- 05000272/LER-1986-016-01, :on 860805 & 06,steam Generator Feed Pump 11 Tripped & Feed Flow/Steam Flow Mismatch Alarm Occurred, Respectively.Caused by Diode Failure & Accidental Grounding of Circuit.Diode Replaced.Wiring Relocated + (06:37:37, 4 December 2024)
- IR 05000266/1986013 + (06:37:40, 4 December 2024)
- ML20214L387 + (06:37:40, 4 December 2024)
- ML20214L379 + (06:37:41, 4 December 2024)
- ML20214L375 + (06:37:42, 4 December 2024)
- ML20214L372 + (06:37:43, 4 December 2024)
- ML20214L368 + (06:37:44, 4 December 2024)
- ML20214L367 + (06:37:45, 4 December 2024)
- ML20214L366 + (06:37:45, 4 December 2024)
- U-600699, Responds to NRC Re Concern Noted in Insp Rept 50-461/86-45.Corrective Actions:Maint Work Request Issued, Requiring Stem Lubrication of safety-related motor-operated Valves & External Check of Each Valve + (06:37:46, 4 December 2024)
- ML20214L363 + (06:37:46, 4 December 2024)
- IR 05000206/1986032 + (06:37:48, 4 December 2024)
- ML20214L354 + (06:37:48, 4 December 2024)
- B12226, Requests That Due Dates to Discuss Results of Steam Generator Tube End Study Be Revised to Wk of 861020 & Submittal of Corrective Actions for Undefined Signals to 861114,due to Diversion of Resources for Unplanned Outage + (06:37:49, 4 December 2024)
- ML20214L349 + (06:37:50, 4 December 2024)
- IR 05000213/1986020 + (06:38:02, 4 December 2024)
- ML20214L346 + (06:38:02, 4 December 2024)
- ML20214L340 + (06:38:03, 4 December 2024)
- ML20214L338 + (06:38:04, 4 December 2024)
- 05000272/LER-1986-018-01, :on 860806,Limitorque Motor Valve Operators W/O Environ Qualified Wires Discovered.Caused by Insufficient Control of Wiring During Operator Assembly. Wiring Replaced.Stored Wires Will Be Inspected + (06:38:05, 4 December 2024)
- ML20214L336 + (06:38:06, 4 December 2024)
- ML20214L331 + (06:38:07, 4 December 2024)
- ML20214L326 + (06:38:07, 4 December 2024)
- RBG-24271, Special Rept:On 860729,temps in North End of Main Steam Tunnel Rose Above Tech Spec Limit.Caused by Inadequate Air Circulation & Location of Thermocouples.Permanent Installation of Addl Air Supply Duct Work Planned + (06:38:08, 4 December 2024)
- ML20214L321 + (06:38:09, 4 December 2024)
- ML20214L322 + (06:38:09, 4 December 2024)
- ML20214L319 + (06:38:11, 4 December 2024)
- ML20214L317 + (06:38:11, 4 December 2024)
- ML20214L314 + (06:38:12, 4 December 2024)
- 05000341/LER-1986-024, :on 860806,during Startup,Spurious Actuation of Control Ctr Ventilation Sys Initiated.Caused by Interference from Handheld Radio frequency.Nonradio-based Communication Sys to Be Installed + (06:38:13, 4 December 2024)
- ML20214L309 + (06:38:14, 4 December 2024)
- ML20214L304 + (06:38:15, 4 December 2024)
- ML20214L307 + (06:38:15, 4 December 2024)
- ML20214L301 + (06:38:16, 4 December 2024)
- ML20214L299 + (06:38:17, 4 December 2024)
- ML20214L293 + (06:38:18, 4 December 2024)
- 05000529/LER-1986-021-01, :on 860806,discovered That Train B LPSI Pump Header Discharge Throttle Valve Not Adjusted to Proper Setting.Caused by Personnel Error on 860717 Due to Unclear Procedure.Separate Procedures in Effect + (06:38:21, 4 December 2024)
- ML20214L287 + (06:38:22, 4 December 2024)
- ML20214L286 + (06:38:22, 4 December 2024)
- ML20214L283 + (06:38:23, 4 December 2024)
- ML20214L281 + (06:38:24, 4 December 2024)
- ML20214L279 + (06:38:24, 4 December 2024)
- ML20214L278 + (06:38:25, 4 December 2024)
- 05000348/LER-1986-015, :on 860805,reactor Trip & Subsequent Main Steam Line Isolation Occurred.Caused by Reduction in Feedwater Flow to Steam Generator 1C Due to Failed Printed Circuit Card.Card Replaced + (06:38:27, 4 December 2024)
- ML20214L274 + (06:38:27, 4 December 2024)
- ML20214L273 + (06:38:28, 4 December 2024)
- 05000413/LER-1986-041, :on 860801,reactor Bldg Fire Detection Zones Surveillance Test Not Performed for More than 24 H from 860615-19.Cause Under Investigation.Final Rept Expected by 860926 + (06:38:30, 4 December 2024)
- ML20214L270 + (06:38:30, 4 December 2024)
- ML20214L268 + (06:38:31, 4 December 2024)
- 05000373/LER-1986-034, :on 860807,automatic Start of Diesel Generator 1B Occurred.Caused by Spurious Actuation of Protection Logic Relay.Relay Replaced + (06:38:34, 4 December 2024)