Issue date | Title | Topic | |
---|---|---|---|
ML20199D616 | 4 January 1999 | Notice of Violation from Insp on 981025-1205.Violation Noted:Its Requirements for Valve Position Verifications Not Met as Evidenced by Listed Examples | |
ML20249A294 | 8 June 1998 | Notice of Violation from Insp on 980322-0509.Violation Noted:As of 980423,licensee Had Not Complied W/Requirements of Procedure CP-111,in That,Only Two of Discrepancies Identified in Ioc NL97-0262,had Been Documented | |
ML20216H887 | 8 April 1998 | Notice of Violation from Insp on 980208-0321.Violation Noted:On 980220,Axial Power Imbalance Alarm Was Inoperable for Approx 3.5 Hours & Axial Power Imbalance Was Not Verified to Be within Acceptable Operating Limits | |
ML20248L617 | 16 March 1998 | Notice of Violations from Insp on 980126-30.Violations Noted:Test Program for ECCS Operating in Piggyback Mode Did Not Demonstrate That Sys Would Perform Satisfactorily in Service | Stroke time Condition Adverse to Quality |
ML20216E929 | 4 March 1998 | Notice of Violation from Insp on 980104-0207.Violations Noted:On 980203 Licensee Failed to Accomplish Required Posting of Bulletin Boards | Emergency Lighting |
ML20203F556 | 23 February 1998 | Notice of Violation from Insp on 971021-24,1208-12 & 980105-09.Violations Noted:Implementation of Validation Program Did Not Adequately Demonstrate Usability of Emergency Procedures | Boric Acid Condition Adverse to Quality |
ML20199G676 | 16 January 1998 | Notice of Violation from Insp on 971201-16.Violation Noted: as of 971211,licensee Health Physics Supervisors Failed to Identify & Correct Personnel Contamination Repts That Were Not Completed IAW Requirements of Procedure HPP-104 | |
ML20198N621 | 29 December 1997 | Notice of Violation from Insp on 971026-1129.Violation Noted:On 971105,licensee Failed to Perform Adequate Se,Per 10CFR50.59 for Functional Test Procedure for B Emergency Diesel Generator Power Upgrade & Radiator Replacement Mods | |
ML20203A191 | 4 December 1997 | Notice of Violation from Insp on 971006-24.Violation Noted:Work Request Numbers 333797 & 333798,issued in Mar 1997 to Install Stem Protectors on Actuators Were Closed W/O Performing Work | Stroke time Foreign Material Exclusion |
ML20202D730 | 24 November 1997 | Notice of Violation from Insp on 970921-1025.Violation noted:10CFR50.59 SE Had Not Been Performed as Required within 90 Days on Wds Piping non-conforming Condition | Offsite Dose Calculation Manual |
ML20212B906 | 16 October 1997 | Notice of Violation from Insp on 970817-0920.Violations Noted:Scaffolding Control Program Does Not Contain Measures to Assure That Deviations from Design Quality Std for safety-related Equipment Installed Have Adequate Control | Scaffolding |
ML20211Q258 | 14 October 1997 | Notice of Violation from Insp on 970922-26.Violation Noted:On 970820,individual Was Terminated & Authorized Access Was Not Removed from Plant Security Computer Until 970905 | |
ML20211E489 | 12 September 1997 | Notice of Violation from Insp on 970713-0816.Violations Noted:On 970728,licensee Personnel Performed quality-related Work to Restore once-through SGs During Reduced RCS Inventory Operation Without Written & Approved Procedure | |
ML20210V524 | 5 September 1997 | NOV from Insp on 970602-20.Violation Noted:Licensee Made Change to Facility,W/O Prior Commission Approval,That Involved USQ | |
ML20216E396 | 5 September 1997 | Errata to NOV from Insp on 970804-06.Violation Noted: Licensee Failed to Have Adequate Assessment of 10 Zones to Facilitate Response to Detection of Penetration of Protected Area Perimeter & Assessment of Existence of Threat | |
ML20210R922 | 27 August 1997 | Notice of Violation from Insp on 970804-06.Violation Noted: Licensee Failed to Have Adequate Assessment of 10 Zones to Facilitate Response to Detection of Penetration of Protected Area Perimeter & Assessment of Existence of Threat | |
ML20210M568 | 11 August 1997 | Notice of Violation from Insp on 970608-0712.Violation Noted:Licensee CAs for NRC NOV EA 97-094 Inadequate in That Rev 1 of Procedure CP-151 Inadequate to Prevent Repetition of Violation | |
ML20149G106 | 7 July 1997 | Notice of Violation from Insp on 970504-0607.Violation Noted:Security Staff Failed to Understand Adequately & Develop Guidance Properly to Address Multiple Temporary Losses of Power to Central Alarm Station Computers | Hydrostatic |
ML20148P899 | 6 June 1997 | Notice of Violation from Insp on 970127-0321.Violation Noted:Licensee Failed to Report Condition That Was Outside Design Basis of Plant,Unanalyzed Condition That Compromised Plant Safety & Vulnerability in Safeguard Sys | Unanalyzed Condition |
ML20140E774 | 5 June 1997 | Notice of Violation from Insp on 970319-21.Violation Noted:Licensee Made Changes to Facility & Procedures Described in FSAR That Involved USQs Based on Inadequate SE | |
ML20140D268 | 2 June 1997 | Notice of Violation from Insp on 970330-0503.Violation Noted:On 970327,red Tags from Released Electronic Clearance Order (Eco) 96-012-98 Found on 4160 Volt Breaker Cubicles for a & B Makeup Pumps | |
ML20140F046 | 29 May 1997 | Notice of Violation from Insp on 970317-21.Violation Noted: on 970116,outdated Physical Security & Training & Qualification Plans & 1990 Safeguards Info Insp Repts & LERs Were Left Unattended & Not Locked in Secured Area | |
ML20138J404 | 21 April 1997 | Notice of Violation from Insp on 970223-0329.Violation Noted:Licensee Failed to Accomplish Activities Affecting Quality in Accordance W/Procedures to Control Equipment for Normal Operating Conditions | |
ML20140E741 | 18 April 1997 | Notice of Violation from Insp on 970317-21.Violation Noted: on 960209,licensee,through Deliberate Action of Three Individuals,Allowed Badge/Key to Leave Protected Area W/O Being Under Observation & Control of Security Force | |
ML20148F979 | 4 April 1997 | Notice of Violation from Insp on 960729-0802.Violation Noted:R Stewart Deliberately Failed to Provide Complete & Accurate Info During Preemployment Process & Include History of Criminal Convictions on Personal History Questionnaire | |
ML20137T031 | 24 March 1997 | Notice of Violation from Insp on 970112-0222.Violations Noted:Licensee Failed to Prescribe Quality Related Clearance Tagging Activities Into Appropriate Procedure That Compliance Procedure 115 Nuclear Plant Tags | |
ML20137E529 | 12 March 1997 | Notice of Violation from Insp on 961206.Violation Noted: in April 96 Licensee Made Change to Facility Described in Fsar,Which Involved Three USQ W/O Prior Commission Approval | Ultimate heat sink Condition Adverse to Quality |
ML20137E444 | 28 February 1997 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $50,000.Violation Noted:Procedures Were Not Implemented & Maintained to Detailed Requirements Necessary to Implement Security Plan for Plant Operations | |
ML20135C707 | 21 February 1997 | Notice of Violation from Insp on 960805-09.Violation Noted: Fuel Handling Event Involving Fuel Assembly N8C6 Was Not Recorded in Operating Logs or Refueling Log & Main Fuel Handling Bridge Was Not Verified for Indexing | |
ML20134P395 | 5 February 1997 | Notice of Violation from Insp on 961201-970111.Violations Noted:Rcs Cooldown Rate Allowed to Exceed Limits Specified in PTLR for Approximately One Hour,During Unit Cooldown | |
ML20132C799 | 5 December 1996 | Notice of Violation from DOL Recommended Decision & Order, & Investigation by NRC OI Completed on 960924. Violation Noted:Licensee Discriminated Against Ta James, Former Security Escort & Firewatch | |
ML20135C392 | 27 November 1996 | Notice of Violations from Insp on 961006-1102.Violations Noted:No Licensee Sp Included Channel Check for Motor Driven Emergency Feedwater Pump Discharge Pressure Gauge | Post Accident Monitoring |
ML20129H726 | 30 October 1996 | Notice of Violation from Insp on 960908-1005.Violation Noted:Failure of Clearance for Work Request Nu 0337713 to Require Tripping Fuel Racks Prior to Opening Air Supply Isolation Valve Resulted in Inadvertent Start of Generator | |
ML20129A156 | 4 October 1996 | Notice of Violation from Insp on 960811-0907.Violation Noted:Technician Failed to Follow Requirements of PT-366, Resulting in Inadvertent Initiation of Control Room Emergency Ventilation Sys & Escort Lost Contact W/Visitor | |
ML20134C309 | 12 September 1996 | Notice of Violation from Insp on 960714-0810.Violation Noted:Failure to Take Prompt Corrective Actions to Address Discrepancies Identified in Feb 1995 During make-up Sys Audit | |
ML20149J203 | 16 February 1994 | Notice of Violation from Insp on 930825.Violation Noted: DA Tritt Discharged from Employment on 871203,for Engaging in Protected Activities (88-ERA-29) | |
ML20059C079 | 10 December 1993 | Notice of Violation from Insp on 931108-12.Violations Noted: Surveillance Procedure SP-182,rev 10, Reactor Bldg Structural Integrity Surveillance Program Not Implemented as Described | |
ML20058P678 | 3 December 1993 | Notice of Violation from Insp on 931101-19.Violation Noted: Facility Licensee Physician Made Determination That Two Operators Eyesight No Longer Met Min Stds Required by 10CFR55.33(a)(1) | |
ML20057B420 | 10 September 1993 | Notice of Violation from Insp on 930628-0730.Violation Noted:Design Control Measures Had Not Assured Design Bases Were Properly Translated Into Min Terminal Voltage Specified by Battery Svc Test Surveillance Procedure SP-523,Rev 28 | |
ML20057C323 | 9 September 1993 | Notice of Violation from Insp on 930711-0814.Violation Noted:Measure Did Not Assure Corrective Actions Preclude Repetition of Reactor Coolant Sys Overcooling Event of 930305 | |
ML20056E986 | 9 August 1993 | Notice of Violation from Insp on 930606-0710.Violation Noted:Mut Hydrogen Regulator Adjusted W/O Required Safety Evaluation Being Performed | |
ML20126F188 | 11 December 1992 | Notice of Violation from Insp on 921018-1114.Violation Noted:Dg Inoperable for Two H During Performance of Surveillance procedure,SP-907B.Required Breaker Alignment & Power Availability Verifications Not Performed | |
ML20062D945 | 7 November 1990 | Notice of Violation from Insp on 900918-1005.Violation Noted:On 900918,containment Integrity for Unit Not Maintained While in Mode 1 in That Valve Dhv 43 Did Not Fully Shut After Performing Cycling & Disabling Evolution | Stroke time |
ML20059G600 | 31 August 1990 | Notice of Violation from Insp on 900707-0810.Violation Noted:Valve Realignment Sequence Violated in That Air Dryer Bypass Valve Closed First Instead of Last While Releasing Work Request 90-07-036 | |
ML20247Q179 | 13 September 1989 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $100,000.Noncompliance noted:safety-related Motor Control Ctrs in Auxiliary Bldg Had Not Been Demonstrated to Be Qualified for Environ Conditions | Post Accident Monitoring |
ML20246Q332 | 1 September 1989 | Notice of Violation from Insp on 890708-0804.Violations Noted:Channel Functional Test Not Performed on Containment Hydrogen Monitors & Six Manual Valves Associated W/Emergency Containment Not Verified Closed Every 31 Days | |
ML20246N757 | 21 August 1989 | Notice of Violation from Insp on 890710-14.Violations Noted: Verification of Remote Position Indicators at Remote Shut Down Panel Not Being Performed & Record of Results for Relief Valve BSV-19 Vacuum Function Testing Did Not Exist | |
ML20245K289 | 11 August 1989 | Notice of Violation from Insp on 890619 & 20.Violation Noted:No Surveillance Procedure Written or Implemented to Test Automatic Start Logic Paths for motor-operated Emergency Feedwater Pump | |
ML20245K033 | 1 August 1989 | Notice of Violation from Insp on 890603-0707.Violation Noted:On 890621,several Cells of Station Batteries a & B Had Electrolyte Levels Greater than Max Level Mark & Four Unqualified Personnel Assigned Duty on Fire Brigade | Fire Protection Program |
ML20246K725 | 7 July 1989 | Notice of Violation from Insp on 890531-0602.Violations Noted:Operator Failed to Have Procedures Present for Performing Actions Not Routine & Rev 80 to General Plant Operating Procedure OP-02 Re Plant Heatup Inadequate |