ML19190A044

From kanterella
Jump to navigation Jump to search
10 CFR Part 21 Reporting of Defects for Introl Positioner 890265-010 - Cw SAS Initial Report No. 10CFR21-48
ML19190A044
Person / Time
Site: Hatch, Harris, Point Beach, Watts Bar, Cooper, Sequoyah, Farley, Clinton, San Onofre  
Issue date: 06/07/2019
From: Iantorno R
Curtiss-Wright Corp
To:
Document Control Desk, Office of Nuclear Reactor Regulation
Shared Package
ML19190A048 List:
References
Download: ML19190A044 (15)


Text

~----~------

From:

To:

Cc:

Subject:

Date:

Attachments:

Iantorno. Randy F Hoc. HOOX Miller. Craig; Sablotsky. Shane; Johnson. Todd D; Pierce. Justin T (WLS)

[External_Sender] 10 CFR Part 21 Reporting of Defects for Intro! Positioner 890265-010 - CW SAS Initial Report

. No. 10CFR21-48 Friday, June 07, 2019 3:37:57 PM 10 CFR Part 21 Reporting of Defects for Introl Positioner 890265-010.pdf

Dear NRG Operations Center,

A notification was given to the NRG by Paragon dated May 31, 2019.

Because of this there are two actions for Curtiss-Wright Steam Air Solutions (SAS).

1) Curtiss-Wright SAS (Formerly Dresser-Rand) has 5 business days from May 31st, 2019 to notify individual customers of this issue. This notification is attached as CW SAS Initial Report No.

1 OCFR21-48. A separate email is being sent to the end users to advise them of this report.

2) Curtiss-Wright SAS (Formerly Dresser-Rand) has a maximum of 30 business days from May 31st, 2019 to provide final findings to the notified customers.

Please reply to me to acknowledge receipt of this notice.

Please call or email me anytime if you need more information.

Thanks in advance and have a great day/weekend.

Randy F. lantorno Project Manager, Govemment Aftermarket SAS, EMS Division Curtiss-Wright 37 Coats Street, Suite 200, Wellsville, NY 14895 T: 585.596.3831 I M: 585.596.9248 I F: 585.596.3369 riantorno@curtisswright.com I www.cw-ems.com/sas This e-mail and any files transmitted with it are proprietary and intended solely for the use of the individual or entity to whom they are addressed. If you have reason to believe that you have received this e-mail in error, please notify the sender and destroy this e-mail and any attached files. Please note that any views or opinions presented in this e-mail are solely those of the author and do not necessarily represent those of the Curtiss-Wright Corporation or any of its subsidiaries. Documents.attached hereto may contain technology subject to the U.S.

Export-Regulations. Recipient is solely responsible for ensuring that any re-export, transfer or disclosure of this information is in accordance with U.S. Export Regulations. The recipient should check this e-mail and any attachments for the presence of viruses. Curtiss-Wright Corporation and its subsidiaries accept no liability for any damage caus~d by any virus transmitted by this e-mail.

CURTISS-WRIGHT Date: June 7, 2019 NRC Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 SAS Division 37 Coats Street Suite 200 Wellsville, NY 14895 T: 585-596-3289 IF: 585-596-3369 www.cw-ems.com/epd

Subject:

10 CFR Part 21 Reporting of Defects for lntrol Positioner 890265-010 To whom it may concern:

The attached initial reports from Paragon Energy Solutions (PES) and Curtiss-Wright SAS (CW SAS) are intended to inform the NRC and affected customers of a potential defect related to lntrol Positioner, CW SAS part no. 890265-010, installed as p~rt of the CW SAS Electronic Governor Speed Control System (EGSCS).

Shearon Harris Nuclear Plant experienced an overspeed trip of the Turbine Driven Auxiliary Feedwater Pump (TDAFW) on January 18, 2019 during routine system testing. Upon receipt of the initial start signal, the valve remained in the fully open position causing the TDAFW to trip on overspeed. Investigation into the overspeed trip revealed the positioner was not controlling the actuator properly in response to the governor command signal. This situation and subsequent troubleshooting led to replacement with the site spare positioner. Once installed, the system responded as expected and the suspect positioner was sent to Curtiss-Wright SAS for evaluation.

In a joint effort between CW SAS and PES, the positioner was tested and evaluated to determine the cause of the failure. The attachments listed below describe the defect, probable cause and provide testing recommendations until a path forward and final resolution are determined.

CW SAS Initial Report No. 48 PES report dated May 31, 2019 890265-TEST Sincerely, Todd Johnson Mgr., Aftermarket Government. Engineering Curtiss-Wright SAS

INITIAL REPORT 10CFR PART 21 REPORT OF A POTENTIAL SAFETY HAZARD Report No.*

48 eage 1 of 4 Prepared by:

Todd Johnson Date:

June 6, 2019 File No:

F38483A

Title:

Mgr., Aftermarket Government. Engineering Serial No:

T38483A Curtiss-Wright SAS Type:

GS-2 Part No:

890265-010 Part Name:

I ntrol Positioner (890265-010)

Dwg. No:

890265 Rev. Level:

L (i) Name and address of the individual or individuals informing the Commission Todd Johnson, Mgr., Aftermarket Government. Engineering (ii) Identification of the facility, the activity, or the basic component supplied for such facHity or such activity within the United States which fails to comply or contains defect Basis Component: lntrol Positioner, Curtiss-Wright SAS (CW SAS) Part No. 890265-01 O Facility where failure occurred:

Duke Energy / Shearon Harris Additional facilities with potential defect Alabama Power Farley Southern California Edison - SONGS Cooper/ NPPD CNA T / Almaraz Clinton Wolf Creek NEXTERA ENERGY Point Beach Georgia Power Hatch Tennessee Valley Authority (iii) Identification of the firm constructing the facility or supplying the basic component which falls to comply or contains a defect.

Supplier/Dedicator:

Paragon Energy Solutions, LLC 777 Emory Valley Road Oak Ridge, TN 37830 NNS0P12001F2, Initial Report 10 CFR Part 21 Report of a Potential Safety Hazard, REV. 01, 03JUN14, Ref. NNSOP-1-2-001

INITIAL REPORT 10CFR PART 21 REPORT OF A POTENTIAL SAFETY HAZARD Report No.

48 Page 2 of 4 (iv) Nature of the defect or failure to comply and the safety hazard which is created or could be created by such defect or failure to comply.

Internal corrosion discovered inside Texas Instruments (Tl) model TL084N Operational Amplifier chips on the SL3EX Controller Board inside ttie lntrol positioner resulted in the positioner failing. There are a total of three Tl TL084N chips located on the controller board. There is indication the cause of corrosion resulted from delamination during the initial fabrication/soldering process of the board.

Delamination allows possible ingress of solder flux into the chip. The investigation is ongoing and the findings are preliminary at this point. Refer to PES 10 CFR Part 21 Report dated May 31, 2019 for more specific details.

This failure resulted in a loss of steam turqine speed control capability and caused the Turbine Driven Auxiliary Feedwater (TDAFW) Pump to trip on overspeed.

(v) The date on which the information of such defect or failure to comply was obtained.

Curtiss-Wright SAS was notified of the positioner failure on January 23, 2019.

(vi) In the case of a basic component which contains a defect or fails to comply, the number and location of these components in use at, supplied for, being supplied for, or may be supplied tor, manufacture, or being manufactured for one or more facilities or activities subject to the regulations in this part.

\\

Figure 1 below identifies sites where positioners were provided.

(vii) The corrective action which has been is being, or will be taken: the name of the individual or organization responsible for the action: and the length of time that has been or will be taken to complete the action.

  • The three Tl chips on the affecteo board have been successfully replaced at Paragon Energy Systems (PES). The repaired positioner will be configured and returned to Shearon Harris.
  • The evaluation of suspect chips has been limited to those removed frorn the failed positioner, along with some supplied to PES by CW SAS. Work is ongoing in this area.
  • A complete list of potentially affected installations is listed in Figure 1 below and in the PES Part 21 Report dated May 31, 2019.
  • Although this defect has the potential of preventing the Electronic Governor Speed Control System (EGSCS) from performing its intended safety function, it does not prevent the Terry Steam Turbine from operating. If the EGSCS fails, the turbine can be operated manually using the Trip and Throttle Valve (TTV) to control speed by regulating steam flow to the turbine.
  • Steps are being taken to develop a plan to replace chips on affected positioner boards. This is still in the preliminary stages and specific recommendations will follow.

NNS0P12001 F2, Initial Report 10 CFR Part 21 Report of a Potential Safety Hazard, REV. 01, 03JUN14, Ref. NNSOP-1-2-001

INITIAL REPORT 1 OCFR PART 21 REPORT OF A POTENTIAL SAFETY HAZARD Report No.

48 Page 3 of 4 Figure 1: Affected sites with potentially affected positioners Client / End User 3rd Party Description -

Turbine CW SAS Shipment Engineering Firm HPCI/RCIC Aux Serial No.

Project No.

Year Alabama Power Farley Bechtel GS-2-Aux 37858A 343670 Jan-08 Alabama Power Farley Bechtel GS-2-Aux 378588 343670 Jan-08 Southern California Bechtel GS-2-Aux 40101A 375259 June-09 Edison - SONGS Southern California Bechtel GS-2-Aux 401018 375259 Jun-09 Edison - SONGS Cooper I NPPD Engineering GS-1 RCIC 35939A 478937 Sep-15 Solutions CNA T / Almaraz GS-2 -Aux 38467A 501197 Mar-15 CNAT / Almaraz GS-2 -Aux 384678 501197 Mar-15 Clinton Engineering GS-2 RCIC 38187A 513114 Dec-12 Solutions Duke Energy/ Shearon Engineering GS-2-Aux 41056A C34778 Dec-14 Harris Solutions Wolf Creek Hurst GS-2-Aux 40177A C34590 Decr-12 Technologies NEXTERA ENERGY Sargent Lundy GS-2 -Aux D6729 C34587 Sep-13 Point Beach NEXTERA ENERGY Sargent Lundy GS-2 -Aux D6730 C34587 Sep-13 Point Beach Georgia Power Hatch Bechtel GS-1 RCIC 36681A 142513 Mar-16 Georgia Power Hatch Bechtel GS-1 RCIC 37121A 142513 Mar-16 Tennessee Valley Engineering GS-2AUX 38677A 146320 Jan-17 Authority WB-1 Solutions Tennessee Valley Engineering GS-2AUX 386778 146320 May-17

. Authority WB-2 Solutions Tennessee Valley Engineering GS-2AUX 37480A 160361 Aug-18 Authority SQ-1 Solutions Tennessee Valley Engineering GS-2AUX 374808 160361 Sep-18 Authority SQ-1 Solutions NNS0P12001 F2, Initial Report 1 O CFR Part 2'.I Report of a Potential Safety Hazard, REV. 01, 03jLJN14, Ref. NNSOP-1-2-001 Installed/

Commissioned May-10 May-10.

Jan-10 Jan-10 Oct-18 Jul-17 Jan-17 TBD Oct-16 Mar-13 Sep-14 Sep-14 TBD TBD April-17 Nov-17 October.;19 (Scheduled}

April-20 (Scheduled)

INITIAL REPORT 10CFR PART 21 REPORT OF A POTENTIAL SAFETY HAZARD Report No.

48 Page 4 of 4 (viii)'

Any advice related to the defect or failure to comply about the facility, activity, or basic component that has been, is being, or wilt be given to purchasers or licensees.

Until a solution is finalized, increased monitoring and system testing is recommended. *Test procedure 890265-TEST has been developed to evaluate positioner functionality and determine if performance is degrading. Test instructions and acceptance criteria are included On an individual plant basis, Curtiss-Wright SAS does not have the capability to complete the 1 OCFR Part 21 evaluation to determine if the condition would result in a substantial safety hazard. This notification provides notification of the potential defect so sites can evaluate their individual situations.

Evaluation/Recommendation Prepared By:

Todd Johnson

Title:

Mgr., Aftermarket Govt. Engineering Date:

June 6, 2019 Approved By:

Todd Johnson

Title:

Mgr., Aftermarket Govt. Engineering Date:

June 6, 2019 DISPOSITION, CHECK ONE:

IT] Yes, this constitutes a safety hazard and requires a Final Report be prepared (NNS0P12001F1)

CJ No, this does not constitute a safety hazard and does not require any further reporting.

Reviewed by Curtiss-Wright SAS General Manager:

Signature: ~a A ~,;.!-.,, \\Nn.1 llr o..l 0 Title_:~~-1.

Date:

I.Db \\\\g RETURN TO RESPONSIBLE NUCLEAR PRODUCT ENGINEERING MANAGER NNS0P12001F2, Initial Report 10 CFR Part 21 Report of a Potential Safety Hazard, REV. 01, 03JUN14, Ref. NNSOP-1-2-001

May 31, 2019 Document Control Center U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

10 CFR Part 21 Report of Defect GS2 Terry Turbine Intro! Positioners To whom this may concern:

a) Individual informing NRC and address:

Ray Chalifoux Paragon Energy Solutions LLC 777 Emory Valley Road Oak Ridge, TN 37830 b) Basic component supplied which contains a defect:

GS2 Terry Turbine lritrol Positioners P/N: 890265-010 c)

  • Supplier of the Basic Component:

lntrol Positioners used by stations in GS2 T'en-y T'urb1ne controi*appiicaii011s-have-the-putentiai-io* -

contain a latent defect. The defect is the result of internal corrosion which has been identified in Tl Operational Amplifiers Part No.TL084CN on the SL3EX Controller Boards of the turbine throttle valve positioner. It is believed the likely cause is associated with the ingress of solder flux into the IC Chip package on the controller board due to delamination caused by the soldering process during fabrication. The corrosion over time can result in intermittent open circuiting and high resistance in the aluminum metallization. Chlorine ionic contamination can also result in high leakage currents within the component circuitry:Failures may be manifested by a reduced valve position signal disproportional to the expected demand condition, no actuation signal i.e. throttle valve remaining full open, or other anomalous unexpected behavior. There are three TL084CN chips on each SL3EX Controller Board within the positioner assembly. There have been two documented failures to date occurring in 2015 and 2019 in installed systems.

e) Date determination made:

May 29, 2019 f)

Number and location of these components: identifies positioners provided to stations. Positioners provided to Farley Station and SONGS were not dedicated by ATC-Nuclear.

g) Corrective action taken:

Paragon Energy Solutions replaced the TL084CN Chips on the failed positioner as directed by Curtiss-Wright SAS and the Licensee. Curtiss-Wright SAS has identified the list of Intro! Positioners provided to licensees.

h) Any advice related to the defect:

Licensees should coordinate through Curtiss-Wright SAS (formerly Dresser Rand) to implement repair strategies.

Additional Background ATC-Nuclear (now Paragon Energy Solutions) originally dedicated 35 lntrol assemblies from 2011 to 2013 for Dresser Rand (now Curtiss-Wright SAS) as part of a terry turbine digital control system upgrade utilizing the Intro! Positioner product line.

Recently, Paragon was contracted by Curtiss-Wright SAS under Purchased Order 17029549 to evaluate a Shearon Harris positioner failure. Two units were provided to Paragon under the purchase order listed above for evaluation. The licensee assembly, S/N 01046M13, was installed and had been in service at the station since October 2016. This unit failed prompting this evaluation. Following identification of the failure as described above, corrosion internal to other TL084CN Chip packages in the second positioner' provided by Curtiss-Wright SAS was identified. This positioner, however, did not fail and continued to operate normally. A previous failure of a TL084CN Chip was also identified in 2015.

The

  • analyses and evaluations performed by Paragon do not consider purchasers and/or licensee application-specific information as it only focuses on the functional performance of the positioner. On this basis, Paragon does not have the capability to complete the 10CFR Part 21 evaluation to determine whether the condition reported could cause a substantial safety hazard. This notification serves to inform purchaser(s) and/or affected licensees of this determination, so they may evaluate the identified condition, pursuant to §10CFR 21.21(a).

Stations are advised to work directly with Curtiss-Wright SAS via the technical contacts below.

Randy F. lantorno Project Manager, T: 585.596.3831, M: 585.596.9248, email riantorno@curtisswright.com or*

Justin Pierce 585.596.3866, email jpierce@curtisswright.com

~ (J J. j.L...

I.

Ray6ialifu~~ Paragon ES T: 865.384.0124 or email rchalifoux@paraqones.com

Affected Facilities Client/ End User 3rd Party Engineering Description -

Turbine Serial cw Shipment Year Installed/

Firm HPCI/RCIC Aux Project#

  • commisioned Alabama Power Bechtel GS-2-Aux 37858A 343670 January-OB May-10 Farley Alabama Power Bechtel GS-2-Aux 37858B 343670 January-OB May-10 Farley Southern California Bechtel GS-2-Aux 40101A 375259 June-09 January-10 Edison - SONGS Southern California Bechtel GS-2-Aux 40101B 375259 June-09 January-10 Edison - SONGS Engineering GS-1 RCIC 35939A 478937 September-15 October-18 Cooper/ NPPD Solutions CNAT / Almaraz GS-2-Aux 38467A 501197 March-15 July-17 CNAT / Almaraz GS-2-Aux 38467B 501197 March-15 January-17

- - -- *--~---- -

Engineering GS-2 RCIC 38187A 513114 December-12 To Be Clinton Solutions Determined Duke Energy/

Engineering GS-2-Aux 41056A C34778 December-14 October-16 Shearon Harris Solutions Wolf Creek Hurst Technologies GS-2-Aux 40177A C34590 December-12 March-13 NEXTERA ENERGY Sargent Lundy GS-2-Aux D6729 C34587 Seplember-13 September-14 Point Beach NEXTERA ENERGY Sargent Lundy GS-2-Aux D6730 C34587 September-13 September-14 Point Beach Bechtel GS-1 RCIC 36681A 142513 March-16 To Be Georgia Power Hatch Determined Bechtel GS-1 RCIC 37121A 142513 March-16 To Be Georgia Power Hatch Determined Tennessee Valley Engineering GS-2AUX 38677A 146320 January-17 April-17 Authority WB-1 Solutions Tennessee Valley Engineering GS-2AUX 38677B 146320 May-17 November-17 Authority WB-2 Solutions

Tennessee Valley Engineering GS-2AUX October-19 Authority SQ-1 37480A 160361 August-18 Solutions (Scheduled)

Tennessee Valley Engineering GS-2AUX April-20 Authority SQ-1 37480B 160361 September-18 Solutions (Scheduled)

FUNCTIONAL TEST PROCEDURE FOR INTROL POSITIONER PART# 890265-010.

Document No.: 890265-TEST Created By Mark Konieczny 6/7/2019 1.0 Purpose The purpose of this testing is to ensure proper operability of the lntrol Positioner Curtiss-Wright SAS (CW SAS) part# 890265-010.

2.0 Background

lntrol Positioners used in nuclear safety related digital governor control systems for Terry GS-1 and GS-2 frame turbines have the potential to contain a latent defect. Further information of this defect can be found on the filing of the 10 CFR Part 21 reporting submitted by Paragon Energy Systems to the NRC on May 31 5

\\ 2019 and Curtiss-Wright SAS 10 CFR Part 21 Report 48.

3.0 Equipment 4 to 20 current co111mand source such as an Altex Loop Calibrator Model 434KP Digital multimeter capable of reading both voltage and current such as Fluke model 115 Personal Computer (PC) with DR Positioner 890265-010 GUI software installed Communications cable capable of communicating to the positioner using RS-485 protocol Exlar Actuator DR part# 890267-001 Power Cable DR part #890268-701 or equivalent Resolver Feedback cable DR part #890268-703 or equivalent GS-2 turbine governor valve with actuator adapter bracket or bonnet fixture lntrol Positioner 890265-010 or 890265-701 500 ohm precision resistor Switch to be used as an enable switch for the positioner 4.0 Functional Test Procedure For the following connections refer to Figures 1 and 2 attached and the Installation and Operation manual. Also refer to the ESI site specific schematics. For a copy of schematics; contact CW SAS. If this test is being performed with the positioner installed in a panel, it may be necessary to lift and protect some connections to the lntrol positioner.

1

FUNCTIONAL TEST PROCEDURE FOR INTROL POSITIONER PART# 890265-010

1. Verify power to the system is removed.
2.

Connect the power cable and resolver cable connections at both the actuator end and

\\

positioner end. This can include filters or not.

3.

Connect the RS-485 communications cable from the PC with the lntrol GUI installed to TB3-2 (+)

and TB3-1 (-). See figure 1.

4.

Connect 4 to 20 mA_current command source to TB3-11 (+) and TB3-12 (-). See figure 1. If actuator 1 output from the Woodward 505 governor is connected, these wir~s will have to be lifted first.

5.

Connect a jumper-from TBl-1 to TB3-4. See figure 1.

6.

Connect an enable switch between TBl-6 and TB3-6. Make sure the switch is in the off position.

See figure 1.

7.

Connect a 500 ohm precision resistor in series with a 24 vdc power supply to TB3-7 (+) and TB3-

. 8 (-) a*ctual position output. Refer to figure 7.11 page 21 of the Installation and Operation manual and figure 2.

8.

Ensure the power supply is off. Connect power to TB4-5 (+) and TB4-4 (-).

9.

Power up the PC and open the lntrol Positioner GUI interface. Refer to lntrol Positioner Installation and Operation Manual.

10. Apply power to the lntrol positioner. Verify the Power LED illuminates* and the fans are running.
11. Using the GUI interface, select the Upload/pownload tab. Upload the configuration from the drive to the PC.
12. Change the tab to drive monitor. Select the monitor button to monitor the drive.
13. Using the current command source, ~pply 4 rriA to the command input.
14. Turn on *the 24 vdc power supply that is in series with the resistor.
15. Turn the enable switch to or;i. The actuator should home closing the governor valve (extend).
16. Increment the command signal in 4 mA steps. The resulting position read by the GUI and the voltage across the resistor should match the chart below. It is recommended to use a precision resistor.

2

FUN.CTIONAL TEST PROCEDURE FOR INTROL POSITIONER PART# 890265-010 Position position position mA inches min max volts de de volts min de volts max 4

.750*

.740

.760 2*

1.893 2.107 8

.563

.553

.573 4

3.893 4.107 12

.375

.365

.385 6

5.893 6.107 16

.188

.178

.198 8

7.893 8.107 20

.000

-.010

.010 10 9.893 10.107

  • Note 1-The value may exceed tolerance if fixture lacks rigidity.

5.0 Conclusions If the position values fall within acceptable ranges, the positioner is functioning properly. If the values fall outside of the acceptance criteria, the positioner is not functioning properly. Please contact CW SAS for further instructions.

3

Dresser-Rand PN 890265 Posttioner SFault Fault Power 10 Output 3 9 Output 2 B Output 1 7 Output Power TB4

-Bus 12

+Bus 11 DB 10

.. R s

T r----...i1 6 +Enable Enable Switch RS485 Serial Port

+TxD/RxD-----

- TxD /RxD-'-,lv------'

5 +Emg Position 4 +Home LS.

  • 3 +Home Initiate 2

Input Power Initiate Figure 1 L2 L3

+Exe

-Exe TB2

+Sin

-Sin

+Cos

-Cos Shield

+5VDC 3 rl;4J>,Wi~, 2 TMotor 1 1 herma Foil & Braid II II

+ 120 voe,

~---4---4-------

SHIELD

'1 1----------------,,,_f-n_MOTOR THERMAL 1--------------------------' SWITCH For clarity, not all connections shown. Motor and resolver shown without filter connections.

SOOohm External 24V Dresser-Rand PN 890265 Position er SFault Fault Power 10 Output 3 9 Output 2 8 Output 1 7 Output Power 6 +Enable 5 +Emg Position 4 +Home LS.

3 +Home Initiate 2

Input Power Initiate 6 +15VDC 5 -15VDC

'"-----11 4 COM.

3 2

1 Figure 2 T84

-Bus 12

+Bus 11 DB 10 R

s T

L1 L2 L3

+Exe

-Exe

+Sin

-Sin

+Cos

-Cos T82 Shield

+5VDC 3 Foil & Braid I\\

+ 120 1----4---1------

SHIELD Mt MOTOR T o or 1 2 1-----------0--1::-,:,.........,

erma THERMAL T~fr~~I 1 SWITCH For clarity, not all connections shown. Motor and resolver shown without filter connections.