QualTech NP Cudiss.Wright Nuclear Division 4600 East Tech Drive, Cincinnati, OH 45245 Phone: 513.528.7900 l F: 513.528.9292 www.q u altech np. onfc. cun WruG']T February 6,2023 Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001
Subject:
Follow up to 10CFR Part2L Notification for QualTech NP supplied Eaton TMR5 timing relays
Dear Sir or Madam:
As a follow up to QualTech NP's Part2L Notice dated November 28, 2022for Eaton TMR5 timing relays (NRC Event #
M122341A032), an extent of condition review has been completed and has identified additionalparts which have digital content that was not previously identified. The extent of condition review covered all orders (500+) received by QualTech NP that required a digital content evaluation. The affected orders are attached. As the specific application(s) for each utility is unknown, QualTech NP cannot determine if these programmable logic devices could affect the safety related function of the parts in question. The end users should evaluate whether the installed items are subjected to unevaluated EMI/RFI conditions or other application specific conditions when installed in the plant.
Root Cause:
QualTech NP's root cause investigation is currently in process.
Corrective Action Taken :
Corrective action taken includes the generation of an enhanced, more detailed digital content inspection procedure and updated, formalized training for all personnel involved.
Please phone (513) 528-7900 if you should have any questions.
Tim Franchuk Quality Assu rance Director QualTech NP, Curtiss-Wright Nuclear Division Office: 513-528-7900, ext. 176
QualTech NP Curtiss-Wright Nuclear Division 4600 East Tech Drive, Cincinnati, OH 45245 Phone: 513.528.7900 l F: 513.528.9292 www. q u alte ch np. cwfc. com WN'GHT Table 1: Affected Orders-Energy Harbor (originalfindingl Customer Plant POfl Manufacturer Mfg. Part s QualTech NP Job f Energy Harbor Perry 1 45529688 Eaton TMR5N1512O CI14538 45537060 TMR5N0412O cJ14941 TMR5N0812O TMR5N2212O 45546965 TMR5N04120 cJ15428 TMR5N08l20 TMR5N22120 45565421 R1 TMR5N04l20 cJ16439 45565487 R1 TMR5N0812O cJ16441 TMR5N2212O 45664L44 TMR5N0412O cJ17918 4s676352 TMR5N22120 cJ18824 Note 1: PO # 45676362 is current order where initial discovery was made.
Table 2: Affected Orders (Extent of Condition Review)
Customer Plant POf Manufacturer Part/ Mfg. Part f QualTech NP Job s Constellation Calvert Cliffs 1& 2 00586264 Rev. 1 Eaton Module,700-HT3 cJ6576 Constellation CalvertCliffsl&2 00656739 Eaton Module,700-HT3 cJ14765 Constellation CalvertCliffsl&2 00675482 Rev. 2 Eaton Module,700-HT3 cJ15295 Energy Harbor BeaverValleyl&2 45545451 Littlefuse & CIT Relay Assembly, KRDR424A4 &
J107F1CS cJt54t4 Energy Harbor BeaverValleyl&2 45553835 Rev. 1 Littlefuse & CIT Relay Assembly, KRDR424A4 &
J107F1CS cJr5770 Pacific Gas & Electric DiabloCanyonl&2 3501093866 Rev. 1 Basler
- Relay, A3E-C2J-BOB1F cJ6316 Entergy Arkansas Nuclear One 1& 2 10506334 Rev. 1 Dayton Electric Relay, 1EGC8 cJ7086 Entergy Arkansas Nuclear Onel&2 L0642793 DaWon Electric Relay, 1EGC8 cJr7632 Luminant Comanche Peak 1
&2 1133206 Rev. 2 Allen-Bradley Relay, 193-1EFLZ cJ18066