Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20080H361 + (ML20080H361)
- ML20080H364 + (ML20080H364)
- ML20080H369 + (ML20080H369)
- ML20080H370 + (ML20080H370)
- AECM-83-0590, Final RO 83-082/0:on 830813,fire Penetrations Opened to Support Planned Maint.Fire Watches Established in Accordance W/Tech Spec 3.7.7 Until Penetrations Resealed + (ML20080H372)
- ML20080H374 + (ML20080H374)
- ML20080H384 + (ML20080H384)
- 05000370/LER-1983-090-03, /03L-0:on 831223,isolation Transformer for Circuit Containing Generator 2A Breaker Synchronization Check Relays Overheated.Caused by Short in Synchronization Check Relays. Relay Replaced + (ML20080H385)
- ML20080H386 + (ML20080H386)
- ML20080H387 + (ML20080H387)
- ML20080H389 + (ML20080H389)
- 05000370/LER-1983-041-03, /03L-0:on 830820,while in Mode 1,trouble Alarm for Fire Detection Zone EFA165 Would Not Reset.Cause Unknown.Contacts on Detectors & Bases Cleaned & Annunciator Declared Operable + (ML20080H392)
- ML20080H393 + (ML20080H393)
- 05000370/LER-1983-040-03, /03L-0:on 830810,steam Line 2C Radiation Monitor 2EMF12 Declared Inoperable After Receiving Spurious High Level Alarms.Caused by Bad Solder Joint on Preamplifier Transistor.Joint Resoldered + (ML20080H394)
- 05000327/LER-1984-004-01, :on 840114,high Radiation Alarm Actuated, Causing Control Room Isolation.Caused by Electromagnetic Interference Generated by Switch Actuation.High Radiation Alarm Reset & Monitor Returned to Svc + (ML20080H408)
- ML20080H409 + (ML20080H409)
- ML20080H411 + (ML20080H411)
- TXX-9503, Forwards ISI Summary Rept First Interval,First Period,First Outage CPSES Unit 2 + (ML20080H412)
- ML20080H416 + (ML20080H416)
- AECM-83-0586, Updated RO 83-053/1:on 830601,fire-rated Penetrations Opened to Implement Design Change Packages.Hourly Fire Watches Established.Work Tasks Expected to Be Completed by 831101 + (ML20080H417)
- ML20080H418 + (ML20080H418)
- 05000370/LER-1983-038-03, /03L-0:on 830803,during Containment Pressure Control Functional Test,Alarm Module (Relay K-1) Associated W/Containment Pressure Control Sys Train a Out of Calibr. Caused by Setpoint Drift.Procedure Revised + (ML20080H419)
- ML20080H421 + (ML20080H421)
- ML20080H435 + (ML20080H435)
- PLA-2045, Followup Deficiency Rept Re Mod of RHR Globe Valves F017A & FO17B to Enable Valves in Shutdown Cooling Mode to Perform W/O Adverse Cavitation & Vibration at Low Flow Rates.Initially Reported on 811112.Valves Replaced + (ML20080H444)
- 05000327/LER-1984-006-01, :on 840110,unit Experienced Turbine & Reactor Trip.Turbine Trip Caused by high-high Level in Steam Generator 4.Reactor Trip Caused by low-low Level in Steam Generator 2 + (ML20080H446)
- ML20080H451 + (ML20080H451)
- ML20080H454 + (ML20080H454)
- LIC-95-0021, Provides Listing of TAC Issues Ready to Be Closed + (ML20080H456)
- ML20080H460 + (ML20080H460)
- ML20080H463 + (ML20080H463)
- 05000321/LER-1983-080-03, /03L-0:on 830819,main Steam Line Radiation Monitor D (1D11-K603D) Determined Fluctuating & Drifted Downscale on 830821.Caused by Shorted Connector on Monitor Power Input Cable.Cable Replaced + (ML20080H466)
- ML20080H469 + (ML20080H469)
- 05000395/LER-1983-098-03, /03L-0:on 830816,auxiliary Bldg Charcoal Exhaust Filter Plenum B(XAA-0040B)deluge Valve Tripped Open.Caused by Pressure Surge When Electric Fire Pump Started.Charcoal HEPA & Roughing Filters Replaced + (ML20080H471)
- 05000395/LER-1983-100-01, /01T-0:on 830831,PORV PCV-445A Declared Inoperable Due to Possible Inadvertent Opening of Valve Upon Loss of Power to Protection Cabinet Iv.Caused by Design Error. PCV-445A Closed & Deenergized Until Corrected + (ML20080H474)
- AECM-83-0563, RO-83-078/0:on 830728,fire Detection Zones 2-06 & 2-20 Auxiliary bldg,139-ft Elevation Alarmed & Would Not Reset. Hourly Firewatch Established Per Tech Spec 3.3.7.9.Caused by Accumulation of Dust in Ionization Detectors + (ML20080H477)
- ML20080H483 + (ML20080H483)
- ML20080H484 + (ML20080H484)
- AECM-83-0596, Final Deficiency Rept for Unit 1 & Interim Deficiency Rept for Unit 2 Re Asco Spare Parts Kits for Scram Pilot Valve Solenoids.Initially Reported on 830804.Valves Reworked.Next Rept by 840224.Also Reportable Per Part 21 for Unit 1 + (ML20080H486)
- ML20080H487 + (ML20080H487)
- PLA-4264, Forwards Security Training & Qualification Plan.Plan Withheld,Per 10CFR73.21 + (ML20080H489)
- PLA-4265, Forwards Change Hh to Plant Physical Security Plan.Plan Withheld,Per 10CFR73.21 + (ML20080H490)
- RBG-41228, Responds to Violation & Deviation Noted in Insp Rept 50-458/94-17 on 941031-1110.Corrective Actions:Ventilation Sys Ductwork & Rolls of Plastic Relocated to Appropriate Locations & Rev to FP Program Procedure FPP-0030 Completed + (ML20080H491)
- 05000259/LER-1983-071-03, /03L-0:on 831212,analyst Discovered Broken Vacuum Pump Belt on Reactor & Turbine Vent Monitor 1-RM-90-250. Caused by Normal Wear Due to Continuous Operation.Std V-belt for Schwitzer Model 325 Air Pump Replaced + (ML20080H495)
- 0CAN029505, Forwards Endorsement 24 to Nelia Policy NS-507 & Endorsement 25 to Maelu Policy MS-128 + (ML20080H504)
- 05000287/LER-1983-010-01, /01T-0:on 830830,as Result of QA Review & Other Reanalysis,Determined Axial Power Shaping Rod Limits for U3 C7 After 385 EFPD Not Conservative.Caused by Design Error. Limits Reanalyzed Using More Iterations + (ML20080H505)
- ML20080H519 + (ML20080H519)
- ML20080H522 + (ML20080H522)
- ML20080H523 + (ML20080H523)
- BSEP-83-4016, Responds to NRC Ltr Re Violations Noted in IE Insp Repts 50-324/83-05 & 50-325/83-05.Corrective Actions:Required Training Will Be Completed by 831231 + (ML20080H524)
- ML20080H525 + (ML20080H525)