THIS IS AN EMERGENCY EXERCISE UPDATE AT 0846 PDT PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE-PNO-V-86-64'ADate: September 18, 1986 This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or public interest significance. The information presented is as initially received without verification or evaluation and is basically all that is known by Region V staff on this date.

FACILITY: Washington Public Project Supply System Emergency Classification'-

WNP -2 Notification of Unusual Event Docket No. 50-397 X Alert

- ~ -

Richland, Washington Site Area Emergency General Emergency Not Applicable

SUBJECT:

DRILL: Notification of ALERT - Tornado warnings, winds .

Loss of all service water. DRILL UPDATE: At 0846 PDT, the licensee has declared an ALERT. High winds have cubsided to 58 mph, while facility is in center of storm. 'A' train service wIter system out-of-service because of a fire in the service water pump house.

B' service water train is inoperable because the discharge valve of the 'B' pnp is frozen at 15% open. HPCS is inoperable because of the pump house fire end service no service water to the HPCS diesel.

B3th 'A' and 'B' diesel generators are inoperable because of no service water for their cooling.

'tTh3 licensee is experiencing a low fire main header pressure.

Tha licensee has notified the state and resident.

This information is current as of NPDT, September 18, 1986.

CONTACT: P. Johnson R. Dodds FTS 463-3745 (509) 377-2627

[

8609230129 PDR I&E 860918 PNO-V-86-064A PDR DISTRIBUTION i