4 t

a ATTACHMENT Consumers Power Company Palisades Plant Docket 50-255 SEMIANNUAL RADI0 ACTIVE EFFLUENT RELEASE AND WASTE DISPOSAL REPORT JANUARY THROUGH JUNE 1986 August 27, 1986 i

8609100111 860630 PDR ADOCK 05000255 R

PDR 9 Pages

?

_..e1se._

J

\\/\\

1 PALISADES NUCLEAR PLANT SEMIANNUAL EFFLUENT RELEASE REPORT January - June 1986 This report provides information relating to radioactive effluent releases and solid radioactive waste disposal operations of the Palisades Plant during the period of January through June 1986 in the format contained in Plant Technical Specification 6.9.3.la.

The January - June 1986 semiannual effluent release report reflects effluent Technical Specification changes effective January 1, 1985. Palisades has been off-line since May 19, 1986 due to an extended maintenance outage.

1.

SUPPLEMENTAL INFORMATION A.

BATCH RELEASIS Information relating to batch releases of liquid and gaseous effluent is provided in Table HP 10.5-1.

B.

ABNORMAL RELEASES None I

j 2.

_ GASEOUS EFFLUENTS Table HP 10.5-2 lists and summarizes all gaseous radioactive effluents released during the reporting period. The unidentified beta was 4.04E-05% of the total release.

3.

LIQUID EFFLUENTS Table HP 10.5-3 lists and summarizes all liquid radioactive effluents released during the reporting period. The unidentified beta was 1.35E-02% of the total release.

4.

SOLID WASTE Solid radvaste classification, sources, volume shipped, curie and nuclide content are detailed in Table HP 10.5-4.

All radwaste shipments were made to either Barnwell, South Carolina or Richland, Washington for burial.

i 5.

SUMMARY

OF RADIOLOGICAL IMPACT ON MAN l

Potential doses to individuals and populations were calculated using GASPAR and LADTAP computer program codes. The first and second quarter l

values for curies released were input for each nuclide and summarized as i

follows:

l l

A.

The maximum offsite air doses at site boundary due to noble gases l

were 1.19E-03 and 7.07E-03 millirads beta for the first and second l

i I

i AT0886-0136-NLO2

_._.., _ _ _. _ ~, _ _ _.,, _. _ _ _

t

+

2 quarters respectively. The maximum offsite air doses for gamma were 3.96E-04 and 2.37E-03 millirads, respectively.

B.

The most restrictive organ dose to an individual in an unrestricted area (based on identified critical receptors) from gaseous effluents (tritium, particulate and iodine) was the infant thyroid. Doses were 2.57E-03 and 4.72E-03 millirem for the first and second quarters.

C.

The maximum total body doses to individuals in unrestricted water-related exposure pathways were 1.08E-02 and 5.10E-03 millirem for first and second quarters, respectively, with the maximum organ dose being (teenager bone) 2.07E-02 and (teenager liver) 8.43E-03 millirem per quarter, respectively.

D.

Integrated total body doses to the general population and average doses to individuals within the population from liquid effluent releases within a distance of 50 miles from site boundary were 3.60E-02 and 1.68E-02 manRem for the first and second quarters, respectively, and 3.43E-05 and 1.60E-05 millirem per quarter, respectively.

E.

Integrated total body doses to the general population and average doses to individuals within the population from gaseous effluent releases within a distance of 50 miles from site boundary were 1.04E-02 and 6.26E-03 manRem for the first and second quarters respectively with 9.90E-06 and 5.98E-06 millirem per quarter respectively.

F.

Entrained noble gas DBQ fractions in liquid releases and Se-75 DBQ fractions in gaseous releases were not significant in either wholebody or organ doses.

6.

PROCESS CONTROL PROGRAM (PCP)

There were no changes to the PCP this reporting period.

7.

OFFSITE DOSE CALCULATION MANUAL (ODCM)

There were no changes to the ODCM this reporting period.

AT0886-0136-NLO2

l'..

4 3

TABLE HP 10.5-1 PALISADES PLANT / SEMIANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT BATCH RELEASES JANUARY 1986 to JUNE 1986 A. GASEOUS Units 1st Quarter 2nd Quarter Number of Releases 23 10 Total Release Time Minutes 6.64E+03 3.30E+03 Maximum Release Time Minutes 5.88E+02 7.38E+02 Average Release Time Minutes 2.89E+02 3.30E+02 Minimum Release Time Minutes 9.30E+01 1.45E+02 B. LIQUID Number of Releases 56 19 Total Release Time Minutes 5.23E+03 2.29E+03 Maximum Release Time Minutes 6.15E+02 6.65E+02 Average Release Time Minutes 9.35E+01 1.20E+02 i

Minimum Release Time Minutes 3.80E+01 3.80E+01 l

l I

l I

l j

AT0886-0136-NLO2

- - ~ _. - _. - _,.. -. - -... _

l, I

4 TABLE HF 10.5-2 PALISADES PLANT / SEMIANNUAL RADI0 ACTIVE EFFLUENT RELEASE REPORT GASEOUS EFFLUENTS - SUMMATION OF RELEASES JANUARY 1986 to JUNE 1986 Eat Total A. FISSION AND ACTIVATION CASES Units 1st Qtr 2nd Qtr Error %

1.

Total release C1 2.49E+01 1.48E+02 2.

Average release rate for period uCi/sec 3.20 1.88E+01 4.05 3.

Percent of annual avg MPC 1.52E-03 8.97E-03 B. 10 DINES 1.

Total Iodine Ci 9.33E-04 1.50E-03 2.

Average release rate for period uCi/see 1.20E-04 1.91E-04

  • 6.26 3.

Percent of annual avg MPC 7.63E-05 1.45E-04 C. PARTICULATES 1.

Particulates with half-life >

8 days Ci 3.75E-04 1.37E-04 2.

Average release rate for period uCi/sec 4.82E-05 1.74E-05 27.5 3.

Percent of annual avg MFC 4.14E-05 8.85E-06 4.

Gross alpha radioactivity C1 1.64E-06 1.48E-06 D. TRITIUM 1.

Total Release Ci 8.90E-01 8.13E-01 2.

Average release rate for period uCi/sec 1.14E-01 1.03E-01 3.

Percent of annual avg MPC 8.17E-05 7.39E-05 E.

1.

Beta air dose at Site Boundary due to Noble Gases (TS 3.24.5.2a) mRads 1.19E-03 7.07E-03 2.

Percent limit 1.19E-02 7.07E-02 3.

Gamma. air dose at Site Boundary due to Noble Gases (TS 3.24.5.21) mRads 3.96E-04 2.37E-03 4.

Percent limit 7.92E-03 4.74E-02 F.

1.

Maximum organ dose to public based on Critical Receptors (TS 3.24.5.3) mrem 2.57E-03 4.72E-03 2.

Percent of limit 3.43E-02 6.29E-02 ANote: Data is reported for I-131 and I-133 only.

AT0886-0136-NLO2

-?.

5 TABLE HP 10.5-2 (Cont'd)

PALISADES PLANT / SEMIANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GASEOUS EFFLUENTS JANUARY 1986 to JUNE 1986

1. FISSION CASES Units 1st Quarter 2nd Quarter Krypton-85 Ci 1.18E-01 2.25E-01 Krypton-85m Ci 6.23E-03 2.65E-03 Krypton-87 Ci None 8.76E-04 Krypton-88 Ci None None Xenon-131m Ci 7.10E-02 2.75E-02 Xenon-133 Ci 2.47E+01 1.48E+02 Xenon-133m Ci 5.11E-03 2.98E-02 Xenen-135 Ci 8.88E-04 1.73E-02 Xenon-135m Ci None 1.93E-02 Xenon-138 Ci None None

-Argon-41 Ci None None Total.or Period Ci 2.49E+01 1.48E+02

2. Iodines i

Iodine-131 Ci 3.07E-04 5.64E-04 Iodine-132 Ci None None Iodine-133 Ci 3.06E-04 9.32E-04 Iodine-135 Ci 3.20E-04 None l

Total for Period Ci 9.33E-04 1.50E-03 i

AT0886-0136-NLO2

..... ~

4

'l 6

TABLE HP 10.5-2 (Cont'd)

PALISADES PLANT / SEMIANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GASEOUS EFFLUENTS JANUARY 1986 to JUNE 1986

3. PARTICULATES*

Units let Quarter 2nd Quarter Chromium-51 Ci 3.49E-05 None Manganese-54 Ci None None Cobalt-58 Ci 3.42E-05 2.40E-06 Cobalt-60 Ci 4.81E-06 3.50E-06 Zinc-65 Ci None None Silver-110m Ci None None Cesium-134 Ci None None Cesium-137 Ci 1.76E-06 6.49E-07 Barium-140 Ci None None l

Selenium-75 Ci 2.30E-04 1.17E-04 Cobalt-57 Ci 4.62E-06 None Strontium-89**

C1 1.68E-06 3.10E-06 Strontium-90**

C1 1.90E-06 1.40E-06 l

l l

Net unidentified beta Ci 6.11E-05 8.80E-06 Total Ci 3.75E-04 1.37E-04 c

  • Particulates with half-live >8 days.
    • Calculated from vendor analysis of monthly stack gas filters.

NOTE: Reported not beta and vendor analyzed Sr-89/90 results were input to GASPAR code as Sr-90 to yield conservative dose estimates.

l AT0886-0136-NLO2

.... _. - _ _... -. _ _ _, _. _ _ _ _. _.... _ ~.. _. -. - _..., _

4-7 TABLE HP 10.5-3 PALISADES PLANT / SEMIANNUAL RADI0 ACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES JANUARY 1986 to JUNE 1986 Est Total A. FISSION AND ACTIVATION GASES Units 1st Qtr 2nd Qtr Error %

1.

Total release (not including tritium, gases, alpha)

C1 1.11E-01 7.98E-03 2.

Average diluted concentration during period uCi/ml 4.33E-09 2.56E-10 7.74 3.

Percent of MPC 7.18E-02 9.12E-04 B. TRITIUM 1.

Total Release C1 1.91E+01 1.48E+01 2.

Average diluted concentration during period uCi/ml 7.43E-07 4.75E-07 4.05 3.

Percent of MFC 2.48E-02 1.58E-02 C. DISSOLVED AND ENTRAINED GASES 1.

Total release C1 None 4.87E-05 2.

Average diluted concentration during period uCi/ml None 1.56E-12 11.9 3.

Percent of MPC None 7.80E-07 D. GROSS ALPHA RADI0 ACTIVITY **

(Total Release)

Ci 3.74E-06 4.02E-06 E. VOLUME OF WASTE RELEASED (Prior to Dilution)

Liters 1.16E+06 5.02E+05 F.

VOLUME OF DILUTION WATER USED DURING PERIOD Liters 2.57E+10 3.12E+10 G. MAXIMUM DOSE COMMITMENT - WHOLEBODY mrem 1.08E-02 5.08E-03 Percent of TS 3.24.4.la. limit 7.20E-01 3.39E-01 l

l H. MAXIMUM DOSE COMMITMENT - ORGAN mrem 2.07E-02 8.43E-03 Percent of TS 3.24.4.la limit 4.14E-01 1.692-01

    • Calculated from vendor analysis of monthly radwaste composite samples.

AT0886-0136-NLO2

8 TABLE HP 10.5-3 9

(Cont'd)

PALISADES PLANT / SEMIANNUAL RADIOACTIVE EJFLUENT RELEASE REPORT LIQUID EFFLUENTS JANUARY 1986 to JUNE 1986

1. NUCLIDES RELEASED Units 1st Quarter 2nd Quarter Cesium-137 Ci 3.45E-03 2.01E-03 Cobalt-58 Ci 5.61E-02 3.09E-03 Manganese-54 Ci 2.05E-03 4.71E-04 Cobalt-60 Ci 1.09E-02 1.45E-03 Cesium-134 Ci 6.51E-04 5.11E-04 Iron-59 Ci 7.39E-04 None Niobium-95 Ci 2.80E-04 6.40E-06 Ruthenium-103 Ci 9.56E-06 None Cobalt-57 Ci 6.87E-05 None Selenium-75 C1 3.76E-05 None Zirconium-95 Ci 2.41E-04 None Strontium-89**

Ci 4.83E-04 5.49E-05 Strontium-90**

Ci 7.27E-05 9.04E-06 Chromium-51 Ci 3.17E-02 3.78E-04 Net Unidentified Beta Ci 4.59E-03 None Fission & Activation Product Total (above)

Ci 1.11E-01 7.98E-03 Xenon-133 Ci None 4.87E-05 Xenon-133m Ci None None Xenon-135 Ci None None Krypton-85m Ci None None Tritium C1 1.91E+01 1.48E+01 Grand Tocal Ci 1.92E+01 1.48E+01 wa Calculated from vendor analysis of monthly radwaste composite samples.

Nste: Reported net beta and vendor analyzed Sr-89/90 results were input to LADTAP code as Sr-90 to yield conservative dose estimates.

AT0886-0136-NLO2

f l

9 TABLE HP 10.5-4 PALISADES PLANT / SEMIANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SOLID WASTE' JANUARY 1986 to JUNE 1986 Wnate Source of Solidification Container Volume Total

  • Principal Clans Waste Agent Type (Cu.ft.)

Curies Radionuclides A

DAW N/A B-25 Box-LSA 4900 15.7 H,Mn-54,Fe-55,Co-57, C$-60,NI-63,Sb-125, Cs-134,Cs-137,Ce-144, Pu-241,Te-125 A

Waste Oil Delaware Cust.

Drums-LSA 11.6 0.02 Mn-54,Co-58,Co-60, Cement Cs-134,Cs-137,Fe-55, H,C-14,Pu-241 3

A Filters &

N/A HIC-14-195H 193.0 6.9 Co-58,Co-60,Cs-134, DAW Cs-137,Fe-55,H,Cr-51 3

Mn-54 A

Evaporator Delaware Cust.

Drums-LSA 38.2 0.40 Mn-54,Co-58,Co-60, Bottoms Cement Cs-134,Cs-137,t-14, Fe-55,Ni-63,Cm-242, Pu-242,Cm-244,Am-241, Pu-239,Pu-238,Sr-90, Tc-99,H3 A

Evaporator Asphalt Drums-LSA 897.5 53.3 Mn-54,Co-58,Co-60, Bottoms Cs-134,Cs-137,C-14, Fe-55.Ni-63,Cm-242, Pu-242,Cm-244,Am-241, Pu-239,Pu-238,Sr-90, Tc-99,H3 Total Shipped 6040.3 76.3

  • Note: Gamma Isotopes are measured quantities, all other isotopes are estimated.

AT0886-0136-NLO2

PRIORITY ROUTING

@newsmus First Egj;d; Consumers A

@r Power 3;

p-n[yv au Fk mannansranensa General offices: 1946 West Parnall Road, Jackson, MI 49201 e (517) 788-0550 August 27, 1986 James G Keppler, Administrator Region III US Nuclear Regulatory Commissien 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

SEMIANNUAL RADI0 ACTIVE EFFLUENT RELEASE AND WASTE DISPOSAL REPORT - JANUARY THROUGH JUNE 1986 Attached is the Semiannual Radioactive Effluent Release and Waste Disposal Report for Palisades Plant for the period January through June 1986. The attached report is submitted in accordance with 10CFR50.36a(2) and Technical Specification Section 6.9.3.

A b

Ralp R risch Senior Licensing Analyst CC Director, Office of Nuclear Reactor Regulation Director, Office on Inspection and Enforcement NRC Resident Inspector - Palisades Attachment

/y }

/

U I

t OC0886-0136-NLO2 AUG 29 m