ML11251A198: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
(2 intermediate revisions by the same user not shown)
Line 3: Line 3:
| issue date = 09/06/2011
| issue date = 09/06/2011
| title = Notification Under 10 CFR Part 21 on Certain Rosemount Model 1153 Series B, 1164 and 1154 Series H Pressure Transmitters, May Not Perform Their Intended Safety Function
| title = Notification Under 10 CFR Part 21 on Certain Rosemount Model 1153 Series B, 1164 and 1154 Series H Pressure Transmitters, May Not Perform Their Intended Safety Function
| author name = Bumgarner M D, Pham D
| author name = Bumgarner M, Pham D
| author affiliation = Rosemount Nuclear Instruments, Inc
| author affiliation = Rosemount Nuclear Instruments, Inc
| addressee name =  
| addressee name =  
Line 14: Line 14:
| page count = 20
| page count = 20
}}
}}
=Text=
{{#Wiki_filter:0910612011                      U.S. Nuclear Regulatory Commission OperationsCenter Event Report                    Page I Part 21 (PAR)                                                                                    Event#      47246 Rep Org: ROSEMOUNT NUCLEAR INSTRUMENTS                          Notification Date I Time: 09/06/2011 15:59    (EDT)
Supplier: ROSEMOUNT NUCLEAR INSTRUMENTS                                Event Date / Time: 08/30/2011          (CDT)
Last Modification: 09/06/2011 Region:    3                                                Docket #:
City:  CHANHASSEN                              Agreement State:              Yes County:                                                    License #:
State:  MN NRC Notified by:    DUYEN PHAM                            Notifications: TODD JACKSON                      R1DO HQ Ops Officer:  BILL HUFFMAN                                            DANIEL RICH                    R2DO Emergency Class:      NON EMERGENCY                                          JAMES DRAKE                    R4DO 10 CFR Section:                                                            CHRISTINE LIPA                  R3DO 21.21                UNSPECIFIED PARAGRAPH                                  PART 21 E-MAIL GROUP NOTIFICATION THAT CERTAIN ROSEMOUNT PRESSURE TRANSMITTERS MAY NOT PERFORM THEIR INTENDED SAFETY FUNCTION The following is a summary of a Part 21 notification was received from Rosemount via facsimile:
  "Re: Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series B, 1154 and 1164 Series H Pressure Transmitters "Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform [the NRC] that one (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H pressure transmitters may not perform their intended safety function.
  "Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.
  "The thirty-five (35) potentially affected Model 1153 Series B, 1154, and 1154 Series H pressure transmitters were shipped from RNII between April 19, 2011 and August 12, 2011. [The list of Plant Sites that have received the affected transmitters is provided at the end of this report.]
  "If you have any questions, or require additional information related to this issue, please contact: Mike Dougherty (208) 865 -1112 or Tracy Kaluzniak (952) 949-7159.
  "Identification of items supplied:
  "One (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H potentially affected units have been shipped.
0910612011                    U.S. NuclearRegulatory Commission OperationsCenter Event Report                          Paize 2 Part 21 (PAR)                                                                                    Event#          47246 "Identification of firm supplying the item:
"Rosemount Nuclear Instruments, Inc. 8200 Market Boulevard Chanhassen, MN 55317 "Nature of the failure and potential safety hazard:
"On each Model 1153 Series B, 1154, and 1154 Series H transmitter, four diodes are used on a circuit card assembly which is installed within the welded sensor module subassembly. These diodes convert the AC oscillator signal to a DC current proportional to the pressure applied to the sensor. The diodes (P/N DZ911218A) are manufactured by Microsemi Corporation (MSC).
  "Recently an unexpected drop in yield was identified during electrical testing of the circuit card assembly. A hold was placed on production to further investigate the issue. It was determined that the drop in yield was caused by intermittent open diodes on the circuit card assembly. Failure of one diode will result in an off-scale failure of transmitter output. Failure of two or more diodes may result in an on-scale failure of transmitter output.
  "MSC determined that the intermittent open electrical failures were the result of a poor solder bond formation within the diode at the cathode lead. This was caused by either inadequate heat flow or surface contamination during the component manufacturing process.
  "Working with MSC, RNII used material traceability data to confirm the potential problem was limited to one manufacturer's lot code of the diode. RNII was then able to utilize material traceability data to further identify the specific shipped transmitters affected by this notification.
  "On August 30, 2011, it was concluded that a substantial safety hazard may exist. Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the safety impact related to the potentially anomalous output in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased one or more of the thirty-five (35) potentially affected Model 1153 Series B, 1154, or 1154 Series H pressure transmitters.
  "The corrective action which is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:
  "(a) RNII held shipments of completed Model 1153 Series B, 1154, and 1154 Series H transmitters and determined which specific units were assembled with diodes from the suspect lot code.
  "(b) RNII quarantined all Model 1153 Series B, 1154, and 1154 Series H transmitters and sub-assemblies in manufacturing while a determination was made as to which specific units were assembled with diodes from the suspect lot code.
  "(c) RNII worked with the diode supplier (MSC) to determine the root cause and identify the suspect lot code. Since this part is no longer being manufactured by MSC, no corrective actions were implemented at MSC.
  "(d) RNII is in the process of reworking all unshipped Model 1153 Series B, 1154, and 1154 Series H transmitters and subassemblies that were completed or in manufacturing that contained diodes from the suspect lot code.
  "(e) Potentially affected pressure transmitters can be returned and reworked at the factory at the end user's request.
  "(f) RNII is qualifying a substitute diode to replace the obsolete DZ911218A diode. The qualification is expected to be complete within the next six months. This qualification will be documented in an update to the Model 1153 Series B, 1154, and 1154 Series H qualification reports "Any advice related to the potential failure of the Item:
  "RNII recommends that users review the application where any of the thirty-five (35) potentially affected Model
0910612011                      U.S. Nuclear Regulatory Commission Operations Center Event Report                  Page3 Part 21 (PAR)                                                                                Event#        47246 1153 Series B, 1154 and 1154 Series H transmitters are used to determine any safety considerations in the operation of the plant. RNII recommends that potentially affected transmitters be returned to RNII for rework at the end user's earliest opportunity."
List of Affected Sites:
U.S Facilities Calvert Cliffs -5 Transmitters Oconee          -2 Transmitters San Onofre -1 Transmitter River Bend      -2 Transmitters Waterford        -1 Transmitter Diablo Canyon -1 Transmitter Farley          -4 Transmitters Foreign Facilities Shin Kori                -1 Transmitter Ringhals                -3 Transmitters Fuqing                  -4 Transmitters Fangjishan              -4 Transmitters Yangjiang              -4 Transmitters Tihange                -1 Transmitter Asco I1/ Vandellos II    -3 Transmitters
Received at: 09/06/2011 15:59 2011 Sep 06 02,48 PM            EPM OUT ROSEMOUNT NUCLEAR 952-949-                              1/17 EMERSON
                        .4,                                                                  ROSEMOUNT*
Process Management                                                                          Nuclear 8200 Market Boulevard Chanhassen, MN 55317 USA Facsimile                                                                        Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 No. of Pages:      17 Induding cover page To:              NRC Operations Center            Fax Number:        (301) 816-5151 Company:
Date:            Tuesday, September 6th, 2011 Duyen Pham, Quality              Phone;      (952) 949-5363 From:            Manager E-Mail:          Duyen. Pham('oEmerson.com
==Subject:==
Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series 8, 1164 and 1154 Series H Pressure Transmitters Rosemount Nuclear Instruments, Inc. is submitting the attached notification as required by 10 CFR Part 21. Please contact me if you have any questions.
Sincerely,
                              /10ý0p;zzý)
Duyen Pham Quality Manager Rosemount Nuclear Instruments, Inc.
7/o      //I 0C74a10        cen-i/Yrni catjC2-;
c-P-e c-- rf o4 www. RosemountNuclear.com RNI l.1nfoOEmersonProcess. corn
2011 Sep 06 02,48 PM                EPM OUT ROSEMOUNT NUCLEAR 952-949-                              2/17 Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard ROSEMOUNT                                                              Chanhassen, MN 55317 USA Nuclear                                                Tel 1 (952) 949-5210 Fax 1 (952) 94M-201 Www.RosjmountNuenear.eom 06 September 2011 US, Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re:  Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series B, 1154 and 1164 Series H Pressure Transmitters Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that one (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H pressure transmitters may not perform their intended safety function.
Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.
The thirty-five (35) potentially affected Model 1153 Series B, 1154, and 1154 Series H pressure transmitters were shipped from RNII between April 19, 2011 and August 12, 2011.
1.0  Name and address of the individual providing the information:
Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard Chanhassen, MN 55317 2.0    Identification of items supplied:
One (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H potentially affected units have been shipped. See the enclosed Attachment A for the list of these thirty-five (35) transmitters shipped by customer and/or plant site.
3.0  Identification of firm supplying the item:
Rosemount Nuclear Instruments, Inc.
8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:
On each Model 1153 Series B, 1154, and 1154 Series H transmitter, four diodes are used on a circuit card assembly which is installed within the welded sensor module sub-assembly. These diodes convert the AC oscillator signal to a DC current proportional to Page 1 of 3
2011 Sep 06 02,48 PM              EPM OUT ROSEMOUNT NUCLEAR 952-949-                              3/17 the pressure applied to the sensor. The diodes (PIN DZ91 1218A) are manufactured by Microsemi Corporation (MSC).
Recently an unexpected drop in yield was identified during electrical testing of the circuit card assembly. A hold was placed on production to further Investigate the issue. It was determined that the drop in yield was caused by intermittent open diodes on the circuit card assembly. Failure of one diode will result in an off-scale failure of transmitter output.
Failure of two or more diodes may result in an on-scale failure of transmitter output.
MSC determined that the intermittent open electrical failures were the result of a poor solder bond formation within the diode at the cathode lead. This was caused by either inadequate heat flow or surface contamination during the component manufacturing process.
Working with MSC, RNII used material traceability data to confirm the potential problem was limited to one manufacturers lot code of the diode. RNII was then able to utilize material traceability data to further identify the specific shipped transmitters affected by this notification.
On August 30, 2011, it was concluded that a substantial safety hazard may exist.
Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the safety impact related to the potentially anomalous output in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased one or more of the thirty-five (35) potentially affected Model 1153 Series B, 1154, or 1154 Series H pressure transmitters.
5.0  The corrective action which is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:
(a) RNII held shipments of completed Model 1153 Series B, 1154, and 1154 Series H transmitters and determined which specific units were assembled with diodes from the suspect lot code.
(b) RNII quarantined all Model 1153 Series B, 1154, and 1154 Series H transmitters and sub-assemblies in manufacturing while a determination was made as to which specific units were assembled with diodes from the suspect lot code.
(c) RNII worked with the diode supplier (MSC) to determine the root cause and identify the suspect lot code. Since this part is no longer being manufactured by MSC, no corrective actions were implemented at MSC.
(d) RNII is in the process of reworking all unshipped Model 1153 Series B, 1154, and 1154 Series H transmitters and subassemblies that were completed or in manufacturing that contained diodes from the suspect lot code.
(e) Potentially affected pressure transmitters can be returned and reworked at the factory at the end user's request.
(f) RNII is qualifying a substitute diode to replace the obsolete DZ911218A diode. The qualification Is expected to be complete within the next six months. This qualification ROSEMOUNT" Nuclear                                                                          Page 2 of 3
2011 Sep 06 02AB PM                EPM OUT ROSEMOUNT NUCLEAR 952-949-                            4/17 will be documented In an update to the Model 1153 Series B, 1154, and 1154 Series H qualification reports.
Mr. Marc Bumgarner, VP&GM of Rosemount Nuclear Instruments, Inc. is responsible for any further action related to this issue.
6.0  Any advice related to the potential failure of the Item:
RNII recommends that users review the application where any of the thirty-five (35) potentially affected Model 1153 Series B, 1154 and 1164 Series H transmitters are used to determine any safety considerations in the operation of the plant. RNII recommends that potentially affected transmitters be returned to RNII for rework at the end user's earliest opportunity.
Rosemount Nuclear Instruments, Inc. is committed to the nuclear industry and remains dedicated to the supply of high quality products to our customers. If you have any questions, or require additional information related to this issue, please contact: Mike Dougherty (208) 865-1112 or Tracy Kaluzniak (952) 949-7159.
Sincerely, Marc D. Bu rJarmer Vice President & General Manager Rosemount Nuclear Instruments, Inc.
Enc.: Attachment A - List of Affected Transmitters by Company Name and/or Plant Site ROSEMOUNT' Nuclear                                                                        Page 3 of 3
2011 Sep 06 02:48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-                        5/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
CONSTELLATION ENERGY GROUP INC Sales Order    Purchase Order  Model Number  Serial Number Ship Date                  Site Number 3052851          432255        1154OPSRC    "0544060    7-Jun-li  CALVERT CLIFF NUCLEAR  POWER PLANT INC 3052851          432256        1154DPSRC      0544061    7-Jun-11  CALVERT CLIFF NUCLEAR  POWER PLANT INC 3052851          432256        1154DPSRC .      544062  7-Jun-1l  CALVERT CLIFF NUCLEAR  POWER PLANT INC 3063381          432246    1154HHSRCNO011    0544056    15-Jun-11 CALVERT CLIFF NUCLEAR  POWER PLANT INC 3063381          432246    1154HHSRCNO011    0544057    15-Jun-11 CALVERT CLIFF NUCLEAR  POWER PLANT INC
2011 Sep 06 02:48 PM        EPM OUT ROSEMOUNT NUCLEAR 952-949-                        6/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
DUKE ENERGY CAROLINAS LLC Sales Order    Purchase Order Model Number  Serial Number Ship Date        Site Number 3048416          00143867    11S4DP5RB        0543802    9-May-11 OCONEE NUCLEAR STATION 3048416          00143867    1154DPSRB        0543803    9-May-11 OCONEE NUCLEAR STATION
2011 Sep 06 02:48 PM      EPM OUT ROSEMOUNT NUCLEAR 952-949- 7/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
EDISON MATERIAL SUPPLY LLC I
2011 Sep 06 02,48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-                        8/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT AB Sales Order  Purchase Order Model Number  Serial Number  Ship Date                Site Number 3055811        46989079    1154DPSRC      0544312 . 30-Jun-1J  RINGHALS NUCLEAR POWER STATION 3055811        46989079    2154DPSRC      0544313    30-Jun-1l  RINGHALS NUCLEAR POWER STATION 3055811        46989079    1154EPSRC      0544314    130-Jun-11l RINGHALS NUCLEAR POWER STATION 3
2011 Sep 06 02:48 PM            EPM OUT ROSEMOUNT NUCLEAR 952-949-        9/17 ATTACHMENT: 10 CFR Part 21 NotificatIon - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order f  Purchase Order Number Model Number  Serial Number Ship Date  Site 2597488      HP 80805199/CP2. 1154HSRAN0167      0543641    20-May-11 FUQING 2597488      HP 80805199/CP2. 1154DH5RAN01G7    0543642    20-May-11 FUQING 2597488      HP 80805199/CP1  1154DHSRAN0167    0543643    20-May-11 FUQING 2597488      HP 80805199/CP1  I.1154DHSRAN0172    0543650    20-May-11 FUQING
                                                    '4
2011 Sep 06 02,48 PM            EPM OUT ROSEMOUNT NUCLEAR 952-949-    10/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order    Purchase Order    Model Number  Serial Number Ship Data    Site Number 2597497      HP 80805206/CP1  1154DH5RAN0167    0543697    20-May-11 FANGJISHAN 2597497      HP 80805206/CP2  1154DHSRAN0167    0543698    20-May-11 FANGJISHAN 2597497      HP 80805206/CP3  1154DHSRAN0167    0543699    20-May-11 FANGJISHAN 2597497      HP 80805206/CP4 - 1154DH5RAN0172    0543710    20-May-11 FANGJISHAN LA
2011 Sep 06 02-48 PM            EPM OUT ROSEMOUNT NUCLEAR 952-949-                11/17 ATTACHMENT: 10 CFR Part 21 NotIfication - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order    Purchase Order    Model Number  Serial Number      Ship Date        Site Number 2526350      HP 80805673/CPS  1154DHSRAN0152    0543560          20-Apr-11    YANG.JANG 2626350      HP 80805673/CPB  1154DHSRAN0,152    0543561          20-Apr-11    YANGJIANG 262690            m HP ,80805673_/CPS 1154DHSRAN0152    0543558 ........ 20-Apr-      YANGIA'NG..
2626350    HP80805673/CPB    1154DHSRAN0152    0543559          20-Apr-11    YANGJIANG 26630 P OBSS3IPB      114D5RNO5Z        05359            0-pr11YAGIAN
2011 Sep 06 02:48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-                    12/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT NV SA Sales Order  Purchase Order 2
Number Model Number    FSerial Number    Ship Date          Site 4                0 3036646          S233042'  11i54HPS RCN0096 1 0'5'4382P7  125-May-21  ITIHANGE
                                                      'I
2011 Sep 06 02,48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-                13/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
EMERSON PROCESS MANAGEMENT SL Sales Order J  Purchase Order  Model Number  Serial Number Ship Date            Site Number 2595531.        35014658    1154SH9RANO060    0543795    14-Jun-l1 ASCO II/VANDELLOS ii 2595531          35014658    1154SH9RAN006    0543797    14-Jun-11 ASCO II / VANDELLOS It 2595531          35014658    1154SH9RAN0062    0543798    14-Jun-li ASCO II/ VANDELLOS II 3
2011 Sep 06 02:48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-                    14/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
ENTERGY OPERATIONS INC Sales Order    Purchase Order  Model Number  Serial Number Ship Date            Site Number 3084741          10315334    1153DBSPCN0016    0544302    12-Aug-11 RIVERBEND NUCLEAR STATION 3084741          10315334    1153DBSPCNO016    0544303    12-Aug-11 RIVERBEND NUCLEAR STATION 3069060          10312980    11S4DPSRCNO012    0543654    19-Apr-11    WATERFORD 3 NUCLEAR 3
2011 Sep 06 02:48 PM        EPM OUT ROSEMOUNT NUCLEAR 952-949-                      15/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
PACIFIC GAS AND ELECTRIC CO Sales Order    Purchase Order Model Number  Serial Number  Ship Date            Site Number3                                    1                A 3052849        3500892008    1154DHSRC  1    0543822    1 12-May-11 ...... DIABLO CANYON It
2011 Sep 06 02:48 PM          EPM OUT ROSEMOUNT NUCLEAR 952-949-            16/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.
SOUTHERN NUCLEAR OPERATING CO INC Sales Order    Purchase Order  Model Number  Serial Number  Ship Date          Site Number 3034520      QP1,005/001 . 1154DPSRA      0543725    " 27-Apr-11 FARLEY NUCLEAR PLANT 3034520      QPi,10105/00  j  1S4DP5RA      0543726      27-Apr-11 FARLEY NUCLEAR PLANT 3034520      QP1.0_l05/001    1154DPSRA      0543820      9-May-l1  FARLEY NUCLEAR PLANT 3034520      QP110105/001      1154DPSRA      0543821      9-May-11  FARLEY NUCLEAR PLANT
2011 Sep 06 02,48 PM        EPM OUT ROSEMOUNT NUCLEAR 952-949-              17/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011, WESTINGHOUSE Sales Order    Purchase Order Model Number  Serial Number Ship Date        Site Number 3065873        4500385592    1154HHSRB      0543715    17-Jun-11 SHIN KORI UNIT 1}}

Latest revision as of 15:04, 12 November 2019

Notification Under 10 CFR Part 21 on Certain Rosemount Model 1153 Series B, 1164 and 1154 Series H Pressure Transmitters, May Not Perform Their Intended Safety Function
ML11251A198
Person / Time
Site: Calvert Cliffs, Oconee, River Bend, Diablo Canyon, Waterford, Farley, San Onofre  Duke Energy icon.png
Issue date: 09/06/2011
From: Bumgarner M, Pham D
Rosemount Nuclear Instruments
To:
Office of Nuclear Reactor Regulation
References
47246
Download: ML11251A198 (20)


Text

0910612011 U.S. Nuclear Regulatory Commission OperationsCenter Event Report Page I Part 21 (PAR) Event# 47246 Rep Org: ROSEMOUNT NUCLEAR INSTRUMENTS Notification Date I Time: 09/06/2011 15:59 (EDT)

Supplier: ROSEMOUNT NUCLEAR INSTRUMENTS Event Date / Time: 08/30/2011 (CDT)

Last Modification: 09/06/2011 Region: 3 Docket #:

City: CHANHASSEN Agreement State: Yes County: License #:

State: MN NRC Notified by: DUYEN PHAM Notifications: TODD JACKSON R1DO HQ Ops Officer: BILL HUFFMAN DANIEL RICH R2DO Emergency Class: NON EMERGENCY JAMES DRAKE R4DO 10 CFR Section: CHRISTINE LIPA R3DO 21.21 UNSPECIFIED PARAGRAPH PART 21 E-MAIL GROUP NOTIFICATION THAT CERTAIN ROSEMOUNT PRESSURE TRANSMITTERS MAY NOT PERFORM THEIR INTENDED SAFETY FUNCTION The following is a summary of a Part 21 notification was received from Rosemount via facsimile:

"Re: Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series B, 1154 and 1164 Series H Pressure Transmitters "Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform [the NRC] that one (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H pressure transmitters may not perform their intended safety function.

"Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

"The thirty-five (35) potentially affected Model 1153 Series B, 1154, and 1154 Series H pressure transmitters were shipped from RNII between April 19, 2011 and August 12, 2011. [The list of Plant Sites that have received the affected transmitters is provided at the end of this report.]

"If you have any questions, or require additional information related to this issue, please contact: Mike Dougherty (208) 865 -1112 or Tracy Kaluzniak (952) 949-7159.

"Identification of items supplied:

"One (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H potentially affected units have been shipped.

0910612011 U.S. NuclearRegulatory Commission OperationsCenter Event Report Paize 2 Part 21 (PAR) Event# 47246 "Identification of firm supplying the item:

"Rosemount Nuclear Instruments, Inc. 8200 Market Boulevard Chanhassen, MN 55317 "Nature of the failure and potential safety hazard:

"On each Model 1153 Series B, 1154, and 1154 Series H transmitter, four diodes are used on a circuit card assembly which is installed within the welded sensor module subassembly. These diodes convert the AC oscillator signal to a DC current proportional to the pressure applied to the sensor. The diodes (P/N DZ911218A) are manufactured by Microsemi Corporation (MSC).

"Recently an unexpected drop in yield was identified during electrical testing of the circuit card assembly. A hold was placed on production to further investigate the issue. It was determined that the drop in yield was caused by intermittent open diodes on the circuit card assembly. Failure of one diode will result in an off-scale failure of transmitter output. Failure of two or more diodes may result in an on-scale failure of transmitter output.

"MSC determined that the intermittent open electrical failures were the result of a poor solder bond formation within the diode at the cathode lead. This was caused by either inadequate heat flow or surface contamination during the component manufacturing process.

"Working with MSC, RNII used material traceability data to confirm the potential problem was limited to one manufacturer's lot code of the diode. RNII was then able to utilize material traceability data to further identify the specific shipped transmitters affected by this notification.

"On August 30, 2011, it was concluded that a substantial safety hazard may exist. Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the safety impact related to the potentially anomalous output in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased one or more of the thirty-five (35) potentially affected Model 1153 Series B, 1154, or 1154 Series H pressure transmitters.

"The corrective action which is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:

"(a) RNII held shipments of completed Model 1153 Series B, 1154, and 1154 Series H transmitters and determined which specific units were assembled with diodes from the suspect lot code.

"(b) RNII quarantined all Model 1153 Series B, 1154, and 1154 Series H transmitters and sub-assemblies in manufacturing while a determination was made as to which specific units were assembled with diodes from the suspect lot code.

"(c) RNII worked with the diode supplier (MSC) to determine the root cause and identify the suspect lot code. Since this part is no longer being manufactured by MSC, no corrective actions were implemented at MSC.

"(d) RNII is in the process of reworking all unshipped Model 1153 Series B, 1154, and 1154 Series H transmitters and subassemblies that were completed or in manufacturing that contained diodes from the suspect lot code.

"(e) Potentially affected pressure transmitters can be returned and reworked at the factory at the end user's request.

"(f) RNII is qualifying a substitute diode to replace the obsolete DZ911218A diode. The qualification is expected to be complete within the next six months. This qualification will be documented in an update to the Model 1153 Series B, 1154, and 1154 Series H qualification reports "Any advice related to the potential failure of the Item:

"RNII recommends that users review the application where any of the thirty-five (35) potentially affected Model

0910612011 U.S. Nuclear Regulatory Commission Operations Center Event Report Page3 Part 21 (PAR) Event# 47246 1153 Series B, 1154 and 1154 Series H transmitters are used to determine any safety considerations in the operation of the plant. RNII recommends that potentially affected transmitters be returned to RNII for rework at the end user's earliest opportunity."

List of Affected Sites:

U.S Facilities Calvert Cliffs -5 Transmitters Oconee -2 Transmitters San Onofre -1 Transmitter River Bend -2 Transmitters Waterford -1 Transmitter Diablo Canyon -1 Transmitter Farley -4 Transmitters Foreign Facilities Shin Kori -1 Transmitter Ringhals -3 Transmitters Fuqing -4 Transmitters Fangjishan -4 Transmitters Yangjiang -4 Transmitters Tihange -1 Transmitter Asco I1/ Vandellos II -3 Transmitters

Received at: 09/06/2011 15:59 2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 1/17 EMERSON

.4, ROSEMOUNT*

Process Management Nuclear 8200 Market Boulevard Chanhassen, MN 55317 USA Facsimile Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 No. of Pages: 17 Induding cover page To: NRC Operations Center Fax Number: (301) 816-5151 Company:

Date: Tuesday, September 6th, 2011 Duyen Pham, Quality Phone; (952) 949-5363 From: Manager E-Mail: Duyen. Pham('oEmerson.com

Subject:

Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series 8, 1164 and 1154 Series H Pressure Transmitters Rosemount Nuclear Instruments, Inc. is submitting the attached notification as required by 10 CFR Part 21. Please contact me if you have any questions.

Sincerely,

/10ý0p;zzý)

Duyen Pham Quality Manager Rosemount Nuclear Instruments, Inc.

7/o //I 0C74a10 cen-i/Yrni catjC2-;

c-P-e c-- rf o4 www. RosemountNuclear.com RNI l.1nfoOEmersonProcess. corn

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 2/17 Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard ROSEMOUNT Chanhassen, MN 55317 USA Nuclear Tel 1 (952) 949-5210 Fax 1 (952) 94M-201 Www.RosjmountNuenear.eom 06 September 2011 US, Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re: Notification under 10 CFR Part 21 on certain Rosemount Model 1153 Series B, 1154 and 1164 Series H Pressure Transmitters Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that one (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H pressure transmitters may not perform their intended safety function.

Rosemount Nuclear Instruments, Inc. does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

The thirty-five (35) potentially affected Model 1153 Series B, 1154, and 1154 Series H pressure transmitters were shipped from RNII between April 19, 2011 and August 12, 2011.

1.0 Name and address of the individual providing the information:

Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 2.0 Identification of items supplied:

One (1) Model 1153 Series B, fourteen (14) Model 1154, and twenty (20) Model 1154 Series H potentially affected units have been shipped. See the enclosed Attachment A for the list of these thirty-five (35) transmitters shipped by customer and/or plant site.

3.0 Identification of firm supplying the item:

Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:

On each Model 1153 Series B, 1154, and 1154 Series H transmitter, four diodes are used on a circuit card assembly which is installed within the welded sensor module sub-assembly. These diodes convert the AC oscillator signal to a DC current proportional to Page 1 of 3

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 3/17 the pressure applied to the sensor. The diodes (PIN DZ91 1218A) are manufactured by Microsemi Corporation (MSC).

Recently an unexpected drop in yield was identified during electrical testing of the circuit card assembly. A hold was placed on production to further Investigate the issue. It was determined that the drop in yield was caused by intermittent open diodes on the circuit card assembly. Failure of one diode will result in an off-scale failure of transmitter output.

Failure of two or more diodes may result in an on-scale failure of transmitter output.

MSC determined that the intermittent open electrical failures were the result of a poor solder bond formation within the diode at the cathode lead. This was caused by either inadequate heat flow or surface contamination during the component manufacturing process.

Working with MSC, RNII used material traceability data to confirm the potential problem was limited to one manufacturers lot code of the diode. RNII was then able to utilize material traceability data to further identify the specific shipped transmitters affected by this notification.

On August 30, 2011, it was concluded that a substantial safety hazard may exist.

Rosemount Nuclear Instruments, Inc. does not have sufficient information to determine the safety impact related to the potentially anomalous output in plant applications. As a result, a notification about the potential substantial safety hazard is being made in accordance with 10 CFR Part 21 to customers who purchased one or more of the thirty-five (35) potentially affected Model 1153 Series B, 1154, or 1154 Series H pressure transmitters.

5.0 The corrective action which is taken, the name of the individual or organization responsible for that action, and the length of time taken to complete that action:

(a) RNII held shipments of completed Model 1153 Series B, 1154, and 1154 Series H transmitters and determined which specific units were assembled with diodes from the suspect lot code.

(b) RNII quarantined all Model 1153 Series B, 1154, and 1154 Series H transmitters and sub-assemblies in manufacturing while a determination was made as to which specific units were assembled with diodes from the suspect lot code.

(c) RNII worked with the diode supplier (MSC) to determine the root cause and identify the suspect lot code. Since this part is no longer being manufactured by MSC, no corrective actions were implemented at MSC.

(d) RNII is in the process of reworking all unshipped Model 1153 Series B, 1154, and 1154 Series H transmitters and subassemblies that were completed or in manufacturing that contained diodes from the suspect lot code.

(e) Potentially affected pressure transmitters can be returned and reworked at the factory at the end user's request.

(f) RNII is qualifying a substitute diode to replace the obsolete DZ911218A diode. The qualification Is expected to be complete within the next six months. This qualification ROSEMOUNT" Nuclear Page 2 of 3

2011 Sep 06 02AB PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 4/17 will be documented In an update to the Model 1153 Series B, 1154, and 1154 Series H qualification reports.

Mr. Marc Bumgarner, VP&GM of Rosemount Nuclear Instruments, Inc. is responsible for any further action related to this issue.

6.0 Any advice related to the potential failure of the Item:

RNII recommends that users review the application where any of the thirty-five (35) potentially affected Model 1153 Series B, 1154 and 1164 Series H transmitters are used to determine any safety considerations in the operation of the plant. RNII recommends that potentially affected transmitters be returned to RNII for rework at the end user's earliest opportunity.

Rosemount Nuclear Instruments, Inc. is committed to the nuclear industry and remains dedicated to the supply of high quality products to our customers. If you have any questions, or require additional information related to this issue, please contact: Mike Dougherty (208) 865-1112 or Tracy Kaluzniak (952) 949-7159.

Sincerely, Marc D. Bu rJarmer Vice President & General Manager Rosemount Nuclear Instruments, Inc.

Enc.: Attachment A - List of Affected Transmitters by Company Name and/or Plant Site ROSEMOUNT' Nuclear Page 3 of 3

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 5/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

CONSTELLATION ENERGY GROUP INC Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3052851 432255 1154OPSRC "0544060 7-Jun-li CALVERT CLIFF NUCLEAR POWER PLANT INC 3052851 432256 1154DPSRC 0544061 7-Jun-11 CALVERT CLIFF NUCLEAR POWER PLANT INC 3052851 432256 1154DPSRC . 544062 7-Jun-1l CALVERT CLIFF NUCLEAR POWER PLANT INC 3063381 432246 1154HHSRCNO011 0544056 15-Jun-11 CALVERT CLIFF NUCLEAR POWER PLANT INC 3063381 432246 1154HHSRCNO011 0544057 15-Jun-11 CALVERT CLIFF NUCLEAR POWER PLANT INC

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 6/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

DUKE ENERGY CAROLINAS LLC Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3048416 00143867 11S4DP5RB 0543802 9-May-11 OCONEE NUCLEAR STATION 3048416 00143867 1154DPSRB 0543803 9-May-11 OCONEE NUCLEAR STATION

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 7/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

EDISON MATERIAL SUPPLY LLC I

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 8/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT AB Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3055811 46989079 1154DPSRC 0544312 . 30-Jun-1J RINGHALS NUCLEAR POWER STATION 3055811 46989079 2154DPSRC 0544313 30-Jun-1l RINGHALS NUCLEAR POWER STATION 3055811 46989079 1154EPSRC 0544314 130-Jun-11l RINGHALS NUCLEAR POWER STATION 3

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 9/17 ATTACHMENT: 10 CFR Part 21 NotificatIon - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order f Purchase Order Number Model Number Serial Number Ship Date Site 2597488 HP 80805199/CP2. 1154HSRAN0167 0543641 20-May-11 FUQING 2597488 HP 80805199/CP2. 1154DH5RAN01G7 0543642 20-May-11 FUQING 2597488 HP 80805199/CP1 1154DHSRAN0167 0543643 20-May-11 FUQING 2597488 HP 80805199/CP1 I.1154DHSRAN0172 0543650 20-May-11 FUQING

'4

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 10/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order Purchase Order Model Number Serial Number Ship Data Site Number 2597497 HP 80805206/CP1 1154DH5RAN0167 0543697 20-May-11 FANGJISHAN 2597497 HP 80805206/CP2 1154DHSRAN0167 0543698 20-May-11 FANGJISHAN 2597497 HP 80805206/CP3 1154DHSRAN0167 0543699 20-May-11 FANGJISHAN 2597497 HP 80805206/CP4 - 1154DH5RAN0172 0543710 20-May-11 FANGJISHAN LA

2011 Sep 06 02-48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 11/17 ATTACHMENT: 10 CFR Part 21 NotIfication - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT ASIA PACIFIC PTE LTD Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 2526350 HP 80805673/CPS 1154DHSRAN0152 0543560 20-Apr-11 YANG.JANG 2626350 HP 80805673/CPB 1154DHSRAN0,152 0543561 20-Apr-11 YANGJIANG 262690 m HP ,80805673_/CPS 1154DHSRAN0152 0543558 ........ 20-Apr- YANGIA'NG..

2626350 HP80805673/CPB 1154DHSRAN0152 0543559 20-Apr-11 YANGJIANG 26630 P OBSS3IPB 114D5RNO5Z 05359 0-pr11YAGIAN

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 12/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT NV SA Sales Order Purchase Order 2

Number Model Number FSerial Number Ship Date Site 4 0 3036646 S233042' 11i54HPS RCN0096 1 0'5'4382P7 125-May-21 ITIHANGE

'I

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 13/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

EMERSON PROCESS MANAGEMENT SL Sales Order J Purchase Order Model Number Serial Number Ship Date Site Number 2595531. 35014658 1154SH9RANO060 0543795 14-Jun-l1 ASCO II/VANDELLOS ii 2595531 35014658 1154SH9RAN006 0543797 14-Jun-11 ASCO II / VANDELLOS It 2595531 35014658 1154SH9RAN0062 0543798 14-Jun-li ASCO II/ VANDELLOS II 3

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 14/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

ENTERGY OPERATIONS INC Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3084741 10315334 1153DBSPCN0016 0544302 12-Aug-11 RIVERBEND NUCLEAR STATION 3084741 10315334 1153DBSPCNO016 0544303 12-Aug-11 RIVERBEND NUCLEAR STATION 3069060 10312980 11S4DPSRCNO012 0543654 19-Apr-11 WATERFORD 3 NUCLEAR 3

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 15/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

PACIFIC GAS AND ELECTRIC CO Sales Order Purchase Order Model Number Serial Number Ship Date Site Number3 1 A 3052849 3500892008 1154DHSRC 1 0543822 1 12-May-11 ...... DIABLO CANYON It

2011 Sep 06 02:48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 16/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011.

SOUTHERN NUCLEAR OPERATING CO INC Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3034520 QP1,005/001 . 1154DPSRA 0543725 " 27-Apr-11 FARLEY NUCLEAR PLANT 3034520 QPi,10105/00 j 1S4DP5RA 0543726 27-Apr-11 FARLEY NUCLEAR PLANT 3034520 QP1.0_l05/001 1154DPSRA 0543820 9-May-l1 FARLEY NUCLEAR PLANT 3034520 QP110105/001 1154DPSRA 0543821 9-May-11 FARLEY NUCLEAR PLANT

2011 Sep 06 02,48 PM EPM OUT ROSEMOUNT NUCLEAR 952-949- 17/17 ATTACHMENT: 10 CFR Part 21 Notification - 06 SEPTEMBER 2011, WESTINGHOUSE Sales Order Purchase Order Model Number Serial Number Ship Date Site Number 3065873 4500385592 1154HHSRB 0543715 17-Jun-11 SHIN KORI UNIT 1