Responds to NRC Re Violations Noted in IE Insp Repts 50-348/81-17 & 50-364/81-20.Corrective Actions: Training Will Include Discussion of Entering Operating Mode W/O Required Equipment Being Operable
ML20031F748
Person / Time
Site: Farley  
Issue date: 08/31/1981
From: Clayton F
ALABAMA POWER CO.
To: Robert Lewis
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20031F736 List:
References
NUDOCS 8110200387
Download: ML20031F748 (2)


Text

.

l Malling A:dr:ss Alabama Power Company 600 North 18th Street Post Office Box 2641 Ottmingham. Alabama 35291 Telephone 205 783-6081 F. L. Clayton Jr.

gyg[)OWCf Senior Vice President y

g Flintndge Guilding r_D {

av wouan,+xue sem August 31, 1981 Mr. R. C. Lewis U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N.W.

Suite 3100 Atlanta, Georgia 30303

Subject:

J. M. Farley Nuclear Plant NRC Inspection of June 16 -

July 15, 1981

Reference:

Report Numbers 50-348/80-17 and 50-364/81-20

Dear Mr. Lewis:

This letter refers to the following violation in the subject inspec-tion report:

" Technical Specification 3.0.4 requires that entry into an opera-tional mode or other specified applicability condition shall not be made unless the conditions of the Limiting Condition of Operation are met without reliance on provisions contained in the action state-ments.

Contrary to the above, entry into an operational mode was made on two occasions without the required equipment being operable as specified in section 3.8.1.1 of the Technical Specification. On March 17, 1981 Unit 1 reactor operational mode was changed from Mode 5 to Mode 4 while diesel generator 1-2A was inoperable. On May 29, 1981, Unit 2 reactor operational mode was changed from Mode 2 to Mode 1 while generator 1-2A was inoperable."

Response

The following corrective action has been accomplished:

1.

The personnel involved have been counseled concerning the signi-ficance of this incident.

l OMo$[05 y

u t

q i

Mr. n C. Lewis August 31, 1981 Page 5fo 2.

The Training Department has been notified to include these inci-dents in Licensed Operator requalification training.

3.

An Operations memorandum (81-08) has been written emphasizing proper shift turnover in order to insure that personnel know the the exact status of plant equipment.

Yours very truly, A