IR 05000440/199901313 September 1999Insp Rept 50-440/99-13 on 990712-30.Violations Noted. Major Areas Inspected:Effectiveness of Pnpp Program for Identification,Resolution & Prevention of Technical Issues & Problems That Could Degrade Quality of Plant OperationsTime of Discovery
Weld Overlay
Hydrostatic
Probabilistic Risk Assessment
Temporary Modification
Foreign Material Exclusion
Operability Determination
Operability Assessment
Power Uprate
ML20212A85313 September 1999Notice of Violation from Insp on 990712-30.Violation Noted: from 980324-990730,TS SR 3.5.1.4 & 3.5.2.5 Failed to Require Each ECCS Pump to Develop Pump Differential Pressure Greater than or Equal to ECCS Total Flow Resistance
IR 05000440/19990099 September 1999Insp Rept 50-440/99-09 on 990709-0825.One Violation Occurred & Being Treated as Ncv.Major Areas Inspected:Aspects of Licensee Operations,Engineering,Maint & Plant SupportHigh winds
Ultimate heat sink
Past operability
Downpower
ML20211M65231 August 1999Revised Page Number 4, P2 Status of EP Facilities,Equipment & Resources
IR 05000440/199901212 August 1999Insp Rept 50-440/99-12 on 990712-16.No Violations Noted. Major Areas Inspected:Emergency Preparedness ProgramFitness for Duty
Siren
IR 05000440/199900822 July 1999Insp Rept 50-440/99-08 on 990518-0708.No Violations Noted. Major Areas Inspected:Operations,Engineering,Maintenance & Plant SupportDownpower
IR 05000440/199900310 June 1999Insp Rept 50-440/99-03 on 990407-0517.Two Violations Noted & Being Treated as non-cited Violations.Major Areas Inspected: Aspects of Licensee Operations,Maint,Engineering & Plant SupportShutdown Margin
ML20207B12920 May 1999Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $110,000.Violation Noted:Centerior Energy Corp Through Actions of RPM Discriminated Againt Rps,On 970716,as Result of RPS Engaging in Protected Activities
ML20209B88917 May 1999EN-99-019:on 990520,notice of Proposed Imposition of Civil Penalty in Amount of $110,000 Issued to Licensee.Action Based Upon Severity Level II Violation Involving Radiation Protection Manager Discrimination Against Supervisor
IR 05000440/199900712 May 1999Insp Rept 50-440/99-07 on 990412-16.No Violations Noted. Major Areas Inspected:Rp Performance & Oversight of Refueling Outage ActivitiesHigh Radiation Area
Scaffolding
ML20206Q23010 May 1999Notice of Violation from Investigation Completed on 990129. Violation Noted:On 970114,info Required by Commission Regulations Not Maintained Complete & Accurate in All Matl Respects
ML20196A31310 May 1999Notice of Violation from Investigation on 990129.Violation Noted:On 970114,K Wierman Employed as Training Instructor at Plant & Deliberately Submitted Info to Util That Wierman Knew to Be Incomplete or Inaccurate
IR 05000440/19990066 May 1999Insp Rept 50-440/99-06 on 990303-04 & 0412-16.No Violations Noted.Major Areas Inspected:Inservice Insp Efforts & Overlay Repairs of N4C Feedwater NozzleWeld Overlay
Nondestructive Examination
Operability Determination
Dissimilar Metal Weld
IR 05000440/19990023 May 1999Insp Rept 50-440/99-02 on 990225-0406.Non-cited Violations Noted.Major Areas Inspected:Operations,Maintenance, Engineering & Plant Support
IR 05000440/19990052 April 1999Insp Rept 50-440/99-05 on 990301-05.No Violations Noted. Major Areas Inspected:Licensee Implementation of 10CFR50.65, Requirements for Monitoring Effectiveness of Maint at NppsMaintenance Rule Program
Fuel cladding
ML20204E79017 March 1999Insp Rept 50-440/99-01 on 990113-0224.Non-cited Violation Identified.Major Areas Inspected:Aspects of Licensee Operations,Engineering,Maint & Plant SupportGrace period
Power change
IR 05000440/199900417 March 1999Insp Rept 50-440/99-04 on 990222-26.No Violations Noted. Major Areas Inspected:Radiation Protection Program & Radiological Planning for Upcoming Refueling Outage,Which Included Review of Rwps,Alara Reviews & Dose GoalsHigh Radiation Area
Locked High Radiation Area
Scaffolding
IR 05000440/199801923 December 1998Insp Rept 50-440/98-19 on 981021-1202.No Violations Noted. Major Areas Inspected:Operations,Maint & EngineeringOperability Determination
Breakaway torque
Scaffolding
Power change
ML20210Q92910 December 1998Investigation Rept 3-1998-007.No Noncompliance Noted.Major Areas Investigated:Alleged Discrimination Against Radiation Protection Supervisor for Testifying as Witness in Dept of Labor Proceedings
IR 05000440/199802225 November 1998Chemistry & RP Insp Rept 50-440/98-22 on 981102-06.No Violations Noted:Major Areas Inspected:Implementation of Chemistry Program,Meteorological Monitoring Program & Control & Monitoring of Personnel Radiation DoseGrab sample
IR 05000440/199802118 November 1998Insp Rept 50-440/98-21 on 981019-22.No Violations Noted. Major Areas Inspected:Licensed Operator Requalification ProgramJob Performance Measure
Systematic Assessment of Licensee Performance
ML20195C72310 November 1998Notice of Violation from Insp on 980909-1020.Violation Noted:On 980902,inspectors Identified That Fire Watch Did Not Verify That Special Instructions of Burn Permit B98-DG-83,used for Welding Conducted on DG Were MetFire Protection Program
Fire Watch
ML20195C73610 November 1998Insp Rept 50-440/98-18 on 980909-1020.Violations Noted. Major Areas Inspected:Operations,Maintenance,Engineering & Plant SupportStroke time
Foreign Material Exclusion
Earthquake
Fire Protection Program
Fire Watch
Power change
IR 05000440/19980177 October 1998Insp Rept 50-440/98-17 on 980831-0914.Violations Noted. Major Areas Inspected:Review of Implementation of Solid Radwaste Mgt & Shipping Program.Insp Also Reviewed Conduct of Radiological Environ Monitoring ProgramHigh Radiation Area
Offsite Dose Calculation Manual
Process Control Program
ML20154H1687 October 1998Notice of Violation from Insp on 980831-0914.Violation Noted:As of 980415,licensee Had Not Made Adequate Surveys to Assure Compliance with 10CFR20.2006
IR 05000440/199801625 September 1998Insp Rept 50-440/98-16 on 980723-0908.No Violations Noted. Major Areas Inspected:Resident Inspectors Evaluation of Aspects of Licensee Operations,Engineering,Maint & Plant SupportSafe Shutdown
Fire Barrier
Probabilistic Risk Assessment
Fire Protection Program
Scaffolding
ML20151V3528 September 1998Notice of Violation from Insp on 980727-31.Violation Noted: on 971219,licensee Conducted Breath Analysis as Part of for Cause Test Based on Odor of Alcohol,However Drug Portion of for Cause Test Not Conducted in Timely MannerFitness for Duty
IR 05000440/19980158 September 1998Insp Rept 50-440/98-15 on 980727-31.Violations Noted. Major Areas Inspected:Effectiveness of Selected Elements of Security ProgramFitness for Duty
Contraband
IR 05000440/199801321 August 1998Insp Rept 50-440/98-13 on 980605-0722.No Violations Noted. Major Areas Inspected:Operations,Maintenance,Engineering & Plant SupportSafe Shutdown
Scaffolding
Downpower
IR 05000440/199801419 August 1998Insp Rept 50-440/98-14 on 980620-24 & 0720-22.No Violations Noted.Major Areas Inspected:Licensee C/A for Issues Identified by NRC Inspections & Licensee Event Repts Submitted to NRCPacking leak
Stroke time
Design basis earthquake
Foreign Material Exclusion
ML20236R82516 July 1998Insp Rept 50-440/98-11 on 980518-22.Violations Noted.Major Areas Inspected:Adequacy of Licensee Programs,Procedures, Training,Equipment & Supporting Documentation for Maint of medium-voltage & low-voltage Power Circuit Breakers
ML20236R81116 July 1998Notice of Violation from Insp on 980518-22.Violations Noted: as of 980520,as-tested Instantaneous Trip Function of Circuit Breaker EF1B04 Used for Emergency Closed Cooling Pump Motor 1P42C001A,inadequate
ML20236N0239 July 1998Notice of Violation from Insp on 980421-0604.Violation Noted:Inspectors Identified That on 980504,operations Personnel Failed to Verify 1 Restoration Items Specified in Surveillance Instruction Sys Restoration Checklist
ML20236N0289 July 1998Insp Rept 50-440/98-10 on 980421-0604.Violations Noted.Major Areas Inspected:Operations,Maint & Surveillance,Engineering & Plant SupportHalf scram
Past operability
Condition Adverse to Quality
Scram Discharge Volume
Fire Protection Program
Power change
ML20236L8948 July 1998Errata to Notice of Violation from Insp Rept 50-440/97-21 on 971202-980127.Violation Noted:On 980106,combustible Matl W/No Transient Combustible Permit in Fire Area Containing Redundant Trains of safety-related Equipment,IdentifiedFire Protection Program
IR 05000440/199801225 June 1998Insp Rept 50-440/98-12 on 980601-05.Violations Noted.Major Areas Inspected:Plant SupportHigh Radiation Area
Grab sample
Offsite Dose Calculation Manual
Missed surveillance
ML20249C56425 June 1998Notice of Violation from Insp on 980601-05.Violation Noted: on 980504-21,an Individual,Conducting Radiologically Restricted Area Entries Under Radiation Work Permits 980003, 980047 & 980051 Did Not Wear Thermoluminescent Dosimeter
ML20217M13129 April 1998Insp Rept 50-440/98-07 on 980223-0305.Violations Noted. Major Areas Inspected:Operations,Engineering & Maintenance
ML20217M11429 April 1998Notice of Violation from Insp on 980223-0305.Violation Noted:On 980227,licensed Operator Incorrectly Removed Red Tag & Installed Fuse for Annulus Exhaust Gas Treatment Sys Instead of Installing Fuse for ESW Ventilation Sys
IR 05000440/199800527 April 1998Insp Rept 50-440/98-05 on 980209-0408.No Violations Noted. Major Areas Inspected:Portions of Licensee Fire Protection ProgramSafe Shutdown
Fire Barrier
Fire impairment
Missed surveillance
Fire Protection Program
ML20212H3339 April 1998EN-97-106A:on 971218,licensee Responded to NOV & Proposed Imposition of Civil Penalty in Amount $100,000.Licensee Denied Violation Re 10CFR50.59 & Requested Remission.Request Denied & Order Imposing Civil Monetary Penalty Issued
IR 05000440/19980017 April 1998SALP 15 Rept 50-440/98-01 for Plant Covering Period from 960915-980228Half scram
Job Performance Measure
Systematic Assessment of Licensee Performance
Fire Protection Program
Fire Watch
IR 05000440/19980061 April 1998Insp Rept 50-440/98-06 on 980128-0310.Violations Noted.Major Areas Inspected:Licensee Operations,Maint & EngineeringOperability Determination
Scaffolding
IR 05000440/199800326 March 1998Insp Rept 50-440/98-03 on 980223-27.No Violations Noted. Major Areas Inspected:Licensee Performance During Plant Biennial Exercise of Emergency Plan
IR 05000440/199800212 March 1998Insp Rept 50-440/98-02 on 980112-16 & 26-30.No Violations Noted.Major Areas Inspected:Operations,Engineering & Review of Effectiveness of CA ProgramHydrostatic
ML20203D82420 February 1998Insp Rept 50-440/97-21 on 971202-980127.Violations Noted. Major Areas Inspected:Operations,Maint,Engineering & Plant SupportFire Barrier
ML20203D82120 February 1998Notice of Violation from Insp on 971202-980127.Violation Noted:On 971208,an Inspector Observed Fire Door Between Div 2 & 3 Emergency Diesel Generator Rooms Stuck in Fully Open Position
PNO-III-98-009, on 980123,licensee Declared Unusual Event Under Emergency Plan Because of Spill of Up to 275 Gallons of Refrigerant Called Trichlorethylene.No Plant Personnel Were in Bldg at Time of Spill23 January 1998PNO-III-98-009:on 980123,licensee Declared Unusual Event Under Emergency Plan Because of Spill of Up to 275 Gallons of Refrigerant Called Trichlorethylene.No Plant Personnel Were in Bldg at Time of Spill
IR 05000440/199701721 January 1998Insp Rept 50-440/97-17 on 971103-07 & 971215-18.No Violations Noted.Major Areas Inspected:Ep ProgramSiren
IR 05000440/199800416 January 1998Insp Rept 50-440/98-04 on 980105-09.No Violations Noted. Major Areas Inspected:Radiolological,Environ & Chemistry Sections Programs