERMISSIVES TEST FUNCTION Pll P8 RCP BREAKERS P8 RCP BREAKERS OFF FUNCTION LOGIC REQUIRED ACTUAL 2/3 I

I 1/4 1/4 OFF BLOCKING FUNCTION TEST SWITCH BLOCKS INHIBIT NOT BLOCKS INHIBITED

  • X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

_l~~~~~~

DATE

_5/,__24~/~8_2~~~~

PAGE _3_3 __ OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.16 Perform the following Memories Testing._

Record results on TABLE II.

8.16.l 8.16.2 8.16.3 8.16.4 Place MEMORIES switch to position "l".

(The 1/4 function logic lamp will light whenever the MEMORIES switch is not in the OFF position)..

In the MEMORY FUNCTION TEST portion of the LOGIC TEST PANEL, depress and. release the RED pushbutton and verify that the MEMORY SET lamp lights.

(If already on, depress and release BLACK pushbutton).

After MEMORY SET lamp lights, depress and release BLACK pushbutton.

Repeat Steps 8.16.2 and 8.16.3 for the positions of the MEMORIES switch as listed oh TABLE II.

I & C - 001 Initial

NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE PAGE _3_4 __ OF 50 TITLE FUNCTION SELECTOR MEMORIES OFF 1

  • 2 3

4 5

6 7

8 9

10

    • 11 OFF I & C - 001 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B TEST FUNCTION OFF POWER RANGE BLOCK TABLE 2 MEMORIES INTERMEDIATE RANGE BLOCK SOURCE RANGE BLOCK SOURCE RANGE BLOCK SAFETY INJECTION BLOCK, PRESSURIZER SAFETY INJECTION BLOCK, PRESSURIZER SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LEVEL,

SAFETY INJECTION BLOCK, STEAM LINE PRESSURE AND LOGIC AUTOMATIC SAFETY INJECTION BLOCK FEEDWATER VALVE CONTROL FEEDWATER VALVE CONTROL OFF FUNCTION LOGIC 1/4 MEMORY TEST RED FUNCTION PUSHBUTTON BLACK (ON OR OFF)

.~

".i.

1 a. r nn1 SALEM GENERATING STATION PERFORMANCE DEPARTMENT° (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

_l ______ _

DATE 5/24/82


'----~---

PAGE 35 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued)

Initial 8.17 Perform the following for Output Relay Testing and Record'results on TABLE III.

8.17.1 8.17.2 8.17.3 8.17.4 c..*

~*

('. \\ \\.

~

Place the MASTER RELAY SELECTOR in Position "l".

Depress SLAVE TEST A pushbutton and verify that the required "A" lamps lights while pushbutton is depressed.

Verify the required lamps light by placing an "X" under each on*requirement.

Repeat Step 8.17.2 for SLAVE TEST B.

Repeat Steps 8.17.2 and 8.17.3 for each MASTER RELAY SELECTOR position listed on TABLE III.

(I H

'II

\\-z:..:........... -1...*.i '--

~

\\::""l...

~ <"

i...

\\

"'"'"~

~*J

...... "'\\_.,.

,~,.,,,

'~~ \\....

\\.:>f';,..; ;...\\... *

\\j"~,...~ \\,:\\

\\°")*~t:. <!..

C'\\~

c ~

V---~*C. \\ ~

¥..i.vc i_.,

-~\\:!C<'3;

\\I... "-.:*<.*l\\ ~

\\<... lcC:~.

\\.;.. \\..:: '.C

-~~-Q..

\\

'.'\\

~\\'\\""c.c.... "A

~(...

~~.;* \\-

(-'1- *"..:. \\... _

  • S:\\v:..... * *~

\\t. 1<:C 'C. \\

SALEM G.ATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDUHE NUMBER -

lPD-18.1. 009 REV. NO.

1 DATE 5/24/82 PAGE 36 OF 50 TITLE SOI.ID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B MASTER RELAY SELECTOR 1

2 3

4 5

6 7

TABLE III LOGIC & PERMISSIVES SLAVE RELAY FUNCTION CONTAINMENT ISOLATION, PHASE A CONTAINMENT VENTILATION ISOLATION STEAM STOP VALVES SPRAY ACTUATION CONTAINMENT ISOLATION, PHASE B FEEDWATER VALVES (HI-HI STEAM GENERATOR LEVEL)

TRIP TURBINE/MAIN FEEDWATER PUMPS Al ON ON ON ON ON ON ON A2 ON OFF OFF OFF ON OFF OFF SLAVE RELAY CONTINUITY LAMPS A3 A4 Bl B2 B3 B4 ON OFF ON ON ON OFF OFF OFF ON

  • oFF OFF OFF OFF OFF ON O;F'F OFF OFF OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF pFF OFF OFF OFF OFF OFF OFF OFF OFF

SALEM GE.TING STATION PERF0Rf.1ANCE DEPARTMENT (I & C)

TEST PROCEDUHE NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 PAGE 37 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B MASTER RELAY SELECTOR 8

9 10 11 12 13 14 15 TABLE III LOGIC & PERMISSIVES SLAVE RELAY FUNCTION Al A2 RCP UNDERFREQUENCY ON OFF SPARE ON OFF (NOT USED)

OFF OFF (NOT USED)

OFF OFF LO-LO TAVG STEAM DUMP INTERLOCK ON OFF LOSS OF POWER/TURBINE AUXILIARY PUMP ON OFF LOW WATER LEVEL/MOTOR AUXILIARY PUMP ON OFF LOW WATER LEVEL/TURBINE AUXILIARY PUMP ON OFF SLAVE RELAY CONTINUITY LAMPS A3 A4 Bl B2 B3 B4 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF.

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

,/\\

SALEM GE.A TING STATION NUMBER -

lPD-18.1. 009 PERF0Rf..1ANCE DEPARTMENT (I & C)

REV. NO.

1 TEST PAOCEDUUE DATE 5/24/82 PAGE 38 OF 50 TITLE SOI, ID STATE PROTECTION SYSTEM FUNCTION~L TEST TRAIN B TABLE III LOGIC & PERMISSIVES MASTER RELAY SLAVE RELAY CONTINUITY LAMPS SELECTOR SLAVE RELAY FUNCTION Al A2 A3 A4.

Bl B2 B3 B4 16 GENERATOR TRIP &.STEAM DUMP INTERLOCK ON OFF OFF OFF OFF OFF OFF OFF 17 TAVG AND REACTOR TRIPPED ON OFP OFF OFF ON OFF OFF OFF 18 SAFETY INJECTION.

ON ON ON ON ON ON ON ON 19 (NOT USED)

OFF OFF OFF OFF OFF OFF OFF OFF 20 (NOT USED)

OFF OFF OFF OFF OFF OFF OFF OFF 21 (NOT USED)

OFF OFF OFF OFF OFF OFF OFF OFF 22 (NOT USED)

OFF OFF OFF OFF OFF OFF OFF OFF 23 (NOT USED)

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 PAGE 39 OF SO TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL T.EST TRAIN B

8.0 Instructions

(Continued) 8.18 Place the MULTIPLEXER TEST switch to Normal.

8.19 Replace (if required) the field lead to TB-506-2 lifted ~n Step 8.14.

8.20 Inform the Control Operator that a containment ventilation isolation will be initiated if a high radiation alarm is present when this procedure is completed.

Inform him that -he may reset the containment ventilation isolation at this time.

8.21 Manual Input Function Test

-NOTE-8.~\\.\\) 8.ai.\\.°t Omit steps 8.21.4, 8.21.5, 8.21.14, 8.21.16 6'.,l.\\,\\0 and &.21.19 if Reactor is Tripped 8.21.1 Tripped Operational Have the Control Operator rack in and close Reactor By-pass Breaker B, and verify that the breaker is in Operate position and its light is illuminated.

I & C

  • 001 Initial

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lP D-18. 1. 0 0 9 5/24/82 PAGE 40 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued)

  • -WARNING-Reactor By-pass Breaker B must remain energized for the duration of the manual testing, otherwise a Reactor Trip will occur
  • 8.21.2 8.21.3
8. 21. 4
8. 21. 5 8.21.6 At the LOGIC TEST Panel place the LOGIC A Test Switch in Position 7.

(Pressurizer High Pressure Trip).

In the MANUAL INPUT FUNCTION TEST portion of the LOGIC TEST PANEL, depress and hold any TWO pushbuttons.

At the Control Board, verify that Reactor Trip Break~r B is OPEN.

Verify the UV COIL VOLTAGE meter indicates approximately 0 VDC.

Release the pushbuttons depressed in Step 8.21.3.

I & C - 001 Initial

'x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV. NO.

-*--=l=--------

DATE 5/24/82 PAGE 41 OF 50 TITLE

. SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued)

8. 21. 7
8. 21. 8 8.21.9 8.21.10 8.21.11 Place the LOGIC A Test Switch in the OFF position.

Have the Control Opeator close the Reactor Trip Breaker B.

Have the Control Operator OPEN Reactor By-Pass Breaker B.

Have the Control Operator rack Out Reactor By-Pass Breaker B.

Verify that the general warning test LED for SSPS Train B is extinguished in both Train A and Train B.

I I & C

  • 001 Initial

. )<

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

_l ______ ~

DATE 5/24/82 PAGE 42 OF 50 SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.22 Perform the following for SAFETY INJECTION RESET TIMING TEST.

8.22.1 8.22.2 8.22.3 Select position 9 on the MEMORIES switch and if the MEMORY SET lamp is illuminated, depress the BLACK button to extinguish it.

In the OUTPUT TEST cabinet, place test switch 602 in the BLOCK OUT~UT position.

Connect the Digital Voltmeter as follows:

8.22.3Al

  • TD-1, Terminal 6 (+)

8.22.3.2 Logic Ground (GND) 8.-22.4 8.22.5 8.22.6 The DVM should read approximately +48 VDC.

Move the positive lead of the DVM from TD-1, Terminal 6 to TD-1, Terminal 2.

The DVM should indicate 0 VDC.

I & C - 001 Initial

.x SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

_l ______ _

DATE 5/24/82 PAGE 43 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.22.7 8.22.8 Latch-up Relay K602 by depressing the latch plunger and time the interval from this point until the voltmeter reads approximately *+48 VDC.

(The time should be 60 to 65 sec.)

sec.

At the Control Board depress the S.I.

Block/Reset pushbutton and verify the following:

8.22.8.1 DVM indicates 0 VDC 8.22.8.2 MEMORY SET lamp lights 8.22.8.3 Relay K602 Resets 8.22.9 8.22.10 Return the MEMORIES switch to the OFF position.

Connect the Digital Voltmeter as follows:

8.22.10.l TD-1, Terminal 6 (+)

- 8.22.10.2 IDgic Ground (GND) 8.22.11 The DVM.should read approximately +48 VDC.

I & C - 001 Initial

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER_

lPD-18.1. 009 REV.NO.

~l~~~~~~~

DATE 5/24/82 PAGE 44 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.22.12 8.22.13 Move the positive lead of the DVM to TD-1 Terminal 2 and measure the resistance to gr_ound (GND).

The DVM should indicate an Open.

Connect the Digital Voltmeter (AC Scale) as follows:

8.22.13.l TD-1, Terminal 1 8.22.13.2 TD-1, Terminal 5 8.22.14 NOTE:

8.22.15 The.DVM* should read 0 VAC.

A DVM indication of 25 VAC or less is considered noise.

Measure the resi.stance between* TD-1, Terminal 1 and TD-1, Terminal 5.

The DVM should indicate an OPEN.

Initial 8.22.16 In the output test cabinet, return the test switch 602 to the UNBLOCK outp~t position and verify the TL/TXC Alarm light extinguishes.

. }(

SALEM GENERATING STATION.

PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 PAGE 45 OF 50 TITLE *~~-S~O.:..=L~I~D-*~s~TA_..:.TE:::._P~R-O_T_E~C~T.:.:..;_IO~N:..:..._S~Y.:.:..;_S_TE_M~F-U_N_C_T~IO_N_A_L~T~E~S-T~T-RA~I-N_B~

8.0 Instructions

(Continued) 8.22.17 Have the Control Operator reinstate the FLUX TRIP MANUAL Blocks from the Control

. Board.

NOTE:

The pushbutton must be pushed even when BEZEL block light is lit.

(ND block~ can be applied if their permissives are not present, therefore, only those permitted will be set.)

8.22.17.1 Block Source Range-Train B pu~hed 8.22.17.2 Block Intermediate Range-Train B pushed.

8.22.17.3 Block Power Range -

Train B pushed.

WARNING:

The Flux Trip Manual Blocks. must*be reinstated prior to placing the input error inhibit switch in the normal position.

8.22.18 Place the Input Error Inhibit Switch in the NORMAL position

  • I & C -001 Initial

. 'X SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1.009 1

5/24/82 PAGE 46 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.23 Perform the following for Spray Actuation Test.

8.23.1 Depreas Spray Test pushbutton for each of the individual channels and verify proper indication at the Control Board.

8.23;1.l Channel I Containment Pressure Hi-Hi I

8. 23.1. 2 Channel II Containment Pressure Hi-Hi II 8.23.1.3 Channel III Containment Pressure Hi-Hi III 8.23.1.4 Channel IV Containment Pressure 8.23.2 8.23.3 "Hi-Hi.

IV Place input ERROR INHIBIT Switch in the INHIBIT position.

Place the MODE Selector switch in the OPERATE position.

I Iii c j 001

    • ) *,o**~**-*'<**"*O.-.~: *.-*o*.-,...._.,.~-.-.-..*-*,-*.*.-*o*r-Y-~*-- *-~***

--~*--**-*-'*"*'*- * --****.**

Initial

~

. x' I & C -001 SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

REV. NO.

DATE lPD-18.1. 009 1

5/24/82 PAGE 47 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

(Continued) 8.23.4 Actuate"the following MANUAL BLOCKS using the pushbuttons on the Control Board.

No blocks can be applied if their permissives are not present; therefore, only those per-rni tted will be set.

8.23.4.1 Pressurizer Safety Injection.

8.23.4.2 Steamline Pressure Safety Injection.

-NOTE-Safeguard actions which are being blocked by virtue of having been Reset from the Control Bezels will be re-initiated *at this time if necessary logic signal is present.

The safe-guard actions involved are:

1.

Containment Spray

2.

Phase A Isolation

3.

Phase B Isolation

4.

Feedwater Isolation

5.

Containment Ventilation Isolation from Safety Injection Signal.

Inform the Control Operator of this condition.

Control Operator

    • ...* --*,.. *"...... - **. -.... :::**._"!'. r-.-.- *-***""!--*...... _._,._. *****---:-**--*-- -*~ -..........,.. -,. -..... - -*. *-..... ****-.*...

Initial

SALEM GENERATING STATION PERFORMANCE DEPARTMENT {I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

__;;l;;__~~~~~~

DATE 5/24/82 PAGE 48 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

8.0 Instructions

  • 8.23.s 8.23.6 (Continued)

Place the Input ERROR Inhibit switch in the NORMAL position.

Have the Control Operator reset all unwanted safeguards actions which were re-initiated as a iesult of this test

  • 8.24 Perform the following for the Multiplexer checks.
  • WARNING:

It is necessary that SSPS Train A Mul tip],exer.

Switch be in the normal position and that its general warning lamp be off.

If the lamp is already on, it is necessary that it be cleared before the A & B position is selected in the

  • other train.

8.24.1 8.24.2 NOTE:

Place Train B Multiplexer Test Switch to the A & B position.

Verify no intermittent condition exists.

An intermittent (on/off) condition is when the indication appears at the control board and the computer at approximately one repetition per second.

This indicates one of the two trains has a malfunction in its data multiplexing.

I & C - 001 Initial

X*

-~-------

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE*

NUMBER -

lPD-18.1. 009 REV.NO.

_l ______ _

DATE.

5/24/82 PAGE 49 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

~.*o Instructions:

(Continued) 8.24.3 8.24.4 Place Train B Multiplexer Test Switch to the Normal position.

If the Shift Supervisor wants the Safety Injection block re-initiated for the train, short terminals 2 and 6 on TDl and have the Controls Operator depress S.I. Reset for Train B.

Remove jumper: ----

Initial Senior Shift Supervisor/Shift Supervisor 9.0 System Return to Normal:

9.1 The Senior Shift Supervisor/Shift Supervisor has been notified that this channel has been returned to normal.

Senior Shift Supervisor/Shift Supervisor Date/Time 1 s. c -001 Initial

~

.. x,*

SALEM GENERATING STATION PERFORMANCE DEPARTMENT (I & C)

TEST PROCEDURE NUMBER -

lPD-18.1. 009 REV.NO.

--"l~------

DATE 5/24/82 PAGE 50 OF 50 TITLE SOLID STATE PROTECTION SYSTEM FUNCTIONAL TEST TRAIN B

10. 0 Remarks:

w.o.

I.O.

11.0 Completion:

11.l Completed by: --------

Technician Date Time 11.2 Approved by: --------

Supervisor Time Date I & C -001

......................,..-... -*.***-.-:.***-... --..................... --.-**~***... *-,,... -.......