- 05000320/LER-1981-021, Forwards LER 81-021/03L-0 + (ML20031F719)
- 05000320/LER-1981-021-03, /03L-0:on 810907,manual Inlet Damper to Control Room Bypass Supply Fan Failed Closed During Control Room Emergency Ventilation Performance Analysis.Caused by Loose Set Screw on Manual Actuation Control Arm + (ML20031F723)
- ML20031F725 + (ML20031F725)
- ML20031F726 + (ML20031F726)
- 05000335/LER-1981-043-03, /03L-0:on 810918,1A Battery Charger Shut Down on High Voltage During Battery Charging Surveillance.Caused by Defective Shutdown Device.Device Replaced + (ML20031F728)
- ML20031F733 + (ML20031F733)
- ML20031F735 + (ML20031F735)
- 05000325/LER-1981-063, Forwards LER 81-063/03L-0 + (ML20031F737)
- ML20031F742 + (ML20031F742)
- ML20031F744 + (ML20031F744)
- 05000334/LER-1981-084, Forwards LER 81-084/03L-0 + (ML20031F745)
- ML20031F747 + (ML20031F747)
- ML20031F748 + (ML20031F748)
- FVY-81-139, Responds to NRC Re Violations Noted in IE Insp Rept 50-271/81-13.Notarized Statement Added + (ML20031F749)
- 05000334/LER-1981-084-03, /03L-0:on 810907,train B Quench Spray Flow Reduction Control Valve Failed to Stroke Closed from Full Open Position.Caused by Failed Torque Switch.Switch Readjusted + (ML20031F750)
- 05000325/LER-1981-063-03, /03L-0:on 810924,during Reactor Startup,Control Rod 26-31 Set Off Rod Drift Alarm When Fully Inserted W/ full-in RTGB Position Indication.Caused by Failed Reed Switch.Switch Will Be Repaired + (ML20031F751)
- ML20031F752 + (ML20031F752)
- ML20031F753 + (ML20031F753)
- 05000334/LER-1981-079, Forwards LER 81-079/01T-0 + (ML20031F754)
- ML20031F758 + (ML20031F758)
- ML20031F759 + (ML20031F759)
- 05000334/LER-1981-079-01, /01T-0:on 810922,containment Radioactivity Monitors Failed Due to Power Supply Loss.Caused by Formation of Temporary Ground Between Two Adjacent Radiation Monitors. Frayed Power Cable Repaired + (ML20031F761)
- IR 05000348/1981017 + (ML20031F762)
- 05000304/LER-1981-023, Forwards LER 81-023/03L-0 + (ML20031F763)
- ML20031F765 + (ML20031F765)
- ML20031F767 + (ML20031F767)
- 05000304/LER-1981-023-03, /03L-0:on 810913,reactor Coolant Boron Sample Not Obtained on Second Shift.Caused by Normal Sampling Path Being Isolated Due to Mod on Sampling Sys.Alternate Sample Point Isolated for Repairs + (ML20031F768)
- ML20031F769 + (ML20031F769)
- ML20031F770 + (ML20031F770)
- 05000334/LER-1981-083, Forwards LER 81-083/03L-0 + (ML20031F771)
- ML20031F778 + (ML20031F778)
- ML20031F779 + (ML20031F779)
- ML20031F780 + (ML20031F780)
- ML20031F781 + (ML20031F781)
- 05000311/LER-1981-102, Forwards LER 81-102/03L-0.Detailed Event Analysis Encl + (ML20031F782)
- ML20031F784 + (ML20031F784)
- ML20031F786 + (ML20031F786)
- ML20031F788 + (ML20031F788)
- ML20031F790 + (ML20031F790)
- 05000327/LER-1981-119, Forwards LER 81-119/03L-0 + (ML20031F791)
- ML20031F793 + (ML20031F793)
- ML20031F794 + (ML20031F794)
- 05000311/LER-1981-102-03, /03L-0:on 810915,low Reading Discovered on Reactor Coolant Loop Flow Channel 2.Caused by Failure of Flow Transmitter & Equalizing Valve Assembly.Channel Placed in Tripped Condition.Transmitter & Assembly Replaced + (ML20031F796)
- PNO-III-81-087, on 811015,NRC & Kerr-McGee Chemical Co Named as Defendants in Suit Filed in Federal Court by City of West Chicago.Suit Seeks to Halt Dismantling of Kerr-McGee Bldgs Where Thorium & U Compounds Were Processed + (ML20031F797)
- ML20031F798 + (ML20031F798)
- ML20031F799 + (ML20031F799)
- ML20031F802 + (ML20031F802)
- 05000327/LER-1981-119-03, /03L-0:on 810914,while Performing Surveillance Instruction 157,containment Penetration Leak Rate Test Penetrations X-1,X-108 & X-109 Were Found W/Pipe Plugs Missing.Caused by Personnel Error.Instructions Revised + (ML20031F804)
- ML20031F805 + (ML20031F805)
- GO2-81-341, Responds to IE Bulletin 80-21 Re Valve Yokes Supplied by Malcolm Foundry Co,Inc.No Malcolm Foundry Components Used by Manufacturers or Contractors as Supply Source.Manpower Estimate & List of Manufacturers Encl + (ML20031F807)
- IR 05000361/1981020 + (ML20031F808)