Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19331B720 + (09:13:41, 31 December 2024)
- ML19331B719 + (09:13:42, 31 December 2024)
- ML19331B718 + (09:13:43, 31 December 2024)
- IR 05000352/1980002 + (09:13:53, 31 December 2024)
- ML19331B713 + (09:13:55, 31 December 2024)
- ML19331B710 + (09:13:58, 31 December 2024)
- ML19331B709 + (09:13:59, 31 December 2024)
- ML19331B707 + (09:14:00, 31 December 2024)
- ML19331B706 + (09:14:01, 31 December 2024)
- ML19331B705 + (09:14:02, 31 December 2024)
- ML19331B703 + (09:14:03, 31 December 2024)
- ML19331B702 + (09:14:04, 31 December 2024)
- ML19331B701 + (09:14:05, 31 December 2024)
- ML19331B699 + (09:14:07, 31 December 2024)
- ML19331B698 + (09:14:08, 31 December 2024)
- IR 05000280/1980025 + (09:14:09, 31 December 2024)
- IR 05000213/1980005 + (09:14:11, 31 December 2024)
- ML19331B693 + (09:14:12, 31 December 2024)
- ML19331B692 + (09:14:13, 31 December 2024)
- IR 05000338/1980027 + (09:14:15, 31 December 2024)
- ML19331B689 + (09:14:16, 31 December 2024)
- ML19331B686 + (09:14:17, 31 December 2024)
- ML19331B681 + (09:14:24, 31 December 2024)
- ML19331B680 + (09:14:25, 31 December 2024)
- 05000346/LER-1980-057-03, /03L-0:on 800710,while de-energizing Sfas Channel 2 for Maint on Bus Y2,control Room Operator Received Decay Heat Loop 2 High Flow Alarm.Decay Heat Cooler 1-2 Discharge Control Valve DH14A Failed Open.Caused by Procedural Er + (09:14:26, 31 December 2024)
- ML19331B678 + (09:14:27, 31 December 2024)
- ML19331B676 + (09:14:29, 31 December 2024)
- ML19331B677 + (09:14:29, 31 December 2024)
- ML19331B675 + (09:14:30, 31 December 2024)
- ML19331B673 + (09:14:31, 31 December 2024)
- ML19331B672 + (09:14:31, 31 December 2024)
- 05000346/LER-1980-056-03, /03L-0:on 800709,while Performing ST 5030.09 in Reactor Protection Sys Channel 3,insulated Alligator Clip Slipped Off Terminal Stud Causing Short Circuit Between Terminals 3 & 4.Caused by Personnel Error + (09:14:33, 31 December 2024)
- 05000346/LER-1980-057, Forwards LER 80-057/03L-0 + (09:14:35, 31 December 2024)
- 05000346/LER-1980-054-01, /01T-0:on 800724,loss of Decay Heat Flow Found Due to DH12 Closing.Decay Heat Pump 1-2 Halted.Bypass Valves DH21 & DH23 Opened & Pump Restarted.Caused by Shorted Fuse Clip Due to Personnel Pulling Wires + (09:14:36, 31 December 2024)
- 05000346/LER-1980-056, Forwards LER 80-056/03L-0 + (09:14:38, 31 December 2024)
- 05000278/LER-1980-015-03, /03L-0:on 800707,during Full Power operation,3A Refuel Floor Exhaust Rad Monitor Found Drifting Downscale. Cause Has Not Been Determined.New Gm Tube & Electronic Circuitry Installed + (09:14:40, 31 December 2024)
- 05000346/LER-1980-054, Forwards LER 80-054/01T-0 + (09:14:44, 31 December 2024)
- ML19331B661 + (09:14:45, 31 December 2024)
- 05000346/LER-1980-055-03, /03L-0:on 800709,position Indication for ECCS Room Ventilation Exhaust damper,HA5441,lost.Cause Unknown.Damper Manually Closed + (09:14:47, 31 December 2024)
- 05000285/LER-1980-014-03, /03L-0:on 800709,transformer T4 of Diesel Generator 1 Failed.Caused by Shorted Coil.Transformer Replaced + (09:14:49, 31 December 2024)
- ML19331B656 + (09:14:50, 31 December 2024)
- ML19331B655 + (09:14:50, 31 December 2024)
- 05000346/LER-1980-055, Forwards LER 80-055/03L-0 + (09:14:52, 31 December 2024)
- ML19331B651 + (09:14:57, 31 December 2024)
- 05000285/LER-1980-014, Forwards LER 80-014/03L-0 + (09:14:58, 31 December 2024)
- ML19331B646 + (09:15:02, 31 December 2024)
- ML19331B645 + (09:15:03, 31 December 2024)
- AECM-80-170, Submits Addl Response to NRC Ltr Re Deficiency Noted in IE Insp Repts 50-416/80-07 & 50-417/80-06.Equipment to Complete Dredging Operation Has Not Been Available.Full Compliance Will Be Achieved by 800905 + (09:15:04, 31 December 2024)
- ML19331B643 + (09:15:07, 31 December 2024)
- ML19331B641 + (09:15:08, 31 December 2024)
- ML19331B640 + (09:15:09, 31 December 2024)
- 05000278/LER-1980-016-01, /01T-0:on 800717,reanalysis by Bechtel of as-built Piping Determined That Stresses on Snubber 3-10-GB-S-44 Exceeded Operability Criteria.Caused by Inadequate Design Due to as-built Condition & Seismic Analysis Info Variance + (09:15:10, 31 December 2024)