Enclosure 13 to ULNRC-06696 Page 1 of 456 Enclosure 13 to ULNRC-06696 PAVAN-NAI Output for Reactor Building and Refueling Water Storage Tank Releases Evaluated at Exclusion Area Boundary and Low Population Zone Boundary (456 pages) 3 to ULNRC-06696 Page 2 of 456 Table of Contents PAVAN Case: clwAST_PAVAN_RB.out............................................................................................................................................................................ 3 PAVAN Case: clwAST_PAVAN_RWST.out .................................................................................................................................................................. 230 3 to ULNRC-06696 Page 3 of 456 PAVAN Case: clwAST_PAVAN_RB.out NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 1 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 ENHANCED PRINTOUT OF INPUT CARDS KOPT 1 2 3 4 5 6 7 8 9 10 11 12 1 0 1 0 0 0 0 0 1 0 1 0 0 KOPT(1) = 0 ; X/Q Without Desert Sigmas KOPT(2) = 1 ; Evaluate X/Q with & w/o Bldg Wake KOPT(3) = 0 ; Skip print of Upper Envelope Edit KOPT(4) = 0 ; Skip print of Upper Envelope Pts KOPT(5) Not used.
KOPT(6) = 0 ; JFD Input: Units = Hours KOPT(7) = 0 ; Skip print of X/Q calc details KOPT(8) = 1 ; Input calms distributed into Bin 1 Card Type 8 values contain Calms JFD input array starts with Bin 2 KOPT(9) = 0 ; No Input Terrain Adj. - Card 12 KOPT(10)= 1 ; Use Card 12 Terrain Adj if input; if no user input, use default.
- End of ORNL/RSICC PAVAN Options ******
KOPT(11)= 0 ; Number of Boundaries- Default = 0 KOPT(12)= 0 ; Read JFD on Card Type=9 - Default l* PLANT NAME *ll* PERIOD OF DATA *ll* TYPE OF RELEASE*l 2 Callaway AST 2013-2016 METD Ground Level Release l* HGT-WIND SENSOR*ll** HGTS DELTA-T **l 3 10.0 Meters Delta-T from 10-60m l** REFERENCE FOR METEOROLOGICAL DATA **l 4 Meteorological Data JFD data from METD MJFREQ module - RB l** Special Comments: NONE, if None. **l 5 JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph Specify Wind Bins & Ter. Dist. & Receptor Names 6 13 0 SB LPZ # Hours Counted In FREQ Array: 35470 Cont Cont RlseHgt Wind Meas Area Height10=Grnd Height 7 1526.00 66.30 10.00 10.00 Internal Constant for Building Wake Term Calc: 0.500 3 to ULNRC-06696 Page 4 of 456 ENHANCED PRINTOUT OF INPUT CARDS - CONTINUED ON NEXT PAGE 3 to ULNRC-06696 Page 5 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 2 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 Calms measured in each of 7 Stability Classes, 8 0.0 0.0 0.0 1.0 585.0 136.0 198.0 KOPT(8) = 1. Card 8 calms distributed into Bin 1.
Stability Class: A 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 6 0.0 1.0 1.0 2.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 9 7 0.0 3.0 3.0 3.0 1.0 1.0 14.0 23.0 17.0 15.0 8.0 9.0 7.0 11.0 4.0 1.0 9 8 4.0 4.0 6.0 2.0 8.0 4.0 47.0 29.0 10.0 22.0 38.0 24.0 28.0 28.0 30.0 11.0 9 9 3.0 12.0 2.0 3.0 2.0 3.0 26.0 21.0 22.0 20.0 35.0 15.0 29.0 47.0 39.0 17.0 9 10 6.0 4.0 5.0 1.0 0.0 7.0 10.0 16.0 12.0 28.0 24.0 15.0 24.0 29.0 24.0 7.0 9 11 1.0 2.0 1.0 0.0 0.0 0.0 0.0 3.0 13.0 11.0 5.0 4.0 11.0 2.0 12.0 11.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: B 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 4 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 5 2.0 1.0 1.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 9 6 2.0 1.0 2.0 2.0 1.0 1.0 2.0 4.0 4.0 2.0 1.0 1.0 1.0 0.0 1.0 0.0 9 7 10.0 13.0 16.0 11.0 4.0 13.0 36.0 49.0 46.0 26.0 26.0 18.0 19.0 16.0 17.0 10.0 9 8 21.0 15.0 21.0 16.0 9.0 11.0 39.0 51.0 32.0 51.0 45.0 18.0 25.0 37.0 42.0 47.0 9 9 17.0 7.0 5.0 10.0 8.0 7.0 14.0 24.0 28.0 44.0 26.0 17.0 25.0 22.0 32.0 39.0 9 10 15.0 8.0 2.0 2.0 0.0 2.0 2.0 12.0 37.0 22.0 16.0 3.0 9.0 15.0 9.0 11.0 9 11 1.0 4.0 0.0 1.0 1.0 0.0 1.0 8.0 13.0 11.0 10.0 6.0 5.0 5.0 5.0 13.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 5.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: C 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 9 3 1.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 1.0 1.0 0.0 0.0 0.0 0.0 9 4 0.0 1.0 0.0 0.0 0.0 0.0 0.0 1.0 1.0 0.0 2.0 0.0 0.0 0.0 0.0 0.0 9 5 0.0 2.0 0.0 1.0 1.0 1.0 5.0 3.0 6.0 1.0 2.0 1.0 2.0 0.0 3.0 1.0 9 6 6.0 4.0 9.0 7.0 8.0 5.0 7.0 26.0 12.0 16.0 11.0 9.0 15.0 19.0 9.0 2.0 9 7 30.0 30.0 35.0 29.0 23.0 26.0 99.0 96.0 76.0 76.0 42.0 29.0 39.0 46.0 36.0 36.0 9 8 25.0 37.0 17.0 23.0 16.0 21.0 66.0 75.0 71.0 57.0 45.0 26.0 34.0 41.0 46.0 41.0 9 9 34.0 16.0 8.0 11.0 7.0 17.0 19.0 28.0 34.0 52.0 32.0 13.0 17.0 20.0 19.0 40.0 9 10 17.0 11.0 2.0 2.0 2.0 6.0 3.0 12.0 32.0 26.0 14.0 10.0 12.0 18.0 16.0 26.0 9 11 5.0 0.0 0.0 1.0 1.0 0.0 0.0 9.0 29.0 12.0 3.0 5.0 5.0 10.0 11.0 6.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 2.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 Stability Class: D 9 2 3.0 4.0 4.0 5.0 2.0 3.0 1.0 0.0 3.0 2.0 3.0 3.0 2.0 7.0 3.0 3.0 9 3 19.0 6.0 8.0 13.0 8.0 8.0 20.0 11.0 15.0 11.0 11.0 15.0 12.0 8.0 15.0 4.0 3 to ULNRC-06696 Page 6 of 456 9 4 11.0 9.0 18.0 6.0 7.0 12.0 20.0 13.0 7.0 8.0 12.0 8.0 7.0 12.0 13.0 8.0 9 5 26.0 33.0 36.0 42.0 43.0 50.0 68.0 40.0 41.0 23.0 32.0 20.0 34.0 40.0 40.0 29.0 9 6 73.0 87.0 61.0 81.0 70.0 105.0 170.0 146.0 86.0 60.0 72.0 48.0 104.0 108.0 92.0 81.0 9 7 203.0 212.0 208.0 213.0 209.0 282.0 471.0 344.0 220.0 163.0 171.0 118.0 172.0 255.0 285.0 277.0 9 8 291.0 201.0 155.0 135.0 139.0 175.0 254.0 249.0 220.0 196.0 159.0 86.0 128.0 234.0 236.0 338.0 9 9 283.0 138.0 74.0 49.0 60.0 94.0 73.0 139.0 187.0 137.0 106.0 63.0 123.0 174.0 195.0 203.0 9 10 156.0 55.0 24.0 17.0 19.0 16.0 11.0 62.0 133.0 73.0 59.0 33.0 88.0 106.0 116.0 127.0 9 11 66.0 20.0 22.0 9.0 4.0 4.0 1.0 31.0 183.0 48.0 35.0 29.0 71.0 61.0 49.0 79.0 9 12 5.0 0.0 7.0 0.0 0.0 0.0 0.0 0.0 16.0 4.0 3.0 4.0 7.0 1.0 1.0 9.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 2.0 1.0 0.0 0.0 1.0 3 to ULNRC-06696 Page 7 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 3 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 Stability Class: E 9 2 6.0 2.0 8.0 6.0 9.0 8.0 10.0 6.0 8.0 9.0 6.0 7.0 8.0 12.0 12.0 7.0 9 3 23.0 22.0 17.0 20.0 25.0 22.0 39.0 33.0 22.0 18.0 22.0 17.0 26.0 36.0 31.0 13.0 9 4 12.0 15.0 16.0 15.0 12.0 18.0 43.0 18.0 19.0 11.0 17.0 26.0 17.0 37.0 33.0 21.0 9 5 28.0 45.0 40.0 41.0 39.0 59.0 149.0 53.0 33.0 22.0 35.0 42.0 41.0 61.0 48.0 42.0 9 6 92.0 68.0 80.0 81.0 94.0 127.0 327.0 180.0 77.0 57.0 70.0 79.0 61.0 94.0 125.0 87.0 9 7 158.0 125.0 118.0 93.0 132.0 167.0 464.0 632.0 308.0 215.0 186.0 132.0 182.0 168.0 182.0 208.0 9 8 72.0 34.0 24.0 27.0 47.0 65.0 136.0 330.0 411.0 229.0 151.0 85.0 151.0 71.0 68.0 94.0 9 9 11.0 6.0 7.0 3.0 8.0 14.0 26.0 133.0 247.0 103.0 47.0 32.0 52.0 33.0 19.0 22.0 9 10 1.0 1.0 3.0 0.0 0.0 7.0 5.0 52.0 143.0 47.0 12.0 4.0 19.0 9.0 9.0 7.0 9 11 1.0 0.0 3.0 0.0 0.0 0.0 2.0 23.0 65.0 16.0 3.0 5.0 4.0 0.0 1.0 1.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2.0 1.0 0.0 0.0 2.0 1.0 0.0 1.0 1.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: F 9 2 7.0 6.0 9.0 13.0 10.0 16.0 23.0 16.0 15.0 7.0 7.0 4.0 14.0 7.0 6.0 9.0 9 3 22.0 27.0 31.0 23.0 29.0 37.0 68.0 37.0 22.0 12.0 17.0 22.0 26.0 38.0 26.0 29.0 9 4 24.0 17.0 22.0 22.0 24.0 24.0 72.0 35.0 14.0 13.0 16.0 18.0 13.0 23.0 22.0 4.0 9 5 24.0 31.0 48.0 48.0 39.0 53.0 140.0 89.0 34.0 39.0 28.0 28.0 19.0 61.0 66.0 21.0 9 6 58.0 39.0 37.0 40.0 28.0 46.0 147.0 229.0 93.0 66.0 74.0 30.0 34.0 65.0 86.0 49.0 9 7 33.0 25.0 19.0 18.0 12.0 15.0 93.0 550.0 236.0 118.0 121.0 38.0 35.0 44.0 38.0 81.0 9 8 2.0 1.0 0.0 0.0 1.0 0.0 1.0 96.0 123.0 63.0 28.0 6.0 6.0 0.0 0.0 5.0 9 9 0.0 0.0 0.0 0.0 0.0 0.0 2.0 2.0 15.0 6.0 0.0 2.0 1.0 0.0 0.0 0.0 9 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 11 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: G 9 2 11.0 15.0 9.0 11.0 10.0 13.0 20.0 18.0 19.0 10.0 7.0 9.0 6.0 5.0 4.0 10.0 9 3 34.0 32.0 31.0 18.0 16.0 15.0 41.0 60.0 29.0 10.0 18.0 12.0 11.0 23.0 29.0 15.0 9 4 14.0 19.0 15.0 9.0 5.0 7.0 12.0 37.0 15.0 7.0 6.0 6.0 5.0 19.0 22.0 12.0 9 5 25.0 25.0 34.0 9.0 7.0 8.0 27.0 60.0 26.0 20.0 11.0 9.0 7.0 24.0 29.0 30.0 9 6 26.0 23.0 15.0 6.0 2.0 2.0 19.0 79.0 37.0 17.0 13.0 4.0 6.0 14.0 27.0 29.0 9 7 5.0 3.0 1.0 0.0 0.0 0.0 6.0 117.0 32.0 13.0 7.0 1.0 2.0 3.0 18.0 10.0 9 8 0.0 0.0 0.0 0.0 1.0 0.0 0.0 28.0 9.0 2.0 2.0 0.0 0.0 0.0 0.0 0.0 9 9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 11 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Wind Bin Definitions: MPS - No Corrections Calm Bin 2 Bin 3 Bin 4 Bin 5 Bin 6 Bin 7 Bin 8 Bin 9 Bin10 Bin11 Bin12 Bin13 Bin14 10 -1. 0.50 0.75 1.00 1.25 1.50 2.00 3.00 4.00 5.00 6.00 8.00 10.00 99.00 0.00 Site Exclusion Boundary (SB) Downwind Distances (METERS) by Sector at which X/Q Estimates will be made.
3 to ULNRC-06696 Page 8 of 456 11 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200.
Low Population Zone (LPZ) Downwind Distances (METERS) by Sector at which X/Q Estimates will be made.
11 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023.
END OF ENHANCED INPUT ECHO - BEGIN PAVAN OUTPUT 3 to ULNRC-06696 Page 9 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 4 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS A WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.00 1.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.25 1.25 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.50 1.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.00 2.00 0.000 0.003 0.003 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.014 3.00 3.00 0.000 0.008 0.008 0.008 0.003 0.003 0.039 0.065 0.048 0.042 0.023 0.025 0.020 0.031 0.011 0.003 0.338 4.00 4.00 0.011 0.011 0.017 0.006 0.023 0.011 0.133 0.082 0.028 0.062 0.107 0.068 0.079 0.079 0.085 0.031 0.832 5.00 5.00 0.008 0.034 0.006 0.008 0.006 0.008 0.073 0.059 0.062 0.056 0.099 0.042 0.082 0.133 0.110 0.048 0.835 6.00 6.00 0.017 0.011 0.014 0.003 0.000 0.020 0.028 0.045 0.034 0.079 0.068 0.042 0.068 0.082 0.068 0.020 0.598 8.00 8.00 0.003 0.006 0.003 0.000 0.000 0.000 0.000 0.008 0.037 0.031 0.014 0.011 0.031 0.006 0.034 0.031 0.214 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.04 0.07 0.05 0.03 0.03 0.04 0.27 0.26 0.21 0.27 0.31 0.19 0.28 0.33 0.31 0.13 2.84 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS B WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.00 1.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.25 1.25 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 1.50 1.50 0.006 0.003 0.003 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.017 2.00 2.00 0.006 0.003 0.006 0.006 0.003 0.003 0.006 0.011 0.011 0.006 0.003 0.003 0.003 0.000 0.003 0.000 0.070 3.00 3.00 0.028 0.037 0.045 0.031 0.011 0.037 0.101 0.138 0.130 0.073 0.073 0.051 0.054 0.045 0.048 0.028 0.930 4.00 4.00 0.059 0.042 0.059 0.045 0.025 0.031 0.110 0.144 0.090 0.144 0.127 0.051 0.070 0.104 0.118 0.133 1.353 5.00 5.00 0.048 0.020 0.014 0.028 0.023 0.020 0.039 0.068 0.079 0.124 0.073 0.048 0.070 0.062 0.090 0.110 0.916 6.00 6.00 0.042 0.023 0.006 0.006 0.000 0.006 0.006 0.034 0.104 0.062 0.045 0.008 0.025 0.042 0.025 0.031 0.465 8.00 8.00 0.003 0.011 0.000 0.003 0.003 0.000 0.003 0.023 0.037 0.031 0.028 0.017 0.014 0.014 0.014 0.037 0.237 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.014 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.017 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.19 0.14 0.13 0.12 0.06 0.10 0.27 0.42 0.47 0.44 0.35 0.18 0.24 0.27 0.30 0.34 4.01 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS C 3 to ULNRC-06696 Page 10 of 456 WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 1.00 1.00 0.003 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.003 0.003 0.000 0.000 0.000 0.000 0.014 1.25 1.25 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.003 0.003 0.000 0.006 0.000 0.000 0.000 0.000 0.000 0.014 1.50 1.50 0.000 0.006 0.000 0.003 0.003 0.003 0.014 0.008 0.017 0.003 0.006 0.003 0.006 0.000 0.008 0.003 0.082 2.00 2.00 0.017 0.011 0.025 0.020 0.023 0.014 0.020 0.073 0.034 0.045 0.031 0.025 0.042 0.054 0.025 0.006 0.465 3.00 3.00 0.085 0.085 0.099 0.082 0.065 0.073 0.279 0.271 0.214 0.214 0.118 0.082 0.110 0.130 0.101 0.101 2.109 4.00 4.00 0.070 0.104 0.048 0.065 0.045 0.059 0.186 0.211 0.200 0.161 0.127 0.073 0.096 0.116 0.130 0.116 1.807 5.00 5.00 0.096 0.045 0.023 0.031 0.020 0.048 0.054 0.079 0.096 0.147 0.090 0.037 0.048 0.056 0.054 0.113 1.035 6.00 6.00 0.048 0.031 0.006 0.006 0.006 0.017 0.008 0.034 0.090 0.073 0.039 0.028 0.034 0.051 0.045 0.073 0.589 8.00 8.00 0.014 0.000 0.000 0.003 0.003 0.000 0.000 0.025 0.082 0.034 0.008 0.014 0.014 0.028 0.031 0.017 0.273 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.006 0.014 0.000 0.000 0.000 0.000 0.000 0.000 0.023 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 TOTAL 0.33 0.28 0.20 0.21 0.16 0.21 0.56 0.71 0.74 0.69 0.43 0.27 0.36 0.43 0.39 0.43 6.42 3 to ULNRC-06696 Page 11 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 5 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS D WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.75 0.75 0.008 0.011 0.011 0.014 0.006 0.008 0.003 0.000 0.008 0.006 0.008 0.008 0.006 0.020 0.008 0.008 0.135 1.00 1.00 0.054 0.017 0.023 0.037 0.023 0.023 0.056 0.031 0.042 0.031 0.031 0.042 0.034 0.023 0.042 0.011 0.519 1.25 1.25 0.031 0.025 0.051 0.017 0.020 0.034 0.056 0.037 0.020 0.023 0.034 0.023 0.020 0.034 0.037 0.023 0.482 1.50 1.50 0.073 0.093 0.101 0.118 0.121 0.141 0.192 0.113 0.116 0.065 0.090 0.056 0.096 0.113 0.113 0.082 1.683 2.00 2.00 0.206 0.245 0.172 0.228 0.197 0.296 0.479 0.412 0.242 0.169 0.203 0.135 0.293 0.304 0.259 0.228 4.071 3.00 3.00 0.572 0.598 0.586 0.601 0.589 0.795 1.328 0.970 0.620 0.460 0.482 0.333 0.485 0.719 0.803 0.781 10.722 4.00 4.00 0.820 0.567 0.437 0.381 0.392 0.493 0.716 0.702 0.620 0.553 0.448 0.242 0.361 0.660 0.665 0.953 9.010 5.00 5.00 0.798 0.389 0.209 0.138 0.169 0.265 0.206 0.392 0.527 0.386 0.299 0.178 0.347 0.491 0.550 0.572 5.915 6.00 6.00 0.440 0.155 0.068 0.048 0.054 0.045 0.031 0.175 0.375 0.206 0.166 0.093 0.248 0.299 0.327 0.358 3.087 8.00 8.00 0.186 0.056 0.062 0.025 0.011 0.011 0.003 0.087 0.516 0.135 0.099 0.082 0.200 0.172 0.138 0.223 2.007 10.00 10.00 0.014 0.000 0.020 0.000 0.000 0.000 0.000 0.000 0.045 0.011 0.008 0.011 0.020 0.003 0.003 0.025 0.161 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.006 0.003 0.000 0.000 0.003 0.014 TOTAL 3.20 2.16 1.74 1.61 1.58 2.11 3.07 2.92 3.13 2.04 1.87 1.21 2.11 2.84 2.95 3.27 37.81 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS E WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.070 0.086 0.083 0.084 0.087 0.109 0.246 0.112 0.084 0.061 0.082 0.094 0.094 0.149 0.126 0.085 1.649 0.75 0.75 0.017 0.006 0.023 0.017 0.025 0.023 0.028 0.017 0.023 0.025 0.017 0.020 0.023 0.034 0.034 0.020 0.350 1.00 1.00 0.065 0.062 0.048 0.056 0.070 0.062 0.110 0.093 0.062 0.051 0.062 0.048 0.073 0.101 0.087 0.037 1.088 1.25 1.25 0.034 0.042 0.045 0.042 0.034 0.051 0.121 0.051 0.054 0.031 0.048 0.073 0.048 0.104 0.093 0.059 0.930 1.50 1.50 0.079 0.127 0.113 0.116 0.110 0.166 0.420 0.149 0.093 0.062 0.099 0.118 0.116 0.172 0.135 0.118 2.193 2.00 2.00 0.259 0.192 0.226 0.228 0.265 0.358 0.922 0.507 0.217 0.161 0.197 0.223 0.172 0.265 0.352 0.245 4.790 3.00 3.00 0.445 0.352 0.333 0.262 0.372 0.471 1.308 1.782 0.868 0.606 0.524 0.372 0.513 0.474 0.513 0.586 9.783 4.00 4.00 0.203 0.096 0.068 0.076 0.133 0.183 0.383 0.930 1.159 0.646 0.426 0.240 0.426 0.200 0.192 0.265 5.624 5.00 5.00 0.031 0.017 0.020 0.008 0.023 0.039 0.073 0.375 0.696 0.290 0.133 0.090 0.147 0.093 0.054 0.062 2.151 6.00 6.00 0.003 0.003 0.008 0.000 0.000 0.020 0.014 0.147 0.403 0.133 0.034 0.011 0.054 0.025 0.025 0.020 0.899 8.00 8.00 0.003 0.000 0.008 0.000 0.000 0.000 0.006 0.065 0.183 0.045 0.008 0.014 0.011 0.000 0.003 0.003 0.350 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.003 0.000 0.000 0.006 0.003 0.000 0.003 0.003 0.023 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.21 0.98 0.97 0.89 1.12 1.48 3.63 4.23 3.84 2.11 1.63 1.31 1.68 1.62 1.62 1.50 29.83 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS F 3 to ULNRC-06696 Page 12 of 456 WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.017 0.018 0.024 0.023 0.022 0.028 0.066 0.038 0.018 0.015 0.015 0.016 0.016 0.028 0.026 0.014 0.383 0.75 0.75 0.020 0.017 0.025 0.037 0.028 0.045 0.065 0.045 0.042 0.020 0.020 0.011 0.039 0.020 0.017 0.025 0.476 1.00 1.00 0.062 0.076 0.087 0.065 0.082 0.104 0.192 0.104 0.062 0.034 0.048 0.062 0.073 0.107 0.073 0.082 1.314 1.25 1.25 0.068 0.048 0.062 0.062 0.068 0.068 0.203 0.099 0.039 0.037 0.045 0.051 0.037 0.065 0.062 0.011 1.023 1.50 1.50 0.068 0.087 0.135 0.135 0.110 0.149 0.395 0.251 0.096 0.110 0.079 0.079 0.054 0.172 0.186 0.059 2.165 2.00 2.00 0.164 0.110 0.104 0.113 0.079 0.130 0.414 0.646 0.262 0.186 0.209 0.085 0.096 0.183 0.242 0.138 3.160 3.00 3.00 0.093 0.070 0.054 0.051 0.034 0.042 0.262 1.551 0.665 0.333 0.341 0.107 0.099 0.124 0.107 0.228 4.161 4.00 4.00 0.006 0.003 0.000 0.000 0.003 0.000 0.003 0.271 0.347 0.178 0.079 0.017 0.017 0.000 0.000 0.014 0.936 5.00 5.00 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.006 0.042 0.017 0.000 0.006 0.003 0.000 0.000 0.000 0.079 6.00 6.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 8.00 8.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.50 0.43 0.49 0.49 0.43 0.57 1.61 3.02 1.58 0.93 0.84 0.43 0.43 0.70 0.71 0.57 13.71 3 to ULNRC-06696 Page 13 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 6 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS G WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.041 0.045 0.044 0.023 0.019 0.021 0.049 0.086 0.044 0.023 0.021 0.018 0.014 0.035 0.041 0.033 0.558 0.75 0.75 0.031 0.042 0.025 0.031 0.028 0.037 0.056 0.051 0.054 0.028 0.020 0.025 0.017 0.014 0.011 0.028 0.499 1.00 1.00 0.096 0.090 0.087 0.051 0.045 0.042 0.116 0.169 0.082 0.028 0.051 0.034 0.031 0.065 0.082 0.042 1.111 1.25 1.25 0.039 0.054 0.042 0.025 0.014 0.020 0.034 0.104 0.042 0.020 0.017 0.017 0.014 0.054 0.062 0.034 0.592 1.50 1.50 0.070 0.070 0.096 0.025 0.020 0.023 0.076 0.169 0.073 0.056 0.031 0.025 0.020 0.068 0.082 0.085 0.990 2.00 2.00 0.073 0.065 0.042 0.017 0.006 0.006 0.054 0.223 0.104 0.048 0.037 0.011 0.017 0.039 0.076 0.082 0.899 3.00 3.00 0.014 0.008 0.003 0.000 0.000 0.000 0.017 0.330 0.090 0.037 0.020 0.003 0.006 0.008 0.051 0.028 0.615 4.00 4.00 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.079 0.025 0.006 0.006 0.000 0.000 0.000 0.000 0.000 0.118 5.00 5.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 6.00 6.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 8.00 8.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.37 0.37 0.34 0.17 0.13 0.15 0.40 1.22 0.52 0.25 0.20 0.13 0.12 0.28 0.41 0.33 5.39 WIND MEASURED AT 10.0 METERS.
WIND SPEED CORRECTED TO THE RELEASE HEIGHT OF 10.0 METERS.
OVERALL WIND DIRECTION FREQUENCY WIND DIRECTION: N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW FREQUENCY: 5.8 4.4 3.9 3.5 3.5 4.7 9.8 12.8 10.5 6.7 5.6 3.7 5.2 6.5 6.7 6.6 OVERALL WIND SPEED FREQUENCY AS MEASURED ON THE TOWER:
MAX.WIND SPEED (M/S): 0.50 0.75 1.00 1.25 1.50 2.00 3.00 4.00 5.00 6.00 8.00 10.00 99.00 WIND SPEED FREQUENCY: 2.59 1.46 4.05 3.04 7.13 13.47 28.66 19.68 10.93 5.64 3.09 0.23 0.02 BUILDING AND RELEASE CHARACTERISTICS:
RELEASE HEIGHT: 10.00 METERS MIXING VOLUME COEFFICIENT: 0.50 BUILDING CROSS-SECTIONAL AREA: 1526.00 SQUARE METERS BOUNDARY DISTANCES (METERS) FROM THE SOURCE FOR EACH DOWNWIND SECTOR:
DOWNWIND SECTOR S SSW SW WSW W WNW NW NNW N NNE NE ENE E ESE SE SSE SB BOUNDARY 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200.
3 to ULNRC-06696 Page 14 of 456 LPZ BOUNDARY 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023.
3 to ULNRC-06696 Page 15 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 7 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph WINDSPEEDS ADJUSTED TO 10.0 METERS.
PERCENT OF THE TIME A GIVEN WINDSPEED IS LOWER:
WINDSPEED CUMULATIVE FREQUENCY (METER/SEC) (PERCENT) 0.50 2.59 0.75 4.06 1.00 8.10 1.25 11.15 1.50 18.28 2.00 31.75 3.00 60.41 4.00 80.09 5.00 91.02 6.00 96.66 8.00 99.75 10.00 99.98 99.00 100.00 ERROR IN NORMAL TRANSFORMATION FOR A( 13)= 100.00002 3 to ULNRC-06696 Page 16 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 8 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOG-NORMAL INTERPOLATION PERCENTILES WINDSPEED CUMULATIVE FREQUENCY (METER/SEC) (PERCENT) 0.23 1.00 0.57 3.00 0.81 5.00 1.16 10.00 1.39 15.00 1.56 20.00 1.75 25.00 1.93 30.00 2.10 35.00 2.26 40.00 2.42 45.00 2.60 50.00 2.78 55.00 2.98 60.00 3.19 65.00 3.41 70.00 3.68 75.00 3.99 80.00 4.45 85.00 4.87 90.00 3 to ULNRC-06696 Page 17 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 9 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.710 1.241 1.527 3.169 3.507 4.183 5.388 6.596 7.658 7.900 0.04142 0.07243 0.08915 0.18501 0.20474 0.24421 0.31455 0.38503 0.44705 0.46115 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 9.059 9.061 9.351 10.607 11.766 12.877 13.022 13.118 14.712 17.513 0.52881 0.52898 0.54589 0.61920 0.68686 0.75170 0.76016 0.76580 0.85884 1.02235 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 3.408E-05 18.093 19.010 20.362 20.894 25.337 32.967 34.223 37.700 38.231 38.280 1.05619 1.10975 1.18869 1.21970 1.47908 1.92452 1.99783 2.20081 2.23183 2.23465 2.964E-05 2.949E-05 2.412E-05 2.223E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 38.328 41.853 51.657 51.706 65.759 79.427 79.716 87.250 90.438 91.887 2.23747 2.44327 3.01559 3.01841 3.83882 4.63668 4.65359 5.09340 5.27947 5.36405 9.417E-06 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 2.825E-06 91.983 92.225 93.432 93.529 95.171 95.992 96.475 96.716 97.730 98.551 5.36969 5.38379 5.45427 5.45991 5.55576 5.60369 5.63188 5.64598 5.70518 5.75311 2.354E-06 1.766E-06 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 18 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 19 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 10 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.877E-04 0.058 1.000 2.353E-04 0.175 3.000 1.834E-04 0.292 5.000 1.181E-04 0.584 10.000 8.421E-05 0.876 15.000 6.613E-05 1.168 20.000 5.482E-05 1.459 25.000 4.682E-05 1.751 30.000 4.084E-05 2.043 35.000 3.616E-05 2.335 40.000 3.239E-05 2.627 45.000 2.929E-05 2.919 50.000 2.671E-05 3.211 55.000 2.451E-05 3.503 60.000 2.263E-05 3.794 65.000 2.099E-05 4.086 70.000 1.955E-05 4.378 75.000 1.818E-05 4.670 80.000 1.624E-05 4.962 85.000 1.345E-04 0.5 8.57 ANNUAL AVERAGE = 5.99E-06 3 to ULNRC-06696 Page 20 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 11 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.011 1.964 2.360 4.392 4.773 5.980 7.909 9.496 11.211 11.402 0.04487 0.08716 0.10475 0.19497 0.21188 0.26545 0.35107 0.42156 0.49768 0.50613 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 12.481 12.484 12.611 14.072 16.041 17.438 17.692 17.756 19.343 21.820 0.55406 0.55421 0.55985 0.62469 0.71209 0.77411 0.78539 0.78821 0.85869 0.96864 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.964E-05 22.773 23.154 26.012 26.583 30.902 38.841 40.937 43.096 43.477 43.540 1.01093 1.02785 1.15472 1.18009 1.37180 1.72421 1.81725 1.91310 1.93002 1.93284 2.949E-05 2.726E-05 2.412E-05 2.272E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 49.066 49.129 62.593 62.720 75.485 84.250 84.504 87.997 89.267 91.172 2.17812 2.18094 2.77862 2.78426 3.35094 3.74000 3.75128 3.90634 3.96272 4.04730 9.417E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 3.532E-06 2.825E-06 2.354E-06 1.766E-06 91.236 93.586 93.649 94.665 95.364 96.189 97.142 97.587 98.095 98.349 4.05012 4.15443 4.15725 4.20236 4.23337 4.27002 4.31231 4.33205 4.35460 4.36588 1.085E-06 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 21 of 456 98.412 98.603 98.857 99.619 99.873 100.000 4.36870 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 22 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 12 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.513E-04 0.044 1.000 2.795E-04 0.133 3.000 2.203E-04 0.222 5.000 1.564E-04 0.444 10.000 1.062E-04 0.666 15.000 8.010E-05 0.888 20.000 6.497E-05 1.110 25.000 5.463E-05 1.332 30.000 4.702E-05 1.554 35.000 4.118E-05 1.776 40.000 3.652E-05 1.998 45.000 3.271E-05 2.220 50.000 2.956E-05 2.442 55.000 2.692E-05 2.664 60.000 2.466E-05 2.885 65.000 2.272E-05 3.107 70.000 2.103E-05 3.329 75.000 1.954E-05 3.551 80.000 1.778E-05 3.773 85.000 1.467E-04 0.5 11.26 ANNUAL AVERAGE = 5.62E-06 3 to ULNRC-06696 Page 23 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 13 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.116 1.762 2.369 4.593 5.238 6.314 8.414 10.852 13.076 13.147 0.04389 0.06926 0.09314 0.18054 0.20592 0.24820 0.33077 0.42663 0.51402 0.51684 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 14.725 14.730 15.303 16.379 19.822 21.041 21.328 22.690 25.344 26.491 0.57887 0.57905 0.60161 0.64390 0.77922 0.82715 0.83843 0.89199 0.99631 1.04142 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 3.408E-05 2.964E-05 27.065 29.934 31.224 36.962 45.424 48.006 49.727 50.229 50.301 50.516 1.06397 1.17674 1.22749 1.45303 1.78571 1.88720 1.95486 1.97460 1.97742 1.98588 2.949E-05 2.412E-05 2.223E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 9.417E-06 54.891 69.808 70.023 81.139 86.446 87.091 88.812 90.390 92.900 92.972 2.15785 2.74426 2.75272 3.18971 3.39834 3.42371 3.49137 3.55340 3.65207 3.65489 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 3.532E-06 2.825E-06 2.354E-06 1.085E-06 93.474 94.693 94.836 95.410 95.554 96.701 98.207 98.566 98.709 98.781 3.67463 3.72256 3.72819 3.75075 3.75639 3.80150 3.86070 3.87480 3.88044 3.88326 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 24 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 25 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 14 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.698E-04 0.039 1.000 2.955E-04 0.118 3.000 2.347E-04 0.197 5.000 1.687E-04 0.393 10.000 1.293E-04 0.590 15.000 9.733E-05 0.786 20.000 7.496E-05 0.983 25.000 6.291E-05 1.179 30.000 5.423E-05 1.376 35.000 4.756E-05 1.572 40.000 4.227E-05 1.769 45.000 3.794E-05 1.966 50.000 3.382E-05 2.162 55.000 3.041E-05 2.359 60.000 2.753E-05 2.555 65.000 2.509E-05 2.752 70.000 2.298E-05 2.948 75.000 2.115E-05 3.145 80.000 1.902E-05 3.342 85.000 1.496E-04 0.5 12.72 ANNUAL AVERAGE = 5.51E-06 3 to ULNRC-06696 Page 26 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 15 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.660 1.542 2.198 3.642 4.685 5.408 7.787 8.509 10.355 12.120 0.02318 0.05419 0.07720 0.12795 0.16460 0.18997 0.27356 0.29893 0.36378 0.42580 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 12.126 12.607 13.089 16.941 18.546 18.947 20.391 23.601 24.805 25.849 0.42599 0.44290 0.45982 0.59514 0.65153 0.66563 0.71637 0.82914 0.87143 0.90808 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.949E-05 2.412E-05 2.272E-05 29.139 29.620 36.121 43.584 46.954 49.121 49.362 55.862 72.956 73.036 1.02368 1.04059 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.56582 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 8.519E-06 7.063E-06 6.815E-06 5.679E-06 83.870 87.802 88.364 89.728 90.450 92.777 94.623 94.784 95.666 95.827 2.94643 3.08457 3.10431 3.15223 3.17761 3.25937 3.32421 3.32985 3.36086 3.36650 4.709E-06 4.259E-06 3.532E-06 2.825E-06 2.354E-06 1.766E-06 1.085E-06 7.231E-07 5.423E-07 4.338E-07 96.710 96.790 98.074 98.876 99.037 99.117 99.278 99.519 99.679 99.920 3.39751 3.40033 3.44544 3.47363 3.47927 3.48209 3.48773 3.49619 3.50183 3.51028 3.615E-07 3 to ULNRC-06696 Page 27 of 456 100.000 3.51310 3 to ULNRC-06696 Page 28 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 16 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.900E-04 0.035 1.000 2.599E-04 0.105 3.000 2.095E-04 0.176 5.000 1.504E-04 0.351 10.000 1.089E-04 0.527 15.000 8.527E-05 0.703 20.000 7.019E-05 0.878 25.000 5.988E-05 1.054 30.000 5.219E-05 1.230 35.000 4.623E-05 1.405 40.000 4.146E-05 1.581 45.000 3.746E-05 1.757 50.000 3.372E-05 1.932 55.000 3.059E-05 2.108 60.000 2.794E-05 2.284 65.000 2.567E-05 2.459 70.000 2.369E-05 2.635 75.000 2.196E-05 2.810 80.000 1.138E-04 0.5 14.23 ANNUAL AVERAGE = 4.70E-06 3 to ULNRC-06696 Page 29 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 17 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.532 1.334 1.963 3.245 4.046 4.446 6.908 7.469 9.792 9.872 0.01874 0.04693 0.06908 0.11419 0.14238 0.15647 0.24312 0.26285 0.34461 0.34743 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 11.795 11.800 12.521 12.681 15.805 17.808 17.968 18.048 19.009 21.253 0.41509 0.41526 0.44064 0.44628 0.55623 0.62671 0.63235 0.63517 0.66900 0.74794 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.949E-05 22.214 22.855 25.979 26.540 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.80432 0.91428 0.93401 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 2.412E-05 2.272E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 8.519E-06 7.063E-06 74.846 74.926 86.061 90.868 91.508 93.030 93.351 95.193 96.475 96.555 2.63404 2.63686 3.02874 3.19790 3.22045 3.27402 3.28529 3.35014 3.39525 3.39807 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 2.825E-06 1.766E-06 7.231E-07 5.423E-07 4.338E-07 97.116 97.276 97.597 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.41780 3.42344 3.43472 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 30 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 18 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.684E-04 0.035 1.000 2.480E-04 0.106 3.000 1.995E-04 0.176 5.000 1.450E-04 0.352 10.000 1.029E-04 0.528 15.000 7.830E-05 0.704 20.000 6.579E-05 0.880 25.000 5.771E-05 1.056 30.000 5.154E-05 1.232 35.000 4.663E-05 1.408 40.000 4.263E-05 1.584 45.000 3.930E-05 1.760 50.000 3.567E-05 1.936 55.000 3.221E-05 2.112 60.000 2.928E-05 2.288 65.000 2.679E-05 2.464 70.000 2.463E-05 2.639 75.000 2.275E-05 2.815 80.000 2.110E-05 2.991 85.000 1.078E-04 0.5 14.21 ANNUAL AVERAGE = 4.57E-06 3 to ULNRC-06696 Page 31 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 19 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.455 1.240 1.846 2.752 3.720 4.143 6.481 6.965 9.201 10.652 0.02120 0.05786 0.08608 0.12837 0.17348 0.19321 0.30228 0.32484 0.42915 0.49681 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 10.657 11.140 11.261 14.465 15.795 15.976 16.883 19.664 20.752 21.235 0.49702 0.51957 0.52521 0.67463 0.73666 0.74511 0.78740 0.91709 0.96784 0.99039 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.964E-05 2.949E-05 2.412E-05 24.802 25.527 33.204 43.299 46.321 50.251 51.097 51.520 57.867 74.914 1.15673 1.19056 1.54861 2.01943 2.16040 2.34365 2.38312 2.40285 2.69888 3.49392 2.272E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 1.130E-05 8.519E-06 7.063E-06 74.974 85.553 91.235 91.537 92.504 92.746 94.318 94.378 95.648 95.708 3.49674 3.99011 4.25512 4.26922 4.31433 4.32560 4.39891 4.40173 4.46093 4.46375 6.815E-06 5.679E-06 4.709E-06 3.532E-06 2.825E-06 2.354E-06 7.231E-07 5.423E-07 4.338E-07 3.615E-07 96.736 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.51168 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 32 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 20 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.565E-04 0.047 1.000 2.418E-04 0.140 3.000 1.943E-04 0.233 5.000 1.371E-04 0.466 10.000 9.510E-05 0.700 15.000 7.293E-05 0.933 20.000 6.282E-05 1.166 25.000 5.543E-05 1.399 30.000 4.974E-05 1.632 35.000 4.519E-05 1.866 40.000 4.146E-05 2.099 45.000 3.834E-05 2.332 50.000 3.457E-05 2.565 55.000 3.137E-05 2.798 60.000 2.865E-05 3.032 65.000 2.631E-05 3.265 70.000 2.428E-05 3.498 75.000 2.250E-05 3.731 80.000 2.093E-05 3.964 85.000 1.289E-04 0.5 10.72 ANNUAL AVERAGE = 5.81E-06 3 to ULNRC-06696 Page 33 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 21 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 1.078 1.748 2.927 3.588 3.933 6.437 7.213 9.168 9.340 0.04931 0.10570 0.17148 0.28707 0.35192 0.38575 0.63141 0.70753 0.89924 0.91616 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 11.410 11.413 11.701 12.247 16.271 17.392 17.420 17.449 20.122 24.348 1.11914 1.11945 1.14764 1.20121 1.59591 1.70586 1.70868 1.71150 1.97370 2.38813 6.896E-05 6.748E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 25.584 25.641 26.216 30.499 31.074 40.473 53.810 55.764 59.673 60.420 2.50936 2.51500 2.57138 2.99146 3.04784 3.96975 5.27790 5.46961 5.85303 5.92633 2.964E-05 2.949E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 60.564 65.451 78.989 79.132 79.190 86.491 88.589 88.790 89.106 89.135 5.94043 6.41971 7.74759 7.76169 7.76732 8.48342 8.68923 8.70896 8.73998 8.74279 1.136E-05 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 3.532E-06 2.825E-06 2.354E-06 1.766E-06 91.981 93.878 93.935 94.481 94.568 95.602 96.723 97.126 97.183 97.212 9.02190 9.20798 9.21362 9.26718 9.27564 9.37713 9.48709 9.52656 9.53219 9.53501 7.231E-07 5.423E-07 4.338E-07 3.615E-07 3 to ULNRC-06696 Page 34 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 35 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 22 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.581E-04 0.098 1.000 2.384E-04 0.294 3.000 1.928E-04 0.490 5.000 1.390E-04 0.981 10.000 1.044E-04 1.471 15.000 8.506E-05 1.962 20.000 7.244E-05 2.452 25.000 6.387E-05 2.943 30.000 5.724E-05 3.433 35.000 5.193E-05 3.923 40.000 4.755E-05 4.414 45.000 4.388E-05 4.904 50.000 4.074E-05 5.395 55.000 3.787E-05 5.885 60.000 3.334E-05 6.376 65.000 2.958E-05 6.866 70.000 2.641E-05 7.356 75.000 2.371E-05 7.847 80.000 2.140E-05 8.337 85.000 1.912E-04 0.5 5.10 ANNUAL AVERAGE = 1.28E-05 3 to ULNRC-06696 Page 36 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 23 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.676 1.073 1.374 2.698 3.051 3.868 4.745 6.069 6.886 7.504 0.08630 0.13704 0.17547 0.34463 0.38974 0.49405 0.60618 0.77534 0.87965 0.95859 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.763E-05 7.690E-05 7.375E-05 10.086 10.859 10.860 10.992 12.736 14.700 15.428 17.547 29.686 34.740 1.28845 1.38712 1.38730 1.40422 1.62694 1.87786 1.97089 2.24154 3.79215 4.43777 7.104E-05 6.896E-05 6.748E-05 5.898E-05 5.747E-05 5.683E-05 4.718E-05 4.310E-05 4.217E-05 4.050E-05 34.762 35.159 35.203 35.446 36.615 36.638 36.924 40.897 40.919 54.867 4.44059 4.49133 4.49697 4.52798 4.67740 4.68022 4.71687 5.22435 5.22716 7.00895 3.932E-05 3.819E-05 3.557E-05 3.374E-05 2.964E-05 2.949E-05 2.726E-05 2.412E-05 2.272E-05 2.223E-05 55.750 63.033 65.968 65.990 67.138 70.360 70.382 77.974 78.041 78.548 7.12172 8.05209 8.42705 8.42987 8.57647 8.98809 8.99091 9.96074 9.96920 10.03404 2.077E-05 1.842E-05 1.778E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 9.417E-06 8.519E-06 7.063E-06 84.044 87.111 87.155 87.729 89.098 89.782 91.900 91.922 93.578 93.666 10.73604 11.12793 11.13356 11.20687 11.38166 11.46906 11.73971 11.74253 11.95398 11.96525 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 3.408E-06 2.825E-06 2.354E-06 1.766E-06 7.231E-07 3 to ULNRC-06696 Page 37 of 456 94.284 94.549 95.630 95.829 96.954 96.976 97.506 97.771 97.948 98.455 12.04419 12.07803 12.21617 12.24154 12.38533 12.38815 12.45581 12.48964 12.51220 12.57704 5.423E-07 4.338E-07 3.615E-07 2.712E-07 2.169E-07 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 38 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 24 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.790E-04 0.128 1.000 2.277E-04 0.383 3.000 1.761E-04 0.639 5.000 1.364E-04 1.277 10.000 1.134E-04 1.916 15.000 9.850E-05 2.555 20.000 8.793E-05 3.194 25.000 7.987E-05 3.832 30.000 7.199E-05 4.471 35.000 4.641E-05 5.110 40.000 4.225E-05 5.748 45.000 4.132E-05 6.387 50.000 4.046E-05 7.026 55.000 3.901E-05 7.665 60.000 3.640E-05 8.303 65.000 3.127E-05 8.942 70.000 2.686E-05 9.581 75.000 2.324E-05 10.220 80.000 1.996E-04 0.5 3.91 ANNUAL AVERAGE = 1.42E-05 3 to ULNRC-06696 Page 39 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 25 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.418 0.929 1.105 1.884 2.287 2.690 3.486 4.185 4.776 5.018 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.36583 0.43913 0.50116 0.52653 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.137E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 5.878 6.254 6.256 6.471 6.498 7.492 8.405 8.996 9.077 12.382 0.61675 0.65622 0.65640 0.67896 0.68178 0.78609 0.88195 0.94397 0.95243 1.29920 7.690E-05 7.375E-05 6.896E-05 6.748E-05 5.898E-05 5.747E-05 5.623E-05 4.718E-05 4.310E-05 4.050E-05 18.723 21.221 21.732 22.135 22.538 23.425 23.452 23.640 25.709 33.984 1.96455 2.22675 2.28031 2.32260 2.36489 2.45793 2.46075 2.48048 2.69757 3.56591 3.932E-05 3.819E-05 3.557E-05 3.408E-05 2.964E-05 2.949E-05 2.726E-05 2.412E-05 2.272E-05 2.223E-05 35.086 46.129 52.765 52.792 56.634 58.945 58.972 64.883 65.044 66.791 3.68150 4.84022 5.53658 5.53940 5.94256 6.18502 6.18784 6.80808 6.82500 7.00825 2.077E-05 1.842E-05 1.778E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 9.280E-06 8.519E-06 7.063E-06 72.702 77.726 77.753 78.075 81.649 86.566 88.608 89.038 90.945 91.053 7.62849 8.15570 8.15852 8.19235 8.56732 9.08324 9.29751 9.34262 9.54279 9.55406 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 3.408E-06 2.825E-06 2.354E-06 1.766E-06 1.413E-06 3 to ULNRC-06696 Page 40 of 456 91.966 92.826 94.062 94.841 95.701 95.755 96.507 97.501 97.851 97.985 9.64992 9.74014 9.86982 9.95158 10.04180 10.04744 10.12638 10.23069 10.26734 10.28144 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 2.169E-07 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 41 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 26 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.097E-04 0.105 1.000 1.861E-04 0.315 3.000 1.450E-04 0.525 5.000 9.172E-05 1.049 10.000 7.729E-05 1.574 15.000 7.523E-05 2.099 20.000 6.043E-05 2.623 25.000 4.811E-05 3.148 30.000 3.944E-05 3.673 35.000 3.878E-05 4.197 40.000 3.830E-05 4.722 45.000 3.660E-05 5.246 50.000 3.324E-05 5.771 55.000 2.880E-05 6.296 60.000 2.518E-05 6.820 65.000 2.218E-05 7.345 70.000 1.964E-05 7.870 75.000 1.477E-04 0.5 4.77 ANNUAL AVERAGE = 8.90E-06 3 to ULNRC-06696 Page 42 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 27 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.344 0.763 0.992 1.411 1.704 1.997 2.906 3.744 4.246 4.330 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19561 0.25199 0.28582 0.29146 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 4.875 5.419 5.421 5.798 6.510 8.144 8.898 8.981 11.620 16.563 0.32811 0.36476 0.36489 0.39026 0.43819 0.54814 0.59889 0.60453 0.78214 1.11482 7.375E-05 6.896E-05 6.748E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 19.327 19.788 20.039 20.500 21.422 21.757 24.144 33.150 34.113 43.705 1.30089 1.33190 1.34882 1.37983 1.44186 1.46441 1.62511 2.23125 2.29610 2.94171 3.557E-05 2.964E-05 2.949E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 48.019 49.988 52.501 59.329 59.370 60.041 68.250 73.989 74.659 77.717 3.23210 3.36461 3.53376 3.99331 3.99613 4.04123 4.59381 4.98006 5.02517 5.23097 1.160E-05 1.136E-05 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 79.727 82.910 83.078 85.466 85.549 87.727 88.816 89.905 90.408 92.544 5.36630 5.58056 5.59184 5.75254 5.75818 5.90478 5.97808 6.05138 6.08522 6.22900 3.408E-06 2.825E-06 2.354E-06 1.766E-06 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 43 of 456 92.754 94.597 95.518 95.979 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.46018 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 44 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 28 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.940E-04 0.067 1.000 1.755E-04 0.202 3.000 1.348E-04 0.337 5.000 9.833E-05 0.673 10.000 8.080E-05 1.010 15.000 7.186E-05 1.346 20.000 6.045E-05 1.683 25.000 5.226E-05 2.019 30.000 4.606E-05 2.356 35.000 4.119E-05 2.692 40.000 3.736E-05 3.029 45.000 1.129E-04 0.5 7.43 ANNUAL AVERAGE = 5.56E-06 3 to ULNRC-06696 Page 45 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 29 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.368 0.718 0.980 1.881 2.232 2.532 3.980 4.531 5.382 5.482 0.02071 0.04045 0.05521 0.10596 0.12569 0.14261 0.22415 0.25517 0.30309 0.30873 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 5.832 6.633 6.636 6.937 7.588 8.989 10.091 10.241 11.642 17.700 0.32847 0.37358 0.37374 0.39066 0.42731 0.50625 0.56827 0.57673 0.65567 0.99680 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 21.404 22.255 22.806 24.558 25.159 28.663 37.975 39.576 47.136 49.489 1.20543 1.25336 1.28437 1.38304 1.41688 1.61422 2.13861 2.22883 2.65454 2.78705 3.408E-05 2.964E-05 2.949E-05 2.726E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.704E-05 49.539 50.139 53.744 53.844 62.404 62.504 62.655 70.614 75.921 76.471 2.78987 2.82370 3.02669 3.03232 3.51442 3.52006 3.52852 3.97678 4.27563 4.30664 1.547E-05 1.160E-05 1.136E-05 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 79.425 81.177 83.280 83.430 85.683 85.733 87.335 88.035 89.337 89.487 4.47298 4.57165 4.69006 4.69852 4.82539 4.82821 4.91843 4.95790 5.03120 5.03965 3.532E-06 2.825E-06 2.354E-06 1.766E-06 1.413E-06 1.085E-06 9.374E-07 7.231E-07 5.423E-07 4.338E-07 3 to ULNRC-06696 Page 46 of 456 91.740 93.042 93.843 94.343 94.393 94.443 94.493 94.894 96.796 98.548 5.16652 5.23982 5.28493 5.31312 5.31594 5.31876 5.32158 5.34414 5.45127 5.54995 3.615E-07 2.712E-07 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 47 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 30 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.069E-04 0.056 1.000 1.951E-04 0.169 3.000 1.533E-04 0.282 5.000 9.507E-05 0.563 10.000 8.329E-05 0.845 15.000 7.552E-05 1.126 20.000 6.518E-05 1.408 25.000 5.618E-05 1.690 30.000 4.940E-05 1.971 35.000 4.408E-05 2.253 40.000 3.979E-05 2.534 45.000 3.504E-05 2.816 50.000 3.042E-05 3.097 55.000 2.669E-05 3.379 60.000 2.362E-05 3.661 65.000 2.106E-05 3.942 70.000 1.880E-05 4.224 75.000 9.933E-05 0.5 8.88 ANNUAL AVERAGE = 5.31E-06 3 to ULNRC-06696 Page 48 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 31 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.477 1.160 1.580 2.490 2.793 3.248 5.769 6.451 8.119 8.195 0.01775 0.04313 0.05876 0.09259 0.10387 0.12078 0.21456 0.23993 0.30196 0.30478 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 9.560 9.563 10.094 10.397 12.519 13.808 14.036 14.490 17.371 19.645 0.35553 0.35566 0.37539 0.38667 0.46561 0.51353 0.52199 0.53891 0.64604 0.73062 6.896E-05 6.748E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 21.616 21.768 22.905 26.089 26.695 32.684 42.690 44.207 50.650 53.076 0.80392 0.80956 0.85185 0.97026 0.99281 1.21554 1.58768 1.64407 1.88371 1.97392 3.408E-05 2.964E-05 2.949E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.778E-05 1.704E-05 53.152 53.455 57.094 66.039 66.115 66.494 73.013 77.789 77.940 78.623 1.97674 1.98802 2.12335 2.45602 2.45884 2.47294 2.71540 2.89301 2.89865 2.92402 1.547E-05 1.160E-05 1.136E-05 9.417E-06 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 81.124 83.323 85.521 85.597 85.900 87.871 87.947 88.932 89.690 91.055 3.01706 3.09882 3.18058 3.18340 3.19467 3.26798 3.27079 3.30745 3.33564 3.38639 4.259E-06 3.532E-06 2.825E-06 2.354E-06 1.766E-06 9.374E-07 7.231E-07 5.423E-07 4.338E-07 3.615E-07 3 to ULNRC-06696 Page 49 of 456 91.434 92.798 94.087 94.315 94.769 94.921 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.52453 3.53017 3.55554 3.62320 3.66549 3.70778 2.712E-07 100.000 3.71906 3 to ULNRC-06696 Page 50 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 32 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.479E-04 0.037 1.000 2.278E-04 0.112 3.000 1.835E-04 0.186 5.000 1.216E-04 0.372 10.000 8.777E-05 0.558 15.000 7.289E-05 0.744 20.000 6.286E-05 0.930 25.000 5.552E-05 1.116 30.000 4.987E-05 1.302 35.000 4.536E-05 1.488 40.000 4.166E-05 1.674 45.000 3.856E-05 1.860 50.000 3.354E-05 2.045 55.000 2.901E-05 2.231 60.000 2.535E-05 2.417 65.000 2.234E-05 2.603 70.000 1.974E-05 2.789 75.000 9.405E-05 0.5 13.44 ANNUAL AVERAGE = 4.24E-06 3 to ULNRC-06696 Page 51 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 33 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.274 0.599 0.899 1.494 2.251 2.521 4.320 4.699 6.105 6.213 0.01430 0.03122 0.04685 0.07786 0.11733 0.13143 0.22521 0.24494 0.31824 0.32388 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 6.916 6.919 7.352 7.677 8.704 10.110 10.219 10.543 12.436 14.275 0.36053 0.36069 0.38324 0.40016 0.45372 0.52702 0.53266 0.54958 0.64825 0.74411 6.896E-05 6.748E-05 5.898E-05 5.747E-05 4.718E-05 4.543E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 15.194 15.249 15.898 18.115 18.494 18.548 21.847 31.690 33.529 41.696 0.79204 0.79486 0.82869 0.94428 0.96401 0.96683 1.13881 1.65192 1.74777 2.17349 3.557E-05 2.964E-05 2.949E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.778E-05 1.704E-05 44.509 45.536 51.161 60.464 60.572 60.788 67.711 74.364 74.418 75.229 2.32009 2.37366 2.66686 3.15178 3.15742 3.16869 3.52956 3.87633 3.87915 3.92144 1.547E-05 1.160E-05 1.136E-05 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 79.989 83.829 85.938 86.316 88.155 88.209 89.129 89.778 90.806 91.076 4.16954 4.36971 4.47966 4.49940 4.59525 4.59807 4.64600 4.67983 4.73340 4.74749 3.532E-06 2.825E-06 2.354E-06 1.766E-06 9.374E-07 7.231E-07 5.423E-07 4.338E-07 3.615E-07 3.442E-07 3 to ULNRC-06696 Page 52 of 456 92.428 93.780 94.267 94.537 94.591 94.970 96.484 98.053 99.351 99.405 4.81797 4.88846 4.91383 4.92793 4.93075 4.95048 5.02942 5.11118 5.17884 5.18166 2.712E-07 100.000 5.21267 3 to ULNRC-06696 Page 53 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 34 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.939E-04 0.052 1.000 1.981E-04 0.156 3.000 1.615E-04 0.261 5.000 8.724E-05 0.521 10.000 7.124E-05 0.782 15.000 5.801E-05 1.043 20.000 4.921E-05 1.303 25.000 4.285E-05 1.564 30.000 3.910E-05 1.824 35.000 3.841E-05 2.085 40.000 3.509E-05 2.346 45.000 3.079E-05 2.606 50.000 2.730E-05 2.867 55.000 2.442E-05 3.128 60.000 2.201E-05 3.388 65.000 1.996E-05 3.649 70.000 9.129E-05 0.5 9.59 ANNUAL AVERAGE = 4.86E-06 3 to ULNRC-06696 Page 54 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 35 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.541 0.759 1.192 2.195 2.500 3.328 5.629 6.675 8.331 8.462 0.03501 0.04911 0.07712 0.14196 0.16169 0.21526 0.36408 0.43175 0.53888 0.54734 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.465 9.468 9.991 10.601 13.260 14.829 15.134 17.052 19.885 21.498 0.61218 0.61237 0.64620 0.68567 0.85765 0.95914 0.97888 1.10292 1.28618 1.39049 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.964E-05 2.949E-05 21.847 24.506 25.029 29.126 36.449 38.192 41.287 42.725 43.118 47.825 1.41305 1.58502 1.61885 1.88387 2.35751 2.47028 2.67045 2.76348 2.78886 3.09334 2.412E-05 2.077E-05 1.842E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 9.280E-06 8.519E-06 6.815E-06 58.940 69.140 76.724 77.552 82.173 84.831 86.836 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.01609 5.31493 5.48691 5.61660 5.61942 5.73501 5.79139 5.679E-06 4.709E-06 4.259E-06 3.532E-06 2.825E-06 2.354E-06 1.766E-06 7.231E-07 5.423E-07 4.338E-07 90.323 91.021 91.457 93.070 94.028 94.682 94.900 95.380 96.600 98.649 5.84214 5.88725 5.91544 6.01976 6.08178 6.12407 6.13817 6.16918 6.24812 6.38062 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 55 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 56 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 36 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.576E-04 0.065 1.000 2.309E-04 0.194 3.000 1.856E-04 0.323 5.000 1.261E-04 0.647 10.000 9.024E-05 0.970 15.000 7.339E-05 1.294 20.000 6.047E-05 1.617 25.000 5.138E-05 1.940 30.000 4.461E-05 2.264 35.000 3.936E-05 2.587 40.000 3.468E-05 2.911 45.000 3.075E-05 3.234 50.000 2.753E-05 3.557 55.000 2.485E-05 3.881 60.000 2.257E-05 4.204 65.000 2.063E-05 4.528 70.000 1.895E-05 4.851 75.000 1.527E-04 0.5 7.73 ANNUAL AVERAGE = 7.14E-06 3 to ULNRC-06696 Page 57 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 37 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.620 0.788 1.178 2.401 2.654 3.582 5.473 6.697 7.793 8.553 0.04142 0.05270 0.07875 0.16051 0.17743 0.23945 0.36585 0.44761 0.52091 0.57166 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.480 9.483 9.990 11.128 13.912 15.220 15.346 16.949 20.577 21.969 0.63368 0.63388 0.66771 0.74383 0.92991 1.01730 1.02576 1.13290 1.37535 1.46839 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.964E-05 2.949E-05 22.601 24.626 25.174 30.447 38.123 39.810 42.679 43.480 43.860 47.740 1.51068 1.64600 1.68266 2.03507 2.54818 2.66095 2.85266 2.90622 2.93160 3.19097 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.778E-05 1.704E-05 1.547E-05 1.160E-05 1.136E-05 59.761 59.888 59.930 69.884 78.109 78.151 78.531 83.424 85.490 87.009 3.99447 4.00293 4.00575 4.67110 5.22086 5.22368 5.24905 5.57609 5.71423 5.81573 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 2.825E-06 2.354E-06 87.051 88.991 89.033 89.835 90.510 91.227 91.691 93.462 94.812 95.192 5.81855 5.94823 5.95105 6.00462 6.04973 6.09766 6.12867 6.24708 6.33729 6.36267 1.766E-06 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 58 of 456 95.403 95.571 96.837 98.482 99.494 100.000 6.37676 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 59 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 38 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.705E-04 0.067 1.000 2.313E-04 0.201 3.000 1.828E-04 0.334 5.000 1.243E-04 0.668 10.000 9.315E-05 1.003 15.000 7.535E-05 1.337 20.000 6.230E-05 1.671 25.000 5.297E-05 2.005 30.000 4.601E-05 2.339 35.000 4.062E-05 2.674 40.000 3.594E-05 3.008 45.000 3.180E-05 3.342 50.000 2.840E-05 3.676 55.000 2.558E-05 4.010 60.000 2.319E-05 4.345 65.000 2.116E-05 4.679 70.000 1.940E-05 5.013 75.000 1.729E-05 5.347 80.000 1.505E-04 0.5 7.48 ANNUAL AVERAGE = 7.33E-06 3 to ULNRC-06696 Page 60 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 39 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 0.932 1.140 1.783 2.169 2.684 3.971 5.257 6.501 6.930 0.03304 0.06123 0.07491 0.11720 0.14257 0.17640 0.26101 0.34559 0.42735 0.45554 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 7.101 7.103 7.404 8.647 9.548 10.106 10.234 10.449 13.923 16.024 0.46682 0.46694 0.48668 0.56844 0.62764 0.66429 0.67275 0.68685 0.91521 1.05335 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 2.964E-05 16.925 17.096 18.898 19.241 22.972 31.893 33.137 37.168 38.112 38.412 1.11256 1.12383 1.24224 1.26480 1.51008 2.09649 2.17825 2.44326 2.50528 2.52502 2.949E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.778E-05 1.704E-05 1.547E-05 1.160E-05 41.886 53.766 53.809 53.852 68.348 77.055 77.098 77.183 82.630 86.018 2.75338 3.53432 3.53714 3.53996 4.49288 5.06519 5.06801 5.07365 5.43170 5.65442 1.136E-05 9.280E-06 8.519E-06 6.815E-06 5.679E-06 4.709E-06 4.259E-06 3.532E-06 2.825E-06 2.354E-06 87.562 87.948 89.707 91.422 92.537 92.966 93.224 95.239 96.912 97.384 5.75592 5.78129 5.89688 6.00965 6.08295 6.11115 6.12806 6.26057 6.37052 6.40153 1.766E-06 9.374E-07 7.231E-07 5.423E-07 4.338E-07 3.615E-07 2.712E-07 3 to ULNRC-06696 Page 61 of 456 97.941 97.984 98.027 98.499 99.228 99.528 100.000 6.43818 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 62 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 40 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.407E-04 0.066 1.000 2.121E-04 0.197 3.000 1.674E-04 0.329 5.000 1.020E-04 0.657 10.000 7.727E-05 0.986 15.000 6.248E-05 1.315 20.000 5.260E-05 1.643 25.000 4.551E-05 1.972 30.000 4.014E-05 2.301 35.000 3.564E-05 2.629 40.000 3.183E-05 2.958 45.000 2.871E-05 3.287 50.000 2.612E-05 3.615 55.000 2.392E-05 3.944 60.000 2.203E-05 4.273 65.000 2.039E-05 4.601 70.000 1.896E-05 4.930 75.000 1.677E-05 5.259 80.000 1.271E-04 0.5 7.61 ANNUAL AVERAGE = 6.06E-06 3 to ULNRC-06696 Page 63 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 41 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 1200.0 METERS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.137E-03 7.577E-04 6.748E-04 5.683E-04 4.546E-04 4.498E-04 3.789E-04 3.557E-04 3.374E-04 2.841E-04 0.558 1.057 1.441 2.551 3.143 3.620 4.610 6.259 7.573 8.472 0.55822 1.05723 1.44065 2.55145 3.14350 3.61996 4.60953 6.25881 7.57260 8.47195 2.699E-04 2.371E-04 2.249E-04 1.894E-04 1.856E-04 1.778E-04 1.687E-04 1.423E-04 1.421E-04 1.237E-04 9.495 9.845 12.010 12.625 12.628 13.716 16.876 17.807 17.925 18.060 9.49535 9.84494 12.01015 12.62475 12.62757 13.71581 16.87623 17.80659 17.92501 18.06033 1.186E-04 1.137E-04 1.125E-04 9.280E-05 8.891E-05 8.435E-05 7.424E-05 7.104E-05 6.748E-05 6.187E-05 20.254 20.257 24.418 24.937 29.726 30.662 31.145 31.147 31.226 32.909 20.25373 20.25655 24.41782 24.93656 29.72653 30.66253 31.14463 31.14745 31.22639 32.90950 5.928E-05 5.683E-05 5.623E-05 4.640E-05 4.543E-05 4.446E-05 4.217E-05 3.557E-05 3.408E-05 3.374E-05 42.692 42.695 42.698 46.769 46.772 52.396 52.399 54.550 54.564 54.567 42.69241 42.69523 42.69805 46.76909 46.77191 52.39638 52.39920 54.55032 54.56441 54.56723 3.093E-05 2.964E-05 2.726E-05 2.320E-05 2.272E-05 2.223E-05 1.856E-05 1.778E-05 1.704E-05 1.547E-05 65.289 66.188 66.202 75.213 75.294 75.644 81.559 81.581 82.047 85.134 65.28896 66.18832 66.20242 75.21284 75.29460 75.64420 81.55906 81.58161 82.04679 85.13390 1.160E-05 1.136E-05 1.130E-05 9.417E-06 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 87.141 89.250 89.253 89.270 89.430 91.238 91.308 92.343 92.932 93.862 87.14124 89.25005 89.25288 89.26979 89.43049 91.23766 91.30814 92.34281 92.93204 93.86240 4.259E-06 3.532E-06 3.408E-06 2.825E-06 2.354E-06 1.766E-06 1.413E-06 1.085E-06 9.374E-07 7.231E-07 3 to ULNRC-06696 Page 64 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13586 95.48912 95.51167 96.42795 96.89313 97.12994 97.14686 97.16096 97.17506 97.51337 5.423E-07 4.338E-07 3.615E-07 3.442E-07 2.712E-07 2.169E-07 98.345 99.179 99.777 99.780 99.994 100.000 98.34505 99.17956 99.77724 99.78007 99.99433 99.99997 3 to ULNRC-06696 Page 65 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 42 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.008E-04 1.000 1.000 5.516E-04 3.000 3.000 4.254E-04 5.000 5.000 2.700E-04 10.000 10.000 1.888E-04 15.000 15.000 1.414E-04 20.000 20.000 1.101E-04 25.000 25.000 8.810E-05 30.000 30.000 7.492E-05 35.000 35.000 6.424E-05 40.000 40.000 5.532E-05 45.000 45.000 4.771E-05 50.000 50.000 4.151E-05 55.000 55.000 3.632E-05 60.000 60.000 3.163E-05 65.000 65.000 2.734E-05 70.000 70.000 2.336E-05 75.000 75.000 1.968E-05 80.000 80.000 4.254E-04 5.0 5.00 3 to ULNRC-06696 Page 66 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 43 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.421E-04 0.558 1.057 1.441 2.551 3.028 3.620 5.269 6.259 7.573 7.691 0.55822 1.05723 1.44065 2.55145 3.02791 3.61996 5.26924 6.25881 7.57260 7.69101 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.137E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 8.306 9.329 9.332 9.681 9.684 10.584 12.749 13.837 13.972 14.908 8.30561 9.32901 9.33183 9.68142 9.68424 10.58359 12.74880 13.83704 13.97236 14.90837 7.690E-05 7.375E-05 7.104E-05 6.896E-05 6.748E-05 5.898E-05 5.747E-05 5.683E-05 5.623E-05 4.718E-05 19.070 22.230 22.233 23.163 23.242 23.761 25.954 25.957 25.960 26.442 19.06962 22.23004 22.23286 23.16322 23.24216 23.76091 25.95432 25.95713 25.95995 26.44205 4.543E-05 4.310E-05 4.217E-05 4.050E-05 3.932E-05 3.819E-05 3.557E-05 3.408E-05 3.374E-05 2.964E-05 26.445 31.235 31.238 41.021 42.704 48.328 50.479 50.493 50.496 51.395 26.44487 31.23483 31.23765 41.02057 42.70368 48.32815 50.47926 50.49336 50.49618 51.39552 2.949E-05 2.726E-05 2.412E-05 2.272E-05 2.223E-05 2.077E-05 1.842E-05 1.778E-05 1.704E-05 1.547E-05 55.466 55.481 66.202 66.284 66.634 75.644 81.559 81.582 82.047 85.134 55.46658 55.48067 66.20239 66.28418 66.63379 75.64422 81.55908 81.58165 82.04684 85.13394 1.160E-05 1.136E-05 1.130E-05 9.417E-06 9.280E-06 8.519E-06 7.063E-06 6.815E-06 5.679E-06 4.709E-06 87.141 89.250 89.253 89.270 89.430 91.238 91.308 92.343 92.932 93.862 87.14129 89.25010 89.25292 89.26985 89.43056 91.23774 91.30824 92.34293 92.93214 93.86250 4.259E-06 3.532E-06 3.408E-06 2.825E-06 2.354E-06 1.766E-06 1.413E-06 1.085E-06 9.374E-07 7.231E-07 3 to ULNRC-06696 Page 67 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13599 95.48925 95.51181 96.42809 96.89328 97.13012 97.14704 97.16115 97.17525 97.51358 5.423E-07 4.338E-07 3.615E-07 3.442E-07 2.712E-07 2.169E-07 98.345 99.180 99.777 99.780 99.994 100.000 98.34527 99.17979 99.77749 99.78031 99.99459 100.00024 3 to ULNRC-06696 Page 68 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 44 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00024 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.630E-04 1.000 1.000 2.315E-04 3.000 3.000 1.824E-04 5.000 5.000 1.196E-04 10.000 10.000 9.092E-05 15.000 15.000 7.826E-05 20.000 20.000 6.114E-05 25.000 25.000 5.296E-05 30.000 30.000 4.819E-05 35.000 35.000 4.407E-05 40.000 40.000 4.042E-05 45.000 45.000 3.663E-05 50.000 50.000 3.231E-05 55.000 55.000 2.844E-05 60.000 60.000 2.492E-05 65.000 65.000 2.277E-05 70.000 70.000 2.100E-05 75.000 75.000 1.824E-04 5.0 5.00 3 to ULNRC-06696 Page 69 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 45 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION AREA BOUNDARY (SB OR EAB)
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX SB AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 1200. 1.34E-04 8.04E-05 6.22E-05 3.56E-05 1.60E-05 5.99E-06 21.5 S SSW 1200. 1.47E-04 8.56E-05 6.53E-05 3.64E-05 1.57E-05 5.62E-06 363.1 SSW SW 1200. 1.50E-04 8.67E-05 6.60E-05 3.65E-05 1.56E-05 5.51E-06 24.3 SW WSW 1200. 1.14E-04 6.72E-05 5.16E-05 2.92E-05 1.28E-05 4.70E-06 17.2 WSW W 1200. 1.08E-04 6.39E-05 4.92E-05 2.79E-05 1.24E-05 4.57E-06 15.4 W WNW 1200. 1.29E-04 7.72E-05 5.98E-05 3.43E-05 1.54E-05 5.81E-06 19.2 WNW NW 1200. 1.91E-04 1.22E-04 9.78E-05 6.02E-05 3.00E-05 1.28E-05 39.6 NW NNW 1200. 2.00E-04 1.29E-04 1.04E-04 6.45E-05 3.27E-05 1.42E-05 43.7 NNW N 1200. 1.48E-04 9.28E-05 7.36E-05 4.44E-05 2.16E-05 8.90E-06 23.8 N NNE 1200. 1.13E-04 6.86E-05 5.35E-05 3.12E-05 1.44E-05 5.56E-06 13.6 NNE NE 1200. 9.93E-05 6.12E-05 4.80E-05 2.84E-05 1.34E-05 5.31E-06 14.0 NE ENE 1200. 9.41E-05 5.63E-05 4.36E-05 2.50E-05 1.13E-05 4.24E-06 13.4 ENE E 1200. 9.13E-05 5.62E-05 4.41E-05 2.61E-05 1.22E-05 4.86E-06 13.4 E ESE 1200. 1.53E-04 9.20E-05 7.14E-05 4.12E-05 1.87E-05 7.14E-06 23.9 ESE SE 1200. 1.51E-04 9.13E-05 7.11E-05 4.14E-05 1.90E-05 7.33E-06 24.2 SE SSE 1200. 1.27E-04 7.68E-05 5.98E-05 3.46E-05 1.58E-05 6.06E-06 19.7 SSE MAX X/Q 2.00E-04 1.29E-04 1.04E-04 6.45E-05 3.27E-05 TOTAL HOURS: 690.2 SRP 2.3.4 1200. 4.25E-04 2.42E-04 1.83E-04 9.95E-05 4.15E-05 1.42E-05 SITE LIMIT 1.82E-04 1.20E-04 9.69E-05 6.13E-05 3.17E-05 1.42E-05 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 70 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 46 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.710 1.241 1.527 3.169 3.845 4.183 5.391 6.596 7.658 8.914 0.04142 0.07243 0.08915 0.18501 0.22448 0.24421 0.31470 0.38503 0.44705 0.52035 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.155 10.314 10.604 11.763 11.766 12.877 15.678 17.272 17.851 17.948 0.53445 0.60211 0.61903 0.68669 0.68686 0.75170 0.91522 1.00826 1.04209 1.04773 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 18.093 19.445 20.362 24.805 25.337 32.967 34.223 37.700 38.231 41.757 1.05619 1.13512 1.18869 1.44807 1.47908 1.92452 1.99783 2.20081 2.23183 2.43763 5.430E-06 4.541E-06 4.072E-06 3.886E-06 3.596E-06 2.987E-06 2.530E-06 1.943E-06 1.898E-06 1.518E-06 41.805 51.609 51.657 51.706 65.759 79.427 86.961 87.250 90.438 90.679 2.44045 3.01277 3.01559 3.01841 3.83882 4.63668 5.07648 5.09340 5.27947 5.29357 1.295E-06 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.204E-07 2.563E-07 92.128 93.335 93.432 95.074 95.895 95.992 96.233 96.716 97.730 98.551 5.37815 5.44863 5.45427 5.55012 5.59805 5.60369 5.61779 5.64598 5.70518 5.75311 2.136E-07 1.602E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 71 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 72 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 47 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.410E-04 0.058 1.000 8.431E-05 0.175 3.000 6.099E-05 0.292 5.000 3.725E-05 0.584 10.000 2.386E-05 0.876 15.000 1.695E-05 1.168 20.000 1.287E-05 1.459 25.000 1.021E-05 1.751 30.000 8.375E-06 2.043 35.000 7.053E-06 2.335 40.000 6.043E-06 2.627 45.000 5.250E-06 2.919 50.000 4.612E-06 3.211 55.000 4.090E-06 3.503 60.000 3.656E-06 3.794 65.000 3.385E-06 4.086 70.000 3.163E-06 4.378 75.000 4.221E-05 0.5 8.57 ANNUAL AVERAGE = 4.16E-07 3 to ULNRC-06696 Page 73 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 48 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.011 1.964 2.360 4.392 5.599 5.980 7.567 9.496 11.211 12.672 0.04487 0.08716 0.10475 0.19497 0.24853 0.26545 0.33593 0.42156 0.49768 0.56252 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 12.862 13.942 14.069 16.038 16.041 17.438 19.915 21.503 22.455 22.519 0.57098 0.61891 0.62454 0.71194 0.71209 0.77411 0.88406 0.95455 0.99684 0.99965 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.773 25.631 26.012 30.331 30.902 38.841 40.937 43.096 43.477 49.002 1.01093 1.13780 1.15472 1.34643 1.37180 1.72421 1.81725 1.91310 1.93002 2.17530 5.430E-06 4.541E-06 3.596E-06 3.109E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.295E-06 49.066 62.530 75.295 75.358 84.123 84.250 87.743 87.997 89.267 91.172 2.17812 2.77580 3.34248 3.34530 3.73436 3.74000 3.89506 3.90634 3.96272 4.04730 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.272E-07 3.204E-07 2.563E-07 2.416E-07 2.136E-07 93.522 93.586 94.602 95.300 95.364 96.189 97.142 97.587 97.650 98.158 4.15161 4.15443 4.19954 4.23055 4.23337 4.27002 4.31231 4.33205 4.33487 4.35742 1.611E-07 1.602E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 74 of 456 98.349 98.603 98.857 99.619 99.873 100.000 4.36588 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 75 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 49 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.649E-04 0.044 1.000 9.905E-05 0.133 3.000 7.585E-05 0.222 5.000 4.891E-05 0.444 10.000 3.301E-05 0.666 15.000 2.255E-05 0.888 20.000 1.673E-05 1.110 25.000 1.302E-05 1.332 30.000 1.049E-05 1.554 35.000 8.690E-06 1.776 40.000 7.422E-06 1.998 45.000 6.430E-06 2.220 50.000 5.636E-06 2.442 55.000 4.988E-06 2.664 60.000 4.451E-06 2.885 65.000 4.000E-06 3.107 70.000 3.617E-06 3.329 75.000 3.251E-06 3.551 80.000 4.519E-05 0.5 11.26 ANNUAL AVERAGE = 3.91E-07 3 to ULNRC-06696 Page 76 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 50 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.116 1.762 2.369 4.593 5.668 6.314 8.752 10.852 13.076 14.151 0.04389 0.06926 0.09314 0.18054 0.22283 0.24820 0.34406 0.42663 0.51402 0.55631 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 14.223 15.801 16.374 19.817 19.822 21.041 23.694 25.057 26.204 26.491 0.55913 0.62116 0.64371 0.77904 0.77922 0.82715 0.93146 0.98503 1.03014 1.04142 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.430E-06 29.360 29.934 35.671 36.962 45.424 48.006 49.727 50.229 54.604 54.819 1.15419 1.17674 1.40228 1.45303 1.78571 1.88720 1.95486 1.97460 2.14658 2.15503 4.541E-06 4.072E-06 3.886E-06 3.596E-06 2.987E-06 2.530E-06 1.943E-06 1.898E-06 1.518E-06 1.295E-06 69.736 69.951 70.023 81.139 86.446 88.167 88.812 90.390 90.892 93.402 2.74144 2.74990 2.75272 3.18971 3.39834 3.46600 3.49137 3.55340 3.57313 3.67181 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.272E-07 3.204E-07 2.563E-07 2.416E-07 2.136E-07 94.621 94.693 95.267 95.410 95.554 96.701 98.207 98.566 98.637 98.781 3.71974 3.72256 3.74511 3.75075 3.75639 3.80150 3.86070 3.87480 3.87762 3.88326 1.611E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 77 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 78 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 51 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.727E-04 0.039 1.000 1.020E-04 0.118 3.000 7.838E-05 0.197 5.000 5.312E-05 0.393 10.000 3.976E-05 0.590 15.000 2.980E-05 0.786 20.000 2.109E-05 0.983 25.000 1.640E-05 1.179 30.000 1.319E-05 1.376 35.000 1.089E-05 1.572 40.000 9.161E-06 1.769 45.000 7.805E-06 1.966 50.000 6.732E-06 2.162 55.000 5.871E-06 2.359 60.000 5.167E-06 2.555 65.000 4.585E-06 2.752 70.000 4.096E-06 2.948 75.000 3.682E-06 3.145 80.000 3.139E-06 3.342 85.000 4.611E-05 0.5 12.72 ANNUAL AVERAGE = 3.88E-07 3 to ULNRC-06696 Page 79 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 52 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.660 1.542 2.198 3.642 4.364 5.408 6.130 8.509 10.355 10.836 0.02318 0.05419 0.07720 0.12795 0.15332 0.18997 0.21535 0.29893 0.36378 0.38069 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 12.602 13.083 16.935 16.941 18.546 21.756 23.200 24.404 24.805 28.096 0.44272 0.45963 0.59496 0.59514 0.65153 0.76430 0.81505 0.85734 0.87143 0.98702 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 4.541E-06 3.596E-06 29.139 35.639 36.121 43.584 46.954 49.121 49.362 55.862 72.956 83.789 1.02368 1.25204 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.94361 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 87.722 87.802 89.166 89.728 90.450 92.777 94.623 95.506 95.666 95.827 3.08175 3.08457 3.13250 3.15223 3.17761 3.25937 3.32421 3.35522 3.36086 3.36650 4.858E-07 4.272E-07 3.204E-07 2.563E-07 2.416E-07 2.136E-07 1.611E-07 1.602E-07 1.208E-07 9.665E-08 95.907 96.790 98.074 98.876 99.037 99.197 99.438 99.519 99.679 99.920 3.36932 3.40033 3.44544 3.47363 3.47927 3.48491 3.49337 3.49619 3.50183 3.51028 8.054E-08 3 to ULNRC-06696 Page 80 of 456 100.000 3.51310 3 to ULNRC-06696 Page 81 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 53 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.398E-04 0.035 1.000 8.921E-05 0.105 3.000 6.898E-05 0.176 5.000 4.631E-05 0.351 10.000 3.349E-05 0.527 15.000 2.500E-05 0.703 20.000 1.905E-05 0.878 25.000 1.509E-05 1.054 30.000 1.234E-05 1.230 35.000 1.033E-05 1.405 40.000 8.806E-06 1.581 45.000 7.641E-06 1.757 50.000 6.720E-06 1.932 55.000 5.966E-06 2.108 60.000 5.341E-06 2.284 65.000 4.814E-06 2.459 70.000 4.336E-06 2.635 75.000 3.890E-06 2.810 80.000 3.499E-05 0.5 14.23 ANNUAL AVERAGE = 3.34E-07 3 to ULNRC-06696 Page 82 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 54 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.532 1.334 1.963 3.245 3.645 4.446 5.007 7.469 9.792 9.952 0.01874 0.04693 0.06908 0.11419 0.12828 0.15647 0.17621 0.26285 0.34461 0.35025 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 10.032 11.955 12.676 15.800 15.805 17.808 20.051 21.012 21.974 22.054 0.35307 0.42073 0.44611 0.55606 0.55623 0.62671 0.70565 0.73948 0.77331 0.77613 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.214 25.338 25.979 33.509 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.89172 0.91428 1.17929 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 4.541E-06 3.596E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.295E-06 9.716E-07 7.772E-07 74.846 85.981 90.787 90.868 92.390 93.030 93.351 95.193 96.475 97.036 2.63404 3.02592 3.19508 3.19790 3.25146 3.27402 3.28529 3.35014 3.39525 3.41498 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.204E-07 2.563E-07 1.611E-07 1.602E-07 1.208E-07 9.665E-08 97.196 97.276 97.356 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.42062 3.42344 3.42626 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 83 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 55 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.302E-04 0.035 1.000 8.475E-05 0.106 3.000 6.553E-05 0.176 5.000 4.458E-05 0.352 10.000 3.163E-05 0.528 15.000 2.275E-05 0.704 20.000 1.776E-05 0.880 25.000 1.444E-05 1.056 30.000 1.208E-05 1.232 35.000 1.031E-05 1.408 40.000 8.955E-06 1.584 45.000 3.315E-05 0.5 14.21 ANNUAL AVERAGE = 3.27E-07 3 to ULNRC-06696 Page 84 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 56 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.455 1.240 1.846 2.752 3.176 4.143 4.626 6.965 9.201 9.322 0.02120 0.05786 0.08608 0.12837 0.14810 0.19321 0.21577 0.32484 0.42915 0.43479 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 10.773 11.257 14.461 14.465 15.795 18.575 19.482 20.570 20.752 24.318 0.50245 0.52500 0.67443 0.67463 0.73666 0.86634 0.90863 0.95938 0.96784 1.13418 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.430E-06 4.541E-06 24.802 32.479 33.204 43.299 46.321 50.251 51.097 57.444 57.867 74.914 1.15673 1.51478 1.54861 2.01943 2.16040 2.34365 2.38312 2.67914 2.69888 3.49392 3.596E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.295E-06 1.025E-06 9.716E-07 7.772E-07 85.492 91.174 91.235 92.202 92.504 92.746 94.318 94.378 95.648 96.675 3.98729 4.25230 4.25512 4.30023 4.31433 4.32561 4.39891 4.40173 4.46093 4.50886 6.477E-07 6.408E-07 4.272E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.208E-07 9.665E-08 8.054E-08 97.038 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.52577 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 85 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 57 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.226E-04 0.047 1.000 7.884E-05 0.140 3.000 6.173E-05 0.233 5.000 4.216E-05 0.466 10.000 2.901E-05 0.700 15.000 2.101E-05 0.933 20.000 1.662E-05 1.166 25.000 1.364E-05 1.399 30.000 1.150E-05 1.632 35.000 9.895E-06 1.866 40.000 8.625E-06 2.099 45.000 7.587E-06 2.332 50.000 6.743E-06 2.565 55.000 6.045E-06 2.798 60.000 5.459E-06 3.032 65.000 4.962E-06 3.265 70.000 4.532E-06 3.498 75.000 4.046E-06 3.731 80.000 3.633E-06 3.964 85.000 3.964E-05 0.5 10.72 ANNUAL AVERAGE = 4.17E-07 3 to ULNRC-06696 Page 86 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 58 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 1.078 1.748 2.927 3.272 3.933 4.709 7.213 9.168 9.714 0.04931 0.10570 0.17148 0.28707 0.32091 0.38575 0.46187 0.70753 0.89924 0.95281 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.887 11.956 12.244 16.268 16.271 17.392 21.617 24.290 25.526 25.555 0.96972 1.17271 1.20090 1.59560 1.59591 1.70586 2.12030 2.38249 2.50372 2.50654 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 25.584 29.866 29.924 30.499 39.898 40.473 53.810 55.764 59.673 60.420 2.50936 2.92943 2.93507 2.99146 3.91336 3.96975 5.27790 5.46961 5.85303 5.92633 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.596E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 65.307 65.451 78.989 79.046 86.347 88.445 88.589 88.905 89.106 89.135 6.40561 6.41971 7.74759 7.75323 8.46933 8.67513 8.68923 8.72024 8.73998 8.74279 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 4.272E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 91.981 93.878 94.424 94.510 94.568 95.602 96.723 97.126 97.183 97.586 9.02190 9.20798 9.26154 9.27000 9.27564 9.37713 9.48709 9.52656 9.53219 9.57166 1.602E-07 1.208E-07 9.665E-08 8.054E-08 3 to ULNRC-06696 Page 87 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 88 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 59 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.268E-04 0.098 1.000 8.108E-05 0.294 3.000 6.272E-05 0.490 5.000 4.274E-05 0.981 10.000 3.209E-05 1.471 15.000 2.457E-05 1.962 20.000 1.939E-05 2.452 25.000 1.584E-05 2.943 30.000 1.329E-05 3.433 35.000 1.138E-05 3.923 40.000 1.040E-05 4.414 45.000 9.578E-06 4.904 50.000 8.700E-06 5.395 55.000 7.477E-06 5.885 60.000 6.487E-06 6.376 65.000 5.675E-06 6.866 70.000 5.000E-06 7.356 75.000 4.393E-06 7.847 80.000 3.749E-06 8.337 85.000 6.210E-05 0.5 5.10 ANNUAL AVERAGE = 9.26E-07 3 to ULNRC-06696 Page 89 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 60 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.676 1.073 1.374 2.698 3.514 3.868 5.192 6.069 6.886 8.630 0.08630 0.13704 0.17547 0.34463 0.44894 0.49405 0.66321 0.77534 0.87965 1.10237 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.954E-05 1.937E-05 11.212 11.830 12.602 12.735 14.699 14.700 15.428 20.482 20.505 32.643 1.43223 1.51117 1.60984 1.62676 1.87768 1.87786 1.97089 2.61651 2.61933 4.16993 1.824E-05 1.666E-05 1.563E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.091E-06 9.035E-06 33.040 35.159 35.181 36.351 36.395 36.638 40.610 40.897 40.919 54.867 4.22068 4.49133 4.49415 4.64357 4.64921 4.68022 5.18770 5.22435 5.22716 7.00895 8.308E-06 7.482E-06 7.273E-06 6.384E-06 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.596E-06 3.258E-06 55.750 63.033 63.055 65.990 69.213 70.360 77.952 78.460 83.955 83.999 7.12172 8.05209 8.05491 8.42987 8.84149 8.98809 9.95792 10.02277 10.72477 10.73041 3.109E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.295E-06 9.716E-07 8.544E-07 7.772E-07 84.021 87.089 87.155 88.524 89.098 89.782 91.900 93.556 93.578 94.196 10.73323 11.12511 11.13356 11.30836 11.38166 11.46906 11.73971 11.95116 11.95398 12.03292 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.886E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 3 to ULNRC-06696 Page 90 of 456 94.460 94.549 94.747 95.829 95.851 96.976 97.506 97.771 98.279 98.455 12.06675 12.07803 12.10340 12.24154 12.24436 12.38815 12.45581 12.48964 12.55449 12.57704 1.208E-07 9.665E-08 8.054E-08 6.041E-08 4.833E-08 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 91 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 61 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.360E-04 0.128 1.000 7.806E-05 0.383 3.000 6.086E-05 0.639 5.000 4.236E-05 1.277 10.000 3.308E-05 1.916 15.000 2.736E-05 2.555 20.000 2.346E-05 3.194 25.000 2.060E-05 3.832 30.000 1.682E-05 4.471 35.000 1.404E-05 5.110 40.000 1.195E-05 5.748 45.000 1.032E-05 6.387 50.000 9.005E-06 7.026 55.000 8.006E-06 7.665 60.000 7.049E-06 8.303 65.000 6.049E-06 8.942 70.000 5.038E-06 9.581 75.000 6.869E-05 0.5 3.91 ANNUAL AVERAGE = 1.02E-06 3 to ULNRC-06696 Page 92 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 62 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.418 0.929 1.105 1.884 2.287 2.690 3.388 4.185 4.776 5.770 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.35555 0.43913 0.50116 0.60547 3.977E-05 3.643E-05 3.629E-05 3.126E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 6.630 6.872 7.248 7.275 7.490 8.403 8.405 8.996 11.495 17.836 0.69569 0.72106 0.76053 0.76335 0.78591 0.88176 0.88195 0.94397 1.20616 1.87152 1.824E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.212E-05 1.140E-05 9.969E-06 9.035E-06 18.347 21.651 21.732 22.619 23.022 23.425 23.452 25.520 25.709 33.984 1.92508 2.27185 2.28031 2.37335 2.41564 2.45793 2.46075 2.67783 2.69757 3.56591 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.886E-06 3.596E-06 3.258E-06 35.086 46.129 52.765 55.076 58.918 64.829 66.576 66.602 72.514 72.540 3.68150 4.84022 5.53658 5.77904 6.18220 6.80244 6.98570 6.98852 7.60876 7.61158 3.109E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.518E-06 1.295E-06 9.716E-07 7.772E-07 72.567 77.592 77.753 81.326 81.649 86.566 86.996 89.038 90.945 91.859 7.61440 8.14160 8.15852 8.53348 8.56732 9.08325 9.12835 9.34262 9.54279 9.63864 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.886E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 3 to ULNRC-06696 Page 93 of 456 92.719 92.826 93.605 94.841 94.895 95.755 96.507 97.501 97.958 98.307 9.72886 9.74014 9.82190 9.95158 9.95722 10.04744 10.12638 10.23069 10.27862 10.31527 1.282E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 4.833E-08 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 94 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 63 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.110E-04 0.105 1.000 6.346E-05 0.315 3.000 4.718E-05 0.525 5.000 2.983E-05 1.049 10.000 2.212E-05 1.574 15.000 1.773E-05 2.099 20.000 1.443E-05 2.623 25.000 1.196E-05 3.148 30.000 1.015E-05 3.673 35.000 8.777E-06 4.197 40.000 7.695E-06 4.722 45.000 6.891E-06 5.246 50.000 6.240E-06 5.771 55.000 5.284E-06 6.296 60.000 4.855E-05 0.5 4.77 ANNUAL AVERAGE = 6.30E-07 3 to ULNRC-06696 Page 95 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 64 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.344 0.763 0.992 1.411 1.704 1.997 2.835 3.744 4.246 4.959 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19083 0.25199 0.28582 0.33375 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 5.503 5.587 6.131 6.508 8.142 8.144 8.898 11.662 16.605 17.065 0.37040 0.37604 0.41269 0.43807 0.54802 0.54814 0.59889 0.78496 1.11764 1.14865 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 19.704 19.788 20.710 20.961 21.422 23.809 24.144 33.150 34.113 43.705 1.32626 1.33190 1.39393 1.41084 1.44186 1.60255 1.62511 2.23125 2.29610 2.94171 6.384E-06 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.596E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 48.019 50.533 52.501 59.329 59.999 68.208 73.947 73.989 77.046 77.717 3.23210 3.40126 3.53376 3.99331 4.03842 4.59100 4.97724 4.98006 5.18586 5.23097 1.898E-06 1.518E-06 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.886E-07 79.727 79.895 83.078 85.466 87.644 88.733 88.816 89.319 90.408 90.618 5.36630 5.37758 5.59184 5.75254 5.89914 5.97244 5.97808 6.01191 6.08522 6.09931 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 96 of 456 92.754 94.597 95.518 96.146 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.47146 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 97 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 65 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.811E-05 0.067 1.000 5.510E-05 0.202 3.000 4.177E-05 0.337 5.000 2.726E-05 0.673 10.000 2.078E-05 1.010 15.000 1.645E-05 1.346 20.000 1.326E-05 1.683 25.000 1.106E-05 2.019 30.000 9.450E-06 2.356 35.000 8.221E-06 2.692 40.000 7.214E-06 3.029 45.000 6.316E-06 3.365 50.000 3.300E-05 0.5 7.43 ANNUAL AVERAGE = 3.93E-07 3 to ULNRC-06696 Page 98 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 66 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.368 0.718 0.980 1.881 2.182 2.532 3.083 4.531 5.382 6.033 0.02071 0.04045 0.05521 0.10596 0.12287 0.14261 0.17362 0.25517 0.30309 0.33975 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 6.383 6.483 7.284 7.585 8.986 8.989 10.091 13.795 19.852 20.703 0.35948 0.36512 0.41023 0.42714 0.50608 0.50625 0.56827 0.77690 1.11803 1.16596 1.666E-05 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 22.105 22.255 24.008 24.558 28.062 28.663 37.975 39.576 47.136 49.489 1.24490 1.25336 1.35203 1.38304 1.58039 1.61422 2.13861 2.22883 2.65454 2.78705 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.886E-06 3.596E-06 3.109E-06 2.987E-06 2.591E-06 2.530E-06 53.093 53.694 62.254 62.404 62.454 70.414 70.514 75.821 75.921 78.874 2.99004 3.02387 3.50596 3.51442 3.51724 3.96551 3.97115 4.26999 4.27563 4.44197 1.943E-06 1.898E-06 1.518E-06 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 4.272E-07 79.425 81.177 81.327 83.430 85.683 87.285 87.985 88.035 88.186 89.487 4.47298 4.57165 4.58011 4.69852 4.82539 4.91561 4.95508 4.95790 4.96635 5.03965 3.204E-07 2.563E-07 2.416E-07 2.136E-07 1.611E-07 1.602E-07 1.534E-07 1.282E-07 1.208E-07 9.665E-08 3 to ULNRC-06696 Page 99 of 456 91.740 93.042 93.092 93.893 94.293 94.794 94.844 94.894 96.796 98.548 5.16652 5.23982 5.24264 5.28775 5.31031 5.33850 5.34132 5.34414 5.45127 5.54995 8.054E-08 6.041E-08 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 100 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 67 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.084E-04 0.056 1.000 6.351E-05 0.169 3.000 4.737E-05 0.282 5.000 2.898E-05 0.563 10.000 2.189E-05 0.845 15.000 1.921E-05 1.126 20.000 1.489E-05 1.408 25.000 1.202E-05 1.690 30.000 9.984E-06 1.971 35.000 8.639E-06 2.253 40.000 7.795E-06 2.534 45.000 6.836E-06 2.816 50.000 5.826E-06 3.097 55.000 4.928E-06 3.379 60.000 4.214E-06 3.661 65.000 3.639E-06 3.942 70.000 3.070E-06 4.224 75.000 3.165E-05 0.5 8.88 ANNUAL AVERAGE = 3.77E-07 3 to ULNRC-06696 Page 101 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 68 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.477 1.160 1.580 2.490 2.944 3.248 3.930 6.451 8.119 8.422 0.01775 0.04313 0.05876 0.09259 0.10951 0.12078 0.14616 0.23993 0.30196 0.31324 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.498 9.863 10.393 12.516 12.519 13.808 16.082 18.963 20.934 21.389 0.31606 0.36680 0.38654 0.46548 0.46561 0.51353 0.59811 0.70525 0.77855 0.79546 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 21.616 24.800 24.952 26.089 32.078 32.684 42.690 44.207 50.650 53.076 0.80392 0.92233 0.92797 0.97026 1.19298 1.21554 1.58768 1.64407 1.88371 1.97392 6.231E-06 5.430E-06 4.541E-06 4.072E-06 3.886E-06 3.596E-06 3.258E-06 2.987E-06 2.591E-06 2.530E-06 56.715 57.018 65.963 66.342 66.418 72.937 73.089 77.865 77.940 80.442 2.10925 2.12053 2.45320 2.46730 2.47012 2.71258 2.71821 2.89583 2.89865 2.99169 1.943E-06 1.898E-06 1.518E-06 1.295E-06 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 81.124 83.323 83.626 85.824 87.795 87.871 88.856 89.615 89.690 90.069 3.01706 3.09882 3.11010 3.19185 3.26516 3.26798 3.30463 3.33282 3.33564 3.34973 4.272E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 1.534E-07 1.208E-07 9.665E-08 8.054E-08 3 to ULNRC-06696 Page 102 of 456 91.434 92.798 94.087 94.315 94.997 95.452 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.53299 3.54990 3.55554 3.62320 3.66549 3.70778 6.041E-08 100.000 3.71906 3 to ULNRC-06696 Page 103 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 69 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.216E-04 0.037 1.000 7.504E-05 0.112 3.000 5.829E-05 0.186 5.000 3.740E-05 0.372 10.000 2.540E-05 0.558 15.000 1.910E-05 0.744 20.000 1.540E-05 0.930 25.000 1.290E-05 1.116 30.000 1.106E-05 1.302 35.000 9.661E-06 1.488 40.000 8.529E-06 1.674 45.000 7.590E-06 1.860 50.000 6.550E-06 2.045 55.000 5.543E-06 2.231 60.000 4.684E-06 2.417 65.000 2.824E-05 0.5 13.44 ANNUAL AVERAGE = 3.03E-07 3 to ULNRC-06696 Page 104 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 70 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.274 0.599 0.899 1.494 1.764 2.521 2.900 4.699 6.105 6.430 0.01430 0.03122 0.04685 0.07786 0.09196 0.13143 0.15116 0.24494 0.31824 0.33516 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 6.538 7.241 7.674 8.701 8.704 10.110 11.949 13.842 14.762 15.086 0.34080 0.37745 0.40000 0.45357 0.45372 0.52702 0.62288 0.72155 0.76948 0.78640 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 15.194 17.412 17.466 18.115 21.414 21.793 31.636 33.475 41.642 44.455 0.79204 0.90763 0.91045 0.94428 1.11625 1.13599 1.64910 1.74495 2.17067 2.31727 6.231E-06 5.430E-06 5.182E-06 4.541E-06 4.072E-06 3.596E-06 3.258E-06 2.987E-06 2.591E-06 2.530E-06 50.079 51.107 51.161 60.464 60.680 67.603 67.657 74.310 74.418 79.177 2.61048 2.66404 2.66686 3.15178 3.16305 3.52392 3.52674 3.87351 3.87915 4.12725 1.943E-06 1.898E-06 1.518E-06 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 4.272E-07 79.989 83.829 84.207 86.316 88.155 89.075 89.724 89.778 90.048 91.076 4.16954 4.36971 4.38944 4.49940 4.59525 4.64318 4.67701 4.67983 4.69393 4.74749 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 1.534E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 105 of 456 92.428 93.780 94.267 94.646 94.916 94.970 96.484 98.053 99.351 99.946 4.81797 4.88846 4.91383 4.93356 4.94766 4.95048 5.02942 5.11118 5.17884 5.20985 3.925E-08 100.000 5.21267 3 to ULNRC-06696 Page 106 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 71 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.966E-05 0.052 1.000 6.272E-05 0.156 3.000 4.979E-05 0.261 5.000 2.741E-05 0.521 10.000 1.805E-05 0.782 15.000 1.393E-05 1.043 20.000 1.132E-05 1.303 25.000 9.513E-06 1.564 30.000 8.437E-06 1.824 35.000 7.695E-06 2.085 40.000 6.933E-06 2.346 45.000 6.241E-06 2.606 50.000 5.330E-06 2.867 55.000 4.601E-06 3.128 60.000 2.863E-05 0.5 9.59 ANNUAL AVERAGE = 3.45E-07 3 to ULNRC-06696 Page 107 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 72 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.541 0.759 1.192 2.195 3.023 3.328 4.374 6.675 8.331 8.942 0.03501 0.04911 0.07712 0.14196 0.19553 0.21526 0.28292 0.43175 0.53888 0.57835 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.072 10.075 10.598 13.257 13.260 14.829 17.662 19.580 21.193 21.498 0.58681 0.65165 0.68548 0.85746 0.85765 0.95914 1.14239 1.26644 1.37076 1.39049 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.430E-06 24.157 24.506 28.603 29.126 36.449 38.192 41.287 42.725 47.433 47.825 1.56247 1.58502 1.85003 1.88387 2.35751 2.47028 2.67045 2.76348 3.06797 3.09334 4.541E-06 3.596E-06 2.987E-06 2.530E-06 1.943E-06 1.898E-06 1.518E-06 1.295E-06 9.716E-07 7.772E-07 58.940 69.140 76.724 81.344 82.172 84.831 84.875 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.26137 5.31493 5.48691 5.48973 5.61942 5.73501 5.79139 6.477E-07 4.858E-07 4.272E-07 3.204E-07 2.563E-07 2.136E-07 1.611E-07 1.602E-07 1.208E-07 9.665E-08 90.323 90.759 91.457 93.069 94.028 94.682 95.162 95.380 96.600 98.649 5.84214 5.87033 5.91544 6.01975 6.08178 6.12407 6.15508 6.16918 6.24812 6.38062 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 108 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 109 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 73 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.261E-04 0.065 1.000 7.611E-05 0.194 3.000 5.914E-05 0.323 5.000 3.878E-05 0.647 10.000 2.675E-05 0.970 15.000 1.956E-05 1.294 20.000 1.481E-05 1.617 25.000 1.170E-05 1.940 30.000 9.541E-06 2.264 35.000 7.953E-06 2.587 40.000 6.747E-06 2.911 45.000 5.808E-06 3.234 50.000 5.059E-06 3.557 55.000 4.451E-06 3.881 60.000 3.949E-06 4.204 65.000 3.518E-06 4.528 70.000 3.112E-06 4.851 75.000 4.720E-05 0.5 7.73 ANNUAL AVERAGE = 5.07E-07 3 to ULNRC-06696 Page 110 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 74 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.620 0.788 1.178 2.401 3.329 3.582 4.806 6.697 7.793 8.932 0.04142 0.05270 0.07875 0.16051 0.22254 0.23945 0.32121 0.44761 0.52091 0.59703 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.691 10.619 11.125 13.909 13.912 15.220 18.847 20.450 21.842 21.969 0.64778 0.70980 0.74363 0.92971 0.92991 1.01730 1.25976 1.36690 1.45993 1.46839 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.430E-06 23.993 24.626 29.898 30.447 38.123 39.810 42.679 43.480 47.360 47.740 1.60372 1.64600 1.99842 2.03507 2.54818 2.66095 2.85266 2.90622 3.16560 3.19097 4.541E-06 4.072E-06 3.596E-06 3.258E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 1.518E-06 59.761 59.803 69.758 69.800 78.025 78.151 83.044 83.424 85.490 85.533 3.99447 3.99729 4.66264 4.66546 5.21522 5.22368 5.55071 5.57609 5.71423 5.71705 1.295E-06 9.716E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 4.272E-07 3.204E-07 2.563E-07 2.136E-07 87.051 88.991 89.793 90.468 90.510 90.974 91.691 93.462 94.812 95.192 5.81855 5.94823 6.00180 6.04691 6.04973 6.08074 6.12867 6.24708 6.33729 6.36267 1.611E-07 1.602E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 111 of 456 95.360 95.571 96.837 98.482 99.494 100.000 6.37394 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 112 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 75 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.314E-04 0.067 1.000 7.626E-05 0.201 3.000 5.811E-05 0.334 5.000 3.885E-05 0.668 10.000 2.818E-05 1.003 15.000 2.106E-05 1.337 20.000 1.586E-05 1.671 25.000 1.249E-05 2.005 30.000 1.016E-05 2.339 35.000 8.426E-06 2.674 40.000 7.085E-06 3.008 45.000 6.049E-06 3.342 50.000 5.229E-06 3.676 55.000 4.568E-06 4.010 60.000 4.027E-06 4.345 65.000 3.576E-06 4.679 70.000 3.191E-06 5.013 75.000 4.643E-05 0.5 7.48 ANNUAL AVERAGE = 5.17E-07 3 to ULNRC-06696 Page 113 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 76 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 0.932 1.140 1.783 2.298 2.684 3.970 5.257 6.501 7.745 0.03304 0.06123 0.07491 0.11720 0.15103 0.17640 0.26098 0.34559 0.42735 0.50911 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.174 8.345 8.645 9.546 9.548 10.106 12.207 15.681 16.582 16.796 0.53730 0.54858 0.56831 0.62752 0.62764 0.66429 0.80244 1.03080 1.09000 1.10410 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 16.925 18.726 18.898 22.629 22.972 31.893 33.137 37.168 38.112 41.586 1.11256 1.23097 1.24224 1.48752 1.51008 2.09649 2.17825 2.44326 2.50528 2.73365 5.430E-06 4.541E-06 4.072E-06 3.596E-06 3.258E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 1.898E-06 41.886 53.766 53.809 68.305 68.348 77.055 77.098 82.544 82.630 86.018 2.75338 3.53432 3.53714 4.49006 4.49288 5.06519 5.06801 5.42606 5.43170 5.65442 1.518E-06 1.295E-06 9.716E-07 7.772E-07 6.477E-07 4.858E-07 4.272E-07 3.204E-07 2.563E-07 2.136E-07 86.404 87.948 89.707 91.422 92.537 92.795 93.224 95.239 96.912 97.384 5.67980 5.78129 5.89688 6.00965 6.08295 6.09987 6.12806 6.26057 6.37052 6.40153 1.611E-07 1.602E-07 1.534E-07 1.208E-07 9.665E-08 8.054E-08 6.041E-08 3 to ULNRC-06696 Page 114 of 456 97.427 97.984 98.027 98.499 99.228 99.528 100.000 6.40435 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 115 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 77 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.193E-04 0.066 1.000 6.899E-05 0.197 3.000 5.249E-05 0.329 5.000 3.206E-05 0.657 10.000 2.046E-05 0.986 15.000 1.501E-05 1.315 20.000 1.183E-05 1.643 25.000 9.676E-06 1.972 30.000 8.124E-06 2.301 35.000 6.955E-06 2.629 40.000 6.047E-06 2.958 45.000 5.323E-06 3.287 50.000 4.733E-06 3.615 55.000 4.244E-06 3.944 60.000 3.833E-06 4.273 65.000 3.464E-06 4.601 70.000 3.115E-06 4.930 75.000 4.146E-05 0.5 7.61 ANNUAL AVERAGE = 4.23E-07 3 to ULNRC-06696 Page 116 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 78 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 4023.0 METERS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
3.126E-04 2.084E-04 1.563E-04 1.455E-04 1.251E-04 1.042E-04 9.697E-05 7.816E-05 7.273E-05 6.515E-05 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 5.818E-05 5.211E-05 4.849E-05 4.344E-05 3.908E-05 3.637E-05 3.258E-05 3.126E-05 3.036E-05 2.606E-05 9.495 10.110 12.275 12.625 12.743 15.904 16.992 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 16.99183 16.99464 16.99746 17.92783 2.424E-05 2.172E-05 2.024E-05 1.954E-05 1.818E-05 1.629E-05 1.563E-05 1.518E-05 1.455E-05 1.215E-05 22.089 24.282 24.418 24.421 25.357 30.147 30.149 30.668 30.747 31.229 22.08909 24.28249 24.41782 24.42064 25.35664 30.14660 30.14942 30.66817 30.74711 31.22920 1.212E-05 1.086E-05 1.012E-05 9.091E-06 8.144E-06 7.591E-06 7.273E-06 6.515E-06 5.430E-06 5.182E-06 31.232 41.015 42.698 42.701 48.325 52.396 52.399 54.550 55.450 55.452 31.23202 41.01494 42.69805 42.70087 48.32534 52.39639 52.39921 54.55032 55.44968 55.45250 5.061E-06 4.072E-06 3.886E-06 3.795E-06 3.258E-06 3.109E-06 3.036E-06 2.591E-06 2.530E-06 1.943E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.581 84.669 85.134 66.17422 66.52383 66.53793 75.54835 75.57090 75.58500 81.49986 81.58162 84.66873 85.13391 1.898E-06 1.518E-06 1.295E-06 1.025E-06 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 87.141 87.302 89.411 89.413 91.221 91.238 92.272 92.861 92.932 93.205 87.14124 87.30194 89.41076 89.41358 91.22075 91.23766 92.27234 92.86156 92.93204 93.20551 4.272E-07 3.886E-07 3.204E-07 2.563E-07 2.416E-07 2.136E-07 1.611E-07 1.602E-07 1.534E-07 1.282E-07 3 to ULNRC-06696 Page 117 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.245 97.482 97.496 97.513 94.13587 94.15842 95.51168 96.42796 96.44205 96.90723 97.24554 97.48236 97.49646 97.51337 1.208E-07 9.665E-08 8.054E-08 6.041E-08 4.833E-08 3.925E-08 98.345 99.179 99.777 99.991 99.997 100.000 98.34506 99.17957 99.77725 99.99152 99.99715 99.99998 3 to ULNRC-06696 Page 118 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 79 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.373E-04 1.000 1.000 1.319E-04 3.000 3.000 9.500E-05 5.000 5.000 5.731E-05 10.000 10.000 3.906E-05 15.000 15.000 2.788E-05 20.000 20.000 2.093E-05 25.000 25.000 1.640E-05 30.000 30.000 1.351E-05 35.000 35.000 1.126E-05 40.000 40.000 9.628E-06 45.000 45.000 8.298E-06 50.000 50.000 7.151E-06 55.000 55.000 6.146E-06 60.000 60.000 5.256E-06 65.000 65.000 4.523E-06 70.000 70.000 3.865E-06 75.000 75.000 9.500E-05 5.0 5.00 3 to ULNRC-06696 Page 119 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 80 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.558 1.057 1.441 2.551 3.143 3.620 4.610 6.259 7.573 8.472 0.55822 1.05723 1.44065 2.55145 3.14350 3.61996 4.60953 6.25881 7.57260 8.47195 3.977E-05 3.643E-05 3.629E-05 3.126E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.954E-05 9.087 9.205 10.228 10.231 10.581 12.746 12.749 13.837 16.997 17.000 9.08655 9.20496 10.22836 10.23118 10.58077 12.74598 12.74880 13.83704 16.99746 17.00028 1.937E-05 1.824E-05 1.666E-05 1.662E-05 1.563E-05 1.520E-05 1.453E-05 1.246E-05 1.212E-05 1.140E-05 21.162 22.092 23.028 23.163 23.166 25.359 25.438 25.957 25.960 30.750 21.16154 22.09190 23.02790 23.16322 23.16603 25.35944 25.43838 25.95713 25.95995 30.74991 9.969E-06 9.091E-06 9.035E-06 8.308E-06 7.482E-06 7.273E-06 6.384E-06 6.231E-06 5.430E-06 5.182E-06 31.232 31.235 41.018 42.701 48.325 48.328 50.479 54.550 55.450 55.452 31.23201 31.23483 41.01775 42.70085 48.32533 48.32814 50.47926 54.55030 55.44965 55.45247 4.541E-06 4.072E-06 3.886E-06 3.596E-06 3.258E-06 3.109E-06 2.987E-06 2.591E-06 2.530E-06 1.943E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.582 84.669 85.134 66.17419 66.52380 66.53792 75.54835 75.57092 75.58502 81.49989 81.58167 84.66878 85.13396 1.898E-06 1.518E-06 1.295E-06 1.025E-06 9.716E-07 8.544E-07 7.772E-07 6.477E-07 6.408E-07 4.858E-07 87.141 87.302 89.411 89.414 91.221 91.238 92.272 92.862 92.932 93.206 87.14131 87.30202 89.41084 89.41366 91.22083 91.23776 92.27245 92.86166 92.93217 93.20565 4.272E-07 3.886E-07 3.204E-07 2.563E-07 2.416E-07 2.136E-07 1.611E-07 1.602E-07 1.534E-07 1.282E-07 3 to ULNRC-06696 Page 120 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.246 97.482 97.497 97.513 94.13601 94.15857 95.51183 96.42812 96.44222 96.90741 97.24574 97.48257 97.49668 97.51360 1.208E-07 9.665E-08 8.054E-08 6.041E-08 4.833E-08 3.925E-08 98.345 99.180 99.777 99.992 99.997 100.000 98.34529 99.17982 99.77751 99.99179 99.99744 100.00026 3 to ULNRC-06696 Page 121 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 81 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00026 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.283E-04 1.000 1.000 7.634E-05 3.000 3.000 5.798E-05 5.000 5.000 3.694E-05 10.000 10.000 2.657E-05 15.000 15.000 2.046E-05 20.000 20.000 1.551E-05 25.000 25.000 1.297E-05 30.000 30.000 1.107E-05 35.000 35.000 9.520E-06 40.000 40.000 8.230E-06 45.000 45.000 7.175E-06 50.000 50.000 6.331E-06 55.000 55.000 5.573E-06 60.000 60.000 4.885E-06 65.000 65.000 4.251E-06 70.000 70.000 3.659E-06 75.000 75.000 3.140E-06 80.000 80.000 5.798E-05 5.0 5.00 3 to ULNRC-06696 Page 122 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 82 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE BOUNDARY (LPZ)
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 1526. D= 66.3 RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX LPZ AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 4023. 4.22E-05 1.97E-05 1.34E-05 5.86E-06 1.78E-06 4.16E-07 21.3 S SSW 4023. 4.52E-05 2.06E-05 1.39E-05 5.94E-06 1.75E-06 3.91E-07 321.2 SSW SW 4023. 4.61E-05 2.09E-05 1.41E-05 5.98E-06 1.75E-06 3.88E-07 21.9 SW WSW 4023. 3.50E-05 1.62E-05 1.10E-05 4.79E-06 1.45E-06 3.34E-07 15.5 WSW W 4023. 3.31E-05 1.54E-05 1.05E-05 4.60E-06 1.40E-06 3.27E-07 14.1 W WNW 4023. 3.96E-05 1.87E-05 1.28E-05 5.66E-06 1.75E-06 4.17E-07 16.4 WNW NW 4023. 6.21E-05 3.10E-05 2.19E-05 1.03E-05 3.48E-06 9.26E-07 35.9 NW NNW 4023. 6.87E-05 3.42E-05 2.42E-05 1.13E-05 3.83E-06 1.02E-06 43.7 NNW N 4023. 4.86E-05 2.37E-05 1.65E-05 7.58E-06 2.48E-06 6.30E-07 23.9 N NNE 4023. 3.30E-05 1.59E-05 1.10E-05 4.97E-06 1.59E-06 3.93E-07 11.8 NNE NE 4023. 3.17E-05 1.52E-05 1.06E-05 4.77E-06 1.52E-06 3.77E-07 12.8 NE ENE 4023. 2.82E-05 1.33E-05 9.17E-06 4.07E-06 1.26E-06 3.03E-07 11.7 ENE E 4023. 2.86E-05 1.38E-05 9.57E-06 4.33E-06 1.39E-06 3.45E-07 11.1 E ESE 4023. 4.72E-05 2.23E-05 1.53E-05 6.80E-06 2.11E-06 5.07E-07 21.0 ESE SE 4023. 4.64E-05 2.21E-05 1.52E-05 6.79E-06 2.13E-06 5.17E-07 21.4 SE SSE 4023. 4.15E-05 1.94E-05 1.33E-05 5.84E-06 1.79E-06 4.23E-07 17.4 SSE MAX X/Q 6.87E-05 3.42E-05 2.42E-05 1.13E-05 3.83E-06 TOTAL HOURS: 621.2 SRP 2.3.4 4023. 9.50E-05 4.49E-05 3.08E-05 1.37E-05 4.24E-06 1.02E-06 SITE LIMIT 5.80E-05 2.97E-05 2.13E-05 1.03E-05 3.63E-06 1.02E-06 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 123 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 83 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.710 1.241 1.527 3.169 3.507 4.183 5.388 6.596 7.658 7.900 0.04142 0.07243 0.08915 0.18501 0.20474 0.24421 0.31455 0.38503 0.44705 0.46115 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 9.059 9.061 9.351 10.607 11.766 12.877 13.022 13.118 14.712 17.513 0.52881 0.52898 0.54589 0.61920 0.68686 0.75170 0.76016 0.76580 0.85884 1.02235 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 18.093 19.010 20.362 20.894 25.337 32.967 34.223 37.700 38.231 38.280 1.05619 1.10975 1.18869 1.21970 1.47908 1.92452 1.99783 2.20081 2.23183 2.23465 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 38.328 41.853 41.902 51.706 65.759 79.427 79.716 87.250 90.438 91.887 2.23747 2.44327 2.44609 3.01841 3.83882 4.63668 4.65359 5.09340 5.27947 5.36405 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 92.128 92.225 93.432 93.529 95.171 95.992 96.475 96.716 97.730 98.551 5.37815 5.38379 5.45427 5.45991 5.55576 5.60369 5.63188 5.64598 5.70518 5.75311 2.380E-06 1.785E-06 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 124 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 125 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 84 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.877E-04 0.058 1.000 2.353E-04 0.175 3.000 1.834E-04 0.292 5.000 1.181E-04 0.584 10.000 8.421E-05 0.876 15.000 6.613E-05 1.168 20.000 5.482E-05 1.459 25.000 4.682E-05 1.751 30.000 4.084E-05 2.043 35.000 3.616E-05 2.335 40.000 3.239E-05 2.627 45.000 2.929E-05 2.919 50.000 2.671E-05 3.211 55.000 2.451E-05 3.503 60.000 2.263E-05 3.794 65.000 2.099E-05 4.086 70.000 1.955E-05 4.378 75.000 1.828E-05 4.670 80.000 1.712E-05 4.962 85.000 1.345E-04 0.5 8.57 ANNUAL AVERAGE = 9.11E-06 3 to ULNRC-06696 Page 126 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 85 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.011 1.964 2.360 4.392 4.773 5.980 7.909 9.496 11.211 11.402 0.04487 0.08716 0.10475 0.19497 0.21188 0.26545 0.35107 0.42156 0.49768 0.50613 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 12.481 12.484 12.611 14.072 16.041 17.438 17.692 17.756 19.343 21.820 0.55406 0.55421 0.55985 0.62469 0.71209 0.77411 0.78539 0.78821 0.85869 0.96864 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 22.773 23.154 26.012 26.583 30.902 38.841 40.937 43.096 43.477 43.540 1.01093 1.02785 1.15472 1.18009 1.37180 1.72421 1.81725 1.91310 1.93002 1.93284 2.949E-05 2.799E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 49.066 49.129 62.593 62.720 75.485 84.250 84.504 87.997 89.267 91.172 2.17812 2.18094 2.77862 2.78426 3.35094 3.74000 3.75128 3.90634 3.96272 4.04730 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 91.236 93.586 93.649 94.665 95.364 96.189 97.142 97.587 98.095 98.349 4.05012 4.15443 4.15725 4.20236 4.23337 4.27002 4.31231 4.33205 4.35460 4.36588 1.086E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 127 of 456 98.412 98.603 98.857 99.619 99.873 100.000 4.36870 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 128 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 86 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.513E-04 0.044 1.000 2.795E-04 0.133 3.000 2.203E-04 0.222 5.000 1.564E-04 0.444 10.000 1.062E-04 0.666 15.000 8.010E-05 0.888 20.000 6.497E-05 1.110 25.000 5.463E-05 1.332 30.000 4.702E-05 1.554 35.000 4.118E-05 1.776 40.000 3.652E-05 1.998 45.000 3.271E-05 2.220 50.000 2.956E-05 2.442 55.000 2.692E-05 2.664 60.000 2.466E-05 2.885 65.000 2.272E-05 3.107 70.000 2.103E-05 3.329 75.000 1.954E-05 3.551 80.000 1.804E-05 3.773 85.000 1.467E-04 0.5 11.26 ANNUAL AVERAGE = 8.67E-06 3 to ULNRC-06696 Page 129 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 87 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.116 1.762 2.369 4.593 5.238 6.314 8.414 10.852 13.076 13.147 0.04389 0.06926 0.09314 0.18054 0.20592 0.24820 0.33077 0.42663 0.51402 0.51684 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 14.725 14.730 15.303 16.379 19.822 21.041 21.328 22.690 25.344 26.491 0.57887 0.57905 0.60161 0.64390 0.77922 0.82715 0.83843 0.89199 0.99631 1.04142 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 27.065 29.934 31.224 36.962 45.424 48.006 49.727 50.229 50.301 50.516 1.06397 1.17674 1.22749 1.45303 1.78571 1.88720 1.95486 1.97460 1.97742 1.98588 2.949E-05 2.572E-05 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 54.891 55.106 70.023 81.139 86.446 87.091 88.812 90.390 92.900 93.402 2.15785 2.16631 2.75272 3.18971 3.39834 3.42371 3.49137 3.55340 3.65207 3.67181 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.086E-06 93.474 94.693 94.836 95.410 95.554 96.701 98.207 98.566 98.709 98.781 3.67463 3.72256 3.72819 3.75075 3.75639 3.80150 3.86070 3.87480 3.88044 3.88326 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 130 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 131 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 88 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.698E-04 0.039 1.000 2.955E-04 0.118 3.000 2.347E-04 0.197 5.000 1.687E-04 0.393 10.000 1.293E-04 0.590 15.000 9.733E-05 0.786 20.000 7.496E-05 0.983 25.000 6.291E-05 1.179 30.000 5.423E-05 1.376 35.000 4.756E-05 1.572 40.000 4.227E-05 1.769 45.000 3.794E-05 1.966 50.000 3.382E-05 2.162 55.000 3.041E-05 2.359 60.000 2.753E-05 2.555 65.000 2.509E-05 2.752 70.000 2.298E-05 2.948 75.000 2.115E-05 3.145 80.000 1.902E-05 3.342 85.000 1.496E-04 0.5 12.72 ANNUAL AVERAGE = 8.56E-06 3 to ULNRC-06696 Page 132 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 89 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.660 1.542 2.198 3.642 4.685 5.408 7.787 8.509 10.355 12.120 0.02318 0.05419 0.07720 0.12795 0.16460 0.18997 0.27356 0.29893 0.36378 0.42580 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 12.126 12.607 13.089 16.941 18.546 18.947 20.391 23.601 24.805 25.849 0.42599 0.44290 0.45982 0.59514 0.65153 0.66563 0.71637 0.82914 0.87143 0.90808 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 2.412E-05 2.332E-05 29.139 29.620 36.121 43.584 46.954 49.121 49.362 55.862 72.956 73.036 1.02368 1.04059 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.56582 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 8.746E-06 7.140E-06 6.997E-06 5.831E-06 83.870 87.802 88.364 89.728 90.450 92.777 94.623 94.784 95.666 95.827 2.94643 3.08457 3.10431 3.15223 3.17761 3.25937 3.32421 3.32985 3.36086 3.36650 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.086E-06 7.243E-07 5.432E-07 4.346E-07 96.710 96.790 98.074 98.876 99.037 99.117 99.278 99.519 99.679 99.920 3.39751 3.40033 3.44544 3.47363 3.47927 3.48209 3.48773 3.49619 3.50183 3.51028 3.621E-07 3 to ULNRC-06696 Page 133 of 456 100.000 3.51310 3 to ULNRC-06696 Page 134 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 90 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.900E-04 0.035 1.000 2.599E-04 0.105 3.000 2.095E-04 0.176 5.000 1.504E-04 0.351 10.000 1.089E-04 0.527 15.000 8.527E-05 0.703 20.000 7.019E-05 0.878 25.000 5.988E-05 1.054 30.000 5.219E-05 1.230 35.000 4.623E-05 1.405 40.000 4.146E-05 1.581 45.000 3.746E-05 1.757 50.000 3.372E-05 1.932 55.000 3.059E-05 2.108 60.000 2.794E-05 2.284 65.000 2.567E-05 2.459 70.000 2.369E-05 2.635 75.000 2.196E-05 2.810 80.000 1.138E-04 0.5 14.23 ANNUAL AVERAGE = 7.18E-06 3 to ULNRC-06696 Page 135 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 91 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.532 1.334 1.963 3.245 4.046 4.446 6.908 6.988 7.549 9.872 0.01874 0.04693 0.06908 0.11419 0.14238 0.15647 0.24312 0.24594 0.26567 0.34743 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 11.795 11.800 12.521 12.681 15.805 17.808 17.968 18.048 19.009 21.253 0.41509 0.41526 0.44064 0.44628 0.55623 0.62671 0.63235 0.63517 0.66900 0.74794 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 22.214 22.855 25.979 26.540 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.80432 0.91428 0.93401 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 8.746E-06 7.140E-06 74.846 74.926 86.061 90.868 91.508 93.030 93.351 95.193 96.475 96.555 2.63404 2.63686 3.02874 3.19790 3.22045 3.27402 3.28529 3.35014 3.39525 3.39807 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 97.116 97.276 97.597 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.41780 3.42344 3.43472 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 136 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 92 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.684E-04 0.035 1.000 2.482E-04 0.106 3.000 1.999E-04 0.176 5.000 1.459E-04 0.352 10.000 1.030E-04 0.528 15.000 7.830E-05 0.704 20.000 6.579E-05 0.880 25.000 5.771E-05 1.056 30.000 5.154E-05 1.232 35.000 4.663E-05 1.408 40.000 4.263E-05 1.584 45.000 3.930E-05 1.760 50.000 3.567E-05 1.936 55.000 3.221E-05 2.112 60.000 2.928E-05 2.288 65.000 2.679E-05 2.464 70.000 2.463E-05 2.639 75.000 2.275E-05 2.815 80.000 2.110E-05 2.991 85.000 1.080E-04 0.5 14.21 ANNUAL AVERAGE = 6.94E-06 3 to ULNRC-06696 Page 137 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 93 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.455 1.240 1.846 2.752 3.720 4.143 6.481 6.965 9.201 10.652 0.02120 0.05786 0.08608 0.12837 0.17348 0.19321 0.30228 0.32484 0.42915 0.49681 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 10.657 11.140 11.261 14.465 15.795 15.976 16.883 19.664 20.752 21.235 0.49702 0.51957 0.52521 0.67463 0.73666 0.74511 0.78740 0.91709 0.96784 0.99039 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 2.412E-05 24.802 25.527 33.204 43.299 46.321 50.251 51.097 51.520 57.867 74.914 1.15673 1.19056 1.54861 2.01943 2.16040 2.34365 2.38312 2.40285 2.69888 3.49392 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 1.142E-05 8.746E-06 7.140E-06 74.974 85.553 91.235 91.537 92.504 92.746 94.318 94.378 95.648 95.708 3.49674 3.99011 4.25512 4.26922 4.31433 4.32560 4.39891 4.40173 4.46093 4.46375 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 96.736 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.51168 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 138 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 94 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.565E-04 0.047 1.000 2.418E-04 0.140 3.000 1.943E-04 0.233 5.000 1.371E-04 0.466 10.000 9.510E-05 0.700 15.000 7.293E-05 0.933 20.000 6.282E-05 1.166 25.000 5.543E-05 1.399 30.000 4.974E-05 1.632 35.000 4.519E-05 1.866 40.000 4.146E-05 2.099 45.000 3.834E-05 2.332 50.000 3.457E-05 2.565 55.000 3.137E-05 2.798 60.000 2.865E-05 3.032 65.000 2.631E-05 3.265 70.000 2.428E-05 3.498 75.000 2.250E-05 3.731 80.000 2.093E-05 3.964 85.000 1.289E-04 0.5 10.72 ANNUAL AVERAGE = 8.80E-06 3 to ULNRC-06696 Page 139 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 95 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 1.078 1.748 2.927 3.588 3.933 6.437 7.213 9.168 9.340 0.04931 0.10570 0.17148 0.28707 0.35192 0.38575 0.63141 0.70753 0.89924 0.91616 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 11.410 11.413 11.701 12.247 16.271 17.392 17.420 17.449 17.507 20.180 1.11914 1.11945 1.14764 1.20121 1.59591 1.70586 1.70868 1.71150 1.71714 1.97933 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 24.405 25.641 26.216 30.499 31.074 40.473 53.810 55.764 59.673 60.420 2.39377 2.51500 2.57138 2.99146 3.04784 3.96975 5.27790 5.46961 5.85303 5.92633 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 60.564 65.451 65.508 79.046 79.190 86.491 88.589 88.790 89.106 89.135 5.94043 6.41971 6.42534 7.75323 7.76732 8.48342 8.68923 8.70896 8.73998 8.74279 1.166E-05 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 91.981 93.878 93.935 94.481 94.568 95.602 96.723 97.126 97.183 97.212 9.02190 9.20798 9.21361 9.26718 9.27564 9.37713 9.48708 9.52655 9.53219 9.53501 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3 to ULNRC-06696 Page 140 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 141 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 96 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.581E-04 0.098 1.000 2.384E-04 0.294 3.000 1.928E-04 0.490 5.000 1.390E-04 0.981 10.000 1.044E-04 1.471 15.000 8.513E-05 1.962 20.000 7.255E-05 2.452 25.000 6.395E-05 2.943 30.000 5.729E-05 3.433 35.000 5.197E-05 3.923 40.000 4.758E-05 4.414 45.000 4.390E-05 4.904 50.000 4.075E-05 5.395 55.000 3.787E-05 5.885 60.000 3.334E-05 6.376 65.000 2.958E-05 6.866 70.000 2.641E-05 7.356 75.000 2.371E-05 7.847 80.000 2.140E-05 8.337 85.000 1.912E-04 0.5 5.10 ANNUAL AVERAGE = 1.97E-05 3 to ULNRC-06696 Page 142 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 97 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.676 1.073 1.374 2.698 3.051 3.868 4.745 5.363 6.687 7.504 0.08630 0.13704 0.17547 0.34463 0.38974 0.49405 0.60618 0.68512 0.85428 0.95859 1.363E-04 1.254E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 1.003E-04 9.834E-05 8.620E-05 7.763E-05 10.086 10.108 10.881 10.882 11.015 12.758 12.780 14.744 15.473 17.591 1.28845 1.29126 1.38994 1.39012 1.40704 1.62976 1.63258 1.88349 1.97653 2.24718 7.705E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 5.679E-05 4.718E-05 4.543E-05 4.310E-05 17.635 29.774 34.828 35.225 35.468 36.638 36.660 36.947 36.969 40.941 2.25282 3.80343 4.44904 4.49979 4.53080 4.68022 4.68304 4.71969 4.72251 5.22998 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 54.889 55.772 63.055 65.990 67.138 70.360 70.382 70.890 78.482 78.548 7.01177 7.12454 8.05491 8.42987 8.57647 8.98809 8.99091 9.05575 10.02559 10.03404 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.520E-06 8.746E-06 7.140E-06 84.044 84.088 87.155 87.729 89.098 89.782 91.900 91.922 93.578 93.666 10.73604 10.74168 11.13356 11.20687 11.38166 11.46906 11.73971 11.74253 11.95398 11.96525 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 3 to ULNRC-06696 Page 143 of 456 94.284 94.549 95.630 95.829 96.954 96.976 97.506 97.771 97.948 98.455 12.04419 12.07803 12.21617 12.24154 12.38533 12.38815 12.45581 12.48964 12.51220 12.57704 5.432E-07 4.346E-07 3.621E-07 2.716E-07 2.173E-07 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 144 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 98 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.811E-04 0.128 1.000 2.328E-04 0.383 3.000 1.816E-04 0.639 5.000 1.366E-04 1.277 10.000 1.054E-04 1.916 15.000 9.384E-05 2.555 20.000 8.541E-05 3.194 25.000 7.888E-05 3.832 30.000 7.330E-05 4.471 35.000 6.182E-05 5.110 40.000 5.299E-05 5.748 45.000 4.602E-05 6.387 50.000 4.046E-05 7.026 55.000 3.901E-05 7.665 60.000 3.681E-05 8.303 65.000 2.049E-04 0.5 3.91 ANNUAL AVERAGE = 2.25E-05 3 to ULNRC-06696 Page 145 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 99 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.418 0.929 1.105 1.884 2.287 2.690 3.486 3.513 3.755 4.454 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.36583 0.36865 0.39403 0.46733 1.475E-04 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 5.045 5.905 6.281 6.283 6.498 7.492 8.405 8.996 9.077 12.382 0.52935 0.61957 0.65904 0.65922 0.68178 0.78609 0.88195 0.94397 0.95243 1.29920 7.705E-05 7.690E-05 7.572E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 12.785 19.126 19.153 21.651 22.162 22.565 23.452 23.640 25.709 33.984 1.34149 2.00684 2.00966 2.27185 2.32542 2.36771 2.46075 2.48048 2.69757 3.56591 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 35.086 46.129 52.765 52.792 56.634 58.945 58.972 60.718 66.629 66.791 3.68150 4.84022 5.53658 5.53940 5.94256 6.18502 6.18784 6.37109 6.99133 7.00825 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 72.702 72.728 77.753 78.075 81.649 86.566 88.608 89.038 90.945 91.053 7.62849 7.63131 8.15852 8.19235 8.56732 9.08324 9.29751 9.34262 9.54279 9.55406 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 3 to ULNRC-06696 Page 146 of 456 91.966 92.826 94.062 94.841 95.701 95.755 96.507 97.501 97.851 97.985 9.64992 9.74014 9.86982 9.95158 10.04180 10.04744 10.12638 10.23069 10.26734 10.28144 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 2.173E-07 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 147 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 100 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.094E-04 0.105 1.000 1.857E-04 0.315 3.000 1.481E-04 0.525 5.000 9.293E-05 1.049 10.000 7.699E-05 1.574 15.000 7.576E-05 2.099 20.000 6.622E-05 2.623 25.000 5.755E-05 3.148 30.000 5.093E-05 3.673 35.000 4.569E-05 4.197 40.000 4.142E-05 4.722 45.000 3.786E-05 5.246 50.000 3.505E-05 5.771 55.000 3.072E-05 6.296 60.000 2.632E-05 6.820 65.000 2.275E-05 7.345 70.000 1.981E-05 7.870 75.000 1.512E-04 0.5 4.77 ANNUAL AVERAGE = 1.37E-05 3 to ULNRC-06696 Page 148 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 101 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.344 0.763 0.992 1.411 1.704 1.997 2.906 2.990 3.828 4.330 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19561 0.20125 0.25763 0.29146 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 4.875 5.419 5.421 5.798 6.510 8.144 8.898 8.981 11.620 11.872 0.32811 0.36476 0.36489 0.39026 0.43819 0.54814 0.59889 0.60453 0.78214 0.79906 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 16.814 19.579 20.039 20.500 21.422 21.757 24.144 33.150 34.113 43.705 1.13173 1.31781 1.34882 1.37983 1.44186 1.46441 1.62511 2.23125 2.29610 2.94171 3.614E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 48.019 49.988 52.501 53.171 59.999 60.041 68.250 73.989 74.659 77.717 3.23210 3.36461 3.53376 3.57887 4.03842 4.04123 4.59381 4.98006 5.02517 5.23097 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 79.727 82.910 83.078 85.466 85.549 87.727 88.816 89.905 90.408 92.544 5.36630 5.58056 5.59184 5.75254 5.75818 5.90478 5.97808 6.05138 6.08522 6.22900 3.499E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 149 of 456 92.754 94.597 95.518 95.979 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.46018 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 150 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 102 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.940E-04 0.067 1.000 1.768E-04 0.202 3.000 1.349E-04 0.337 5.000 8.599E-05 0.673 10.000 7.713E-05 1.010 15.000 7.259E-05 1.346 20.000 6.130E-05 1.683 25.000 5.317E-05 2.019 30.000 4.700E-05 2.356 35.000 4.214E-05 2.692 40.000 3.818E-05 3.029 45.000 1.047E-04 0.5 7.43 ANNUAL AVERAGE = 8.44E-06 3 to ULNRC-06696 Page 151 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 103 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.368 0.718 0.980 1.881 2.232 2.532 3.980 4.080 4.631 5.482 0.02071 0.04045 0.05521 0.10596 0.12569 0.14261 0.22415 0.22979 0.26081 0.30873 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 5.832 6.633 6.636 6.937 7.588 8.989 10.091 10.241 11.642 17.700 0.32847 0.37358 0.37374 0.39066 0.42731 0.50625 0.56827 0.57673 0.65567 0.99680 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 21.404 22.255 22.806 24.558 25.159 28.663 37.975 39.576 47.136 49.489 1.20543 1.25336 1.28437 1.38304 1.41688 1.61422 2.13861 2.22883 2.65454 2.78705 3.499E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 49.539 50.139 53.744 53.844 53.994 62.554 62.655 70.614 75.921 76.471 2.78987 2.82370 3.02669 3.03232 3.04078 3.52288 3.52852 3.97678 4.27563 4.30664 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 79.425 81.177 83.280 83.430 85.683 85.733 87.335 88.035 89.337 89.487 4.47298 4.57165 4.69006 4.69852 4.82539 4.82821 4.91843 4.95790 5.03120 5.03965 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3 to ULNRC-06696 Page 152 of 456 91.740 93.042 93.843 94.343 94.393 94.443 94.493 94.894 96.796 98.548 5.16652 5.23982 5.28493 5.31312 5.31594 5.31876 5.32158 5.34414 5.45127 5.54995 3.621E-07 2.716E-07 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 153 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 104 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.069E-04 0.056 1.000 1.951E-04 0.169 3.000 1.543E-04 0.282 5.000 9.507E-05 0.563 10.000 8.329E-05 0.845 15.000 7.552E-05 1.126 20.000 6.518E-05 1.408 25.000 5.618E-05 1.690 30.000 4.940E-05 1.971 35.000 4.408E-05 2.253 40.000 3.979E-05 2.534 45.000 3.558E-05 2.816 50.000 3.077E-05 3.097 55.000 2.689E-05 3.379 60.000 2.371E-05 3.661 65.000 2.106E-05 3.942 70.000 1.880E-05 4.224 75.000 9.937E-05 0.5 8.88 ANNUAL AVERAGE = 8.06E-06 3 to ULNRC-06696 Page 154 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 105 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.477 1.160 1.580 2.490 2.793 3.248 5.769 6.451 8.119 8.195 0.01775 0.04313 0.05876 0.09259 0.10387 0.12078 0.21456 0.23993 0.30196 0.30478 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 9.560 9.563 10.094 10.397 12.519 13.808 14.036 14.490 14.642 17.523 0.35553 0.35566 0.37539 0.38667 0.46561 0.51353 0.52199 0.53891 0.54455 0.65168 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 19.797 21.768 22.905 26.089 26.695 32.684 42.690 44.207 50.650 53.076 0.73626 0.80956 0.85185 0.97026 0.99281 1.21554 1.58768 1.64407 1.88371 1.97392 3.499E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 53.152 53.455 57.094 57.473 66.418 66.494 73.013 73.165 77.940 78.623 1.97674 1.98802 2.12335 2.13744 2.47012 2.47294 2.71540 2.72103 2.89865 2.92402 1.665E-05 1.248E-05 1.166E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 81.124 83.323 85.521 85.824 85.900 87.871 87.947 88.932 89.690 91.055 3.01706 3.09882 3.18058 3.19186 3.19467 3.26798 3.27080 3.30745 3.33564 3.38639 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3 to ULNRC-06696 Page 155 of 456 91.434 92.798 94.087 94.315 94.769 94.921 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.52453 3.53017 3.55554 3.62321 3.66549 3.70778 2.716E-07 100.000 3.71906 3 to ULNRC-06696 Page 156 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 106 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.479E-04 0.037 1.000 2.278E-04 0.112 3.000 1.835E-04 0.186 5.000 1.216E-04 0.372 10.000 8.794E-05 0.558 15.000 7.326E-05 0.744 20.000 6.310E-05 0.930 25.000 5.568E-05 1.116 30.000 4.997E-05 1.302 35.000 4.542E-05 1.488 40.000 4.169E-05 1.674 45.000 3.856E-05 1.860 50.000 3.402E-05 2.045 55.000 2.930E-05 2.231 60.000 2.550E-05 2.417 65.000 2.238E-05 2.603 70.000 1.977E-05 2.789 75.000 9.412E-05 0.5 13.44 ANNUAL AVERAGE = 6.43E-06 3 to ULNRC-06696 Page 157 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 107 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.274 0.599 0.899 1.494 2.251 2.521 4.320 4.699 6.105 6.213 0.01430 0.03122 0.04685 0.07786 0.11733 0.13143 0.22521 0.24494 0.31824 0.32388 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 6.916 6.919 7.352 7.677 8.704 10.110 10.219 10.543 10.597 12.490 0.36053 0.36069 0.38324 0.40016 0.45372 0.52702 0.53266 0.54958 0.55240 0.65107 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.665E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 14.329 15.249 15.898 18.115 18.494 18.548 21.847 31.690 33.529 41.696 0.74693 0.79486 0.82869 0.94428 0.96401 0.96683 1.13881 1.65192 1.74777 2.17349 3.614E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 44.509 45.536 51.161 51.377 60.680 60.788 67.711 67.765 74.418 75.229 2.32009 2.37366 2.66686 2.67814 3.16305 3.16869 3.52956 3.53238 3.87915 3.92144 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 79.989 83.829 85.938 86.316 88.155 88.209 89.129 89.778 90.806 91.076 4.16954 4.36971 4.47966 4.49940 4.59525 4.59807 4.64600 4.67983 4.73340 4.74749 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3.534E-07 3 to ULNRC-06696 Page 158 of 456 92.428 93.780 94.267 94.537 94.591 94.970 96.484 98.053 99.351 99.405 4.81797 4.88846 4.91383 4.92793 4.93075 4.95048 5.02942 5.11118 5.17884 5.18166 2.716E-07 100.000 5.21267 3 to ULNRC-06696 Page 159 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 108 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.939E-04 0.052 1.000 1.981E-04 0.156 3.000 1.615E-04 0.261 5.000 8.724E-05 0.521 10.000 7.183E-05 0.782 15.000 6.066E-05 1.043 20.000 5.297E-05 1.303 25.000 4.727E-05 1.564 30.000 4.283E-05 1.824 35.000 3.926E-05 2.085 40.000 3.564E-05 2.346 45.000 3.118E-05 2.606 50.000 2.757E-05 2.867 55.000 2.461E-05 3.128 60.000 2.212E-05 3.388 65.000 2.002E-05 3.649 70.000 9.129E-05 0.5 9.59 ANNUAL AVERAGE = 7.22E-06 3 to ULNRC-06696 Page 160 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 109 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.541 0.759 1.192 2.195 2.500 3.328 5.629 6.675 8.331 8.462 0.03501 0.04911 0.07712 0.14196 0.16169 0.21526 0.36408 0.43175 0.53888 0.54734 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.465 9.468 9.991 10.601 13.260 14.829 15.134 17.052 19.885 21.498 0.61218 0.61237 0.64620 0.68567 0.85765 0.95914 0.97888 1.10292 1.28618 1.39049 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 21.847 24.506 25.029 29.126 36.449 38.192 41.287 42.725 43.118 47.825 1.41305 1.58502 1.61885 1.88387 2.35751 2.47028 2.67045 2.76348 2.78886 3.09334 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 6.997E-06 58.940 69.140 76.724 77.552 82.173 84.831 86.836 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.01609 5.31493 5.48691 5.61660 5.61942 5.73501 5.79139 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 90.323 91.021 91.457 93.070 94.028 94.682 94.900 95.380 96.600 98.649 5.84214 5.88725 5.91544 6.01976 6.08178 6.12407 6.13817 6.16918 6.24812 6.38062 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 161 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 162 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 110 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.576E-04 0.065 1.000 2.309E-04 0.194 3.000 1.856E-04 0.323 5.000 1.261E-04 0.647 10.000 9.024E-05 0.970 15.000 7.339E-05 1.294 20.000 6.047E-05 1.617 25.000 5.138E-05 1.940 30.000 4.461E-05 2.264 35.000 3.936E-05 2.587 40.000 3.468E-05 2.911 45.000 3.075E-05 3.234 50.000 2.753E-05 3.557 55.000 2.485E-05 3.881 60.000 2.257E-05 4.204 65.000 2.063E-05 4.528 70.000 1.895E-05 4.851 75.000 1.527E-04 0.5 7.73 ANNUAL AVERAGE = 1.08E-05 3 to ULNRC-06696 Page 163 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 111 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.620 0.788 1.178 2.401 2.654 3.582 5.473 6.697 7.793 8.553 0.04142 0.05270 0.07875 0.16051 0.17743 0.23945 0.36585 0.44761 0.52091 0.57166 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.480 9.483 9.990 11.128 13.912 15.220 15.346 16.949 20.577 21.969 0.63368 0.63388 0.66771 0.74383 0.92991 1.01730 1.02576 1.13290 1.37535 1.46839 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 22.601 24.626 25.174 30.447 38.123 39.810 42.679 43.480 43.860 47.740 1.51068 1.64600 1.68266 2.03507 2.54818 2.66095 2.85266 2.90622 2.93160 3.19097 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 47.782 59.803 59.930 69.884 69.926 78.151 78.531 83.424 85.490 87.009 3.19379 3.99729 4.00575 4.67110 4.67392 5.22368 5.24905 5.57609 5.71423 5.81573 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 87.051 88.991 89.033 89.835 90.510 91.227 91.691 93.462 94.812 95.192 5.81855 5.94823 5.95105 6.00462 6.04973 6.09765 6.12867 6.24708 6.33729 6.36267 1.785E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 164 of 456 95.402 95.571 96.837 98.482 99.494 100.000 6.37676 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 165 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 112 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.705E-04 0.067 1.000 2.313E-04 0.201 3.000 1.828E-04 0.334 5.000 1.243E-04 0.668 10.000 9.315E-05 1.003 15.000 7.535E-05 1.337 20.000 6.230E-05 1.671 25.000 5.297E-05 2.005 30.000 4.601E-05 2.339 35.000 4.062E-05 2.674 40.000 3.594E-05 3.008 45.000 3.180E-05 3.342 50.000 2.841E-05 3.676 55.000 2.559E-05 4.010 60.000 2.320E-05 4.345 65.000 2.117E-05 4.679 70.000 1.941E-05 5.013 75.000 1.777E-05 5.347 80.000 1.505E-04 0.5 7.48 ANNUAL AVERAGE = 1.12E-05 3 to ULNRC-06696 Page 166 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 113 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 0.932 1.140 1.783 2.169 2.684 3.971 5.257 6.501 6.930 0.03304 0.06123 0.07491 0.11720 0.14257 0.17640 0.26101 0.34559 0.42735 0.45554 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 7.101 7.103 7.404 8.647 9.548 10.106 10.234 10.449 13.923 16.024 0.46682 0.46694 0.48668 0.56844 0.62764 0.66429 0.67275 0.68685 0.91521 1.05335 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 16.925 17.096 18.898 19.241 22.972 31.893 33.137 37.168 38.112 38.412 1.11256 1.12383 1.24224 1.26480 1.51008 2.09649 2.17825 2.44326 2.50528 2.52502 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 41.886 41.929 53.809 53.852 68.348 68.391 77.098 77.183 82.630 86.018 2.75338 2.75620 3.53714 3.53996 4.49288 4.49570 5.06801 5.07365 5.43170 5.65442 1.166E-05 9.987E-06 8.746E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 87.562 87.948 89.707 91.422 92.537 92.966 93.224 95.239 96.912 97.384 5.75592 5.78129 5.89688 6.00965 6.08295 6.11115 6.12806 6.26057 6.37052 6.40153 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 167 of 456 97.941 97.984 98.027 98.499 99.228 99.528 100.000 6.43818 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 168 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 114 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.407E-04 0.066 1.000 2.121E-04 0.197 3.000 1.674E-04 0.329 5.000 1.020E-04 0.657 10.000 7.727E-05 0.986 15.000 6.248E-05 1.315 20.000 5.260E-05 1.643 25.000 4.551E-05 1.972 30.000 4.014E-05 2.301 35.000 3.564E-05 2.629 40.000 3.183E-05 2.958 45.000 2.872E-05 3.287 50.000 2.613E-05 3.615 55.000 2.393E-05 3.944 60.000 2.204E-05 4.273 65.000 2.040E-05 4.601 70.000 1.897E-05 4.930 75.000 1.745E-05 5.259 80.000 1.271E-04 0.5 7.61 ANNUAL AVERAGE = 9.12E-06 3 to ULNRC-06696 Page 169 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 115 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 1200.0 METERS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
2.007E-03 1.338E-03 1.003E-03 9.087E-04 8.027E-04 6.689E-04 6.058E-04 5.017E-04 4.543E-04 4.115E-04 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 3.635E-04 3.344E-04 3.029E-04 2.743E-04 2.508E-04 2.272E-04 2.057E-04 2.007E-04 1.997E-04 1.646E-04 9.495 10.110 12.275 12.625 12.743 15.904 16.992 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 16.99183 16.99464 16.99746 17.92783 1.514E-04 1.372E-04 1.332E-04 1.254E-04 1.136E-04 1.029E-04 1.003E-04 9.987E-05 9.087E-05 7.990E-05 22.089 24.282 24.418 24.421 25.357 30.147 30.149 30.668 30.747 31.229 22.08909 24.28249 24.41782 24.42064 25.35664 30.14660 30.14942 30.66817 30.74711 31.22920 7.572E-05 6.858E-05 6.658E-05 5.679E-05 5.144E-05 4.994E-05 4.665E-05 4.543E-05 4.115E-05 3.499E-05 31.232 41.015 42.698 42.701 48.325 52.396 52.399 52.402 54.553 54.567 31.23202 41.01494 42.69805 42.70087 48.32534 52.39639 52.39921 52.40203 54.55314 54.56724 3.429E-05 3.329E-05 2.799E-05 2.572E-05 2.497E-05 2.332E-05 2.057E-05 1.997E-05 1.749E-05 1.665E-05 55.467 66.188 66.202 66.552 75.562 75.644 75.667 81.581 82.047 85.134 55.46659 66.18832 66.20242 66.55202 75.56245 75.64420 75.66676 81.58162 82.04680 85.13391 1.248E-05 1.166E-05 1.142E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14124 89.25006 89.25288 89.41358 89.43050 91.23766 91.30814 92.34282 92.93204 93.86240 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 3 to ULNRC-06696 Page 170 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13587 95.48913 95.51168 96.42796 96.89314 97.12995 97.14687 97.16096 97.17506 97.51337 5.432E-07 4.346E-07 3.621E-07 3.534E-07 2.716E-07 2.173E-07 98.345 99.179 99.777 99.780 99.994 100.000 98.34506 99.17957 99.77725 99.78008 99.99434 99.99998 3 to ULNRC-06696 Page 171 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 116 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.512E-03 1.000 1.000 8.278E-04 3.000 3.000 5.979E-04 5.000 5.000 3.602E-04 10.000 10.000 2.447E-04 15.000 15.000 1.755E-04 20.000 20.000 1.322E-04 25.000 25.000 1.036E-04 30.000 30.000 8.639E-05 35.000 35.000 7.282E-05 40.000 40.000 6.225E-05 45.000 45.000 5.387E-05 50.000 50.000 4.661E-05 55.000 55.000 4.023E-05 60.000 60.000 3.455E-05 65.000 65.000 2.977E-05 70.000 70.000 2.544E-05 75.000 75.000 5.979E-04 5.0 5.00 3 to ULNRC-06696 Page 172 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 117 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.558 1.057 1.441 2.551 3.028 3.620 5.269 5.272 5.390 6.380 0.55822 1.05723 1.44065 2.55145 3.02791 3.61996 5.26924 5.27206 5.39047 6.38004 1.475E-04 1.363E-04 1.254E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 1.003E-04 9.834E-05 8.620E-05 7.694 8.308 8.311 9.335 9.337 9.687 10.586 10.589 12.754 13.843 7.69383 8.30843 8.31125 9.33465 9.33747 9.68706 10.58641 10.58922 12.75443 13.84268 7.864E-05 7.763E-05 7.705E-05 7.690E-05 7.572E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 5.679E-05 13.978 14.914 14.993 19.154 19.157 22.317 23.248 23.767 25.960 25.963 13.97800 14.91400 14.99294 19.15420 19.15702 22.31744 23.24780 23.76655 25.95996 25.96277 4.718E-05 4.665E-05 4.543E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 26.445 26.448 26.450 31.240 41.023 42.706 48.331 50.482 50.496 51.395 26.44487 26.44769 26.45051 31.24047 41.02340 42.70650 48.33097 50.48209 50.49618 51.39553 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 55.466 55.481 55.830 66.552 66.634 75.644 75.667 81.581 82.047 85.134 55.46658 55.48067 55.83025 66.55198 66.63377 75.64420 75.66676 81.58163 82.04681 85.13392 1.248E-05 1.166E-05 1.142E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14127 89.25008 89.25290 89.41361 89.43054 91.23772 91.30822 92.34290 92.93212 93.86248 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 3 to ULNRC-06696 Page 173 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13596 95.48923 95.51179 96.42807 96.89326 97.13010 97.14702 97.16113 97.17523 97.51356 5.432E-07 4.346E-07 3.621E-07 3.534E-07 2.716E-07 2.173E-07 98.345 99.180 99.777 99.780 99.994 100.000 98.34525 99.17977 99.77747 99.78029 99.99457 100.00021 3 to ULNRC-06696 Page 174 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 118 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00021 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.604E-04 1.000 1.000 2.265E-04 3.000 3.000 1.771E-04 5.000 5.000 1.204E-04 10.000 10.000 9.099E-05 15.000 15.000 7.841E-05 20.000 20.000 6.689E-05 25.000 25.000 5.653E-05 30.000 30.000 4.836E-05 35.000 35.000 4.171E-05 40.000 40.000 3.922E-05 45.000 45.000 3.690E-05 50.000 50.000 3.326E-05 55.000 55.000 2.993E-05 60.000 60.000 2.684E-05 65.000 65.000 2.392E-05 70.000 70.000 2.112E-05 75.000 75.000 1.906E-05 80.000 80.000 1.771E-04 5.0 5.00 3 to ULNRC-06696 Page 175 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 119 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION AREA BOUNDARY (SB OR EAB)
BUILDING WAKE CREDIT IS NOT INCLUDED.
RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX SB AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 1200. 1.34E-04 8.62E-05 6.90E-05 4.26E-05 2.13E-05 9.11E-06 20.4 S SSW 1200. 1.47E-04 9.19E-05 7.28E-05 4.38E-05 2.11E-05 8.67E-06 325.0 SSW SW 1200. 1.50E-04 9.32E-05 7.36E-05 4.41E-05 2.11E-05 8.56E-06 23.0 SW WSW 1200. 1.14E-04 7.21E-05 5.73E-05 3.49E-05 1.71E-05 7.18E-06 16.2 WSW W 1200. 1.08E-04 6.86E-05 5.47E-05 3.34E-05 1.65E-05 6.94E-06 14.5 W WNW 1200. 1.29E-04 8.27E-05 6.62E-05 4.09E-05 2.05E-05 8.80E-06 18.1 WNW NW 1200. 1.91E-04 1.31E-04 1.09E-04 7.24E-05 4.03E-05 1.97E-05 37.2 NW NNW 1200. 2.05E-04 1.42E-04 1.19E-04 7.98E-05 4.52E-05 2.25E-05 43.7 NNW N 1200. 1.51E-04 1.02E-04 8.33E-05 5.42E-05 2.92E-05 1.37E-05 22.5 N NNE 1200. 1.05E-04 6.91E-05 5.61E-05 3.57E-05 1.87E-05 8.44E-06 13.0 NNE NE 1200. 9.94E-05 6.56E-05 5.33E-05 3.40E-05 1.78E-05 8.06E-06 13.2 NE ENE 1200. 9.41E-05 6.04E-05 4.84E-05 2.99E-05 1.50E-05 6.43E-06 12.6 ENE E 1200. 9.13E-05 6.00E-05 4.87E-05 3.09E-05 1.61E-05 7.22E-06 12.5 E ESE 1200. 1.53E-04 9.86E-05 7.92E-05 4.93E-05 2.49E-05 1.08E-05 22.5 ESE SE 1200. 1.51E-04 9.79E-05 7.90E-05 4.95E-05 2.53E-05 1.12E-05 22.9 SE SSE 1200. 1.27E-04 8.22E-05 6.61E-05 4.12E-05 2.09E-05 9.12E-06 18.6 SSE MAX X/Q 2.05E-04 1.42E-04 1.19E-04 7.98E-05 4.52E-05 TOTAL HOURS: 635.9 SRP 2.3.4 1200. 5.98E-04 3.48E-04 2.65E-04 1.47E-04 6.33E-05 2.25E-05 SITE LIMIT 1.77E-04 1.26E-04 1.06E-04 7.34E-05 4.32E-05 2.25E-05 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 176 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 120 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.710 1.241 1.527 3.169 3.845 4.183 5.391 6.596 7.658 8.914 0.04142 0.07243 0.08915 0.18501 0.22448 0.24421 0.31470 0.38503 0.44705 0.52035 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.155 10.314 10.604 11.763 11.766 12.877 15.678 17.272 17.851 17.948 0.53445 0.60211 0.61903 0.68669 0.68686 0.75170 0.91522 1.00826 1.04209 1.04773 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 18.093 19.445 20.362 24.805 25.337 32.967 34.223 37.700 38.231 41.757 1.05619 1.13512 1.18869 1.44807 1.47908 1.92452 1.99783 2.20081 2.23183 2.43763 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 41.805 51.609 51.657 51.706 65.759 79.427 86.961 87.250 90.438 90.679 2.44045 3.01277 3.01559 3.01841 3.83882 4.63668 5.07648 5.09340 5.27947 5.29357 1.299E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 92.128 93.335 93.432 95.074 95.895 95.992 96.233 96.716 97.730 98.551 5.37815 5.44863 5.45427 5.55012 5.59805 5.60369 5.61779 5.64598 5.70518 5.75311 2.138E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 177 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 178 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 121 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.410E-04 0.058 1.000 8.431E-05 0.175 3.000 6.099E-05 0.292 5.000 3.725E-05 0.584 10.000 2.386E-05 0.876 15.000 1.695E-05 1.168 20.000 1.287E-05 1.459 25.000 1.021E-05 1.751 30.000 8.375E-06 2.043 35.000 7.053E-06 2.335 40.000 6.043E-06 2.627 45.000 5.250E-06 2.919 50.000 4.612E-06 3.211 55.000 4.090E-06 3.503 60.000 3.656E-06 3.794 65.000 3.385E-06 4.086 70.000 3.163E-06 4.378 75.000 4.221E-05 0.5 8.57 ANNUAL AVERAGE = 5.34E-07 3 to ULNRC-06696 Page 179 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 122 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.011 1.964 2.360 4.392 5.599 5.980 7.567 9.496 11.211 12.672 0.04487 0.08716 0.10475 0.19497 0.24853 0.26545 0.33593 0.42156 0.49768 0.56252 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 12.862 13.942 14.069 16.038 16.041 17.438 19.915 21.503 22.455 22.519 0.57098 0.61891 0.62454 0.71194 0.71209 0.77411 0.88406 0.95455 0.99684 0.99965 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.773 25.631 26.012 30.331 30.902 38.841 40.937 43.096 43.477 49.002 1.01093 1.13780 1.15472 1.34643 1.37180 1.72421 1.81725 1.91310 1.93002 2.17530 5.568E-06 4.541E-06 3.596E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 49.066 62.530 75.295 75.358 84.123 84.250 87.743 87.997 89.267 91.172 2.17812 2.77580 3.34248 3.34530 3.73436 3.74000 3.89506 3.90634 3.96272 4.04730 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 93.522 93.586 94.602 95.300 95.364 96.189 97.142 97.587 97.650 98.158 4.15161 4.15443 4.19954 4.23055 4.23337 4.27002 4.31231 4.33205 4.33487 4.35742 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 180 of 456 98.349 98.603 98.857 99.619 99.873 100.000 4.36588 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 181 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 123 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.649E-04 0.044 1.000 9.905E-05 0.133 3.000 7.585E-05 0.222 5.000 4.891E-05 0.444 10.000 3.301E-05 0.666 15.000 2.255E-05 0.888 20.000 1.673E-05 1.110 25.000 1.302E-05 1.332 30.000 1.049E-05 1.554 35.000 8.690E-06 1.776 40.000 7.422E-06 1.998 45.000 6.430E-06 2.220 50.000 5.636E-06 2.442 55.000 4.988E-06 2.664 60.000 4.451E-06 2.885 65.000 4.000E-06 3.107 70.000 3.617E-06 3.329 75.000 3.251E-06 3.551 80.000 4.519E-05 0.5 11.26 ANNUAL AVERAGE = 5.11E-07 3 to ULNRC-06696 Page 182 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 124 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.116 1.762 2.369 4.593 5.668 6.314 8.752 10.852 13.076 14.151 0.04389 0.06926 0.09314 0.18054 0.22283 0.24820 0.34406 0.42663 0.51402 0.55631 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 14.223 15.801 16.374 19.817 19.822 21.041 23.694 25.057 26.204 26.491 0.55913 0.62116 0.64371 0.77904 0.77922 0.82715 0.93146 0.98503 1.03014 1.04142 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 29.360 29.934 35.671 36.962 45.424 48.006 49.727 50.229 54.604 54.819 1.15419 1.17674 1.40228 1.45303 1.78571 1.88720 1.95486 1.97460 2.14658 2.15503 4.541E-06 4.176E-06 3.898E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 69.736 69.951 70.023 81.139 86.446 88.167 88.812 90.390 90.892 93.402 2.74144 2.74990 2.75272 3.18971 3.39834 3.46600 3.49137 3.55340 3.57313 3.67181 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 94.621 94.693 95.267 95.410 95.554 96.701 98.207 98.566 98.637 98.781 3.71974 3.72256 3.74511 3.75075 3.75639 3.80150 3.86070 3.87480 3.87762 3.88326 1.611E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 183 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 184 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 125 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.727E-04 0.039 1.000 1.020E-04 0.118 3.000 7.838E-05 0.197 5.000 5.312E-05 0.393 10.000 3.976E-05 0.590 15.000 2.980E-05 0.786 20.000 2.109E-05 0.983 25.000 1.640E-05 1.179 30.000 1.319E-05 1.376 35.000 1.089E-05 1.572 40.000 9.161E-06 1.769 45.000 7.805E-06 1.966 50.000 6.732E-06 2.162 55.000 5.871E-06 2.359 60.000 5.167E-06 2.555 65.000 4.585E-06 2.752 70.000 4.096E-06 2.948 75.000 3.682E-06 3.145 80.000 3.139E-06 3.342 85.000 4.611E-05 0.5 12.72 ANNUAL AVERAGE = 5.05E-07 3 to ULNRC-06696 Page 185 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 126 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.660 1.542 2.198 3.642 4.364 5.408 6.130 8.509 10.355 10.836 0.02318 0.05419 0.07720 0.12795 0.15332 0.18997 0.21535 0.29893 0.36378 0.38069 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 12.602 13.083 16.935 16.941 18.546 21.756 23.200 24.404 24.805 28.096 0.44272 0.45963 0.59496 0.59514 0.65153 0.76430 0.81505 0.85734 0.87143 0.98702 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 4.541E-06 3.596E-06 29.139 35.639 36.121 43.584 46.954 49.121 49.362 55.862 72.956 83.789 1.02368 1.25204 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.94361 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 87.722 87.802 89.166 89.728 90.450 92.777 94.623 95.506 95.666 95.827 3.08175 3.08457 3.13250 3.15223 3.17761 3.25937 3.32421 3.35522 3.36086 3.36650 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 95.907 96.790 98.074 98.876 99.037 99.197 99.438 99.519 99.679 99.920 3.36932 3.40033 3.44544 3.47363 3.47927 3.48491 3.49337 3.49619 3.50183 3.51028 8.057E-08 3 to ULNRC-06696 Page 186 of 456 100.000 3.51310 3 to ULNRC-06696 Page 187 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 127 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.398E-04 0.035 1.000 8.921E-05 0.105 3.000 6.898E-05 0.176 5.000 4.631E-05 0.351 10.000 3.349E-05 0.527 15.000 2.500E-05 0.703 20.000 1.905E-05 0.878 25.000 1.509E-05 1.054 30.000 1.234E-05 1.230 35.000 1.033E-05 1.405 40.000 8.806E-06 1.581 45.000 7.641E-06 1.757 50.000 6.720E-06 1.932 55.000 5.966E-06 2.108 60.000 5.341E-06 2.284 65.000 4.814E-06 2.459 70.000 4.336E-06 2.635 75.000 3.890E-06 2.810 80.000 3.499E-05 0.5 14.23 ANNUAL AVERAGE = 4.20E-07 3 to ULNRC-06696 Page 188 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 128 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.532 1.334 1.963 3.245 3.645 4.446 5.007 7.469 9.792 9.952 0.01874 0.04693 0.06908 0.11419 0.12828 0.15647 0.17621 0.26285 0.34461 0.35025 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 10.032 11.955 12.676 15.800 15.805 17.808 20.051 21.012 21.974 22.054 0.35307 0.42073 0.44611 0.55606 0.55623 0.62671 0.70565 0.73948 0.77331 0.77613 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.214 25.338 25.979 33.509 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.89172 0.91428 1.17929 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 4.541E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 7.796E-07 74.846 85.981 90.787 90.868 92.390 93.030 93.351 95.193 96.475 97.036 2.63404 3.02592 3.19508 3.19790 3.25146 3.27402 3.28529 3.35014 3.39525 3.41498 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 97.196 97.276 97.356 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.42062 3.42344 3.42626 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 189 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 129 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.302E-04 0.035 1.000 8.475E-05 0.106 3.000 6.553E-05 0.176 5.000 4.458E-05 0.352 10.000 3.163E-05 0.528 15.000 2.275E-05 0.704 20.000 1.776E-05 0.880 25.000 1.444E-05 1.056 30.000 1.208E-05 1.232 35.000 1.031E-05 1.408 40.000 8.955E-06 1.584 45.000 3.315E-05 0.5 14.21 ANNUAL AVERAGE = 4.04E-07 3 to ULNRC-06696 Page 190 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 130 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.455 1.240 1.846 2.752 3.176 4.143 4.626 6.965 9.201 9.322 0.02120 0.05786 0.08608 0.12837 0.14810 0.19321 0.21577 0.32484 0.42915 0.43479 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 10.773 11.257 14.461 14.465 15.795 18.575 19.482 20.570 20.752 24.318 0.50245 0.52500 0.67443 0.67463 0.73666 0.86634 0.90863 0.95938 0.96784 1.13418 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 24.802 32.479 33.204 43.299 46.321 50.251 51.097 57.444 57.867 74.914 1.15673 1.51478 1.54861 2.01943 2.16040 2.34365 2.38312 2.67914 2.69888 3.49392 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 1.026E-06 9.744E-07 7.796E-07 85.492 91.174 91.235 92.202 92.504 92.746 94.318 94.378 95.648 96.675 3.98729 4.25230 4.25512 4.30023 4.31433 4.32561 4.39891 4.40173 4.46093 4.50886 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.209E-07 9.669E-08 8.057E-08 97.038 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.52577 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 191 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 131 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.226E-04 0.047 1.000 7.884E-05 0.140 3.000 6.173E-05 0.233 5.000 4.216E-05 0.466 10.000 2.901E-05 0.700 15.000 2.101E-05 0.933 20.000 1.662E-05 1.166 25.000 1.364E-05 1.399 30.000 1.150E-05 1.632 35.000 9.895E-06 1.866 40.000 8.625E-06 2.099 45.000 7.587E-06 2.332 50.000 6.743E-06 2.565 55.000 6.045E-06 2.798 60.000 5.459E-06 3.032 65.000 4.962E-06 3.265 70.000 4.532E-06 3.498 75.000 4.046E-06 3.731 80.000 3.633E-06 3.964 85.000 3.964E-05 0.5 10.72 ANNUAL AVERAGE = 5.12E-07 3 to ULNRC-06696 Page 192 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 132 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 1.078 1.748 2.927 3.272 3.933 4.709 7.213 9.168 9.714 0.04931 0.10570 0.17148 0.28707 0.32091 0.38575 0.46187 0.70753 0.89924 0.95281 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.887 11.956 12.244 16.268 16.271 17.392 21.617 24.290 25.526 25.555 0.96972 1.17271 1.20090 1.59560 1.59591 1.70586 2.12030 2.38249 2.50372 2.50654 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 25.584 29.866 29.924 30.499 39.898 40.473 53.810 55.764 59.673 60.420 2.50936 2.92943 2.93507 2.99146 3.91336 3.96975 5.27790 5.46961 5.85303 5.92633 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 65.307 65.451 78.989 79.046 86.347 88.445 88.589 88.905 89.106 89.135 6.40561 6.41971 7.74759 7.75323 8.46933 8.67513 8.68923 8.72024 8.73998 8.74279 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 91.981 93.878 94.424 94.510 94.568 95.602 96.723 97.126 97.183 97.586 9.02190 9.20798 9.26154 9.27000 9.27564 9.37713 9.48709 9.52656 9.53219 9.57166 1.604E-07 1.209E-07 9.669E-08 8.057E-08 3 to ULNRC-06696 Page 193 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 194 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 133 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.268E-04 0.098 1.000 8.108E-05 0.294 3.000 6.272E-05 0.490 5.000 4.274E-05 0.981 10.000 3.209E-05 1.471 15.000 2.457E-05 1.962 20.000 1.939E-05 2.452 25.000 1.584E-05 2.943 30.000 1.329E-05 3.433 35.000 1.138E-05 3.923 40.000 1.040E-05 4.414 45.000 9.578E-06 4.904 50.000 8.700E-06 5.395 55.000 7.477E-06 5.885 60.000 6.487E-06 6.376 65.000 5.675E-06 6.866 70.000 5.000E-06 7.356 75.000 4.393E-06 7.847 80.000 3.749E-06 8.337 85.000 6.210E-05 0.5 5.10 ANNUAL AVERAGE = 1.15E-06 3 to ULNRC-06696 Page 195 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 134 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.676 1.073 1.374 2.698 3.514 3.868 5.192 6.069 6.886 8.630 0.08630 0.13704 0.17547 0.34463 0.44894 0.49405 0.66321 0.77534 0.87965 1.10237 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.219E-05 1.937E-05 11.212 11.830 12.602 12.735 14.699 14.700 15.428 20.482 20.505 32.643 1.43223 1.51117 1.60984 1.62676 1.87768 1.87786 1.97089 2.61651 2.61933 4.16993 1.824E-05 1.775E-05 1.666E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.626E-06 9.035E-06 33.040 33.062 35.181 36.351 36.395 36.638 40.610 40.897 40.919 54.867 4.22068 4.22350 4.49415 4.64357 4.64921 4.68022 5.18770 5.22435 5.22716 7.00895 8.308E-06 7.700E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 55.750 55.772 63.055 65.990 69.213 70.360 77.952 78.460 83.955 83.999 7.12172 7.12454 8.05491 8.42987 8.84149 8.98809 9.95792 10.02277 10.72477 10.73041 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 8.553E-07 7.796E-07 84.021 87.089 87.155 88.524 89.098 89.782 91.900 93.556 93.578 94.196 10.73323 11.12511 11.13356 11.30836 11.38166 11.46906 11.73971 11.95116 11.95398 12.03292 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 3 to ULNRC-06696 Page 196 of 456 94.460 94.549 94.747 95.829 95.851 96.976 97.506 97.771 98.279 98.455 12.06675 12.07803 12.10340 12.24154 12.24436 12.38815 12.45581 12.48964 12.55449 12.57704 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 197 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 135 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.360E-04 0.128 1.000 7.806E-05 0.383 3.000 6.086E-05 0.639 5.000 4.236E-05 1.277 10.000 3.308E-05 1.916 15.000 2.736E-05 2.555 20.000 2.346E-05 3.194 25.000 2.060E-05 3.832 30.000 1.684E-05 4.471 35.000 1.404E-05 5.110 40.000 1.196E-05 5.748 45.000 1.032E-05 6.387 50.000 9.006E-06 7.026 55.000 8.009E-06 7.665 60.000 7.052E-06 8.303 65.000 6.869E-05 0.5 3.91 ANNUAL AVERAGE = 1.34E-06 3 to ULNRC-06696 Page 198 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 136 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.418 0.929 1.105 1.884 2.287 2.690 3.388 4.185 4.776 5.770 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.35555 0.43913 0.50116 0.60547 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 6.630 6.872 7.248 7.275 7.490 8.403 8.405 8.996 11.495 17.836 0.69569 0.72106 0.76053 0.76335 0.78591 0.88176 0.88195 0.94397 1.20616 1.87152 1.824E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.283E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 18.347 21.651 21.732 22.619 23.022 23.049 23.452 25.520 25.709 33.984 1.92508 2.27185 2.28031 2.37335 2.41564 2.41846 2.46075 2.67783 2.69757 3.56591 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 35.086 46.129 52.765 55.076 58.918 64.829 66.576 66.602 72.514 72.540 3.68150 4.84022 5.53658 5.77904 6.18220 6.80244 6.98570 6.98852 7.60876 7.61158 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 72.567 77.592 77.753 81.326 81.649 86.566 86.996 89.038 90.945 91.859 7.61440 8.14160 8.15852 8.53348 8.56732 9.08325 9.12835 9.34262 9.54279 9.63864 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 3 to ULNRC-06696 Page 199 of 456 92.719 92.826 93.605 94.841 94.895 95.755 96.507 97.501 97.958 98.307 9.72886 9.74014 9.82190 9.95158 9.95722 10.04744 10.12638 10.23069 10.27862 10.31527 1.283E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 200 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 137 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.110E-04 0.105 1.000 6.346E-05 0.315 3.000 4.718E-05 0.525 5.000 2.983E-05 1.049 10.000 2.212E-05 1.574 15.000 1.773E-05 2.099 20.000 1.443E-05 2.623 25.000 1.196E-05 3.148 30.000 1.015E-05 3.673 35.000 8.777E-06 4.197 40.000 7.695E-06 4.722 45.000 6.891E-06 5.246 50.000 6.240E-06 5.771 55.000 4.855E-05 0.5 4.77 ANNUAL AVERAGE = 8.02E-07 3 to ULNRC-06696 Page 201 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 138 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.344 0.763 0.992 1.411 1.704 1.997 2.835 3.744 4.246 4.959 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19083 0.25199 0.28582 0.33375 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 5.503 5.587 6.131 6.508 8.142 8.144 8.898 11.662 16.605 17.065 0.37040 0.37604 0.41269 0.43807 0.54802 0.54814 0.59889 0.78496 1.11764 1.14865 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 19.704 19.788 20.710 20.961 21.422 23.809 24.144 33.150 34.113 43.705 1.32626 1.33190 1.39393 1.41084 1.44186 1.60255 1.62511 2.23125 2.29610 2.94171 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 48.019 50.533 52.501 59.329 59.999 68.208 73.947 73.989 77.046 77.717 3.23210 3.40126 3.53376 3.99331 4.03842 4.59100 4.97724 4.98006 5.18586 5.23097 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 79.727 79.895 83.078 85.466 87.644 88.733 88.816 89.319 90.408 90.618 5.36630 5.37758 5.59184 5.75254 5.89914 5.97244 5.97808 6.01191 6.08522 6.09931 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 202 of 456 92.754 94.597 95.518 96.146 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.47146 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 203 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 139 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.811E-05 0.067 1.000 5.510E-05 0.202 3.000 4.177E-05 0.337 5.000 2.726E-05 0.673 10.000 2.078E-05 1.010 15.000 1.645E-05 1.346 20.000 1.326E-05 1.683 25.000 1.106E-05 2.019 30.000 9.450E-06 2.356 35.000 8.221E-06 2.692 40.000 7.214E-06 3.029 45.000 6.316E-06 3.365 50.000 3.300E-05 0.5 7.43 ANNUAL AVERAGE = 4.90E-07 3 to ULNRC-06696 Page 204 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 140 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.368 0.718 0.980 1.881 2.182 2.532 3.083 4.531 5.382 6.033 0.02071 0.04045 0.05521 0.10596 0.12287 0.14261 0.17362 0.25517 0.30309 0.33975 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 6.383 6.483 7.284 7.585 8.986 8.989 10.091 13.795 19.852 20.703 0.35948 0.36512 0.41023 0.42714 0.50608 0.50625 0.56827 0.77690 1.11803 1.16596 1.666E-05 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 22.105 22.255 24.008 24.558 28.062 28.663 37.975 39.576 47.136 49.489 1.24490 1.25336 1.35203 1.38304 1.58039 1.61422 2.13861 2.22883 2.65454 2.78705 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 53.093 53.694 62.254 62.404 62.454 70.414 70.514 75.821 75.921 78.874 2.99004 3.02387 3.50596 3.51442 3.51724 3.96551 3.97115 4.26999 4.27563 4.44197 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 79.425 81.177 81.327 83.430 85.683 87.285 87.985 88.035 88.186 89.487 4.47298 4.57165 4.58011 4.69852 4.82539 4.91561 4.95508 4.95790 4.96635 5.03965 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 1.209E-07 9.669E-08 3 to ULNRC-06696 Page 205 of 456 91.740 93.042 93.092 93.893 94.293 94.794 94.844 94.894 96.796 98.548 5.16652 5.23982 5.24264 5.28775 5.31031 5.33850 5.34132 5.34414 5.45127 5.54995 8.057E-08 6.043E-08 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 206 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 141 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.084E-04 0.056 1.000 6.351E-05 0.169 3.000 4.737E-05 0.282 5.000 2.898E-05 0.563 10.000 2.189E-05 0.845 15.000 1.921E-05 1.126 20.000 1.489E-05 1.408 25.000 1.202E-05 1.690 30.000 9.984E-06 1.971 35.000 8.639E-06 2.253 40.000 7.795E-06 2.534 45.000 6.836E-06 2.816 50.000 5.826E-06 3.097 55.000 4.928E-06 3.379 60.000 4.214E-06 3.661 65.000 3.639E-06 3.942 70.000 3.070E-06 4.224 75.000 3.165E-05 0.5 8.88 ANNUAL AVERAGE = 4.68E-07 3 to ULNRC-06696 Page 207 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 142 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.477 1.160 1.580 2.490 2.944 3.248 3.930 6.451 8.119 8.422 0.01775 0.04313 0.05876 0.09259 0.10951 0.12078 0.14616 0.23993 0.30196 0.31324 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.498 9.863 10.393 12.516 12.519 13.808 16.082 18.963 20.934 21.389 0.31606 0.36680 0.38654 0.46548 0.46561 0.51353 0.59811 0.70525 0.77855 0.79546 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 21.616 24.800 24.952 26.089 32.078 32.684 42.690 44.207 50.650 53.076 0.80392 0.92233 0.92797 0.97026 1.19298 1.21554 1.58768 1.64407 1.88371 1.97392 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 56.715 57.018 65.963 66.342 66.418 72.937 73.089 77.865 77.940 80.442 2.10925 2.12053 2.45320 2.46730 2.47012 2.71258 2.71821 2.89583 2.89865 2.99169 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 81.124 83.323 83.626 85.824 87.795 87.871 88.856 89.615 89.690 90.069 3.01706 3.09882 3.11010 3.19185 3.26516 3.26798 3.30463 3.33282 3.33564 3.34973 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 3 to ULNRC-06696 Page 208 of 456 91.434 92.798 94.087 94.315 94.997 95.452 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.53299 3.54990 3.55554 3.62320 3.66549 3.70778 6.043E-08 100.000 3.71906 3 to ULNRC-06696 Page 209 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 143 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.216E-04 0.037 1.000 7.504E-05 0.112 3.000 5.829E-05 0.186 5.000 3.740E-05 0.372 10.000 2.540E-05 0.558 15.000 1.910E-05 0.744 20.000 1.540E-05 0.930 25.000 1.290E-05 1.116 30.000 1.106E-05 1.302 35.000 9.661E-06 1.488 40.000 8.529E-06 1.674 45.000 7.590E-06 1.860 50.000 6.550E-06 2.045 55.000 5.543E-06 2.231 60.000 4.684E-06 2.417 65.000 2.824E-05 0.5 13.44 ANNUAL AVERAGE = 3.74E-07 3 to ULNRC-06696 Page 210 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 144 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.274 0.599 0.899 1.494 1.764 2.521 2.900 4.699 6.105 6.430 0.01430 0.03122 0.04685 0.07786 0.09196 0.13143 0.15116 0.24494 0.31824 0.33516 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 6.538 7.241 7.674 8.701 8.704 10.110 11.949 13.842 14.762 15.086 0.34080 0.37745 0.40000 0.45357 0.45372 0.52702 0.62288 0.72155 0.76948 0.78640 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 15.194 17.412 17.466 18.115 21.414 21.793 31.636 33.475 41.642 44.455 0.79204 0.90763 0.91045 0.94428 1.11625 1.13599 1.64910 1.74495 2.17067 2.31727 6.231E-06 5.568E-06 5.197E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 50.079 51.107 51.161 60.464 60.680 67.603 67.657 74.310 74.418 79.177 2.61048 2.66404 2.66686 3.15178 3.16305 3.52392 3.52674 3.87351 3.87915 4.12725 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 79.989 83.829 84.207 86.316 88.155 89.075 89.724 89.778 90.048 91.076 4.16954 4.36971 4.38944 4.49940 4.59525 4.64318 4.67701 4.67983 4.69393 4.74749 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 211 of 456 92.428 93.780 94.267 94.646 94.916 94.970 96.484 98.053 99.351 99.946 4.81797 4.88846 4.91383 4.93356 4.94766 4.95048 5.02942 5.11118 5.17884 5.20985 3.937E-08 100.000 5.21267 3 to ULNRC-06696 Page 212 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 145 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.966E-05 0.052 1.000 6.272E-05 0.156 3.000 4.979E-05 0.261 5.000 2.741E-05 0.521 10.000 1.805E-05 0.782 15.000 1.393E-05 1.043 20.000 1.132E-05 1.303 25.000 9.513E-06 1.564 30.000 8.437E-06 1.824 35.000 7.695E-06 2.085 40.000 6.933E-06 2.346 45.000 6.241E-06 2.606 50.000 5.330E-06 2.867 55.000 4.601E-06 3.128 60.000 2.863E-05 0.5 9.59 ANNUAL AVERAGE = 4.16E-07 3 to ULNRC-06696 Page 213 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 146 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.541 0.759 1.192 2.195 3.023 3.328 4.374 6.675 8.331 8.942 0.03501 0.04911 0.07712 0.14196 0.19553 0.21526 0.28292 0.43175 0.53888 0.57835 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.072 10.075 10.598 13.257 13.260 14.829 17.662 19.580 21.193 21.498 0.58681 0.65165 0.68548 0.85746 0.85765 0.95914 1.14239 1.26644 1.37076 1.39049 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 24.157 24.506 28.603 29.126 36.449 38.192 41.287 42.725 47.433 47.825 1.56247 1.58502 1.85003 1.88387 2.35751 2.47028 2.67045 2.76348 3.06797 3.09334 4.541E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 58.940 69.140 76.724 81.344 82.172 84.831 84.875 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.26137 5.31493 5.48691 5.48973 5.61942 5.73501 5.79139 6.496E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 90.323 90.759 91.457 93.069 94.028 94.682 95.162 95.380 96.600 98.649 5.84214 5.87033 5.91544 6.01975 6.08178 6.12407 6.15508 6.16918 6.24812 6.38062 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 214 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 215 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 147 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.261E-04 0.065 1.000 7.611E-05 0.194 3.000 5.914E-05 0.323 5.000 3.878E-05 0.647 10.000 2.675E-05 0.970 15.000 1.956E-05 1.294 20.000 1.481E-05 1.617 25.000 1.170E-05 1.940 30.000 9.541E-06 2.264 35.000 7.953E-06 2.587 40.000 6.747E-06 2.911 45.000 5.808E-06 3.234 50.000 5.059E-06 3.557 55.000 4.451E-06 3.881 60.000 3.949E-06 4.204 65.000 3.518E-06 4.528 70.000 3.112E-06 4.851 75.000 4.720E-05 0.5 7.73 ANNUAL AVERAGE = 6.30E-07 3 to ULNRC-06696 Page 216 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 148 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.620 0.788 1.178 2.401 3.329 3.582 4.806 6.697 7.793 8.932 0.04142 0.05270 0.07875 0.16051 0.22254 0.23945 0.32121 0.44761 0.52091 0.59703 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.691 10.619 11.125 13.909 13.912 15.220 18.847 20.450 21.842 21.969 0.64778 0.70980 0.74363 0.92971 0.92991 1.01730 1.25976 1.36690 1.45993 1.46839 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 23.993 24.626 29.898 30.447 38.123 39.810 42.679 43.480 47.360 47.740 1.60372 1.64600 1.99842 2.03507 2.54818 2.66095 2.85266 2.90622 3.16560 3.19097 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 59.761 59.803 69.758 69.800 78.025 78.151 83.044 83.424 85.490 85.533 3.99447 3.99729 4.66264 4.66546 5.21522 5.22368 5.55071 5.57609 5.71423 5.71705 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 87.051 88.991 89.793 90.468 90.510 90.974 91.691 93.462 94.812 95.192 5.81855 5.94823 6.00180 6.04691 6.04973 6.08074 6.12867 6.24708 6.33729 6.36267 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 217 of 456 95.360 95.571 96.837 98.482 99.494 100.000 6.37394 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 218 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 149 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.314E-04 0.067 1.000 7.626E-05 0.201 3.000 5.811E-05 0.334 5.000 3.885E-05 0.668 10.000 2.818E-05 1.003 15.000 2.106E-05 1.337 20.000 1.586E-05 1.671 25.000 1.249E-05 2.005 30.000 1.016E-05 2.339 35.000 8.426E-06 2.674 40.000 7.085E-06 3.008 45.000 6.049E-06 3.342 50.000 5.229E-06 3.676 55.000 4.568E-06 4.010 60.000 4.027E-06 4.345 65.000 3.576E-06 4.679 70.000 3.191E-06 5.013 75.000 4.643E-05 0.5 7.48 ANNUAL AVERAGE = 6.53E-07 3 to ULNRC-06696 Page 219 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 150 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 0.932 1.140 1.783 2.298 2.684 3.970 5.257 6.501 7.745 0.03304 0.06123 0.07491 0.11720 0.15103 0.17640 0.26098 0.34559 0.42735 0.50911 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.174 8.345 8.645 9.546 9.548 10.106 12.207 15.681 16.582 16.796 0.53730 0.54858 0.56831 0.62752 0.62764 0.66429 0.80244 1.03080 1.09000 1.10410 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 16.925 18.726 18.898 22.629 22.972 31.893 33.137 37.168 38.112 41.586 1.11256 1.23097 1.24224 1.48752 1.51008 2.09649 2.17825 2.44326 2.50528 2.73365 5.568E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 41.886 53.766 53.809 68.305 68.348 77.055 77.098 82.544 82.630 86.018 2.75338 3.53432 3.53714 4.49006 4.49288 5.06519 5.06801 5.42606 5.43170 5.65442 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 86.404 87.948 89.707 91.422 92.537 92.795 93.224 95.239 96.912 97.384 5.67980 5.78129 5.89688 6.00965 6.08295 6.09987 6.12806 6.26057 6.37052 6.40153 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 220 of 456 97.427 97.984 98.027 98.499 99.228 99.528 100.000 6.40435 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 221 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 151 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.193E-04 0.066 1.000 6.899E-05 0.197 3.000 5.249E-05 0.329 5.000 3.206E-05 0.657 10.000 2.046E-05 0.986 15.000 1.501E-05 1.315 20.000 1.183E-05 1.643 25.000 9.676E-06 1.972 30.000 8.124E-06 2.301 35.000 6.955E-06 2.629 40.000 6.047E-06 2.958 45.000 5.323E-06 3.287 50.000 4.733E-06 3.615 55.000 4.244E-06 3.944 60.000 3.833E-06 4.273 65.000 3.464E-06 4.601 70.000 3.115E-06 4.930 75.000 4.146E-05 0.5 7.61 ANNUAL AVERAGE = 5.31E-07 3 to ULNRC-06696 Page 222 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 152 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 4023.0 METERS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
3.550E-04 2.367E-04 1.775E-04 1.540E-04 1.420E-04 1.183E-04 1.027E-04 8.875E-05 7.700E-05 6.681E-05 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 6.160E-05 5.916E-05 5.134E-05 4.454E-05 4.437E-05 3.850E-05 3.550E-05 3.341E-05 3.072E-05 2.673E-05 9.495 10.110 12.275 12.625 12.743 15.904 15.906 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 15.90640 16.99464 16.99746 17.92783 2.567E-05 2.227E-05 2.219E-05 2.048E-05 1.925E-05 1.775E-05 1.670E-05 1.540E-05 1.536E-05 1.283E-05 22.089 24.282 24.285 24.421 25.357 25.359 30.149 30.228 30.747 30.750 22.08909 24.28249 24.28531 24.42064 25.35664 25.35946 30.14942 30.22836 30.74711 30.74993 1.229E-05 1.114E-05 1.024E-05 9.626E-06 8.352E-06 7.700E-06 7.680E-06 6.681E-06 5.568E-06 5.197E-06 31.232 41.015 42.698 42.701 48.325 48.328 52.399 54.550 55.450 55.452 31.23202 41.01494 42.69805 42.70087 48.32534 48.32816 52.39920 54.55032 55.44967 55.45249 5.120E-06 4.176E-06 3.898E-06 3.840E-06 3.341E-06 3.118E-06 3.072E-06 2.599E-06 2.560E-06 1.949E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.581 84.669 85.134 66.17422 66.52383 66.53793 75.54835 75.57090 75.58500 81.49986 81.58162 84.66873 85.13391 1.920E-06 1.536E-06 1.299E-06 1.026E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 87.141 87.302 89.411 89.413 91.221 91.238 92.272 92.861 92.932 93.205 87.14124 87.30194 89.41076 89.41358 91.22075 91.23766 92.27234 92.86156 92.93204 93.20551 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 3 to ULNRC-06696 Page 223 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.245 97.482 97.496 97.513 94.13587 94.15842 95.51168 96.42796 96.44205 96.90723 97.24554 97.48236 97.49646 97.51337 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 3.937E-08 98.345 99.179 99.777 99.991 99.997 100.000 98.34506 99.17957 99.77725 99.99152 99.99715 99.99998 3 to ULNRC-06696 Page 224 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 153 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.675E-04 1.000 1.000 1.461E-04 3.000 3.000 1.038E-04 5.000 5.000 6.116E-05 10.000 10.000 4.117E-05 15.000 15.000 2.918E-05 20.000 20.000 2.180E-05 25.000 25.000 1.683E-05 30.000 30.000 1.386E-05 35.000 35.000 1.155E-05 40.000 40.000 9.853E-06 45.000 45.000 8.469E-06 50.000 50.000 7.279E-06 55.000 55.000 6.240E-06 60.000 60.000 5.321E-06 65.000 65.000 4.576E-06 70.000 70.000 3.910E-06 75.000 75.000 1.038E-04 5.0 5.00 3 to ULNRC-06696 Page 225 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 154 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.558 1.057 1.441 2.551 3.143 3.620 4.610 6.259 7.573 8.472 0.55822 1.05723 1.44065 2.55145 3.14350 3.61996 4.60953 6.25881 7.57260 8.47195 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.219E-05 9.087 9.205 10.228 10.231 10.581 12.746 12.749 13.837 16.997 17.000 9.08655 9.20496 10.22836 10.23118 10.58077 12.74598 12.74880 13.83704 16.99746 17.00028 1.937E-05 1.824E-05 1.775E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.283E-05 1.246E-05 1.140E-05 21.162 22.092 22.095 23.031 23.166 25.359 25.438 25.441 25.960 30.750 21.16154 22.09190 22.09472 23.03072 23.16603 25.35944 25.43838 25.44120 25.95995 30.74991 9.969E-06 9.626E-06 9.035E-06 8.308E-06 7.700E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 5.197E-06 31.232 31.235 41.018 42.701 42.704 48.328 50.479 54.550 55.450 55.452 31.23201 31.23483 41.01775 42.70085 42.70367 48.32814 50.47926 54.55030 55.44965 55.45247 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.582 84.669 85.134 66.17419 66.52380 66.53792 75.54835 75.57092 75.58502 81.49989 81.58167 84.66878 85.13396 1.920E-06 1.536E-06 1.299E-06 1.026E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 87.141 87.302 89.411 89.414 91.221 91.238 92.272 92.862 92.932 93.206 87.14131 87.30202 89.41084 89.41366 91.22083 91.23776 92.27245 92.86166 92.93217 93.20565 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 3 to ULNRC-06696 Page 226 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.246 97.482 97.497 97.513 94.13601 94.15857 95.51183 96.42812 96.44222 96.90741 97.24574 97.48257 97.49668 97.51360 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 3.937E-08 98.345 99.180 99.777 99.992 99.997 100.000 98.34529 99.17982 99.77751 99.99179 99.99744 100.00026 3 to ULNRC-06696 Page 227 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 155 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00026 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.283E-04 1.000 1.000 7.634E-05 3.000 3.000 5.798E-05 5.000 5.000 3.694E-05 10.000 10.000 2.657E-05 15.000 15.000 2.046E-05 20.000 20.000 1.551E-05 25.000 25.000 1.288E-05 30.000 30.000 1.091E-05 35.000 35.000 9.322E-06 40.000 40.000 8.148E-06 45.000 45.000 7.176E-06 50.000 50.000 6.331E-06 55.000 55.000 5.574E-06 60.000 60.000 4.885E-06 65.000 65.000 4.251E-06 70.000 70.000 3.659E-06 75.000 75.000 3.140E-06 80.000 80.000 5.798E-05 5.0 5.00 3 to ULNRC-06696 Page 228 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 156 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 10:59:55 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RB COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE BOUNDARY (LPZ)
BUILDING WAKE CREDIT IS NOT INCLUDED.
RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX LPZ AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 4023. 4.22E-05 2.05E-05 1.43E-05 6.52E-06 2.12E-06 5.34E-07 21.3 S SSW 4023. 4.52E-05 2.15E-05 1.49E-05 6.65E-06 2.10E-06 5.11E-07 321.2 SSW SW 4023. 4.61E-05 2.19E-05 1.51E-05 6.70E-06 2.10E-06 5.05E-07 21.9 SW WSW 4023. 3.50E-05 1.68E-05 1.17E-05 5.28E-06 1.69E-06 4.20E-07 15.5 WSW W 4023. 3.31E-05 1.60E-05 1.11E-05 5.04E-06 1.62E-06 4.04E-07 14.1 W WNW 4023. 3.96E-05 1.93E-05 1.35E-05 6.18E-06 2.01E-06 5.12E-07 16.4 WNW NW 4023. 6.21E-05 3.21E-05 2.31E-05 1.13E-05 4.04E-06 1.15E-06 35.9 NW NNW 4023. 6.87E-05 3.58E-05 2.59E-05 1.28E-05 4.62E-06 1.34E-06 43.7 NNW N 4023. 4.86E-05 2.46E-05 1.75E-05 8.41E-06 2.92E-06 8.02E-07 23.9 N NNE 4023. 3.30E-05 1.65E-05 1.16E-05 5.46E-06 1.85E-06 4.90E-07 11.8 NNE NE 4023. 3.17E-05 1.58E-05 1.11E-05 5.23E-06 1.77E-06 4.68E-07 12.8 NE ENE 4023. 2.82E-05 1.38E-05 9.66E-06 4.45E-06 1.46E-06 3.74E-07 11.7 ENE E 4023. 2.86E-05 1.42E-05 1.00E-05 4.69E-06 1.58E-06 4.16E-07 11.1 E ESE 4023. 4.72E-05 2.31E-05 1.62E-05 7.46E-06 2.45E-06 6.30E-07 21.0 ESE SE 4023. 4.64E-05 2.29E-05 1.61E-05 7.51E-06 2.50E-06 6.53E-07 21.4 SE SSE 4023. 4.15E-05 2.02E-05 1.41E-05 6.44E-06 2.10E-06 5.31E-07 17.4 SSE MAX X/Q 6.87E-05 3.58E-05 2.59E-05 1.28E-05 4.62E-06 TOTAL HOURS: 621.2 SRP 2.3.4 4023. 1.04E-04 5.05E-05 3.53E-05 1.62E-05 5.26E-06 1.34E-06 SITE LIMIT 5.80E-05 3.11E-05 2.28E-05 1.16E-05 4.38E-06 1.34E-06 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 229 of 456 END OF PAVAN CARD INPUT.
PAVAN-NAI VERSION- 3.0 EXECUTION TERMINATED.
3 to ULNRC-06696 Page 230 of 456 PAVAN Case: clwAST_PAVAN_RWST.out NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 1 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 ENHANCED PRINTOUT OF INPUT CARDS KOPT 1 2 3 4 5 6 7 8 9 10 11 12 1 0 1 0 0 0 0 0 1 0 1 0 0 KOPT(1) = 0 ; X/Q Without Desert Sigmas KOPT(2) = 1 ; Evaluate X/Q with & w/o Bldg Wake KOPT(3) = 0 ; Skip print of Upper Envelope Edit KOPT(4) = 0 ; Skip print of Upper Envelope Pts KOPT(5) Not used.
KOPT(6) = 0 ; JFD Input: Units = Hours KOPT(7) = 0 ; Skip print of X/Q calc details KOPT(8) = 1 ; Input calms distributed into Bin 1 Card Type 8 values contain Calms JFD input array starts with Bin 2 KOPT(9) = 0 ; No Input Terrain Adj. - Card 12 KOPT(10)= 1 ; Use Card 12 Terrain Adj if input; if no user input, use default.
- End of ORNL/RSICC PAVAN Options ******
KOPT(11)= 0 ; Number of Boundaries- Default = 0 KOPT(12)= 0 ; Read JFD on Card Type=9 - Default l* PLANT NAME *ll* PERIOD OF DATA *ll* TYPE OF RELEASE*l 2 Callaway AST 2013-2016 METD Ground Level Release l* HGT-WIND SENSOR*ll** HGTS DELTA-T **l 3 10.0 Meters Delta-T from 10-60m l** REFERENCE FOR METEOROLOGICAL DATA **l 4 Meteorological Data JFD data from METD MJFREQ module - RWST l** Special Comments: NONE, if None. **l 5 JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph Specify Wind Bins & Ter. Dist. & Receptor Names 6 13 0 SB LPZ # Hours Counted In FREQ Array: 35470 Cont Cont RlseHgt Wind Meas Area Height10=Grnd Height 7 171.00 16.20 10.00 10.00 Internal Constant for Building Wake Term Calc: 0.500 3 to ULNRC-06696 Page 231 of 456 ENHANCED PRINTOUT OF INPUT CARDS - CONTINUED ON NEXT PAGE 3 to ULNRC-06696 Page 232 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 2 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 Calms measured in each of 7 Stability Classes, 8 0.0 0.0 0.0 1.0 585.0 136.0 198.0 KOPT(8) = 1. Card 8 calms distributed into Bin 1.
Stability Class: A 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 6 0.0 1.0 1.0 2.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 9 7 0.0 3.0 3.0 3.0 1.0 1.0 14.0 23.0 17.0 15.0 8.0 9.0 7.0 11.0 4.0 1.0 9 8 4.0 4.0 6.0 2.0 8.0 4.0 47.0 29.0 10.0 22.0 38.0 24.0 28.0 28.0 30.0 11.0 9 9 3.0 12.0 2.0 3.0 2.0 3.0 26.0 21.0 22.0 20.0 35.0 15.0 29.0 47.0 39.0 17.0 9 10 6.0 4.0 5.0 1.0 0.0 7.0 10.0 16.0 12.0 28.0 24.0 15.0 24.0 29.0 24.0 7.0 9 11 1.0 2.0 1.0 0.0 0.0 0.0 0.0 3.0 13.0 11.0 5.0 4.0 11.0 2.0 12.0 11.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: B 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 3 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 4 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 5 2.0 1.0 1.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 9 6 2.0 1.0 2.0 2.0 1.0 1.0 2.0 4.0 4.0 2.0 1.0 1.0 1.0 0.0 1.0 0.0 9 7 10.0 13.0 16.0 11.0 4.0 13.0 36.0 49.0 46.0 26.0 26.0 18.0 19.0 16.0 17.0 10.0 9 8 21.0 15.0 21.0 16.0 9.0 11.0 39.0 51.0 32.0 51.0 45.0 18.0 25.0 37.0 42.0 47.0 9 9 17.0 7.0 5.0 10.0 8.0 7.0 14.0 24.0 28.0 44.0 26.0 17.0 25.0 22.0 32.0 39.0 9 10 15.0 8.0 2.0 2.0 0.0 2.0 2.0 12.0 37.0 22.0 16.0 3.0 9.0 15.0 9.0 11.0 9 11 1.0 4.0 0.0 1.0 1.0 0.0 1.0 8.0 13.0 11.0 10.0 6.0 5.0 5.0 5.0 13.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 5.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: C 9 2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 9 3 1.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 1.0 1.0 0.0 0.0 0.0 0.0 9 4 0.0 1.0 0.0 0.0 0.0 0.0 0.0 1.0 1.0 0.0 2.0 0.0 0.0 0.0 0.0 0.0 9 5 0.0 2.0 0.0 1.0 1.0 1.0 5.0 3.0 6.0 1.0 2.0 1.0 2.0 0.0 3.0 1.0 9 6 6.0 4.0 9.0 7.0 8.0 5.0 7.0 26.0 12.0 16.0 11.0 9.0 15.0 19.0 9.0 2.0 9 7 30.0 30.0 35.0 29.0 23.0 26.0 99.0 96.0 76.0 76.0 42.0 29.0 39.0 46.0 36.0 36.0 9 8 25.0 37.0 17.0 23.0 16.0 21.0 66.0 75.0 71.0 57.0 45.0 26.0 34.0 41.0 46.0 41.0 9 9 34.0 16.0 8.0 11.0 7.0 17.0 19.0 28.0 34.0 52.0 32.0 13.0 17.0 20.0 19.0 40.0 9 10 17.0 11.0 2.0 2.0 2.0 6.0 3.0 12.0 32.0 26.0 14.0 10.0 12.0 18.0 16.0 26.0 9 11 5.0 0.0 0.0 1.0 1.0 0.0 0.0 9.0 29.0 12.0 3.0 5.0 5.0 10.0 11.0 6.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 2.0 5.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 Stability Class: D 9 2 3.0 4.0 4.0 5.0 2.0 3.0 1.0 0.0 3.0 2.0 3.0 3.0 2.0 7.0 3.0 3.0 9 3 19.0 6.0 8.0 13.0 8.0 8.0 20.0 11.0 15.0 11.0 11.0 15.0 12.0 8.0 15.0 4.0 3 to ULNRC-06696 Page 233 of 456 9 4 11.0 9.0 18.0 6.0 7.0 12.0 20.0 13.0 7.0 8.0 12.0 8.0 7.0 12.0 13.0 8.0 9 5 26.0 33.0 36.0 42.0 43.0 50.0 68.0 40.0 41.0 23.0 32.0 20.0 34.0 40.0 40.0 29.0 9 6 73.0 87.0 61.0 81.0 70.0 105.0 170.0 146.0 86.0 60.0 72.0 48.0 104.0 108.0 92.0 81.0 9 7 203.0 212.0 208.0 213.0 209.0 282.0 471.0 344.0 220.0 163.0 171.0 118.0 172.0 255.0 285.0 277.0 9 8 291.0 201.0 155.0 135.0 139.0 175.0 254.0 249.0 220.0 196.0 159.0 86.0 128.0 234.0 236.0 338.0 9 9 283.0 138.0 74.0 49.0 60.0 94.0 73.0 139.0 187.0 137.0 106.0 63.0 123.0 174.0 195.0 203.0 9 10 156.0 55.0 24.0 17.0 19.0 16.0 11.0 62.0 133.0 73.0 59.0 33.0 88.0 106.0 116.0 127.0 9 11 66.0 20.0 22.0 9.0 4.0 4.0 1.0 31.0 183.0 48.0 35.0 29.0 71.0 61.0 49.0 79.0 9 12 5.0 0.0 7.0 0.0 0.0 0.0 0.0 0.0 16.0 4.0 3.0 4.0 7.0 1.0 1.0 9.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 2.0 1.0 0.0 0.0 1.0 3 to ULNRC-06696 Page 234 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 3 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 Stability Class: E 9 2 6.0 2.0 8.0 6.0 9.0 8.0 10.0 6.0 8.0 9.0 6.0 7.0 8.0 12.0 12.0 7.0 9 3 23.0 22.0 17.0 20.0 25.0 22.0 39.0 33.0 22.0 18.0 22.0 17.0 26.0 36.0 31.0 13.0 9 4 12.0 15.0 16.0 15.0 12.0 18.0 43.0 18.0 19.0 11.0 17.0 26.0 17.0 37.0 33.0 21.0 9 5 28.0 45.0 40.0 41.0 39.0 59.0 149.0 53.0 33.0 22.0 35.0 42.0 41.0 61.0 48.0 42.0 9 6 92.0 68.0 80.0 81.0 94.0 127.0 327.0 180.0 77.0 57.0 70.0 79.0 61.0 94.0 125.0 87.0 9 7 158.0 125.0 118.0 93.0 132.0 167.0 464.0 632.0 308.0 215.0 186.0 132.0 182.0 168.0 182.0 208.0 9 8 72.0 34.0 24.0 27.0 47.0 65.0 136.0 330.0 411.0 229.0 151.0 85.0 151.0 71.0 68.0 94.0 9 9 11.0 6.0 7.0 3.0 8.0 14.0 26.0 133.0 247.0 103.0 47.0 32.0 52.0 33.0 19.0 22.0 9 10 1.0 1.0 3.0 0.0 0.0 7.0 5.0 52.0 143.0 47.0 12.0 4.0 19.0 9.0 9.0 7.0 9 11 1.0 0.0 3.0 0.0 0.0 0.0 2.0 23.0 65.0 16.0 3.0 5.0 4.0 0.0 1.0 1.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2.0 1.0 0.0 0.0 2.0 1.0 0.0 1.0 1.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: F 9 2 7.0 6.0 9.0 13.0 10.0 16.0 23.0 16.0 15.0 7.0 7.0 4.0 14.0 7.0 6.0 9.0 9 3 22.0 27.0 31.0 23.0 29.0 37.0 68.0 37.0 22.0 12.0 17.0 22.0 26.0 38.0 26.0 29.0 9 4 24.0 17.0 22.0 22.0 24.0 24.0 72.0 35.0 14.0 13.0 16.0 18.0 13.0 23.0 22.0 4.0 9 5 24.0 31.0 48.0 48.0 39.0 53.0 140.0 89.0 34.0 39.0 28.0 28.0 19.0 61.0 66.0 21.0 9 6 58.0 39.0 37.0 40.0 28.0 46.0 147.0 229.0 93.0 66.0 74.0 30.0 34.0 65.0 86.0 49.0 9 7 33.0 25.0 19.0 18.0 12.0 15.0 93.0 550.0 236.0 118.0 121.0 38.0 35.0 44.0 38.0 81.0 9 8 2.0 1.0 0.0 0.0 1.0 0.0 1.0 96.0 123.0 63.0 28.0 6.0 6.0 0.0 0.0 5.0 9 9 0.0 0.0 0.0 0.0 0.0 0.0 2.0 2.0 15.0 6.0 0.0 2.0 1.0 0.0 0.0 0.0 9 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 11 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Stability Class: G 9 2 11.0 15.0 9.0 11.0 10.0 13.0 20.0 18.0 19.0 10.0 7.0 9.0 6.0 5.0 4.0 10.0 9 3 34.0 32.0 31.0 18.0 16.0 15.0 41.0 60.0 29.0 10.0 18.0 12.0 11.0 23.0 29.0 15.0 9 4 14.0 19.0 15.0 9.0 5.0 7.0 12.0 37.0 15.0 7.0 6.0 6.0 5.0 19.0 22.0 12.0 9 5 25.0 25.0 34.0 9.0 7.0 8.0 27.0 60.0 26.0 20.0 11.0 9.0 7.0 24.0 29.0 30.0 9 6 26.0 23.0 15.0 6.0 2.0 2.0 19.0 79.0 37.0 17.0 13.0 4.0 6.0 14.0 27.0 29.0 9 7 5.0 3.0 1.0 0.0 0.0 0.0 6.0 117.0 32.0 13.0 7.0 1.0 2.0 3.0 18.0 10.0 9 8 0.0 0.0 0.0 0.0 1.0 0.0 0.0 28.0 9.0 2.0 2.0 0.0 0.0 0.0 0.0 0.0 9 9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 11 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 12 0.0 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 9 13 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Wind Bin Definitions: MPS - No Corrections Calm Bin 2 Bin 3 Bin 4 Bin 5 Bin 6 Bin 7 Bin 8 Bin 9 Bin10 Bin11 Bin12 Bin13 Bin14 10 -1. 0.50 0.75 1.00 1.25 1.50 2.00 3.00 4.00 5.00 6.00 8.00 10.00 99.00 0.00 Site Exclusion Boundary (SB) Downwind Distances (METERS) by Sector at which X/Q Estimates will be made.
3 to ULNRC-06696 Page 235 of 456 11 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200.
Low Population Zone (LPZ) Downwind Distances (METERS) by Sector at which X/Q Estimates will be made.
11 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023.
END OF ENHANCED INPUT ECHO - BEGIN PAVAN OUTPUT 3 to ULNRC-06696 Page 236 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 4 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS A WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.00 1.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.25 1.25 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.50 1.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.00 2.00 0.000 0.003 0.003 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.014 3.00 3.00 0.000 0.008 0.008 0.008 0.003 0.003 0.039 0.065 0.048 0.042 0.023 0.025 0.020 0.031 0.011 0.003 0.338 4.00 4.00 0.011 0.011 0.017 0.006 0.023 0.011 0.133 0.082 0.028 0.062 0.107 0.068 0.079 0.079 0.085 0.031 0.832 5.00 5.00 0.008 0.034 0.006 0.008 0.006 0.008 0.073 0.059 0.062 0.056 0.099 0.042 0.082 0.133 0.110 0.048 0.835 6.00 6.00 0.017 0.011 0.014 0.003 0.000 0.020 0.028 0.045 0.034 0.079 0.068 0.042 0.068 0.082 0.068 0.020 0.598 8.00 8.00 0.003 0.006 0.003 0.000 0.000 0.000 0.000 0.008 0.037 0.031 0.014 0.011 0.031 0.006 0.034 0.031 0.214 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.04 0.07 0.05 0.03 0.03 0.04 0.27 0.26 0.21 0.27 0.31 0.19 0.28 0.33 0.31 0.13 2.84 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS B WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.00 1.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.25 1.25 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 1.50 1.50 0.006 0.003 0.003 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.017 2.00 2.00 0.006 0.003 0.006 0.006 0.003 0.003 0.006 0.011 0.011 0.006 0.003 0.003 0.003 0.000 0.003 0.000 0.070 3.00 3.00 0.028 0.037 0.045 0.031 0.011 0.037 0.101 0.138 0.130 0.073 0.073 0.051 0.054 0.045 0.048 0.028 0.930 4.00 4.00 0.059 0.042 0.059 0.045 0.025 0.031 0.110 0.144 0.090 0.144 0.127 0.051 0.070 0.104 0.118 0.133 1.353 5.00 5.00 0.048 0.020 0.014 0.028 0.023 0.020 0.039 0.068 0.079 0.124 0.073 0.048 0.070 0.062 0.090 0.110 0.916 6.00 6.00 0.042 0.023 0.006 0.006 0.000 0.006 0.006 0.034 0.104 0.062 0.045 0.008 0.025 0.042 0.025 0.031 0.465 8.00 8.00 0.003 0.011 0.000 0.003 0.003 0.000 0.003 0.023 0.037 0.031 0.028 0.017 0.014 0.014 0.014 0.037 0.237 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.014 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.017 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.19 0.14 0.13 0.12 0.06 0.10 0.27 0.42 0.47 0.44 0.35 0.18 0.24 0.27 0.30 0.34 4.01 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS C 3 to ULNRC-06696 Page 237 of 456 WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.75 0.75 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 1.00 1.00 0.003 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.003 0.003 0.000 0.000 0.000 0.000 0.014 1.25 1.25 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.003 0.003 0.000 0.006 0.000 0.000 0.000 0.000 0.000 0.014 1.50 1.50 0.000 0.006 0.000 0.003 0.003 0.003 0.014 0.008 0.017 0.003 0.006 0.003 0.006 0.000 0.008 0.003 0.082 2.00 2.00 0.017 0.011 0.025 0.020 0.023 0.014 0.020 0.073 0.034 0.045 0.031 0.025 0.042 0.054 0.025 0.006 0.465 3.00 3.00 0.085 0.085 0.099 0.082 0.065 0.073 0.279 0.271 0.214 0.214 0.118 0.082 0.110 0.130 0.101 0.101 2.109 4.00 4.00 0.070 0.104 0.048 0.065 0.045 0.059 0.186 0.211 0.200 0.161 0.127 0.073 0.096 0.116 0.130 0.116 1.807 5.00 5.00 0.096 0.045 0.023 0.031 0.020 0.048 0.054 0.079 0.096 0.147 0.090 0.037 0.048 0.056 0.054 0.113 1.035 6.00 6.00 0.048 0.031 0.006 0.006 0.006 0.017 0.008 0.034 0.090 0.073 0.039 0.028 0.034 0.051 0.045 0.073 0.589 8.00 8.00 0.014 0.000 0.000 0.003 0.003 0.000 0.000 0.025 0.082 0.034 0.008 0.014 0.014 0.028 0.031 0.017 0.273 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.006 0.014 0.000 0.000 0.000 0.000 0.000 0.000 0.023 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.003 TOTAL 0.33 0.28 0.20 0.21 0.16 0.21 0.56 0.71 0.74 0.69 0.43 0.27 0.36 0.43 0.39 0.43 6.42 3 to ULNRC-06696 Page 238 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 5 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS D WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.75 0.75 0.008 0.011 0.011 0.014 0.006 0.008 0.003 0.000 0.008 0.006 0.008 0.008 0.006 0.020 0.008 0.008 0.135 1.00 1.00 0.054 0.017 0.023 0.037 0.023 0.023 0.056 0.031 0.042 0.031 0.031 0.042 0.034 0.023 0.042 0.011 0.519 1.25 1.25 0.031 0.025 0.051 0.017 0.020 0.034 0.056 0.037 0.020 0.023 0.034 0.023 0.020 0.034 0.037 0.023 0.482 1.50 1.50 0.073 0.093 0.101 0.118 0.121 0.141 0.192 0.113 0.116 0.065 0.090 0.056 0.096 0.113 0.113 0.082 1.683 2.00 2.00 0.206 0.245 0.172 0.228 0.197 0.296 0.479 0.412 0.242 0.169 0.203 0.135 0.293 0.304 0.259 0.228 4.071 3.00 3.00 0.572 0.598 0.586 0.601 0.589 0.795 1.328 0.970 0.620 0.460 0.482 0.333 0.485 0.719 0.803 0.781 10.722 4.00 4.00 0.820 0.567 0.437 0.381 0.392 0.493 0.716 0.702 0.620 0.553 0.448 0.242 0.361 0.660 0.665 0.953 9.010 5.00 5.00 0.798 0.389 0.209 0.138 0.169 0.265 0.206 0.392 0.527 0.386 0.299 0.178 0.347 0.491 0.550 0.572 5.915 6.00 6.00 0.440 0.155 0.068 0.048 0.054 0.045 0.031 0.175 0.375 0.206 0.166 0.093 0.248 0.299 0.327 0.358 3.087 8.00 8.00 0.186 0.056 0.062 0.025 0.011 0.011 0.003 0.087 0.516 0.135 0.099 0.082 0.200 0.172 0.138 0.223 2.007 10.00 10.00 0.014 0.000 0.020 0.000 0.000 0.000 0.000 0.000 0.045 0.011 0.008 0.011 0.020 0.003 0.003 0.025 0.161 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.006 0.003 0.000 0.000 0.003 0.014 TOTAL 3.20 2.16 1.74 1.61 1.58 2.11 3.07 2.92 3.13 2.04 1.87 1.21 2.11 2.84 2.95 3.27 37.81 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS E WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.070 0.086 0.083 0.084 0.087 0.109 0.246 0.112 0.084 0.061 0.082 0.094 0.094 0.149 0.126 0.085 1.649 0.75 0.75 0.017 0.006 0.023 0.017 0.025 0.023 0.028 0.017 0.023 0.025 0.017 0.020 0.023 0.034 0.034 0.020 0.350 1.00 1.00 0.065 0.062 0.048 0.056 0.070 0.062 0.110 0.093 0.062 0.051 0.062 0.048 0.073 0.101 0.087 0.037 1.088 1.25 1.25 0.034 0.042 0.045 0.042 0.034 0.051 0.121 0.051 0.054 0.031 0.048 0.073 0.048 0.104 0.093 0.059 0.930 1.50 1.50 0.079 0.127 0.113 0.116 0.110 0.166 0.420 0.149 0.093 0.062 0.099 0.118 0.116 0.172 0.135 0.118 2.193 2.00 2.00 0.259 0.192 0.226 0.228 0.265 0.358 0.922 0.507 0.217 0.161 0.197 0.223 0.172 0.265 0.352 0.245 4.790 3.00 3.00 0.445 0.352 0.333 0.262 0.372 0.471 1.308 1.782 0.868 0.606 0.524 0.372 0.513 0.474 0.513 0.586 9.783 4.00 4.00 0.203 0.096 0.068 0.076 0.133 0.183 0.383 0.930 1.159 0.646 0.426 0.240 0.426 0.200 0.192 0.265 5.624 5.00 5.00 0.031 0.017 0.020 0.008 0.023 0.039 0.073 0.375 0.696 0.290 0.133 0.090 0.147 0.093 0.054 0.062 2.151 6.00 6.00 0.003 0.003 0.008 0.000 0.000 0.020 0.014 0.147 0.403 0.133 0.034 0.011 0.054 0.025 0.025 0.020 0.899 8.00 8.00 0.003 0.000 0.008 0.000 0.000 0.000 0.006 0.065 0.183 0.045 0.008 0.014 0.011 0.000 0.003 0.003 0.350 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.003 0.000 0.000 0.006 0.003 0.000 0.003 0.003 0.023 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.21 0.98 0.97 0.89 1.12 1.48 3.63 4.23 3.84 2.11 1.63 1.31 1.68 1.62 1.62 1.50 29.83 JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS F 3 to ULNRC-06696 Page 239 of 456 WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.017 0.018 0.024 0.023 0.022 0.028 0.066 0.038 0.018 0.015 0.015 0.016 0.016 0.028 0.026 0.014 0.383 0.75 0.75 0.020 0.017 0.025 0.037 0.028 0.045 0.065 0.045 0.042 0.020 0.020 0.011 0.039 0.020 0.017 0.025 0.476 1.00 1.00 0.062 0.076 0.087 0.065 0.082 0.104 0.192 0.104 0.062 0.034 0.048 0.062 0.073 0.107 0.073 0.082 1.314 1.25 1.25 0.068 0.048 0.062 0.062 0.068 0.068 0.203 0.099 0.039 0.037 0.045 0.051 0.037 0.065 0.062 0.011 1.023 1.50 1.50 0.068 0.087 0.135 0.135 0.110 0.149 0.395 0.251 0.096 0.110 0.079 0.079 0.054 0.172 0.186 0.059 2.165 2.00 2.00 0.164 0.110 0.104 0.113 0.079 0.130 0.414 0.646 0.262 0.186 0.209 0.085 0.096 0.183 0.242 0.138 3.160 3.00 3.00 0.093 0.070 0.054 0.051 0.034 0.042 0.262 1.551 0.665 0.333 0.341 0.107 0.099 0.124 0.107 0.228 4.161 4.00 4.00 0.006 0.003 0.000 0.000 0.003 0.000 0.003 0.271 0.347 0.178 0.079 0.017 0.017 0.000 0.000 0.014 0.936 5.00 5.00 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.006 0.042 0.017 0.000 0.006 0.003 0.000 0.000 0.000 0.079 6.00 6.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 8.00 8.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.50 0.43 0.49 0.49 0.43 0.57 1.61 3.02 1.58 0.93 0.84 0.43 0.43 0.70 0.71 0.57 13.71 3 to ULNRC-06696 Page 240 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 6 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION ATMOSPHERIC STABILITY CLASS G WIND SPEED (M/S)
TOWER RELEASE N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW TOTAL 0.50 0.50 0.041 0.045 0.044 0.023 0.019 0.021 0.049 0.086 0.044 0.023 0.021 0.018 0.014 0.035 0.041 0.033 0.558 0.75 0.75 0.031 0.042 0.025 0.031 0.028 0.037 0.056 0.051 0.054 0.028 0.020 0.025 0.017 0.014 0.011 0.028 0.499 1.00 1.00 0.096 0.090 0.087 0.051 0.045 0.042 0.116 0.169 0.082 0.028 0.051 0.034 0.031 0.065 0.082 0.042 1.111 1.25 1.25 0.039 0.054 0.042 0.025 0.014 0.020 0.034 0.104 0.042 0.020 0.017 0.017 0.014 0.054 0.062 0.034 0.592 1.50 1.50 0.070 0.070 0.096 0.025 0.020 0.023 0.076 0.169 0.073 0.056 0.031 0.025 0.020 0.068 0.082 0.085 0.990 2.00 2.00 0.073 0.065 0.042 0.017 0.006 0.006 0.054 0.223 0.104 0.048 0.037 0.011 0.017 0.039 0.076 0.082 0.899 3.00 3.00 0.014 0.008 0.003 0.000 0.000 0.000 0.017 0.330 0.090 0.037 0.020 0.003 0.006 0.008 0.051 0.028 0.615 4.00 4.00 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.079 0.025 0.006 0.006 0.000 0.000 0.000 0.000 0.000 0.118 5.00 5.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 6.00 6.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 8.00 8.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 10.00 10.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 99.00 99.00 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.37 0.37 0.34 0.17 0.13 0.15 0.40 1.22 0.52 0.25 0.20 0.13 0.12 0.28 0.41 0.33 5.39 WIND MEASURED AT 10.0 METERS.
WIND SPEED CORRECTED TO THE RELEASE HEIGHT OF 10.0 METERS.
OVERALL WIND DIRECTION FREQUENCY WIND DIRECTION: N NNE NE ENE E ESE SE SSE S SSW SW WSW W WNW NW NNW FREQUENCY: 5.8 4.4 3.9 3.5 3.5 4.7 9.8 12.8 10.5 6.7 5.6 3.7 5.2 6.5 6.7 6.6 OVERALL WIND SPEED FREQUENCY AS MEASURED ON THE TOWER:
MAX.WIND SPEED (M/S): 0.50 0.75 1.00 1.25 1.50 2.00 3.00 4.00 5.00 6.00 8.00 10.00 99.00 WIND SPEED FREQUENCY: 2.59 1.46 4.05 3.04 7.13 13.47 28.66 19.68 10.93 5.64 3.09 0.23 0.02 BUILDING AND RELEASE CHARACTERISTICS:
RELEASE HEIGHT: 10.00 METERS MIXING VOLUME COEFFICIENT: 0.50 BUILDING CROSS-SECTIONAL AREA: 171.00 SQUARE METERS BOUNDARY DISTANCES (METERS) FROM THE SOURCE FOR EACH DOWNWIND SECTOR:
DOWNWIND SECTOR S SSW SW WSW W WNW NW NNW N NNE NE ENE E ESE SE SSE SB BOUNDARY 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200. 1200.
3 to ULNRC-06696 Page 241 of 456 LPZ BOUNDARY 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023. 4023.
3 to ULNRC-06696 Page 242 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 7 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph WINDSPEEDS ADJUSTED TO 10.0 METERS.
PERCENT OF THE TIME A GIVEN WINDSPEED IS LOWER:
WINDSPEED CUMULATIVE FREQUENCY (METER/SEC) (PERCENT) 0.50 2.59 0.75 4.06 1.00 8.10 1.25 11.15 1.50 18.28 2.00 31.75 3.00 60.41 4.00 80.09 5.00 91.02 6.00 96.66 8.00 99.75 10.00 99.98 99.00 100.00 ERROR IN NORMAL TRANSFORMATION FOR A( 13)= 100.00002 3 to ULNRC-06696 Page 243 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 8 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOG-NORMAL INTERPOLATION PERCENTILES WINDSPEED CUMULATIVE FREQUENCY (METER/SEC) (PERCENT) 0.23 1.00 0.57 3.00 0.81 5.00 1.16 10.00 1.39 15.00 1.56 20.00 1.75 25.00 1.93 30.00 2.10 35.00 2.26 40.00 2.42 45.00 2.60 50.00 2.78 55.00 2.98 60.00 3.19 65.00 3.41 70.00 3.68 75.00 3.99 80.00 4.45 85.00 4.87 90.00 3 to ULNRC-06696 Page 244 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 9 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.710 1.241 1.527 3.169 3.507 4.183 5.388 6.596 7.658 7.900 0.04142 0.07243 0.08915 0.18501 0.20474 0.24421 0.31455 0.38503 0.44705 0.46115 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 9.059 9.061 9.351 10.607 11.766 12.877 13.022 13.118 14.712 17.513 0.52881 0.52898 0.54589 0.61920 0.68686 0.75170 0.76016 0.76580 0.85884 1.02235 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.488E-05 18.093 19.010 20.362 20.894 25.337 32.967 34.223 37.700 38.231 38.280 1.05619 1.10975 1.18869 1.21970 1.47908 1.92452 1.99783 2.20081 2.23183 2.23465 3.370E-05 2.949E-05 2.527E-05 2.412E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 38.328 41.853 41.902 51.706 65.759 79.427 79.716 87.250 90.438 91.887 2.23747 2.44327 2.44609 3.01841 3.83882 4.63668 4.65359 5.09340 5.27947 5.36405 9.903E-06 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 2.853E-06 92.128 92.225 93.432 93.529 95.171 95.992 96.475 96.716 97.730 98.551 5.37815 5.38379 5.45427 5.45991 5.55576 5.60369 5.63188 5.64598 5.70518 5.75311 2.377E-06 1.783E-06 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 245 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 246 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 10 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.877E-04 0.058 1.000 2.353E-04 0.175 3.000 1.834E-04 0.292 5.000 1.181E-04 0.584 10.000 8.421E-05 0.876 15.000 6.613E-05 1.168 20.000 5.482E-05 1.459 25.000 4.682E-05 1.751 30.000 4.084E-05 2.043 35.000 3.616E-05 2.335 40.000 3.239E-05 2.627 45.000 2.929E-05 2.919 50.000 2.671E-05 3.211 55.000 2.451E-05 3.503 60.000 2.263E-05 3.794 65.000 2.099E-05 4.086 70.000 1.955E-05 4.378 75.000 1.827E-05 4.670 80.000 1.702E-05 4.962 85.000 1.345E-04 0.5 8.57 ANNUAL AVERAGE = 8.44E-06 3 to ULNRC-06696 Page 247 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 11 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.011 1.964 2.360 4.392 4.773 5.980 7.909 9.496 11.211 11.402 0.04487 0.08716 0.10475 0.19497 0.21188 0.26545 0.35107 0.42156 0.49768 0.50613 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 12.481 12.484 12.611 14.072 16.041 17.438 17.692 17.756 19.343 21.820 0.55406 0.55421 0.55985 0.62469 0.71209 0.77411 0.78539 0.78821 0.85869 0.96864 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 22.773 23.154 26.012 26.583 30.902 38.841 40.937 43.096 43.477 43.540 1.01093 1.02785 1.15472 1.18009 1.37180 1.72421 1.81725 1.91310 1.93002 1.93284 2.949E-05 2.791E-05 2.412E-05 2.325E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 49.066 49.129 62.593 62.720 75.485 84.250 84.504 87.997 89.267 91.172 2.17812 2.18094 2.77862 2.78426 3.35094 3.74000 3.75128 3.90634 3.96272 4.04730 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 3.566E-06 2.853E-06 2.377E-06 1.783E-06 91.236 93.586 93.649 94.665 95.364 96.189 97.142 97.587 98.095 98.349 4.05012 4.15443 4.15725 4.20236 4.23337 4.27002 4.31231 4.33205 4.35460 4.36588 1.086E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 248 of 456 98.412 98.603 98.857 99.619 99.873 100.000 4.36870 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 249 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 12 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.513E-04 0.044 1.000 2.795E-04 0.133 3.000 2.203E-04 0.222 5.000 1.564E-04 0.444 10.000 1.062E-04 0.666 15.000 8.010E-05 0.888 20.000 6.497E-05 1.110 25.000 5.463E-05 1.332 30.000 4.702E-05 1.554 35.000 4.118E-05 1.776 40.000 3.652E-05 1.998 45.000 3.271E-05 2.220 50.000 2.956E-05 2.442 55.000 2.692E-05 2.664 60.000 2.466E-05 2.885 65.000 2.272E-05 3.107 70.000 2.103E-05 3.329 75.000 1.954E-05 3.551 80.000 1.801E-05 3.773 85.000 1.467E-04 0.5 11.26 ANNUAL AVERAGE = 7.99E-06 3 to ULNRC-06696 Page 250 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 13 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.116 1.762 2.369 4.593 5.238 6.314 8.414 10.852 13.076 13.147 0.04389 0.06926 0.09314 0.18054 0.20592 0.24820 0.33077 0.42663 0.51402 0.51684 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 14.725 14.730 15.303 16.379 19.822 21.041 21.328 22.690 25.344 26.491 0.57887 0.57905 0.60161 0.64390 0.77922 0.82715 0.83843 0.89199 0.99631 1.04142 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.488E-05 3.370E-05 27.065 29.934 31.224 36.962 45.424 48.006 49.727 50.229 50.301 50.516 1.06397 1.17674 1.22749 1.45303 1.78571 1.88720 1.95486 1.97460 1.97742 1.98588 2.949E-05 2.527E-05 2.412E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 9.903E-06 54.891 55.106 70.023 81.139 86.446 87.091 88.812 90.390 92.900 93.402 2.15785 2.16631 2.75272 3.18971 3.39834 3.42371 3.49137 3.55340 3.65207 3.67181 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 3.566E-06 2.853E-06 2.377E-06 1.086E-06 93.474 94.693 94.836 95.410 95.554 96.701 98.207 98.566 98.709 98.781 3.67463 3.72256 3.72819 3.75075 3.75639 3.80150 3.86070 3.87480 3.88044 3.88326 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 251 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 252 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 14 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.698E-04 0.039 1.000 2.955E-04 0.118 3.000 2.347E-04 0.197 5.000 1.687E-04 0.393 10.000 1.293E-04 0.590 15.000 9.733E-05 0.786 20.000 7.496E-05 0.983 25.000 6.291E-05 1.179 30.000 5.423E-05 1.376 35.000 4.756E-05 1.572 40.000 4.227E-05 1.769 45.000 3.794E-05 1.966 50.000 3.382E-05 2.162 55.000 3.041E-05 2.359 60.000 2.753E-05 2.555 65.000 2.509E-05 2.752 70.000 2.298E-05 2.948 75.000 2.115E-05 3.145 80.000 1.902E-05 3.342 85.000 1.496E-04 0.5 12.72 ANNUAL AVERAGE = 7.90E-06 3 to ULNRC-06696 Page 253 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 15 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.660 1.542 2.198 3.642 4.685 5.408 7.787 8.509 10.355 12.120 0.02318 0.05419 0.07720 0.12795 0.16460 0.18997 0.27356 0.29893 0.36378 0.42580 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 12.126 12.607 13.089 16.941 18.546 18.947 20.391 23.601 24.805 25.849 0.42599 0.44290 0.45982 0.59514 0.65153 0.66563 0.71637 0.82914 0.87143 0.90808 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 2.412E-05 2.325E-05 29.139 29.620 36.121 43.584 46.954 49.121 49.362 55.862 72.956 73.036 1.02368 1.04059 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.56582 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 8.720E-06 7.131E-06 6.976E-06 5.814E-06 83.870 87.802 88.364 89.728 90.450 92.777 94.623 94.784 95.666 95.827 2.94643 3.08457 3.10431 3.15223 3.17761 3.25937 3.32421 3.32985 3.36086 3.36650 4.754E-06 4.360E-06 3.566E-06 2.853E-06 2.377E-06 1.783E-06 1.086E-06 7.241E-07 5.431E-07 4.345E-07 96.710 96.790 98.074 98.876 99.037 99.117 99.278 99.519 99.679 99.920 3.39751 3.40033 3.44544 3.47363 3.47927 3.48209 3.48773 3.49619 3.50183 3.51028 3.621E-07 3 to ULNRC-06696 Page 254 of 456 100.000 3.51310 3 to ULNRC-06696 Page 255 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 16 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.900E-04 0.035 1.000 2.599E-04 0.105 3.000 2.095E-04 0.176 5.000 1.504E-04 0.351 10.000 1.089E-04 0.527 15.000 8.527E-05 0.703 20.000 7.019E-05 0.878 25.000 5.988E-05 1.054 30.000 5.219E-05 1.230 35.000 4.623E-05 1.405 40.000 4.146E-05 1.581 45.000 3.746E-05 1.757 50.000 3.372E-05 1.932 55.000 3.059E-05 2.108 60.000 2.794E-05 2.284 65.000 2.567E-05 2.459 70.000 2.369E-05 2.635 75.000 2.196E-05 2.810 80.000 1.138E-04 0.5 14.23 ANNUAL AVERAGE = 6.71E-06 3 to ULNRC-06696 Page 256 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 17 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.532 1.334 1.963 3.245 4.046 4.446 6.908 6.988 7.549 9.872 0.01874 0.04693 0.06908 0.11419 0.14238 0.15647 0.24312 0.24594 0.26567 0.34743 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 11.795 11.800 12.521 12.681 15.805 17.808 17.968 18.048 19.009 21.253 0.41509 0.41526 0.44064 0.44628 0.55623 0.62671 0.63235 0.63517 0.66900 0.74794 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 22.214 22.855 25.979 26.540 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.80432 0.91428 0.93401 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 2.412E-05 2.325E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 8.720E-06 7.131E-06 74.846 74.926 86.061 90.868 91.508 93.030 93.351 95.193 96.475 96.555 2.63404 2.63686 3.02874 3.19790 3.22045 3.27402 3.28529 3.35014 3.39525 3.39807 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 2.853E-06 1.783E-06 7.241E-07 5.431E-07 4.345E-07 97.116 97.276 97.597 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.41780 3.42344 3.43472 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 257 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 18 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.684E-04 0.035 1.000 2.482E-04 0.106 3.000 1.999E-04 0.176 5.000 1.459E-04 0.352 10.000 1.030E-04 0.528 15.000 7.830E-05 0.704 20.000 6.579E-05 0.880 25.000 5.771E-05 1.056 30.000 5.154E-05 1.232 35.000 4.663E-05 1.408 40.000 4.263E-05 1.584 45.000 3.930E-05 1.760 50.000 3.567E-05 1.936 55.000 3.221E-05 2.112 60.000 2.928E-05 2.288 65.000 2.679E-05 2.464 70.000 2.463E-05 2.639 75.000 2.275E-05 2.815 80.000 2.110E-05 2.991 85.000 1.080E-04 0.5 14.21 ANNUAL AVERAGE = 6.51E-06 3 to ULNRC-06696 Page 258 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 19 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.455 1.240 1.846 2.752 3.720 4.143 6.481 6.965 9.201 10.652 0.02120 0.05786 0.08608 0.12837 0.17348 0.19321 0.30228 0.32484 0.42915 0.49681 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 10.657 11.140 11.261 14.465 15.795 15.976 16.883 19.664 20.752 21.235 0.49702 0.51957 0.52521 0.67463 0.73666 0.74511 0.78740 0.91709 0.96784 0.99039 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 2.949E-05 2.412E-05 24.802 25.527 33.204 43.299 46.321 50.251 51.097 51.520 57.867 74.914 1.15673 1.19056 1.54861 2.01943 2.16040 2.34365 2.38312 2.40285 2.69888 3.49392 2.325E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 1.141E-05 8.720E-06 7.131E-06 74.974 85.553 91.235 91.537 92.504 92.746 94.318 94.378 95.648 95.708 3.49674 3.99011 4.25512 4.26922 4.31433 4.32560 4.39891 4.40173 4.46093 4.46375 6.976E-06 5.814E-06 4.754E-06 3.566E-06 2.853E-06 2.377E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 96.736 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.51168 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 259 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 20 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.565E-04 0.047 1.000 2.418E-04 0.140 3.000 1.943E-04 0.233 5.000 1.371E-04 0.466 10.000 9.510E-05 0.700 15.000 7.293E-05 0.933 20.000 6.282E-05 1.166 25.000 5.543E-05 1.399 30.000 4.974E-05 1.632 35.000 4.519E-05 1.866 40.000 4.146E-05 2.099 45.000 3.834E-05 2.332 50.000 3.457E-05 2.565 55.000 3.137E-05 2.798 60.000 2.865E-05 3.032 65.000 2.631E-05 3.265 70.000 2.428E-05 3.498 75.000 2.250E-05 3.731 80.000 2.093E-05 3.964 85.000 1.289E-04 0.5 10.72 ANNUAL AVERAGE = 8.28E-06 3 to ULNRC-06696 Page 260 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 21 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 1.078 1.748 2.927 3.588 3.933 6.437 7.213 9.168 9.340 0.04931 0.10570 0.17148 0.28707 0.35192 0.38575 0.63141 0.70753 0.89924 0.91616 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 11.410 11.413 11.701 12.247 16.271 17.392 17.420 17.449 17.507 20.180 1.11914 1.11945 1.14764 1.20121 1.59591 1.70586 1.70868 1.71150 1.71714 1.97933 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 24.405 25.641 26.216 30.499 31.074 40.473 53.810 55.764 59.673 60.420 2.39377 2.51500 2.57138 2.99146 3.04784 3.96975 5.27790 5.46961 5.85303 5.92633 3.370E-05 2.949E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 60.564 65.451 65.508 79.046 79.190 86.491 88.589 88.790 89.106 89.135 5.94043 6.41971 6.42534 7.75323 7.76732 8.48342 8.68923 8.70896 8.73998 8.74279 1.163E-05 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 3.566E-06 2.853E-06 2.377E-06 1.783E-06 91.981 93.878 93.935 94.481 94.568 95.602 96.723 97.126 97.183 97.212 9.02190 9.20798 9.21361 9.26718 9.27564 9.37713 9.48708 9.52655 9.53219 9.53501 7.241E-07 5.431E-07 4.345E-07 3.621E-07 3 to ULNRC-06696 Page 261 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 262 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 22 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.581E-04 0.098 1.000 2.384E-04 0.294 3.000 1.928E-04 0.490 5.000 1.390E-04 0.981 10.000 1.044E-04 1.471 15.000 8.513E-05 1.962 20.000 7.255E-05 2.452 25.000 6.395E-05 2.943 30.000 5.729E-05 3.433 35.000 5.197E-05 3.923 40.000 4.758E-05 4.414 45.000 4.390E-05 4.904 50.000 4.075E-05 5.395 55.000 3.787E-05 5.885 60.000 3.334E-05 6.376 65.000 2.958E-05 6.866 70.000 2.641E-05 7.356 75.000 2.371E-05 7.847 80.000 2.140E-05 8.337 85.000 1.912E-04 0.5 5.10 ANNUAL AVERAGE = 1.85E-05 3 to ULNRC-06696 Page 263 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 23 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.676 1.073 1.374 2.698 3.051 3.868 4.745 5.363 6.687 7.504 0.08630 0.13704 0.17547 0.34463 0.38974 0.49405 0.60618 0.68512 0.85428 0.95859 1.363E-04 1.180E-04 1.180E-04 1.155E-04 1.149E-04 1.123E-04 9.834E-05 9.240E-05 8.620E-05 7.763E-05 10.086 10.859 10.860 10.882 11.015 12.758 14.722 14.744 15.473 17.591 1.28845 1.38712 1.38730 1.39012 1.40704 1.62976 1.88068 1.88349 1.97653 2.24718 7.705E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 5.467E-05 4.718E-05 4.373E-05 4.310E-05 17.635 29.774 34.828 35.225 35.468 36.638 36.660 36.947 36.969 40.941 2.25282 3.80343 4.44904 4.49979 4.53080 4.68022 4.68304 4.71969 4.72251 5.22998 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 2.949E-05 2.791E-05 2.527E-05 2.412E-05 2.325E-05 54.889 55.772 63.055 65.990 67.138 70.360 70.382 70.890 78.482 78.548 7.01177 7.12454 8.05491 8.42987 8.57647 8.98809 8.99091 9.05575 10.02559 10.03404 2.077E-05 2.022E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 9.508E-06 8.720E-06 7.131E-06 84.044 84.088 87.155 87.729 89.098 89.782 91.900 91.922 93.578 93.666 10.73604 10.74168 11.13356 11.20687 11.38166 11.46906 11.73971 11.74253 11.95398 11.96525 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 3.488E-06 2.853E-06 2.377E-06 1.783E-06 7.241E-07 3 to ULNRC-06696 Page 264 of 456 94.284 94.549 95.630 95.829 96.954 96.976 97.506 97.771 97.948 98.455 12.04419 12.07803 12.21617 12.24154 12.38533 12.38815 12.45581 12.48964 12.51220 12.57704 5.431E-07 4.345E-07 3.621E-07 2.715E-07 2.172E-07 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 265 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 24 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.811E-04 0.128 1.000 2.328E-04 0.383 3.000 1.816E-04 0.639 5.000 1.366E-04 1.277 10.000 1.054E-04 1.916 15.000 9.384E-05 2.555 20.000 8.541E-05 3.194 25.000 7.888E-05 3.832 30.000 7.330E-05 4.471 35.000 6.182E-05 5.110 40.000 5.299E-05 5.748 45.000 4.602E-05 6.387 50.000 4.046E-05 7.026 55.000 3.901E-05 7.665 60.000 3.681E-05 8.303 65.000 2.049E-04 0.5 3.91 ANNUAL AVERAGE = 2.07E-05 3 to ULNRC-06696 Page 266 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 25 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.418 0.929 1.105 1.884 2.287 2.690 3.486 3.513 3.755 4.454 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.36583 0.36865 0.39403 0.46733 1.475E-04 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 5.045 5.905 6.281 6.283 6.498 7.492 8.405 8.996 9.077 12.382 0.52935 0.61957 0.65904 0.65922 0.68178 0.78609 0.88195 0.94397 0.95243 1.29920 7.705E-05 7.690E-05 7.375E-05 7.289E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 12.785 19.126 21.625 21.651 22.162 22.565 23.452 23.640 25.709 33.984 1.34149 2.00684 2.26903 2.27185 2.32542 2.36771 2.46075 2.48048 2.69757 3.56591 3.932E-05 3.819E-05 3.614E-05 3.488E-05 3.370E-05 2.949E-05 2.791E-05 2.527E-05 2.412E-05 2.325E-05 35.086 46.129 52.765 52.792 56.634 58.945 58.972 60.718 66.629 66.791 3.68150 4.84022 5.53658 5.53940 5.94256 6.18502 6.18784 6.37109 6.99133 7.00825 2.077E-05 2.022E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 9.903E-06 8.720E-06 7.131E-06 72.702 72.728 77.753 78.075 81.649 86.566 88.608 89.038 90.945 91.053 7.62849 7.63131 8.15852 8.19235 8.56732 9.08324 9.29751 9.34262 9.54279 9.55406 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 3.488E-06 2.853E-06 2.377E-06 1.783E-06 1.426E-06 3 to ULNRC-06696 Page 267 of 456 91.966 92.826 94.062 94.841 95.701 95.755 96.507 97.501 97.851 97.985 9.64992 9.74014 9.86982 9.95158 10.04180 10.04744 10.12638 10.23069 10.26734 10.28144 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 2.172E-07 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 268 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 26 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.094E-04 0.105 1.000 1.857E-04 0.315 3.000 1.481E-04 0.525 5.000 9.293E-05 1.049 10.000 7.699E-05 1.574 15.000 7.575E-05 2.099 20.000 6.545E-05 2.623 25.000 5.610E-05 3.148 30.000 4.905E-05 3.673 35.000 4.353E-05 4.197 40.000 3.908E-05 4.722 45.000 3.695E-05 5.246 50.000 3.469E-05 5.771 55.000 3.028E-05 6.296 60.000 2.605E-05 6.820 65.000 2.261E-05 7.345 70.000 1.977E-05 7.870 75.000 1.512E-04 0.5 4.77 ANNUAL AVERAGE = 1.27E-05 3 to ULNRC-06696 Page 269 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 27 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.344 0.763 0.992 1.411 1.704 1.997 2.906 2.990 3.828 4.330 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19561 0.20125 0.25763 0.29146 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 4.875 5.419 5.421 5.798 6.510 8.144 8.898 8.981 11.620 11.872 0.32811 0.36476 0.36489 0.39026 0.43819 0.54814 0.59889 0.60453 0.78214 0.79906 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 16.814 19.579 20.039 20.500 21.422 21.757 24.144 33.150 34.113 43.705 1.13173 1.31781 1.34882 1.37983 1.44186 1.46441 1.62511 2.23125 2.29610 2.94171 3.614E-05 3.370E-05 2.949E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 48.019 49.988 52.501 53.171 59.999 60.041 68.250 73.989 74.659 77.717 3.23210 3.36461 3.53376 3.57887 4.03842 4.04123 4.59381 4.98006 5.02517 5.23097 1.238E-05 1.163E-05 9.903E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 79.727 82.910 83.078 85.466 85.549 87.727 88.816 89.905 90.408 92.544 5.36630 5.58056 5.59184 5.75254 5.75818 5.90478 5.97808 6.05138 6.08522 6.22900 3.488E-06 2.853E-06 2.377E-06 1.783E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 270 of 456 92.754 94.597 95.518 95.979 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.46018 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 271 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 28 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.940E-04 0.067 1.000 1.768E-04 0.202 3.000 1.349E-04 0.337 5.000 8.599E-05 0.673 10.000 7.713E-05 1.010 15.000 7.259E-05 1.346 20.000 6.130E-05 1.683 25.000 5.317E-05 2.019 30.000 4.700E-05 2.356 35.000 4.214E-05 2.692 40.000 3.818E-05 3.029 45.000 3.401E-05 3.365 50.000 2.942E-05 3.702 55.000 2.571E-05 4.038 60.000 2.267E-05 4.375 65.000 2.014E-05 4.712 70.000 1.047E-04 0.5 7.43 ANNUAL AVERAGE = 7.90E-06 3 to ULNRC-06696 Page 272 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 29 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.368 0.718 0.980 1.881 2.232 2.532 3.980 4.080 4.631 5.482 0.02071 0.04045 0.05521 0.10596 0.12569 0.14261 0.22415 0.22979 0.26081 0.30873 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 5.832 6.633 6.636 6.937 7.588 8.989 10.091 10.241 11.642 17.700 0.32847 0.37358 0.37374 0.39066 0.42731 0.50625 0.56827 0.57673 0.65567 0.99680 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 21.404 22.255 22.806 24.558 25.159 28.663 37.975 39.576 47.136 49.489 1.20543 1.25336 1.28437 1.38304 1.41688 1.61422 2.13861 2.22883 2.65454 2.78705 3.488E-05 3.370E-05 2.949E-05 2.791E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 1.842E-05 1.744E-05 49.539 50.139 53.744 53.844 53.994 62.554 62.655 70.614 75.921 76.471 2.78987 2.82370 3.02669 3.03232 3.04078 3.52288 3.52852 3.97678 4.27563 4.30664 1.650E-05 1.238E-05 1.163E-05 9.903E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 79.425 81.177 83.280 83.430 85.683 85.733 87.335 88.035 89.337 89.487 4.47298 4.57165 4.69006 4.69852 4.82539 4.82821 4.91843 4.95790 5.03120 5.03965 3.566E-06 2.853E-06 2.377E-06 1.783E-06 1.426E-06 1.086E-06 1.000E-06 7.241E-07 5.431E-07 4.345E-07 3 to ULNRC-06696 Page 273 of 456 91.740 93.042 93.843 94.343 94.393 94.443 94.493 94.894 96.796 98.548 5.16652 5.23982 5.28493 5.31312 5.31594 5.31876 5.32158 5.34414 5.45127 5.54995 3.621E-07 2.715E-07 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 274 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 30 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.069E-04 0.056 1.000 1.951E-04 0.169 3.000 1.543E-04 0.282 5.000 9.507E-05 0.563 10.000 8.329E-05 0.845 15.000 7.552E-05 1.126 20.000 6.518E-05 1.408 25.000 5.618E-05 1.690 30.000 4.940E-05 1.971 35.000 4.408E-05 2.253 40.000 3.979E-05 2.534 45.000 3.558E-05 2.816 50.000 3.077E-05 3.097 55.000 2.689E-05 3.379 60.000 2.371E-05 3.661 65.000 2.106E-05 3.942 70.000 1.880E-05 4.224 75.000 9.937E-05 0.5 8.88 ANNUAL AVERAGE = 7.56E-06 3 to ULNRC-06696 Page 275 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 31 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.477 1.160 1.580 2.490 2.793 3.248 5.769 6.451 8.119 8.195 0.01775 0.04313 0.05876 0.09259 0.10387 0.12078 0.21456 0.23993 0.30196 0.30478 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 9.560 9.563 10.094 10.397 12.519 13.808 14.036 14.490 14.642 17.523 0.35553 0.35566 0.37539 0.38667 0.46561 0.51353 0.52199 0.53891 0.54455 0.65168 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 19.797 21.768 22.905 26.089 26.695 32.684 42.690 44.207 50.650 53.076 0.73626 0.80956 0.85185 0.97026 0.99281 1.21554 1.58768 1.64407 1.88371 1.97392 3.488E-05 3.370E-05 2.949E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 2.022E-05 1.842E-05 1.744E-05 53.152 53.455 57.094 57.473 66.418 66.494 73.013 73.165 77.940 78.623 1.97674 1.98802 2.12335 2.13744 2.47012 2.47294 2.71540 2.72103 2.89865 2.92402 1.650E-05 1.238E-05 1.163E-05 9.903E-06 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 81.124 83.323 85.521 85.824 85.900 87.871 87.947 88.932 89.690 91.055 3.01706 3.09882 3.18058 3.19186 3.19467 3.26798 3.27080 3.30745 3.33564 3.38639 4.360E-06 3.566E-06 2.853E-06 2.377E-06 1.783E-06 1.000E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 3 to ULNRC-06696 Page 276 of 456 91.434 92.798 94.087 94.315 94.769 94.921 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.52453 3.53017 3.55554 3.62321 3.66549 3.70778 2.715E-07 100.000 3.71906 3 to ULNRC-06696 Page 277 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 32 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.479E-04 0.037 1.000 2.278E-04 0.112 3.000 1.835E-04 0.186 5.000 1.216E-04 0.372 10.000 8.794E-05 0.558 15.000 7.326E-05 0.744 20.000 6.310E-05 0.930 25.000 5.568E-05 1.116 30.000 4.997E-05 1.302 35.000 4.542E-05 1.488 40.000 4.169E-05 1.674 45.000 3.856E-05 1.860 50.000 3.402E-05 2.045 55.000 2.930E-05 2.231 60.000 2.550E-05 2.417 65.000 2.238E-05 2.603 70.000 1.977E-05 2.789 75.000 9.412E-05 0.5 13.44 ANNUAL AVERAGE = 6.04E-06 3 to ULNRC-06696 Page 278 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 33 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.274 0.599 0.899 1.494 2.251 2.521 4.320 4.699 6.105 6.213 0.01430 0.03122 0.04685 0.07786 0.11733 0.13143 0.22521 0.24494 0.31824 0.32388 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 6.916 6.919 7.352 7.677 8.704 10.110 10.219 10.543 10.597 12.490 0.36053 0.36069 0.38324 0.40016 0.45372 0.52702 0.53266 0.54958 0.55240 0.65107 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.651E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 14.329 15.249 15.898 18.115 18.494 18.548 21.847 31.690 33.529 41.696 0.74693 0.79486 0.82869 0.94428 0.96401 0.96683 1.13881 1.65192 1.74777 2.17349 3.614E-05 3.370E-05 2.949E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 2.022E-05 1.842E-05 1.744E-05 44.509 45.536 51.161 51.377 60.680 60.788 67.711 67.765 74.418 75.229 2.32009 2.37366 2.66686 2.67814 3.16305 3.16869 3.52956 3.53238 3.87915 3.92144 1.650E-05 1.238E-05 1.163E-05 9.903E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 79.989 83.829 85.938 86.316 88.155 88.209 89.129 89.778 90.806 91.076 4.16954 4.36971 4.47966 4.49940 4.59525 4.59807 4.64600 4.67983 4.73340 4.74749 3.566E-06 2.853E-06 2.377E-06 1.783E-06 1.000E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 3.523E-07 3 to ULNRC-06696 Page 279 of 456 92.428 93.780 94.267 94.537 94.591 94.970 96.484 98.053 99.351 99.405 4.81797 4.88846 4.91383 4.92793 4.93075 4.95048 5.02942 5.11118 5.17884 5.18166 2.715E-07 100.000 5.21267 3 to ULNRC-06696 Page 280 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 34 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.939E-04 0.052 1.000 1.981E-04 0.156 3.000 1.615E-04 0.261 5.000 8.724E-05 0.521 10.000 7.183E-05 0.782 15.000 6.066E-05 1.043 20.000 5.297E-05 1.303 25.000 4.727E-05 1.564 30.000 4.283E-05 1.824 35.000 3.926E-05 2.085 40.000 3.564E-05 2.346 45.000 3.118E-05 2.606 50.000 2.757E-05 2.867 55.000 2.461E-05 3.128 60.000 2.212E-05 3.388 65.000 2.002E-05 3.649 70.000 9.129E-05 0.5 9.59 ANNUAL AVERAGE = 6.83E-06 3 to ULNRC-06696 Page 281 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 35 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.541 0.759 1.192 2.195 2.500 3.328 5.629 6.675 8.331 8.462 0.03501 0.04911 0.07712 0.14196 0.16169 0.21526 0.36408 0.43175 0.53888 0.54734 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.465 9.468 9.991 10.601 13.260 14.829 15.134 17.052 19.885 21.498 0.61218 0.61237 0.64620 0.68567 0.85765 0.95914 0.97888 1.10292 1.28618 1.39049 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 2.949E-05 21.847 24.506 25.029 29.126 36.449 38.192 41.287 42.725 43.118 47.825 1.41305 1.58502 1.61885 1.88387 2.35751 2.47028 2.67045 2.76348 2.78886 3.09334 2.412E-05 2.077E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 9.903E-06 8.720E-06 6.976E-06 58.940 69.140 76.724 77.552 82.173 84.831 86.836 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.01609 5.31493 5.48691 5.61660 5.61942 5.73501 5.79139 5.814E-06 4.754E-06 4.360E-06 3.566E-06 2.853E-06 2.377E-06 1.783E-06 7.241E-07 5.431E-07 4.345E-07 90.323 91.021 91.457 93.070 94.028 94.682 94.900 95.380 96.600 98.649 5.84214 5.88725 5.91544 6.01976 6.08178 6.12407 6.13817 6.16918 6.24812 6.38062 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 282 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 283 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 36 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.576E-04 0.065 1.000 2.309E-04 0.194 3.000 1.856E-04 0.323 5.000 1.261E-04 0.647 10.000 9.024E-05 0.970 15.000 7.339E-05 1.294 20.000 6.047E-05 1.617 25.000 5.138E-05 1.940 30.000 4.461E-05 2.264 35.000 3.936E-05 2.587 40.000 3.468E-05 2.911 45.000 3.075E-05 3.234 50.000 2.753E-05 3.557 55.000 2.485E-05 3.881 60.000 2.257E-05 4.204 65.000 2.063E-05 4.528 70.000 1.895E-05 4.851 75.000 1.527E-04 0.5 7.73 ANNUAL AVERAGE = 1.01E-05 3 to ULNRC-06696 Page 284 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 37 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.620 0.788 1.178 2.401 2.654 3.582 5.473 6.697 7.793 8.553 0.04142 0.05270 0.07875 0.16051 0.17743 0.23945 0.36585 0.44761 0.52091 0.57166 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.480 9.483 9.990 11.128 13.912 15.220 15.346 16.949 20.577 21.969 0.63368 0.63388 0.66771 0.74383 0.92991 1.01730 1.02576 1.13290 1.37535 1.46839 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 2.949E-05 22.601 24.626 25.174 30.447 38.123 39.810 42.679 43.480 43.860 47.740 1.51068 1.64600 1.68266 2.03507 2.54818 2.66095 2.85266 2.90622 2.93160 3.19097 2.527E-05 2.412E-05 2.325E-05 2.077E-05 2.022E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 1.163E-05 47.782 59.803 59.930 69.884 69.926 78.151 78.531 83.424 85.490 87.009 3.19379 3.99729 4.00575 4.67110 4.67392 5.22368 5.24905 5.57609 5.71423 5.81573 9.903E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 2.853E-06 2.377E-06 87.051 88.991 89.033 89.835 90.510 91.227 91.691 93.462 94.812 95.192 5.81855 5.94823 5.95105 6.00462 6.04973 6.09765 6.12867 6.24708 6.33729 6.36267 1.783E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 285 of 456 95.402 95.571 96.837 98.482 99.494 100.000 6.37676 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 286 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 38 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.705E-04 0.067 1.000 2.313E-04 0.201 3.000 1.828E-04 0.334 5.000 1.243E-04 0.668 10.000 9.315E-05 1.003 15.000 7.535E-05 1.337 20.000 6.230E-05 1.671 25.000 5.297E-05 2.005 30.000 4.601E-05 2.339 35.000 4.062E-05 2.674 40.000 3.594E-05 3.008 45.000 3.180E-05 3.342 50.000 2.841E-05 3.676 55.000 2.559E-05 4.010 60.000 2.320E-05 4.345 65.000 2.117E-05 4.679 70.000 1.941E-05 5.013 75.000 1.771E-05 5.347 80.000 1.505E-04 0.5 7.48 ANNUAL AVERAGE = 1.04E-05 3 to ULNRC-06696 Page 287 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 39 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 0.932 1.140 1.783 2.169 2.684 3.971 5.257 6.501 6.930 0.03304 0.06123 0.07491 0.11720 0.14257 0.17640 0.26101 0.34559 0.42735 0.45554 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 7.101 7.103 7.404 8.647 9.548 10.106 10.234 10.449 13.923 16.024 0.46682 0.46694 0.48668 0.56844 0.62764 0.66429 0.67275 0.68685 0.91521 1.05335 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.370E-05 16.925 17.096 18.898 19.241 22.972 31.893 33.137 37.168 38.112 38.412 1.11256 1.12383 1.24224 1.26480 1.51008 2.09649 2.17825 2.44326 2.50528 2.52502 2.949E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 2.022E-05 1.842E-05 1.744E-05 1.650E-05 1.238E-05 41.886 41.929 53.809 53.852 68.348 68.391 77.098 77.183 82.630 86.018 2.75338 2.75620 3.53714 3.53996 4.49288 4.49570 5.06801 5.07365 5.43170 5.65442 1.163E-05 9.903E-06 8.720E-06 6.976E-06 5.814E-06 4.754E-06 4.360E-06 3.566E-06 2.853E-06 2.377E-06 87.562 87.948 89.707 91.422 92.537 92.966 93.224 95.239 96.912 97.384 5.75592 5.78129 5.89688 6.00965 6.08295 6.11115 6.12806 6.26057 6.37052 6.40153 1.783E-06 1.000E-06 7.241E-07 5.431E-07 4.345E-07 3.621E-07 2.715E-07 3 to ULNRC-06696 Page 288 of 456 97.941 97.984 98.027 98.499 99.228 99.528 100.000 6.43818 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 289 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 40 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.407E-04 0.066 1.000 2.121E-04 0.197 3.000 1.674E-04 0.329 5.000 1.020E-04 0.657 10.000 7.727E-05 0.986 15.000 6.248E-05 1.315 20.000 5.260E-05 1.643 25.000 4.551E-05 1.972 30.000 4.014E-05 2.301 35.000 3.564E-05 2.629 40.000 3.183E-05 2.958 45.000 2.872E-05 3.287 50.000 2.613E-05 3.615 55.000 2.393E-05 3.944 60.000 2.204E-05 4.273 65.000 2.040E-05 4.601 70.000 1.897E-05 4.930 75.000 1.737E-05 5.259 80.000 1.271E-04 0.5 7.61 ANNUAL AVERAGE = 8.51E-06 3 to ULNRC-06696 Page 290 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 41 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 1200.0 METERS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.848E-03 1.232E-03 9.240E-04 8.747E-04 7.392E-04 6.160E-04 5.831E-04 4.620E-04 4.373E-04 4.044E-04 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 3.499E-04 3.080E-04 2.916E-04 2.696E-04 2.310E-04 2.187E-04 2.022E-04 1.981E-04 1.848E-04 1.617E-04 9.495 10.110 12.275 12.625 12.743 15.904 16.992 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 16.99183 16.99464 16.99746 17.92783 1.458E-04 1.348E-04 1.320E-04 1.155E-04 1.093E-04 1.011E-04 9.903E-05 9.240E-05 8.747E-05 7.922E-05 22.089 24.282 24.418 24.421 25.357 30.147 30.665 30.668 30.747 31.229 22.08909 24.28249 24.41782 24.42064 25.35664 30.14660 30.66535 30.66817 30.74711 31.22920 7.289E-05 6.739E-05 6.602E-05 5.467E-05 5.055E-05 4.951E-05 4.651E-05 4.373E-05 4.044E-05 3.488E-05 31.232 41.015 42.698 42.701 48.325 52.396 52.399 52.402 54.553 54.567 31.23202 41.01494 42.69805 42.70087 48.32534 52.39639 52.39921 52.40203 54.55314 54.56724 3.370E-05 3.301E-05 2.791E-05 2.527E-05 2.476E-05 2.325E-05 2.022E-05 1.981E-05 1.744E-05 1.650E-05 55.467 66.188 66.202 66.552 75.562 75.644 75.667 81.581 82.047 85.134 55.46659 66.18832 66.20242 66.55202 75.56245 75.64420 75.66676 81.58162 82.04680 85.13391 1.238E-05 1.163E-05 1.141E-05 9.903E-06 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14124 89.25006 89.25288 89.41358 89.43050 91.23766 91.30814 92.34282 92.93204 93.86240 4.360E-06 3.566E-06 3.488E-06 2.853E-06 2.377E-06 1.783E-06 1.426E-06 1.086E-06 1.000E-06 7.241E-07 3 to ULNRC-06696 Page 291 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13587 95.48913 95.51168 96.42796 96.89314 97.12995 97.14687 97.16096 97.17506 97.51337 5.431E-07 4.345E-07 3.621E-07 3.523E-07 2.715E-07 2.172E-07 98.345 99.179 99.777 99.780 99.994 100.000 98.34506 99.17957 99.77725 99.78008 99.99434 99.99998 3 to ULNRC-06696 Page 292 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 42 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.412E-03 1.000 1.000 7.961E-04 3.000 3.000 5.808E-04 5.000 5.000 3.508E-04 10.000 10.000 2.369E-04 15.000 15.000 1.714E-04 20.000 20.000 1.299E-04 25.000 25.000 1.021E-04 30.000 30.000 8.546E-05 35.000 35.000 7.269E-05 40.000 40.000 6.216E-05 45.000 45.000 5.329E-05 50.000 50.000 4.608E-05 55.000 55.000 4.007E-05 60.000 60.000 3.467E-05 65.000 65.000 2.977E-05 70.000 70.000 2.525E-05 75.000 75.000 2.108E-05 80.000 80.000 5.808E-04 5.0 5.00 3 to ULNRC-06696 Page 293 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 43 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.558 1.057 1.441 2.551 3.028 3.620 5.269 5.272 5.390 6.380 0.55822 1.05723 1.44065 2.55145 3.02791 3.61996 5.26924 5.27206 5.39047 6.38004 1.475E-04 1.363E-04 1.180E-04 1.180E-04 1.155E-04 1.149E-04 1.123E-04 9.834E-05 9.240E-05 8.620E-05 7.694 8.308 9.332 9.335 9.337 9.687 10.586 12.752 12.754 13.843 7.69383 8.30843 9.33183 9.33465 9.33747 9.68706 10.58641 12.75162 12.75443 13.84268 7.864E-05 7.763E-05 7.705E-05 7.690E-05 7.375E-05 7.289E-05 6.896E-05 5.898E-05 5.747E-05 5.467E-05 13.978 14.914 14.993 19.154 22.315 22.317 23.248 23.767 25.960 25.963 13.97800 14.91400 14.99294 19.15420 22.31462 22.31744 23.24780 23.76655 25.95995 25.96277 4.718E-05 4.651E-05 4.373E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.488E-05 3.370E-05 26.445 26.448 26.450 31.240 41.023 42.706 48.331 50.482 50.496 51.395 26.44487 26.44769 26.45051 31.24047 41.02339 42.70650 48.33097 50.48208 50.49618 51.39552 2.949E-05 2.791E-05 2.527E-05 2.412E-05 2.325E-05 2.077E-05 2.022E-05 1.842E-05 1.744E-05 1.650E-05 55.466 55.481 55.830 66.552 66.634 75.644 75.667 81.581 82.047 85.134 55.46658 55.48067 55.83025 66.55198 66.63377 75.64420 75.66676 81.58163 82.04681 85.13392 1.238E-05 1.163E-05 1.141E-05 9.903E-06 9.508E-06 8.720E-06 7.131E-06 6.976E-06 5.814E-06 4.754E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14127 89.25008 89.25290 89.41361 89.43054 91.23772 91.30822 92.34290 92.93212 93.86248 4.360E-06 3.566E-06 3.488E-06 2.853E-06 2.377E-06 1.783E-06 1.426E-06 1.086E-06 1.000E-06 7.241E-07 3 to ULNRC-06696 Page 294 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13596 95.48923 95.51179 96.42807 96.89326 97.13010 97.14702 97.16113 97.17523 97.51356 5.431E-07 4.345E-07 3.621E-07 3.523E-07 2.715E-07 2.172E-07 98.345 99.180 99.777 99.780 99.994 100.000 98.34525 99.17977 99.77747 99.78029 99.99457 100.00021 3 to ULNRC-06696 Page 295 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 44 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00021 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.604E-04 1.000 1.000 2.265E-04 3.000 3.000 1.771E-04 5.000 5.000 1.203E-04 10.000 10.000 9.098E-05 15.000 15.000 7.840E-05 20.000 20.000 6.212E-05 25.000 25.000 4.621E-05 30.000 30.000 4.205E-05 35.000 35.000 4.075E-05 40.000 40.000 3.922E-05 45.000 45.000 3.690E-05 50.000 50.000 3.326E-05 55.000 55.000 2.993E-05 60.000 60.000 2.684E-05 65.000 65.000 2.392E-05 70.000 70.000 2.112E-05 75.000 75.000 1.906E-05 80.000 80.000 1.771E-04 5.0 5.00 3 to ULNRC-06696 Page 296 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 45 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION AREA BOUNDARY (SB OR EAB)
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX SB AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 1200. 1.34E-04 8.51E-05 6.77E-05 4.12E-05 2.02E-05 8.44E-06 20.4 S SSW 1200. 1.47E-04 9.07E-05 7.13E-05 4.23E-05 2.00E-05 7.99E-06 325.0 SSW SW 1200. 1.50E-04 9.20E-05 7.21E-05 4.26E-05 2.00E-05 7.90E-06 23.0 SW WSW 1200. 1.14E-04 7.13E-05 5.64E-05 3.39E-05 1.64E-05 6.71E-06 16.2 WSW W 1200. 1.08E-04 6.79E-05 5.38E-05 3.25E-05 1.58E-05 6.51E-06 14.5 W WNW 1200. 1.29E-04 8.19E-05 6.53E-05 3.99E-05 1.97E-05 8.28E-06 18.1 WNW NW 1200. 1.91E-04 1.30E-04 1.07E-04 7.04E-05 3.86E-05 1.85E-05 37.2 NW NNW 1200. 2.05E-04 1.40E-04 1.16E-04 7.70E-05 4.27E-05 2.07E-05 43.7 NNW N 1200. 1.51E-04 1.00E-04 8.19E-05 5.25E-05 2.78E-05 1.27E-05 22.5 N NNE 1200. 1.05E-04 6.83E-05 5.52E-05 3.47E-05 1.78E-05 7.90E-06 13.0 NNE NE 1200. 9.94E-05 6.49E-05 5.25E-05 3.30E-05 1.70E-05 7.56E-06 13.2 NE ENE 1200. 9.41E-05 5.98E-05 4.76E-05 2.91E-05 1.43E-05 6.04E-06 12.6 ENE E 1200. 9.13E-05 5.95E-05 4.80E-05 3.01E-05 1.55E-05 6.83E-06 12.5 E ESE 1200. 1.53E-04 9.75E-05 7.79E-05 4.79E-05 2.38E-05 1.01E-05 22.5 ESE SE 1200. 1.51E-04 9.68E-05 7.76E-05 4.81E-05 2.42E-05 1.04E-05 22.9 SE SSE 1200. 1.27E-04 8.13E-05 6.50E-05 4.00E-05 1.99E-05 8.51E-06 18.6 SSE MAX X/Q 2.05E-04 1.40E-04 1.16E-04 7.70E-05 4.27E-05 TOTAL HOURS: 635.9 SRP 2.3.4 1200. 5.81E-04 3.35E-04 2.54E-04 1.40E-04 5.93E-05 2.07E-05 SITE LIMIT 1.77E-04 1.24E-04 1.04E-04 7.08E-05 4.08E-05 2.07E-05 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 297 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 46 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.710 1.241 1.527 3.169 3.845 4.183 5.391 6.596 7.658 8.914 0.04142 0.07243 0.08915 0.18501 0.22448 0.24421 0.31470 0.38503 0.44705 0.52035 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.155 10.314 10.604 11.763 11.766 12.877 15.678 17.272 17.851 17.948 0.53445 0.60211 0.61903 0.68669 0.68686 0.75170 0.91522 1.00826 1.04209 1.04773 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 18.093 19.445 20.362 24.805 25.337 32.967 34.223 37.700 38.231 41.757 1.05619 1.13512 1.18869 1.44807 1.47908 1.92452 1.99783 2.20081 2.23183 2.43763 5.552E-06 4.541E-06 4.164E-06 3.896E-06 3.596E-06 2.987E-06 2.557E-06 1.948E-06 1.917E-06 1.534E-06 41.805 51.609 51.657 51.706 65.759 79.427 86.961 87.250 90.438 90.679 2.44045 3.01277 3.01559 3.01841 3.83882 4.63668 5.07648 5.09340 5.27947 5.29357 1.299E-06 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.207E-07 2.566E-07 92.128 93.335 93.432 95.074 95.895 95.992 96.233 96.716 97.730 98.551 5.37815 5.44863 5.45427 5.55012 5.59805 5.60369 5.61779 5.64598 5.70518 5.75311 2.138E-07 1.603E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 298 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 299 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 47 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.410E-04 0.058 1.000 8.431E-05 0.175 3.000 6.099E-05 0.292 5.000 3.725E-05 0.584 10.000 2.386E-05 0.876 15.000 1.695E-05 1.168 20.000 1.287E-05 1.459 25.000 1.021E-05 1.751 30.000 8.375E-06 2.043 35.000 7.053E-06 2.335 40.000 6.043E-06 2.627 45.000 5.250E-06 2.919 50.000 4.612E-06 3.211 55.000 4.090E-06 3.503 60.000 3.656E-06 3.794 65.000 3.385E-06 4.086 70.000 3.163E-06 4.378 75.000 4.221E-05 0.5 8.57 ANNUAL AVERAGE = 5.22E-07 3 to ULNRC-06696 Page 300 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 48 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.011 1.964 2.360 4.392 5.599 5.980 7.567 9.496 11.211 12.672 0.04487 0.08716 0.10475 0.19497 0.24853 0.26545 0.33593 0.42156 0.49768 0.56252 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 12.862 13.942 14.069 16.038 16.041 17.438 19.915 21.503 22.455 22.519 0.57098 0.61891 0.62454 0.71194 0.71209 0.77411 0.88406 0.95455 0.99684 0.99965 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.773 25.631 26.012 30.331 30.902 38.841 40.937 43.096 43.477 49.002 1.01093 1.13780 1.15472 1.34643 1.37180 1.72421 1.81725 1.91310 1.93002 2.17530 5.552E-06 4.541E-06 3.596E-06 3.117E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.299E-06 49.066 62.530 75.295 75.358 84.123 84.250 87.743 87.997 89.267 91.172 2.17812 2.77580 3.34248 3.34530 3.73436 3.74000 3.89506 3.90634 3.96272 4.04730 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 93.522 93.586 94.602 95.300 95.364 96.189 97.142 97.587 97.650 98.158 4.15161 4.15443 4.19954 4.23055 4.23337 4.27002 4.31231 4.33205 4.33487 4.35742 1.611E-07 1.603E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 301 of 456 98.349 98.603 98.857 99.619 99.873 100.000 4.36588 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 302 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 49 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.649E-04 0.044 1.000 9.905E-05 0.133 3.000 7.585E-05 0.222 5.000 4.891E-05 0.444 10.000 3.301E-05 0.666 15.000 2.255E-05 0.888 20.000 1.673E-05 1.110 25.000 1.302E-05 1.332 30.000 1.049E-05 1.554 35.000 8.690E-06 1.776 40.000 7.422E-06 1.998 45.000 6.430E-06 2.220 50.000 5.636E-06 2.442 55.000 4.988E-06 2.664 60.000 4.451E-06 2.885 65.000 4.000E-06 3.107 70.000 3.617E-06 3.329 75.000 3.251E-06 3.551 80.000 4.519E-05 0.5 11.26 ANNUAL AVERAGE = 4.98E-07 3 to ULNRC-06696 Page 303 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 50 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.116 1.762 2.369 4.593 5.668 6.314 8.752 10.852 13.076 14.151 0.04389 0.06926 0.09314 0.18054 0.22283 0.24820 0.34406 0.42663 0.51402 0.55631 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 14.223 15.801 16.374 19.817 19.822 21.041 23.694 25.057 26.204 26.491 0.55913 0.62116 0.64371 0.77904 0.77922 0.82715 0.93146 0.98503 1.03014 1.04142 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 29.360 29.934 35.671 36.962 45.424 48.006 49.727 50.229 54.604 54.819 1.15419 1.17674 1.40228 1.45303 1.78571 1.88720 1.95486 1.97460 2.14658 2.15503 4.541E-06 4.164E-06 3.896E-06 3.596E-06 2.987E-06 2.557E-06 1.948E-06 1.917E-06 1.534E-06 1.299E-06 69.736 69.951 70.023 81.139 86.446 88.167 88.812 90.390 90.892 93.402 2.74144 2.74990 2.75272 3.18971 3.39834 3.46600 3.49137 3.55340 3.57313 3.67181 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 94.621 94.693 95.267 95.410 95.554 96.701 98.207 98.566 98.637 98.781 3.71974 3.72256 3.74511 3.75075 3.75639 3.80150 3.86070 3.87480 3.87762 3.88326 1.611E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 304 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 305 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 51 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.727E-04 0.039 1.000 1.020E-04 0.118 3.000 7.838E-05 0.197 5.000 5.312E-05 0.393 10.000 3.976E-05 0.590 15.000 2.980E-05 0.786 20.000 2.109E-05 0.983 25.000 1.640E-05 1.179 30.000 1.319E-05 1.376 35.000 1.089E-05 1.572 40.000 9.161E-06 1.769 45.000 7.805E-06 1.966 50.000 6.732E-06 2.162 55.000 5.871E-06 2.359 60.000 5.167E-06 2.555 65.000 4.585E-06 2.752 70.000 4.096E-06 2.948 75.000 3.682E-06 3.145 80.000 3.139E-06 3.342 85.000 4.611E-05 0.5 12.72 ANNUAL AVERAGE = 4.93E-07 3 to ULNRC-06696 Page 306 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 52 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.660 1.542 2.198 3.642 4.364 5.408 6.130 8.509 10.355 10.836 0.02318 0.05419 0.07720 0.12795 0.15332 0.18997 0.21535 0.29893 0.36378 0.38069 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 12.602 13.083 16.935 16.941 18.546 21.756 23.200 24.404 24.805 28.096 0.44272 0.45963 0.59496 0.59514 0.65153 0.76430 0.81505 0.85734 0.87143 0.98702 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 4.541E-06 3.596E-06 29.139 35.639 36.121 43.584 46.954 49.121 49.362 55.862 72.956 83.789 1.02368 1.25204 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.94361 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 87.722 87.802 89.166 89.728 90.450 92.777 94.623 95.506 95.666 95.827 3.08175 3.08457 3.13250 3.15223 3.17761 3.25937 3.32421 3.35522 3.36086 3.36650 4.871E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.603E-07 1.209E-07 9.668E-08 95.907 96.790 98.074 98.876 99.037 99.197 99.438 99.519 99.679 99.920 3.36932 3.40033 3.44544 3.47363 3.47927 3.48491 3.49337 3.49619 3.50183 3.51028 8.057E-08 3 to ULNRC-06696 Page 307 of 456 100.000 3.51310 3 to ULNRC-06696 Page 308 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 53 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.398E-04 0.035 1.000 8.921E-05 0.105 3.000 6.898E-05 0.176 5.000 4.631E-05 0.351 10.000 3.349E-05 0.527 15.000 2.500E-05 0.703 20.000 1.905E-05 0.878 25.000 1.509E-05 1.054 30.000 1.234E-05 1.230 35.000 1.033E-05 1.405 40.000 8.806E-06 1.581 45.000 7.641E-06 1.757 50.000 6.720E-06 1.932 55.000 5.966E-06 2.108 60.000 5.341E-06 2.284 65.000 4.814E-06 2.459 70.000 4.336E-06 2.635 75.000 3.890E-06 2.810 80.000 3.499E-05 0.5 14.23 ANNUAL AVERAGE = 4.11E-07 3 to ULNRC-06696 Page 309 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 54 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.532 1.334 1.963 3.245 3.645 4.446 5.007 7.469 9.792 9.952 0.01874 0.04693 0.06908 0.11419 0.12828 0.15647 0.17621 0.26285 0.34461 0.35025 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 10.032 11.955 12.676 15.800 15.805 17.808 20.051 21.012 21.974 22.054 0.35307 0.42073 0.44611 0.55606 0.55623 0.62671 0.70565 0.73948 0.77331 0.77613 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.214 25.338 25.979 33.509 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.89172 0.91428 1.17929 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 4.541E-06 3.596E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.299E-06 9.741E-07 7.793E-07 74.846 85.981 90.787 90.868 92.390 93.030 93.351 95.193 96.475 97.036 2.63404 3.02592 3.19508 3.19790 3.25146 3.27402 3.28529 3.35014 3.39525 3.41498 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.207E-07 2.566E-07 1.611E-07 1.603E-07 1.209E-07 9.668E-08 97.196 97.276 97.356 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.42062 3.42344 3.42626 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 310 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 55 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.302E-04 0.035 1.000 8.475E-05 0.106 3.000 6.553E-05 0.176 5.000 4.458E-05 0.352 10.000 3.163E-05 0.528 15.000 2.275E-05 0.704 20.000 1.776E-05 0.880 25.000 1.444E-05 1.056 30.000 1.208E-05 1.232 35.000 1.031E-05 1.408 40.000 8.955E-06 1.584 45.000 3.315E-05 0.5 14.21 ANNUAL AVERAGE = 3.97E-07 3 to ULNRC-06696 Page 311 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 56 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.455 1.240 1.846 2.752 3.176 4.143 4.626 6.965 9.201 9.322 0.02120 0.05786 0.08608 0.12837 0.14810 0.19321 0.21577 0.32484 0.42915 0.43479 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 10.773 11.257 14.461 14.465 15.795 18.575 19.482 20.570 20.752 24.318 0.50245 0.52500 0.67443 0.67463 0.73666 0.86634 0.90863 0.95938 0.96784 1.13418 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 4.541E-06 24.802 32.479 33.204 43.299 46.321 50.251 51.097 57.444 57.867 74.914 1.15673 1.51478 1.54861 2.01943 2.16040 2.34365 2.38312 2.67914 2.69888 3.49392 3.596E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.299E-06 1.026E-06 9.741E-07 7.793E-07 85.492 91.174 91.235 92.202 92.504 92.746 94.318 94.378 95.648 96.675 3.98729 4.25230 4.25512 4.30023 4.31433 4.32561 4.39891 4.40173 4.46093 4.50886 6.494E-07 6.414E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.209E-07 9.668E-08 8.057E-08 97.038 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.52577 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 312 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 57 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.226E-04 0.047 1.000 7.884E-05 0.140 3.000 6.173E-05 0.233 5.000 4.216E-05 0.466 10.000 2.901E-05 0.700 15.000 2.101E-05 0.933 20.000 1.662E-05 1.166 25.000 1.364E-05 1.399 30.000 1.150E-05 1.632 35.000 9.895E-06 1.866 40.000 8.625E-06 2.099 45.000 7.587E-06 2.332 50.000 6.743E-06 2.565 55.000 6.045E-06 2.798 60.000 5.459E-06 3.032 65.000 4.962E-06 3.265 70.000 4.532E-06 3.498 75.000 4.046E-06 3.731 80.000 3.633E-06 3.964 85.000 3.964E-05 0.5 10.72 ANNUAL AVERAGE = 5.03E-07 3 to ULNRC-06696 Page 313 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 58 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 1.078 1.748 2.927 3.272 3.933 4.709 7.213 9.168 9.714 0.04931 0.10570 0.17148 0.28707 0.32091 0.38575 0.46187 0.70753 0.89924 0.95281 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.887 11.956 12.244 16.268 16.271 17.392 21.617 24.290 25.526 25.555 0.96972 1.17271 1.20090 1.59560 1.59591 1.70586 2.12030 2.38249 2.50372 2.50654 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 25.584 29.866 29.924 30.499 39.898 40.473 53.810 55.764 59.673 60.420 2.50936 2.92943 2.93507 2.99146 3.91336 3.96975 5.27790 5.46961 5.85303 5.92633 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.596E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 65.307 65.451 78.989 79.046 86.347 88.445 88.589 88.905 89.106 89.135 6.40561 6.41971 7.74759 7.75323 8.46933 8.67513 8.68923 8.72024 8.73998 8.74279 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 91.981 93.878 94.424 94.510 94.568 95.602 96.723 97.126 97.183 97.586 9.02190 9.20798 9.26154 9.27000 9.27564 9.37713 9.48709 9.52656 9.53219 9.57166 1.603E-07 1.209E-07 9.668E-08 8.057E-08 3 to ULNRC-06696 Page 314 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 315 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 59 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.268E-04 0.098 1.000 8.108E-05 0.294 3.000 6.272E-05 0.490 5.000 4.274E-05 0.981 10.000 3.209E-05 1.471 15.000 2.457E-05 1.962 20.000 1.939E-05 2.452 25.000 1.584E-05 2.943 30.000 1.329E-05 3.433 35.000 1.138E-05 3.923 40.000 1.040E-05 4.414 45.000 9.578E-06 4.904 50.000 8.700E-06 5.395 55.000 7.477E-06 5.885 60.000 6.487E-06 6.376 65.000 5.675E-06 6.866 70.000 5.000E-06 7.356 75.000 4.393E-06 7.847 80.000 3.749E-06 8.337 85.000 6.210E-05 0.5 5.10 ANNUAL AVERAGE = 1.13E-06 3 to ULNRC-06696 Page 316 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 60 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.676 1.073 1.374 2.698 3.514 3.868 5.192 6.069 6.886 8.630 0.08630 0.13704 0.17547 0.34463 0.44894 0.49405 0.66321 0.77534 0.87965 1.10237 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.186E-05 1.937E-05 11.212 11.830 12.602 12.735 14.699 14.700 15.428 20.482 20.505 32.643 1.43223 1.51117 1.60984 1.62676 1.87768 1.87786 1.97089 2.61651 2.61933 4.16993 1.824E-05 1.748E-05 1.666E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.563E-06 9.035E-06 33.040 33.062 35.181 36.351 36.395 36.638 40.610 40.897 40.919 54.867 4.22068 4.22350 4.49415 4.64357 4.64921 4.68022 5.18770 5.22435 5.22716 7.00895 8.308E-06 7.650E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.596E-06 3.331E-06 55.750 55.772 63.055 65.990 69.213 70.360 77.952 78.460 83.955 83.999 7.12172 7.12454 8.05491 8.42987 8.84149 8.98809 9.95792 10.02277 10.72477 10.73041 3.117E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.299E-06 9.741E-07 8.552E-07 7.793E-07 84.021 87.089 87.155 88.524 89.098 89.782 91.900 93.556 93.578 94.196 10.73323 11.12511 11.13356 11.30836 11.38166 11.46906 11.73971 11.95116 11.95398 12.03292 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.896E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 3 to ULNRC-06696 Page 317 of 456 94.460 94.549 94.747 95.829 95.851 96.976 97.506 97.771 98.279 98.455 12.06675 12.07803 12.10340 12.24154 12.24436 12.38815 12.45581 12.48964 12.55449 12.57704 1.209E-07 9.668E-08 8.057E-08 6.043E-08 4.834E-08 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 318 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 61 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.360E-04 0.128 1.000 7.806E-05 0.383 3.000 6.086E-05 0.639 5.000 4.236E-05 1.277 10.000 3.308E-05 1.916 15.000 2.736E-05 2.555 20.000 2.346E-05 3.194 25.000 2.060E-05 3.832 30.000 1.684E-05 4.471 35.000 1.404E-05 5.110 40.000 1.196E-05 5.748 45.000 1.032E-05 6.387 50.000 9.006E-06 7.026 55.000 8.009E-06 7.665 60.000 7.052E-06 8.303 65.000 6.869E-05 0.5 3.91 ANNUAL AVERAGE = 1.30E-06 3 to ULNRC-06696 Page 319 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 62 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.418 0.929 1.105 1.884 2.287 2.690 3.388 4.185 4.776 5.770 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.35555 0.43913 0.50116 0.60547 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 6.630 6.872 7.248 7.275 7.490 8.403 8.405 8.996 11.495 17.836 0.69569 0.72106 0.76053 0.76335 0.78591 0.88176 0.88195 0.94397 1.20616 1.87152 1.824E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.275E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 18.347 21.651 21.732 22.619 23.022 23.049 23.452 25.520 25.709 33.984 1.92508 2.27185 2.28031 2.37335 2.41564 2.41846 2.46075 2.67783 2.69757 3.56591 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.896E-06 3.596E-06 3.331E-06 35.086 46.129 52.765 55.076 58.918 64.829 66.576 66.602 72.514 72.540 3.68150 4.84022 5.53658 5.77904 6.18220 6.80244 6.98570 6.98852 7.60876 7.61158 3.117E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.534E-06 1.299E-06 9.741E-07 7.793E-07 72.567 77.592 77.753 81.326 81.649 86.566 86.996 89.038 90.945 91.859 7.61440 8.14160 8.15852 8.53348 8.56732 9.08325 9.12835 9.34262 9.54279 9.63864 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.896E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 3 to ULNRC-06696 Page 320 of 456 92.719 92.826 93.605 94.841 94.895 95.755 96.507 97.501 97.958 98.307 9.72886 9.74014 9.82190 9.95158 9.95722 10.04744 10.12638 10.23069 10.27862 10.31527 1.283E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 4.834E-08 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 321 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 63 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.110E-04 0.105 1.000 6.346E-05 0.315 3.000 4.718E-05 0.525 5.000 2.983E-05 1.049 10.000 2.212E-05 1.574 15.000 1.773E-05 2.099 20.000 1.443E-05 2.623 25.000 1.196E-05 3.148 30.000 1.015E-05 3.673 35.000 8.777E-06 4.197 40.000 7.695E-06 4.722 45.000 6.891E-06 5.246 50.000 6.240E-06 5.771 55.000 4.855E-05 0.5 4.77 ANNUAL AVERAGE = 7.84E-07 3 to ULNRC-06696 Page 322 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 64 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.344 0.763 0.992 1.411 1.704 1.997 2.835 3.744 4.246 4.959 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19083 0.25199 0.28582 0.33375 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 5.503 5.587 6.131 6.508 8.142 8.144 8.898 11.662 16.605 17.065 0.37040 0.37604 0.41269 0.43807 0.54802 0.54814 0.59889 0.78496 1.11764 1.14865 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 19.704 19.788 20.710 20.961 21.422 23.809 24.144 33.150 34.113 43.705 1.32626 1.33190 1.39393 1.41084 1.44186 1.60255 1.62511 2.23125 2.29610 2.94171 6.384E-06 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.596E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 48.019 50.533 52.501 59.329 59.999 68.208 73.947 73.989 77.046 77.717 3.23210 3.40126 3.53376 3.99331 4.03842 4.59100 4.97724 4.98006 5.18586 5.23097 1.917E-06 1.534E-06 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.896E-07 79.727 79.895 83.078 85.466 87.644 88.733 88.816 89.319 90.408 90.618 5.36630 5.37758 5.59184 5.75254 5.89914 5.97244 5.97808 6.01191 6.08522 6.09931 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 323 of 456 92.754 94.597 95.518 96.146 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.47146 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 324 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 65 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.811E-05 0.067 1.000 5.510E-05 0.202 3.000 4.177E-05 0.337 5.000 2.726E-05 0.673 10.000 2.078E-05 1.010 15.000 1.645E-05 1.346 20.000 1.326E-05 1.683 25.000 1.106E-05 2.019 30.000 9.450E-06 2.356 35.000 8.221E-06 2.692 40.000 7.214E-06 3.029 45.000 6.316E-06 3.365 50.000 3.300E-05 0.5 7.43 ANNUAL AVERAGE = 4.80E-07 3 to ULNRC-06696 Page 325 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 66 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.368 0.718 0.980 1.881 2.182 2.532 3.083 4.531 5.382 6.033 0.02071 0.04045 0.05521 0.10596 0.12287 0.14261 0.17362 0.25517 0.30309 0.33975 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 6.383 6.483 7.284 7.585 8.986 8.989 10.091 13.795 19.852 20.703 0.35948 0.36512 0.41023 0.42714 0.50608 0.50625 0.56827 0.77690 1.11803 1.16596 1.666E-05 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 22.105 22.255 24.008 24.558 28.062 28.663 37.975 39.576 47.136 49.489 1.24490 1.25336 1.35203 1.38304 1.58039 1.61422 2.13861 2.22883 2.65454 2.78705 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.896E-06 3.596E-06 3.117E-06 2.987E-06 2.598E-06 2.557E-06 53.093 53.694 62.254 62.404 62.454 70.414 70.514 75.821 75.921 78.874 2.99004 3.02387 3.50596 3.51442 3.51724 3.96551 3.97115 4.26999 4.27563 4.44197 1.948E-06 1.917E-06 1.534E-06 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 4.276E-07 79.425 81.177 81.327 83.430 85.683 87.285 87.985 88.035 88.186 89.487 4.47298 4.57165 4.58011 4.69852 4.82539 4.91561 4.95508 4.95790 4.96635 5.03965 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.603E-07 1.549E-07 1.283E-07 1.209E-07 9.668E-08 3 to ULNRC-06696 Page 326 of 456 91.740 93.042 93.092 93.893 94.293 94.794 94.844 94.894 96.796 98.548 5.16652 5.23982 5.24264 5.28775 5.31031 5.33850 5.34132 5.34414 5.45127 5.54995 8.057E-08 6.043E-08 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 327 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 67 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.084E-04 0.056 1.000 6.351E-05 0.169 3.000 4.737E-05 0.282 5.000 2.898E-05 0.563 10.000 2.189E-05 0.845 15.000 1.921E-05 1.126 20.000 1.489E-05 1.408 25.000 1.202E-05 1.690 30.000 9.984E-06 1.971 35.000 8.639E-06 2.253 40.000 7.795E-06 2.534 45.000 6.836E-06 2.816 50.000 5.826E-06 3.097 55.000 4.928E-06 3.379 60.000 4.214E-06 3.661 65.000 3.639E-06 3.942 70.000 3.070E-06 4.224 75.000 3.165E-05 0.5 8.88 ANNUAL AVERAGE = 4.59E-07 3 to ULNRC-06696 Page 328 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 68 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.477 1.160 1.580 2.490 2.944 3.248 3.930 6.451 8.119 8.422 0.01775 0.04313 0.05876 0.09259 0.10951 0.12078 0.14616 0.23993 0.30196 0.31324 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.498 9.863 10.393 12.516 12.519 13.808 16.082 18.963 20.934 21.389 0.31606 0.36680 0.38654 0.46548 0.46561 0.51353 0.59811 0.70525 0.77855 0.79546 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 21.616 24.800 24.952 26.089 32.078 32.684 42.690 44.207 50.650 53.076 0.80392 0.92233 0.92797 0.97026 1.19298 1.21554 1.58768 1.64407 1.88371 1.97392 6.231E-06 5.552E-06 4.541E-06 4.164E-06 3.896E-06 3.596E-06 3.331E-06 2.987E-06 2.598E-06 2.557E-06 56.715 57.018 65.963 66.342 66.418 72.937 73.089 77.865 77.940 80.442 2.10925 2.12053 2.45320 2.46730 2.47012 2.71258 2.71821 2.89583 2.89865 2.99169 1.948E-06 1.917E-06 1.534E-06 1.299E-06 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 81.124 83.323 83.626 85.824 87.795 87.871 88.856 89.615 89.690 90.069 3.01706 3.09882 3.11010 3.19185 3.26516 3.26798 3.30463 3.33282 3.33564 3.34973 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 1.549E-07 1.209E-07 9.668E-08 8.057E-08 3 to ULNRC-06696 Page 329 of 456 91.434 92.798 94.087 94.315 94.997 95.452 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.53299 3.54990 3.55554 3.62320 3.66549 3.70778 6.043E-08 100.000 3.71906 3 to ULNRC-06696 Page 330 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 69 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.216E-04 0.037 1.000 7.504E-05 0.112 3.000 5.829E-05 0.186 5.000 3.740E-05 0.372 10.000 2.540E-05 0.558 15.000 1.910E-05 0.744 20.000 1.540E-05 0.930 25.000 1.290E-05 1.116 30.000 1.106E-05 1.302 35.000 9.661E-06 1.488 40.000 8.529E-06 1.674 45.000 7.590E-06 1.860 50.000 6.550E-06 2.045 55.000 5.543E-06 2.231 60.000 4.684E-06 2.417 65.000 2.824E-05 0.5 13.44 ANNUAL AVERAGE = 3.67E-07 3 to ULNRC-06696 Page 331 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 70 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.274 0.599 0.899 1.494 1.764 2.521 2.900 4.699 6.105 6.430 0.01430 0.03122 0.04685 0.07786 0.09196 0.13143 0.15116 0.24494 0.31824 0.33516 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 6.538 7.241 7.674 8.701 8.704 10.110 11.949 13.842 14.762 15.086 0.34080 0.37745 0.40000 0.45357 0.45372 0.52702 0.62288 0.72155 0.76948 0.78640 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 15.194 17.412 17.466 18.115 21.414 21.793 31.636 33.475 41.642 44.455 0.79204 0.90763 0.91045 0.94428 1.11625 1.13599 1.64910 1.74495 2.17067 2.31727 6.231E-06 5.552E-06 5.195E-06 4.541E-06 4.164E-06 3.596E-06 3.331E-06 2.987E-06 2.598E-06 2.557E-06 50.079 51.107 51.161 60.464 60.680 67.603 67.657 74.310 74.418 79.177 2.61048 2.66404 2.66686 3.15178 3.16305 3.52392 3.52674 3.87351 3.87915 4.12725 1.948E-06 1.917E-06 1.534E-06 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 4.276E-07 79.989 83.829 84.207 86.316 88.155 89.075 89.724 89.778 90.048 91.076 4.16954 4.36971 4.38944 4.49940 4.59525 4.64318 4.67701 4.67983 4.69393 4.74749 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 1.549E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 332 of 456 92.428 93.780 94.267 94.646 94.916 94.970 96.484 98.053 99.351 99.946 4.81797 4.88846 4.91383 4.93356 4.94766 4.95048 5.02942 5.11118 5.17884 5.20985 3.936E-08 100.000 5.21267 3 to ULNRC-06696 Page 333 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 71 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.966E-05 0.052 1.000 6.272E-05 0.156 3.000 4.979E-05 0.261 5.000 2.741E-05 0.521 10.000 1.805E-05 0.782 15.000 1.393E-05 1.043 20.000 1.132E-05 1.303 25.000 9.513E-06 1.564 30.000 8.437E-06 1.824 35.000 7.695E-06 2.085 40.000 6.933E-06 2.346 45.000 6.241E-06 2.606 50.000 5.330E-06 2.867 55.000 4.601E-06 3.128 60.000 2.863E-05 0.5 9.59 ANNUAL AVERAGE = 4.09E-07 3 to ULNRC-06696 Page 334 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 72 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.541 0.759 1.192 2.195 3.023 3.328 4.374 6.675 8.331 8.942 0.03501 0.04911 0.07712 0.14196 0.19553 0.21526 0.28292 0.43175 0.53888 0.57835 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.072 10.075 10.598 13.257 13.260 14.829 17.662 19.580 21.193 21.498 0.58681 0.65165 0.68548 0.85746 0.85765 0.95914 1.14239 1.26644 1.37076 1.39049 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 24.157 24.506 28.603 29.126 36.449 38.192 41.287 42.725 47.433 47.825 1.56247 1.58502 1.85003 1.88387 2.35751 2.47028 2.67045 2.76348 3.06797 3.09334 4.541E-06 3.596E-06 2.987E-06 2.557E-06 1.948E-06 1.917E-06 1.534E-06 1.299E-06 9.741E-07 7.793E-07 58.940 69.140 76.724 81.344 82.172 84.831 84.875 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.26137 5.31493 5.48691 5.48973 5.61942 5.73501 5.79139 6.494E-07 4.871E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.603E-07 1.209E-07 9.668E-08 90.323 90.759 91.457 93.069 94.028 94.682 95.162 95.380 96.600 98.649 5.84214 5.87033 5.91544 6.01975 6.08178 6.12407 6.15508 6.16918 6.24812 6.38062 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 335 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 336 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 73 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.261E-04 0.065 1.000 7.611E-05 0.194 3.000 5.914E-05 0.323 5.000 3.878E-05 0.647 10.000 2.675E-05 0.970 15.000 1.956E-05 1.294 20.000 1.481E-05 1.617 25.000 1.170E-05 1.940 30.000 9.541E-06 2.264 35.000 7.953E-06 2.587 40.000 6.747E-06 2.911 45.000 5.808E-06 3.234 50.000 5.059E-06 3.557 55.000 4.451E-06 3.881 60.000 3.949E-06 4.204 65.000 3.518E-06 4.528 70.000 3.112E-06 4.851 75.000 4.720E-05 0.5 7.73 ANNUAL AVERAGE = 6.18E-07 3 to ULNRC-06696 Page 337 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 74 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.620 0.788 1.178 2.401 3.329 3.582 4.806 6.697 7.793 8.932 0.04142 0.05270 0.07875 0.16051 0.22254 0.23945 0.32121 0.44761 0.52091 0.59703 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.691 10.619 11.125 13.909 13.912 15.220 18.847 20.450 21.842 21.969 0.64778 0.70980 0.74363 0.92971 0.92991 1.01730 1.25976 1.36690 1.45993 1.46839 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 23.993 24.626 29.898 30.447 38.123 39.810 42.679 43.480 47.360 47.740 1.60372 1.64600 1.99842 2.03507 2.54818 2.66095 2.85266 2.90622 3.16560 3.19097 4.541E-06 4.164E-06 3.596E-06 3.331E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 1.534E-06 59.761 59.803 69.758 69.800 78.025 78.151 83.044 83.424 85.490 85.533 3.99447 3.99729 4.66264 4.66546 5.21522 5.22368 5.55071 5.57609 5.71423 5.71705 1.299E-06 9.741E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 87.051 88.991 89.793 90.468 90.510 90.974 91.691 93.462 94.812 95.192 5.81855 5.94823 6.00180 6.04691 6.04973 6.08074 6.12867 6.24708 6.33729 6.36267 1.611E-07 1.603E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 338 of 456 95.360 95.571 96.837 98.482 99.494 100.000 6.37394 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 339 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 75 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.314E-04 0.067 1.000 7.626E-05 0.201 3.000 5.811E-05 0.334 5.000 3.885E-05 0.668 10.000 2.818E-05 1.003 15.000 2.106E-05 1.337 20.000 1.586E-05 1.671 25.000 1.249E-05 2.005 30.000 1.016E-05 2.339 35.000 8.426E-06 2.674 40.000 7.085E-06 3.008 45.000 6.049E-06 3.342 50.000 5.229E-06 3.676 55.000 4.568E-06 4.010 60.000 4.027E-06 4.345 65.000 3.576E-06 4.679 70.000 3.191E-06 5.013 75.000 4.643E-05 0.5 7.48 ANNUAL AVERAGE = 6.39E-07 3 to ULNRC-06696 Page 340 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 76 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 0.932 1.140 1.783 2.298 2.684 3.970 5.257 6.501 7.745 0.03304 0.06123 0.07491 0.11720 0.15103 0.17640 0.26098 0.34559 0.42735 0.50911 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.174 8.345 8.645 9.546 9.548 10.106 12.207 15.681 16.582 16.796 0.53730 0.54858 0.56831 0.62752 0.62764 0.66429 0.80244 1.03080 1.09000 1.10410 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 16.925 18.726 18.898 22.629 22.972 31.893 33.137 37.168 38.112 41.586 1.11256 1.23097 1.24224 1.48752 1.51008 2.09649 2.17825 2.44326 2.50528 2.73365 5.552E-06 4.541E-06 4.164E-06 3.596E-06 3.331E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 1.917E-06 41.886 53.766 53.809 68.305 68.348 77.055 77.098 82.544 82.630 86.018 2.75338 3.53432 3.53714 4.49006 4.49288 5.06519 5.06801 5.42606 5.43170 5.65442 1.534E-06 1.299E-06 9.741E-07 7.793E-07 6.494E-07 4.871E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 86.404 87.948 89.707 91.422 92.537 92.795 93.224 95.239 96.912 97.384 5.67980 5.78129 5.89688 6.00965 6.08295 6.09987 6.12806 6.26057 6.37052 6.40153 1.611E-07 1.603E-07 1.549E-07 1.209E-07 9.668E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 341 of 456 97.427 97.984 98.027 98.499 99.228 99.528 100.000 6.40435 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 342 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 77 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.193E-04 0.066 1.000 6.899E-05 0.197 3.000 5.249E-05 0.329 5.000 3.206E-05 0.657 10.000 2.046E-05 0.986 15.000 1.501E-05 1.315 20.000 1.183E-05 1.643 25.000 9.676E-06 1.972 30.000 8.124E-06 2.301 35.000 6.955E-06 2.629 40.000 6.047E-06 2.958 45.000 5.323E-06 3.287 50.000 4.733E-06 3.615 55.000 4.244E-06 3.944 60.000 3.833E-06 4.273 65.000 3.464E-06 4.601 70.000 3.115E-06 4.930 75.000 4.146E-05 0.5 7.61 ANNUAL AVERAGE = 5.20E-07 3 to ULNRC-06696 Page 343 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 78 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 4023.0 METERS.
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
3.497E-04 2.331E-04 1.748E-04 1.530E-04 1.399E-04 1.166E-04 1.020E-04 8.742E-05 7.650E-05 6.662E-05 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 6.120E-05 5.828E-05 5.100E-05 4.442E-05 4.371E-05 3.825E-05 3.497E-05 3.331E-05 3.068E-05 2.665E-05 9.495 10.110 12.275 12.625 12.743 15.904 15.906 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 15.90640 16.99464 16.99746 17.92783 2.550E-05 2.221E-05 2.186E-05 2.045E-05 1.913E-05 1.748E-05 1.666E-05 1.534E-05 1.530E-05 1.275E-05 22.089 24.282 24.285 24.421 25.357 25.359 30.149 30.668 30.747 30.750 22.08909 24.28249 24.28531 24.42064 25.35664 25.35946 30.14942 30.66817 30.74711 30.74993 1.227E-05 1.110E-05 1.023E-05 9.563E-06 8.328E-06 7.670E-06 7.650E-06 6.662E-06 5.552E-06 5.195E-06 31.232 41.015 42.698 42.701 48.325 52.396 52.399 54.550 55.450 55.452 31.23202 41.01494 42.69805 42.70087 48.32534 52.39639 52.39921 54.55032 55.44968 55.45250 5.113E-06 4.164E-06 3.896E-06 3.835E-06 3.331E-06 3.117E-06 3.068E-06 2.598E-06 2.557E-06 1.948E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.581 84.669 85.134 66.17422 66.52383 66.53793 75.54835 75.57090 75.58500 81.49986 81.58162 84.66873 85.13391 1.917E-06 1.534E-06 1.299E-06 1.026E-06 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 87.141 87.302 89.411 89.413 91.221 91.238 92.272 92.861 92.932 93.205 87.14124 87.30194 89.41076 89.41358 91.22075 91.23766 92.27234 92.86156 92.93204 93.20551 4.276E-07 3.896E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.603E-07 1.549E-07 1.283E-07 3 to ULNRC-06696 Page 344 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.245 97.482 97.496 97.513 94.13587 94.15842 95.51168 96.42796 96.44205 96.90723 97.24554 97.48236 97.49646 97.51337 1.209E-07 9.668E-08 8.057E-08 6.043E-08 4.834E-08 3.936E-08 98.345 99.179 99.777 99.991 99.997 100.000 98.34506 99.17957 99.77725 99.99152 99.99715 99.99998 3 to ULNRC-06696 Page 345 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 79 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.635E-04 1.000 1.000 1.440E-04 3.000 3.000 1.025E-04 5.000 5.000 6.067E-05 10.000 10.000 4.091E-05 15.000 15.000 2.899E-05 20.000 20.000 2.169E-05 25.000 25.000 1.678E-05 30.000 30.000 1.391E-05 35.000 35.000 1.166E-05 40.000 40.000 9.828E-06 45.000 45.000 8.310E-06 50.000 50.000 7.138E-06 55.000 55.000 6.206E-06 60.000 60.000 5.369E-06 65.000 65.000 4.609E-06 70.000 70.000 3.909E-06 75.000 75.000 3.257E-06 80.000 80.000 1.025E-04 5.0 5.00 3 to ULNRC-06696 Page 346 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 80 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.558 1.057 1.441 2.551 3.143 3.620 4.610 6.259 7.573 8.472 0.55822 1.05723 1.44065 2.55145 3.14350 3.61996 4.60953 6.25881 7.57260 8.47195 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.186E-05 9.087 9.205 10.228 10.231 10.581 12.746 12.749 13.837 16.997 17.000 9.08655 9.20496 10.22836 10.23118 10.58077 12.74598 12.74880 13.83704 16.99746 17.00028 1.937E-05 1.824E-05 1.748E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.275E-05 1.246E-05 1.140E-05 21.162 22.092 22.095 23.031 23.166 25.359 25.438 25.441 25.960 30.750 21.16154 22.09190 22.09472 23.03072 23.16603 25.35944 25.43838 25.44120 25.95995 30.74991 9.969E-06 9.563E-06 9.035E-06 8.308E-06 7.650E-06 7.482E-06 6.384E-06 6.231E-06 5.552E-06 5.195E-06 31.232 31.235 41.018 42.701 42.704 48.328 50.479 54.550 55.450 55.452 31.23201 31.23483 41.01775 42.70085 42.70367 48.32814 50.47926 54.55030 55.44965 55.45247 4.541E-06 4.164E-06 3.896E-06 3.596E-06 3.331E-06 3.117E-06 2.987E-06 2.598E-06 2.557E-06 1.948E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.582 84.669 85.134 66.17419 66.52380 66.53792 75.54835 75.57092 75.58502 81.49989 81.58167 84.66878 85.13396 1.917E-06 1.534E-06 1.299E-06 1.026E-06 9.741E-07 8.552E-07 7.793E-07 6.494E-07 6.414E-07 4.871E-07 87.141 87.302 89.411 89.414 91.221 91.238 92.272 92.862 92.932 93.206 87.14131 87.30202 89.41084 89.41366 91.22083 91.23776 92.27245 92.86166 92.93217 93.20565 4.276E-07 3.896E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.603E-07 1.549E-07 1.283E-07 3 to ULNRC-06696 Page 347 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.246 97.482 97.497 97.513 94.13601 94.15857 95.51183 96.42812 96.44222 96.90741 97.24574 97.48257 97.49668 97.51360 1.209E-07 9.668E-08 8.057E-08 6.043E-08 4.834E-08 3.936E-08 98.345 99.180 99.777 99.992 99.997 100.000 98.34529 99.17982 99.77751 99.99179 99.99744 100.00026 3 to ULNRC-06696 Page 348 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 81 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00026 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.283E-04 1.000 1.000 7.634E-05 3.000 3.000 5.798E-05 5.000 5.000 3.694E-05 10.000 10.000 2.657E-05 15.000 15.000 2.046E-05 20.000 20.000 1.551E-05 25.000 25.000 1.288E-05 30.000 30.000 1.091E-05 35.000 35.000 9.322E-06 40.000 40.000 8.148E-06 45.000 45.000 7.176E-06 50.000 50.000 6.331E-06 55.000 55.000 5.574E-06 60.000 60.000 4.885E-06 65.000 65.000 4.251E-06 70.000 70.000 3.659E-06 75.000 75.000 3.140E-06 80.000 80.000 5.798E-05 5.0 5.00 3 to ULNRC-06696 Page 349 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 82 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE BOUNDARY (LPZ)
BUILDING WAKE CREDIT ALLOWED: C= 0.5 A= 171. D= 16.2 RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX LPZ AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 4023. 4.22E-05 2.04E-05 1.42E-05 6.46E-06 2.08E-06 5.22E-07 21.3 S SSW 4023. 4.52E-05 2.14E-05 1.48E-05 6.58E-06 2.06E-06 4.98E-07 321.2 SSW SW 4023. 4.61E-05 2.18E-05 1.50E-05 6.63E-06 2.06E-06 4.93E-07 21.9 SW WSW 4023. 3.50E-05 1.68E-05 1.16E-05 5.24E-06 1.67E-06 4.11E-07 15.5 WSW W 4023. 3.31E-05 1.59E-05 1.11E-05 5.00E-06 1.60E-06 3.97E-07 14.1 W WNW 4023. 3.96E-05 1.93E-05 1.34E-05 6.13E-06 1.99E-06 5.03E-07 16.4 WNW NW 4023. 6.21E-05 3.20E-05 2.30E-05 1.12E-05 3.99E-06 1.13E-06 35.9 NW NNW 4023. 6.87E-05 3.57E-05 2.57E-05 1.26E-05 4.54E-06 1.30E-06 43.7 NNW N 4023. 4.86E-05 2.45E-05 1.75E-05 8.33E-06 2.88E-06 7.84E-07 23.9 N NNE 4023. 3.30E-05 1.64E-05 1.16E-05 5.41E-06 1.82E-06 4.80E-07 11.8 NNE NE 4023. 3.17E-05 1.57E-05 1.11E-05 5.19E-06 1.74E-06 4.59E-07 12.8 NE ENE 4023. 2.82E-05 1.38E-05 9.62E-06 4.41E-06 1.44E-06 3.67E-07 11.7 ENE E 4023. 2.86E-05 1.42E-05 9.98E-06 4.66E-06 1.56E-06 4.09E-07 11.1 E ESE 4023. 4.72E-05 2.30E-05 1.61E-05 7.40E-06 2.42E-06 6.18E-07 21.0 ESE SE 4023. 4.64E-05 2.29E-05 1.60E-05 7.44E-06 2.47E-06 6.39E-07 21.4 SE SSE 4023. 4.15E-05 2.01E-05 1.40E-05 6.38E-06 2.07E-06 5.20E-07 17.4 SSE MAX X/Q 6.87E-05 3.57E-05 2.57E-05 1.26E-05 4.54E-06 TOTAL HOURS: 621.2 SRP 2.3.4 4023. 1.03E-04 4.98E-05 3.47E-05 1.59E-05 5.15E-06 1.30E-06 SITE LIMIT 5.80E-05 3.10E-05 2.26E-05 1.14E-05 4.31E-06 1.30E-06 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 350 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 83 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.710 1.241 1.527 3.169 3.507 4.183 5.388 6.596 7.658 7.900 0.04142 0.07243 0.08915 0.18501 0.20474 0.24421 0.31455 0.38503 0.44705 0.46115 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 9.059 9.061 9.351 10.607 11.766 12.877 13.022 13.118 14.712 17.513 0.52881 0.52898 0.54589 0.61920 0.68686 0.75170 0.76016 0.76580 0.85884 1.02235 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 18.093 19.010 20.362 20.894 25.337 32.967 34.223 37.700 38.231 38.280 1.05619 1.10975 1.18869 1.21970 1.47908 1.92452 1.99783 2.20081 2.23183 2.23465 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 38.328 41.853 41.902 51.706 65.759 79.427 79.716 87.250 90.438 91.887 2.23747 2.44327 2.44609 3.01841 3.83882 4.63668 4.65359 5.09340 5.27947 5.36405 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 92.128 92.225 93.432 93.529 95.171 95.992 96.475 96.716 97.730 98.551 5.37815 5.38379 5.45427 5.45991 5.55576 5.60369 5.63188 5.64598 5.70518 5.75311 2.380E-06 1.785E-06 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 351 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 352 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 84 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.877E-04 0.058 1.000 2.353E-04 0.175 3.000 1.834E-04 0.292 5.000 1.181E-04 0.584 10.000 8.421E-05 0.876 15.000 6.613E-05 1.168 20.000 5.482E-05 1.459 25.000 4.682E-05 1.751 30.000 4.084E-05 2.043 35.000 3.616E-05 2.335 40.000 3.239E-05 2.627 45.000 2.929E-05 2.919 50.000 2.671E-05 3.211 55.000 2.451E-05 3.503 60.000 2.263E-05 3.794 65.000 2.099E-05 4.086 70.000 1.955E-05 4.378 75.000 1.828E-05 4.670 80.000 1.712E-05 4.962 85.000 1.345E-04 0.5 8.57 ANNUAL AVERAGE = 9.11E-06 3 to ULNRC-06696 Page 353 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 85 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.011 1.964 2.360 4.392 4.773 5.980 7.909 9.496 11.211 11.402 0.04487 0.08716 0.10475 0.19497 0.21188 0.26545 0.35107 0.42156 0.49768 0.50613 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 12.481 12.484 12.611 14.072 16.041 17.438 17.692 17.756 19.343 21.820 0.55406 0.55421 0.55985 0.62469 0.71209 0.77411 0.78539 0.78821 0.85869 0.96864 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 22.773 23.154 26.012 26.583 30.902 38.841 40.937 43.096 43.477 43.540 1.01093 1.02785 1.15472 1.18009 1.37180 1.72421 1.81725 1.91310 1.93002 1.93284 2.949E-05 2.799E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 49.066 49.129 62.593 62.720 75.485 84.250 84.504 87.997 89.267 91.172 2.17812 2.18094 2.77862 2.78426 3.35094 3.74000 3.75128 3.90634 3.96272 4.04730 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 91.236 93.586 93.649 94.665 95.364 96.189 97.142 97.587 98.095 98.349 4.05012 4.15443 4.15725 4.20236 4.23337 4.27002 4.31231 4.33205 4.35460 4.36588 1.086E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 354 of 456 98.412 98.603 98.857 99.619 99.873 100.000 4.36870 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 355 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 86 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.513E-04 0.044 1.000 2.795E-04 0.133 3.000 2.203E-04 0.222 5.000 1.564E-04 0.444 10.000 1.062E-04 0.666 15.000 8.010E-05 0.888 20.000 6.497E-05 1.110 25.000 5.463E-05 1.332 30.000 4.702E-05 1.554 35.000 4.118E-05 1.776 40.000 3.652E-05 1.998 45.000 3.271E-05 2.220 50.000 2.956E-05 2.442 55.000 2.692E-05 2.664 60.000 2.466E-05 2.885 65.000 2.272E-05 3.107 70.000 2.103E-05 3.329 75.000 1.954E-05 3.551 80.000 1.804E-05 3.773 85.000 1.467E-04 0.5 11.26 ANNUAL AVERAGE = 8.67E-06 3 to ULNRC-06696 Page 356 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 87 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 1.116 1.762 2.369 4.593 5.238 6.314 8.414 10.852 13.076 13.147 0.04389 0.06926 0.09314 0.18054 0.20592 0.24820 0.33077 0.42663 0.51402 0.51684 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 14.725 14.730 15.303 16.379 19.822 21.041 21.328 22.690 25.344 26.491 0.57887 0.57905 0.60161 0.64390 0.77922 0.82715 0.83843 0.89199 0.99631 1.04142 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 27.065 29.934 31.224 36.962 45.424 48.006 49.727 50.229 50.301 50.516 1.06397 1.17674 1.22749 1.45303 1.78571 1.88720 1.95486 1.97460 1.97742 1.98588 2.949E-05 2.572E-05 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 54.891 55.106 70.023 81.139 86.446 87.091 88.812 90.390 92.900 93.402 2.15785 2.16631 2.75272 3.18971 3.39834 3.42371 3.49137 3.55340 3.65207 3.67181 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.086E-06 93.474 94.693 94.836 95.410 95.554 96.701 98.207 98.566 98.709 98.781 3.67463 3.72256 3.72819 3.75075 3.75639 3.80150 3.86070 3.87480 3.88044 3.88326 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 357 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 358 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 88 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 4.698E-04 0.039 1.000 2.955E-04 0.118 3.000 2.347E-04 0.197 5.000 1.687E-04 0.393 10.000 1.293E-04 0.590 15.000 9.733E-05 0.786 20.000 7.496E-05 0.983 25.000 6.291E-05 1.179 30.000 5.423E-05 1.376 35.000 4.756E-05 1.572 40.000 4.227E-05 1.769 45.000 3.794E-05 1.966 50.000 3.382E-05 2.162 55.000 3.041E-05 2.359 60.000 2.753E-05 2.555 65.000 2.509E-05 2.752 70.000 2.298E-05 2.948 75.000 2.115E-05 3.145 80.000 1.902E-05 3.342 85.000 1.496E-04 0.5 12.72 ANNUAL AVERAGE = 8.56E-06 3 to ULNRC-06696 Page 359 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 89 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.660 1.542 2.198 3.642 4.685 5.408 7.787 8.509 10.355 12.120 0.02318 0.05419 0.07720 0.12795 0.16460 0.18997 0.27356 0.29893 0.36378 0.42580 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 12.126 12.607 13.089 16.941 18.546 18.947 20.391 23.601 24.805 25.849 0.42599 0.44290 0.45982 0.59514 0.65153 0.66563 0.71637 0.82914 0.87143 0.90808 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 2.412E-05 2.332E-05 29.139 29.620 36.121 43.584 46.954 49.121 49.362 55.862 72.956 73.036 1.02368 1.04059 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.56582 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 8.746E-06 7.140E-06 6.997E-06 5.831E-06 83.870 87.802 88.364 89.728 90.450 92.777 94.623 94.784 95.666 95.827 2.94643 3.08457 3.10431 3.15223 3.17761 3.25937 3.32421 3.32985 3.36086 3.36650 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.086E-06 7.243E-07 5.432E-07 4.346E-07 96.710 96.790 98.074 98.876 99.037 99.117 99.278 99.519 99.679 99.920 3.39751 3.40033 3.44544 3.47363 3.47927 3.48209 3.48773 3.49619 3.50183 3.51028 3.621E-07 3 to ULNRC-06696 Page 360 of 456 100.000 3.51310 3 to ULNRC-06696 Page 361 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 90 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.900E-04 0.035 1.000 2.599E-04 0.105 3.000 2.095E-04 0.176 5.000 1.504E-04 0.351 10.000 1.089E-04 0.527 15.000 8.527E-05 0.703 20.000 7.019E-05 0.878 25.000 5.988E-05 1.054 30.000 5.219E-05 1.230 35.000 4.623E-05 1.405 40.000 4.146E-05 1.581 45.000 3.746E-05 1.757 50.000 3.372E-05 1.932 55.000 3.059E-05 2.108 60.000 2.794E-05 2.284 65.000 2.567E-05 2.459 70.000 2.369E-05 2.635 75.000 2.196E-05 2.810 80.000 1.138E-04 0.5 14.23 ANNUAL AVERAGE = 7.18E-06 3 to ULNRC-06696 Page 362 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 91 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.532 1.334 1.963 3.245 4.046 4.446 6.908 6.988 7.549 9.872 0.01874 0.04693 0.06908 0.11419 0.14238 0.15647 0.24312 0.24594 0.26567 0.34743 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 11.795 11.800 12.521 12.681 15.805 17.808 17.968 18.048 19.009 21.253 0.41509 0.41526 0.44064 0.44628 0.55623 0.62671 0.63235 0.63517 0.66900 0.74794 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 2.949E-05 22.214 22.855 25.979 26.540 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.80432 0.91428 0.93401 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 8.746E-06 7.140E-06 74.846 74.926 86.061 90.868 91.508 93.030 93.351 95.193 96.475 96.555 2.63404 2.63686 3.02874 3.19790 3.22045 3.27402 3.28529 3.35014 3.39525 3.39807 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 97.116 97.276 97.597 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.41780 3.42344 3.43472 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 363 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 92 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.684E-04 0.035 1.000 2.482E-04 0.106 3.000 1.999E-04 0.176 5.000 1.459E-04 0.352 10.000 1.030E-04 0.528 15.000 7.830E-05 0.704 20.000 6.579E-05 0.880 25.000 5.771E-05 1.056 30.000 5.154E-05 1.232 35.000 4.663E-05 1.408 40.000 4.263E-05 1.584 45.000 3.930E-05 1.760 50.000 3.567E-05 1.936 55.000 3.221E-05 2.112 60.000 2.928E-05 2.288 65.000 2.679E-05 2.464 70.000 2.463E-05 2.639 75.000 2.275E-05 2.815 80.000 2.110E-05 2.991 85.000 1.080E-04 0.5 14.21 ANNUAL AVERAGE = 6.94E-06 3 to ULNRC-06696 Page 364 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 93 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.180E-04 0.455 1.240 1.846 2.752 3.720 4.143 6.481 6.965 9.201 10.652 0.02120 0.05786 0.08608 0.12837 0.17348 0.19321 0.30228 0.32484 0.42915 0.49681 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 10.657 11.140 11.261 14.465 15.795 15.976 16.883 19.664 20.752 21.235 0.49702 0.51957 0.52521 0.67463 0.73666 0.74511 0.78740 0.91709 0.96784 0.99039 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 2.412E-05 24.802 25.527 33.204 43.299 46.321 50.251 51.097 51.520 57.867 74.914 1.15673 1.19056 1.54861 2.01943 2.16040 2.34365 2.38312 2.40285 2.69888 3.49392 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 1.142E-05 8.746E-06 7.140E-06 74.974 85.553 91.235 91.537 92.504 92.746 94.318 94.378 95.648 95.708 3.49674 3.99011 4.25512 4.26922 4.31433 4.32560 4.39891 4.40173 4.46093 4.46375 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 96.736 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.51168 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 365 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 94 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.565E-04 0.047 1.000 2.418E-04 0.140 3.000 1.943E-04 0.233 5.000 1.371E-04 0.466 10.000 9.510E-05 0.700 15.000 7.293E-05 0.933 20.000 6.282E-05 1.166 25.000 5.543E-05 1.399 30.000 4.974E-05 1.632 35.000 4.519E-05 1.866 40.000 4.146E-05 2.099 45.000 3.834E-05 2.332 50.000 3.457E-05 2.565 55.000 3.137E-05 2.798 60.000 2.865E-05 3.032 65.000 2.631E-05 3.265 70.000 2.428E-05 3.498 75.000 2.250E-05 3.731 80.000 2.093E-05 3.964 85.000 1.289E-04 0.5 10.72 ANNUAL AVERAGE = 8.80E-06 3 to ULNRC-06696 Page 366 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 95 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 1.078 1.748 2.927 3.588 3.933 6.437 7.213 9.168 9.340 0.04931 0.10570 0.17148 0.28707 0.35192 0.38575 0.63141 0.70753 0.89924 0.91616 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 11.410 11.413 11.701 12.247 16.271 17.392 17.420 17.449 17.507 20.180 1.11914 1.11945 1.14764 1.20121 1.59591 1.70586 1.70868 1.71150 1.71714 1.97933 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 24.405 25.641 26.216 30.499 31.074 40.473 53.810 55.764 59.673 60.420 2.39377 2.51500 2.57138 2.99146 3.04784 3.96975 5.27790 5.46961 5.85303 5.92633 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 60.564 65.451 65.508 79.046 79.190 86.491 88.589 88.790 89.106 89.135 5.94043 6.41971 6.42534 7.75323 7.76732 8.48342 8.68923 8.70896 8.73998 8.74279 1.166E-05 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 91.981 93.878 93.935 94.481 94.568 95.602 96.723 97.126 97.183 97.212 9.02190 9.20798 9.21361 9.26718 9.27564 9.37713 9.48708 9.52655 9.53219 9.53501 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3 to ULNRC-06696 Page 367 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 368 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 96 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.581E-04 0.098 1.000 2.384E-04 0.294 3.000 1.928E-04 0.490 5.000 1.390E-04 0.981 10.000 1.044E-04 1.471 15.000 8.513E-05 1.962 20.000 7.255E-05 2.452 25.000 6.395E-05 2.943 30.000 5.729E-05 3.433 35.000 5.197E-05 3.923 40.000 4.758E-05 4.414 45.000 4.390E-05 4.904 50.000 4.075E-05 5.395 55.000 3.787E-05 5.885 60.000 3.334E-05 6.376 65.000 2.958E-05 6.866 70.000 2.641E-05 7.356 75.000 2.371E-05 7.847 80.000 2.140E-05 8.337 85.000 1.912E-04 0.5 5.10 ANNUAL AVERAGE = 1.97E-05 3 to ULNRC-06696 Page 369 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 97 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.676 1.073 1.374 2.698 3.051 3.868 4.745 5.363 6.687 7.504 0.08630 0.13704 0.17547 0.34463 0.38974 0.49405 0.60618 0.68512 0.85428 0.95859 1.363E-04 1.254E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 1.003E-04 9.834E-05 8.620E-05 7.763E-05 10.086 10.108 10.881 10.882 11.015 12.758 12.780 14.744 15.473 17.591 1.28845 1.29126 1.38994 1.39012 1.40704 1.62976 1.63258 1.88349 1.97653 2.24718 7.705E-05 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 5.679E-05 4.718E-05 4.543E-05 4.310E-05 17.635 29.774 34.828 35.225 35.468 36.638 36.660 36.947 36.969 40.941 2.25282 3.80343 4.44904 4.49979 4.53080 4.68022 4.68304 4.71969 4.72251 5.22998 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 54.889 55.772 63.055 65.990 67.138 70.360 70.382 70.890 78.482 78.548 7.01177 7.12454 8.05491 8.42987 8.57647 8.98809 8.99091 9.05575 10.02559 10.03404 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.520E-06 8.746E-06 7.140E-06 84.044 84.088 87.155 87.729 89.098 89.782 91.900 91.922 93.578 93.666 10.73604 10.74168 11.13356 11.20687 11.38166 11.46906 11.73971 11.74253 11.95398 11.96525 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 3 to ULNRC-06696 Page 370 of 456 94.284 94.549 95.630 95.829 96.954 96.976 97.506 97.771 97.948 98.455 12.04419 12.07803 12.21617 12.24154 12.38533 12.38815 12.45581 12.48964 12.51220 12.57704 5.432E-07 4.346E-07 3.621E-07 2.716E-07 2.173E-07 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 371 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 98 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.811E-04 0.128 1.000 2.328E-04 0.383 3.000 1.816E-04 0.639 5.000 1.366E-04 1.277 10.000 1.054E-04 1.916 15.000 9.384E-05 2.555 20.000 8.541E-05 3.194 25.000 7.888E-05 3.832 30.000 7.330E-05 4.471 35.000 6.182E-05 5.110 40.000 5.299E-05 5.748 45.000 4.602E-05 6.387 50.000 4.046E-05 7.026 55.000 3.901E-05 7.665 60.000 3.681E-05 8.303 65.000 2.049E-04 0.5 3.91 ANNUAL AVERAGE = 2.25E-05 3 to ULNRC-06696 Page 372 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 99 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.418 0.929 1.105 1.884 2.287 2.690 3.486 3.513 3.755 4.454 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.36583 0.36865 0.39403 0.46733 1.475E-04 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 5.045 5.905 6.281 6.283 6.498 7.492 8.405 8.996 9.077 12.382 0.52935 0.61957 0.65904 0.65922 0.68178 0.78609 0.88195 0.94397 0.95243 1.29920 7.705E-05 7.690E-05 7.572E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 12.785 19.126 19.153 21.651 22.162 22.565 23.452 23.640 25.709 33.984 1.34149 2.00684 2.00966 2.27185 2.32542 2.36771 2.46075 2.48048 2.69757 3.56591 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 35.086 46.129 52.765 52.792 56.634 58.945 58.972 60.718 66.629 66.791 3.68150 4.84022 5.53658 5.53940 5.94256 6.18502 6.18784 6.37109 6.99133 7.00825 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 72.702 72.728 77.753 78.075 81.649 86.566 88.608 89.038 90.945 91.053 7.62849 7.63131 8.15852 8.19235 8.56732 9.08324 9.29751 9.34262 9.54279 9.55406 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 3 to ULNRC-06696 Page 373 of 456 91.966 92.826 94.062 94.841 95.701 95.755 96.507 97.501 97.851 97.985 9.64992 9.74014 9.86982 9.95158 10.04180 10.04744 10.12638 10.23069 10.26734 10.28144 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 2.173E-07 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 374 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 100 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.094E-04 0.105 1.000 1.857E-04 0.315 3.000 1.481E-04 0.525 5.000 9.293E-05 1.049 10.000 7.699E-05 1.574 15.000 7.576E-05 2.099 20.000 6.622E-05 2.623 25.000 5.755E-05 3.148 30.000 5.093E-05 3.673 35.000 4.569E-05 4.197 40.000 4.142E-05 4.722 45.000 3.786E-05 5.246 50.000 3.505E-05 5.771 55.000 3.072E-05 6.296 60.000 2.632E-05 6.820 65.000 2.275E-05 7.345 70.000 1.981E-05 7.870 75.000 1.512E-04 0.5 4.77 ANNUAL AVERAGE = 1.37E-05 3 to ULNRC-06696 Page 375 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 101 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.344 0.763 0.992 1.411 1.704 1.997 2.906 2.990 3.828 4.330 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19561 0.20125 0.25763 0.29146 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 4.875 5.419 5.421 5.798 6.510 8.144 8.898 8.981 11.620 11.872 0.32811 0.36476 0.36489 0.39026 0.43819 0.54814 0.59889 0.60453 0.78214 0.79906 7.690E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 16.814 19.579 20.039 20.500 21.422 21.757 24.144 33.150 34.113 43.705 1.13173 1.31781 1.34882 1.37983 1.44186 1.46441 1.62511 2.23125 2.29610 2.94171 3.614E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 48.019 49.988 52.501 53.171 59.999 60.041 68.250 73.989 74.659 77.717 3.23210 3.36461 3.53376 3.57887 4.03842 4.04123 4.59381 4.98006 5.02517 5.23097 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 79.727 82.910 83.078 85.466 85.549 87.727 88.816 89.905 90.408 92.544 5.36630 5.58056 5.59184 5.75254 5.75818 5.90478 5.97808 6.05138 6.08522 6.22900 3.499E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 376 of 456 92.754 94.597 95.518 95.979 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.46018 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 377 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 102 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.940E-04 0.067 1.000 1.768E-04 0.202 3.000 1.349E-04 0.337 5.000 8.599E-05 0.673 10.000 7.713E-05 1.010 15.000 7.259E-05 1.346 20.000 6.130E-05 1.683 25.000 5.317E-05 2.019 30.000 4.700E-05 2.356 35.000 4.214E-05 2.692 40.000 3.818E-05 3.029 45.000 1.047E-04 0.5 7.43 ANNUAL AVERAGE = 8.44E-06 3 to ULNRC-06696 Page 378 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 103 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.520E-04 1.497E-04 1.475E-04 0.368 0.718 0.980 1.881 2.232 2.532 3.980 4.080 4.631 5.482 0.02071 0.04045 0.05521 0.10596 0.12569 0.14261 0.22415 0.22979 0.26081 0.30873 1.363E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 5.832 6.633 6.636 6.937 7.588 8.989 10.091 10.241 11.642 17.700 0.32847 0.37358 0.37374 0.39066 0.42731 0.50625 0.56827 0.57673 0.65567 0.99680 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 21.404 22.255 22.806 24.558 25.159 28.663 37.975 39.576 47.136 49.489 1.20543 1.25336 1.28437 1.38304 1.41688 1.61422 2.13861 2.22883 2.65454 2.78705 3.499E-05 3.429E-05 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 1.842E-05 1.749E-05 49.539 50.139 53.744 53.844 53.994 62.554 62.655 70.614 75.921 76.471 2.78987 2.82370 3.02669 3.03232 3.04078 3.52288 3.52852 3.97678 4.27563 4.30664 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 79.425 81.177 83.280 83.430 85.683 85.733 87.335 88.035 89.337 89.487 4.47298 4.57165 4.69006 4.69852 4.82539 4.82821 4.91843 4.95790 5.03120 5.03965 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3 to ULNRC-06696 Page 379 of 456 91.740 93.042 93.843 94.343 94.393 94.443 94.493 94.894 96.796 98.548 5.16652 5.23982 5.28493 5.31312 5.31594 5.31876 5.32158 5.34414 5.45127 5.54995 3.621E-07 2.716E-07 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 380 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 104 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.069E-04 0.056 1.000 1.951E-04 0.169 3.000 1.543E-04 0.282 5.000 9.507E-05 0.563 10.000 8.329E-05 0.845 15.000 7.552E-05 1.126 20.000 6.518E-05 1.408 25.000 5.618E-05 1.690 30.000 4.940E-05 1.971 35.000 4.408E-05 2.253 40.000 3.979E-05 2.534 45.000 3.558E-05 2.816 50.000 3.077E-05 3.097 55.000 2.689E-05 3.379 60.000 2.371E-05 3.661 65.000 2.106E-05 3.942 70.000 1.880E-05 4.224 75.000 9.937E-05 0.5 8.88 ANNUAL AVERAGE = 8.06E-06 3 to ULNRC-06696 Page 381 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 105 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.477 1.160 1.580 2.490 2.793 3.248 5.769 6.451 8.119 8.195 0.01775 0.04313 0.05876 0.09259 0.10387 0.12078 0.21456 0.23993 0.30196 0.30478 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 9.560 9.563 10.094 10.397 12.519 13.808 14.036 14.490 14.642 17.523 0.35553 0.35566 0.37539 0.38667 0.46561 0.51353 0.52199 0.53891 0.54455 0.65168 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 19.797 21.768 22.905 26.089 26.695 32.684 42.690 44.207 50.650 53.076 0.73626 0.80956 0.85185 0.97026 0.99281 1.21554 1.58768 1.64407 1.88371 1.97392 3.499E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 53.152 53.455 57.094 57.473 66.418 66.494 73.013 73.165 77.940 78.623 1.97674 1.98802 2.12335 2.13744 2.47012 2.47294 2.71540 2.72103 2.89865 2.92402 1.665E-05 1.248E-05 1.166E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 81.124 83.323 85.521 85.824 85.900 87.871 87.947 88.932 89.690 91.055 3.01706 3.09882 3.18058 3.19186 3.19467 3.26798 3.27080 3.30745 3.33564 3.38639 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3 to ULNRC-06696 Page 382 of 456 91.434 92.798 94.087 94.315 94.769 94.921 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.52453 3.53017 3.55554 3.62321 3.66549 3.70778 2.716E-07 100.000 3.71906 3 to ULNRC-06696 Page 383 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 106 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.479E-04 0.037 1.000 2.278E-04 0.112 3.000 1.835E-04 0.186 5.000 1.216E-04 0.372 10.000 8.794E-05 0.558 15.000 7.326E-05 0.744 20.000 6.310E-05 0.930 25.000 5.568E-05 1.116 30.000 4.997E-05 1.302 35.000 4.542E-05 1.488 40.000 4.169E-05 1.674 45.000 3.856E-05 1.860 50.000 3.402E-05 2.045 55.000 2.930E-05 2.231 60.000 2.550E-05 2.417 65.000 2.238E-05 2.603 70.000 1.977E-05 2.789 75.000 9.412E-05 0.5 13.44 ANNUAL AVERAGE = 6.43E-06 3 to ULNRC-06696 Page 384 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 107 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.274 0.599 0.899 1.494 2.251 2.521 4.320 4.699 6.105 6.213 0.01430 0.03122 0.04685 0.07786 0.11733 0.13143 0.22521 0.24494 0.31824 0.32388 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.705E-05 7.690E-05 6.916 6.919 7.352 7.677 8.704 10.110 10.219 10.543 10.597 12.490 0.36053 0.36069 0.38324 0.40016 0.45372 0.52702 0.53266 0.54958 0.55240 0.65107 7.375E-05 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.665E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 14.329 15.249 15.898 18.115 18.494 18.548 21.847 31.690 33.529 41.696 0.74693 0.79486 0.82869 0.94428 0.96401 0.96683 1.13881 1.65192 1.74777 2.17349 3.614E-05 3.429E-05 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 44.509 45.536 51.161 51.377 60.680 60.788 67.711 67.765 74.418 75.229 2.32009 2.37366 2.66686 2.67814 3.16305 3.16869 3.52956 3.53238 3.87915 3.92144 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 79.989 83.829 85.938 86.316 88.155 88.209 89.129 89.778 90.806 91.076 4.16954 4.36971 4.47966 4.49940 4.59525 4.59807 4.64600 4.67983 4.73340 4.74749 3.570E-06 2.856E-06 2.380E-06 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 3.534E-07 3 to ULNRC-06696 Page 385 of 456 92.428 93.780 94.267 94.537 94.591 94.970 96.484 98.053 99.351 99.405 4.81797 4.88846 4.91383 4.92793 4.93075 4.95048 5.02942 5.11118 5.17884 5.18166 2.716E-07 100.000 5.21267 3 to ULNRC-06696 Page 386 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 108 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.939E-04 0.052 1.000 1.981E-04 0.156 3.000 1.615E-04 0.261 5.000 8.724E-05 0.521 10.000 7.183E-05 0.782 15.000 6.066E-05 1.043 20.000 5.297E-05 1.303 25.000 4.727E-05 1.564 30.000 4.283E-05 1.824 35.000 3.926E-05 2.085 40.000 3.564E-05 2.346 45.000 3.118E-05 2.606 50.000 2.757E-05 2.867 55.000 2.461E-05 3.128 60.000 2.212E-05 3.388 65.000 2.002E-05 3.649 70.000 9.129E-05 0.5 9.59 ANNUAL AVERAGE = 7.22E-06 3 to ULNRC-06696 Page 387 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 109 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.541 0.759 1.192 2.195 2.500 3.328 5.629 6.675 8.331 8.462 0.03501 0.04911 0.07712 0.14196 0.16169 0.21526 0.36408 0.43175 0.53888 0.54734 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.465 9.468 9.991 10.601 13.260 14.829 15.134 17.052 19.885 21.498 0.61218 0.61237 0.64620 0.68567 0.85765 0.95914 0.97888 1.10292 1.28618 1.39049 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 21.847 24.506 25.029 29.126 36.449 38.192 41.287 42.725 43.118 47.825 1.41305 1.58502 1.61885 1.88387 2.35751 2.47028 2.67045 2.76348 2.78886 3.09334 2.412E-05 2.077E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 9.987E-06 8.746E-06 6.997E-06 58.940 69.140 76.724 77.552 82.173 84.831 86.836 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.01609 5.31493 5.48691 5.61660 5.61942 5.73501 5.79139 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 1.785E-06 7.243E-07 5.432E-07 4.346E-07 90.323 91.021 91.457 93.070 94.028 94.682 94.900 95.380 96.600 98.649 5.84214 5.88725 5.91544 6.01976 6.08178 6.12407 6.13817 6.16918 6.24812 6.38062 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 388 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 389 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 110 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.576E-04 0.065 1.000 2.309E-04 0.194 3.000 1.856E-04 0.323 5.000 1.261E-04 0.647 10.000 9.024E-05 0.970 15.000 7.339E-05 1.294 20.000 6.047E-05 1.617 25.000 5.138E-05 1.940 30.000 4.461E-05 2.264 35.000 3.936E-05 2.587 40.000 3.468E-05 2.911 45.000 3.075E-05 3.234 50.000 2.753E-05 3.557 55.000 2.485E-05 3.881 60.000 2.257E-05 4.204 65.000 2.063E-05 4.528 70.000 1.895E-05 4.851 75.000 1.527E-04 0.5 7.73 ANNUAL AVERAGE = 1.08E-05 3 to ULNRC-06696 Page 390 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 111 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.620 0.788 1.178 2.401 2.654 3.582 5.473 6.697 7.793 8.553 0.04142 0.05270 0.07875 0.16051 0.17743 0.23945 0.36585 0.44761 0.52091 0.57166 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.690E-05 7.375E-05 6.896E-05 9.480 9.483 9.990 11.128 13.912 15.220 15.346 16.949 20.577 21.969 0.63368 0.63388 0.66771 0.74383 0.92991 1.01730 1.02576 1.13290 1.37535 1.46839 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 2.949E-05 22.601 24.626 25.174 30.447 38.123 39.810 42.679 43.480 43.860 47.740 1.51068 1.64600 1.68266 2.03507 2.54818 2.66095 2.85266 2.90622 2.93160 3.19097 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 1.166E-05 47.782 59.803 59.930 69.884 69.926 78.151 78.531 83.424 85.490 87.009 3.19379 3.99729 4.00575 4.67110 4.67392 5.22368 5.24905 5.57609 5.71423 5.81573 9.987E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 87.051 88.991 89.033 89.835 90.510 91.227 91.691 93.462 94.812 95.192 5.81855 5.94823 5.95105 6.00462 6.04973 6.09765 6.12867 6.24708 6.33729 6.36267 1.785E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 391 of 456 95.402 95.571 96.837 98.482 99.494 100.000 6.37676 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 392 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 112 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.705E-04 0.067 1.000 2.313E-04 0.201 3.000 1.828E-04 0.334 5.000 1.243E-04 0.668 10.000 9.315E-05 1.003 15.000 7.535E-05 1.337 20.000 6.230E-05 1.671 25.000 5.297E-05 2.005 30.000 4.601E-05 2.339 35.000 4.062E-05 2.674 40.000 3.594E-05 3.008 45.000 3.180E-05 3.342 50.000 2.841E-05 3.676 55.000 2.559E-05 4.010 60.000 2.320E-05 4.345 65.000 2.117E-05 4.679 70.000 1.941E-05 5.013 75.000 1.777E-05 5.347 80.000 1.505E-04 0.5 7.48 ANNUAL AVERAGE = 1.12E-05 3 to ULNRC-06696 Page 393 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 113 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 1200.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.497E-04 1.475E-04 1.363E-04 0.503 0.932 1.140 1.783 2.169 2.684 3.971 5.257 6.501 6.930 0.03304 0.06123 0.07491 0.11720 0.14257 0.17640 0.26101 0.34559 0.42735 0.45554 1.180E-04 1.180E-04 1.149E-04 1.123E-04 9.834E-05 8.620E-05 7.864E-05 7.763E-05 7.690E-05 7.375E-05 7.101 7.103 7.404 8.647 9.548 10.106 10.234 10.449 13.923 16.024 0.46682 0.46694 0.48668 0.56844 0.62764 0.66429 0.67275 0.68685 0.91521 1.05335 6.896E-05 5.898E-05 5.747E-05 4.718E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.429E-05 16.925 17.096 18.898 19.241 22.972 31.893 33.137 37.168 38.112 38.412 1.11256 1.12383 1.24224 1.26480 1.51008 2.09649 2.17825 2.44326 2.50528 2.52502 2.949E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 1.248E-05 41.886 41.929 53.809 53.852 68.348 68.391 77.098 77.183 82.630 86.018 2.75338 2.75620 3.53714 3.53996 4.49288 4.49570 5.06801 5.07365 5.43170 5.65442 1.166E-05 9.987E-06 8.746E-06 6.997E-06 5.831E-06 4.760E-06 4.373E-06 3.570E-06 2.856E-06 2.380E-06 87.562 87.948 89.707 91.422 92.537 92.966 93.224 95.239 96.912 97.384 5.75592 5.78129 5.89688 6.00965 6.08295 6.11115 6.12806 6.26057 6.37052 6.40153 1.785E-06 1.009E-06 7.243E-07 5.432E-07 4.346E-07 3.621E-07 2.716E-07 3 to ULNRC-06696 Page 394 of 456 97.941 97.984 98.027 98.499 99.228 99.528 100.000 6.43818 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 395 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 114 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.407E-04 0.066 1.000 2.121E-04 0.197 3.000 1.674E-04 0.329 5.000 1.020E-04 0.657 10.000 7.727E-05 0.986 15.000 6.248E-05 1.315 20.000 5.260E-05 1.643 25.000 4.551E-05 1.972 30.000 4.014E-05 2.301 35.000 3.564E-05 2.629 40.000 3.183E-05 2.958 45.000 2.872E-05 3.287 50.000 2.613E-05 3.615 55.000 2.393E-05 3.944 60.000 2.204E-05 4.273 65.000 2.040E-05 4.601 70.000 1.897E-05 4.930 75.000 1.745E-05 5.259 80.000 1.271E-04 0.5 7.61 ANNUAL AVERAGE = 9.12E-06 3 to ULNRC-06696 Page 396 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 115 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 1200.0 METERS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
2.007E-03 1.338E-03 1.003E-03 9.087E-04 8.027E-04 6.689E-04 6.058E-04 5.017E-04 4.543E-04 4.115E-04 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 3.635E-04 3.344E-04 3.029E-04 2.743E-04 2.508E-04 2.272E-04 2.057E-04 2.007E-04 1.997E-04 1.646E-04 9.495 10.110 12.275 12.625 12.743 15.904 16.992 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 16.99183 16.99464 16.99746 17.92783 1.514E-04 1.372E-04 1.332E-04 1.254E-04 1.136E-04 1.029E-04 1.003E-04 9.987E-05 9.087E-05 7.990E-05 22.089 24.282 24.418 24.421 25.357 30.147 30.149 30.668 30.747 31.229 22.08909 24.28249 24.41782 24.42064 25.35664 30.14660 30.14942 30.66817 30.74711 31.22920 7.572E-05 6.858E-05 6.658E-05 5.679E-05 5.144E-05 4.994E-05 4.665E-05 4.543E-05 4.115E-05 3.499E-05 31.232 41.015 42.698 42.701 48.325 52.396 52.399 52.402 54.553 54.567 31.23202 41.01494 42.69805 42.70087 48.32534 52.39639 52.39921 52.40203 54.55314 54.56724 3.429E-05 3.329E-05 2.799E-05 2.572E-05 2.497E-05 2.332E-05 2.057E-05 1.997E-05 1.749E-05 1.665E-05 55.467 66.188 66.202 66.552 75.562 75.644 75.667 81.581 82.047 85.134 55.46659 66.18832 66.20242 66.55202 75.56245 75.64420 75.66676 81.58162 82.04680 85.13391 1.248E-05 1.166E-05 1.142E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14124 89.25006 89.25288 89.41358 89.43050 91.23766 91.30814 92.34282 92.93204 93.86240 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 3 to ULNRC-06696 Page 397 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13587 95.48913 95.51168 96.42796 96.89314 97.12995 97.14687 97.16096 97.17506 97.51337 5.432E-07 4.346E-07 3.621E-07 3.534E-07 2.716E-07 2.173E-07 98.345 99.179 99.777 99.780 99.994 100.000 98.34506 99.17957 99.77725 99.78008 99.99434 99.99998 3 to ULNRC-06696 Page 398 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 116 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.512E-03 1.000 1.000 8.278E-04 3.000 3.000 5.979E-04 5.000 5.000 3.602E-04 10.000 10.000 2.447E-04 15.000 15.000 1.755E-04 20.000 20.000 1.322E-04 25.000 25.000 1.036E-04 30.000 30.000 8.639E-05 35.000 35.000 7.282E-05 40.000 40.000 6.225E-05 45.000 45.000 5.387E-05 50.000 50.000 4.661E-05 55.000 55.000 4.023E-05 60.000 60.000 3.455E-05 65.000 65.000 2.977E-05 70.000 70.000 2.544E-05 75.000 75.000 5.979E-04 5.0 5.00 3 to ULNRC-06696 Page 399 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 117 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION BOUNDARY CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
4.492E-04 2.995E-04 2.950E-04 2.246E-04 1.967E-04 1.797E-04 1.724E-04 1.618E-04 1.520E-04 1.497E-04 0.558 1.057 1.441 2.551 3.028 3.620 5.269 5.272 5.390 6.380 0.55822 1.05723 1.44065 2.55145 3.02791 3.61996 5.26924 5.27206 5.39047 6.38004 1.475E-04 1.363E-04 1.254E-04 1.180E-04 1.180E-04 1.149E-04 1.123E-04 1.003E-04 9.834E-05 8.620E-05 7.694 8.308 8.311 9.335 9.337 9.687 10.586 10.589 12.754 13.843 7.69383 8.30843 8.31125 9.33465 9.33747 9.68706 10.58641 10.58922 12.75443 13.84268 7.864E-05 7.763E-05 7.705E-05 7.690E-05 7.572E-05 7.375E-05 6.896E-05 5.898E-05 5.747E-05 5.679E-05 13.978 14.914 14.993 19.154 19.157 22.317 23.248 23.767 25.960 25.963 13.97800 14.91400 14.99294 19.15420 19.15702 22.31744 23.24780 23.76655 25.95996 25.96277 4.718E-05 4.665E-05 4.543E-05 4.310E-05 4.050E-05 3.932E-05 3.819E-05 3.614E-05 3.499E-05 3.429E-05 26.445 26.448 26.450 31.240 41.023 42.706 48.331 50.482 50.496 51.395 26.44487 26.44769 26.45051 31.24047 41.02340 42.70650 48.33097 50.48209 50.49618 51.39553 2.949E-05 2.799E-05 2.572E-05 2.412E-05 2.332E-05 2.077E-05 2.057E-05 1.842E-05 1.749E-05 1.665E-05 55.466 55.481 55.830 66.552 66.634 75.644 75.667 81.581 82.047 85.134 55.46658 55.48067 55.83025 66.55198 66.63377 75.64420 75.66676 81.58163 82.04681 85.13392 1.248E-05 1.166E-05 1.142E-05 9.987E-06 9.520E-06 8.746E-06 7.140E-06 6.997E-06 5.831E-06 4.760E-06 87.141 89.250 89.253 89.413 89.430 91.238 91.308 92.343 92.932 93.862 87.14127 89.25008 89.25290 89.41361 89.43054 91.23772 91.30822 92.34290 92.93212 93.86248 4.373E-06 3.570E-06 3.499E-06 2.856E-06 2.380E-06 1.785E-06 1.428E-06 1.086E-06 1.009E-06 7.243E-07 3 to ULNRC-06696 Page 400 of 456 94.136 95.489 95.512 96.428 96.893 97.130 97.147 97.161 97.175 97.513 94.13596 95.48923 95.51179 96.42807 96.89326 97.13010 97.14702 97.16113 97.17523 97.51356 5.432E-07 4.346E-07 3.621E-07 3.534E-07 2.716E-07 2.173E-07 98.345 99.180 99.777 99.780 99.994 100.000 98.34525 99.17977 99.77747 99.78029 99.99457 100.00021 3 to ULNRC-06696 Page 401 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 118 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00021 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 3.604E-04 1.000 1.000 2.265E-04 3.000 3.000 1.771E-04 5.000 5.000 1.204E-04 10.000 10.000 9.099E-05 15.000 15.000 7.841E-05 20.000 20.000 6.689E-05 25.000 25.000 5.653E-05 30.000 30.000 4.836E-05 35.000 35.000 4.171E-05 40.000 40.000 3.922E-05 45.000 45.000 3.690E-05 50.000 50.000 3.326E-05 55.000 55.000 2.993E-05 60.000 60.000 2.684E-05 65.000 65.000 2.392E-05 70.000 70.000 2.112E-05 75.000 75.000 1.906E-05 80.000 80.000 1.771E-04 5.0 5.00 3 to ULNRC-06696 Page 402 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 119 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph SITE EXCLUSION AREA BOUNDARY (SB OR EAB)
BUILDING WAKE CREDIT IS NOT INCLUDED.
RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX SB AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 1200. 1.34E-04 8.62E-05 6.90E-05 4.26E-05 2.13E-05 9.11E-06 20.4 S SSW 1200. 1.47E-04 9.19E-05 7.28E-05 4.38E-05 2.11E-05 8.67E-06 325.0 SSW SW 1200. 1.50E-04 9.32E-05 7.36E-05 4.41E-05 2.11E-05 8.56E-06 23.0 SW WSW 1200. 1.14E-04 7.21E-05 5.73E-05 3.49E-05 1.71E-05 7.18E-06 16.2 WSW W 1200. 1.08E-04 6.86E-05 5.47E-05 3.34E-05 1.65E-05 6.94E-06 14.5 W WNW 1200. 1.29E-04 8.27E-05 6.62E-05 4.09E-05 2.05E-05 8.80E-06 18.1 WNW NW 1200. 1.91E-04 1.31E-04 1.09E-04 7.24E-05 4.03E-05 1.97E-05 37.2 NW NNW 1200. 2.05E-04 1.42E-04 1.19E-04 7.98E-05 4.52E-05 2.25E-05 43.7 NNW N 1200. 1.51E-04 1.02E-04 8.33E-05 5.42E-05 2.92E-05 1.37E-05 22.5 N NNE 1200. 1.05E-04 6.91E-05 5.61E-05 3.57E-05 1.87E-05 8.44E-06 13.0 NNE NE 1200. 9.94E-05 6.56E-05 5.33E-05 3.40E-05 1.78E-05 8.06E-06 13.2 NE ENE 1200. 9.41E-05 6.04E-05 4.84E-05 2.99E-05 1.50E-05 6.43E-06 12.6 ENE E 1200. 9.13E-05 6.00E-05 4.87E-05 3.09E-05 1.61E-05 7.22E-06 12.5 E ESE 1200. 1.53E-04 9.86E-05 7.92E-05 4.93E-05 2.49E-05 1.08E-05 22.5 ESE SE 1200. 1.51E-04 9.79E-05 7.90E-05 4.95E-05 2.53E-05 1.12E-05 22.9 SE SSE 1200. 1.27E-04 8.22E-05 6.61E-05 4.12E-05 2.09E-05 9.12E-06 18.6 SSE MAX X/Q 2.05E-04 1.42E-04 1.19E-04 7.98E-05 4.52E-05 TOTAL HOURS: 635.9 SRP 2.3.4 1200. 5.98E-04 3.48E-04 2.65E-04 1.47E-04 6.33E-05 2.25E-05 SITE LIMIT 1.77E-04 1.26E-04 1.06E-04 7.34E-05 4.32E-05 2.25E-05 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 403 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 120 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
S SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.710 1.241 1.527 3.169 3.845 4.183 5.391 6.596 7.658 8.914 0.04142 0.07243 0.08915 0.18501 0.22448 0.24421 0.31470 0.38503 0.44705 0.52035 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.155 10.314 10.604 11.763 11.766 12.877 15.678 17.272 17.851 17.948 0.53445 0.60211 0.61903 0.68669 0.68686 0.75170 0.91522 1.00826 1.04209 1.04773 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 18.093 19.445 20.362 24.805 25.337 32.967 34.223 37.700 38.231 41.757 1.05619 1.13512 1.18869 1.44807 1.47908 1.92452 1.99783 2.20081 2.23183 2.43763 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 41.805 51.609 51.657 51.706 65.759 79.427 86.961 87.250 90.438 90.679 2.44045 3.01277 3.01559 3.01841 3.83882 4.63668 5.07648 5.09340 5.27947 5.29357 1.299E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 92.128 93.335 93.432 95.074 95.895 95.992 96.233 96.716 97.730 98.551 5.37815 5.44863 5.45427 5.55012 5.59805 5.60369 5.61779 5.64598 5.70518 5.75311 2.138E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 404 of 456 99.276 99.324 99.517 99.662 99.952 100.000 5.79540 5.79822 5.80950 5.81796 5.83487 5.83769 3 to ULNRC-06696 Page 405 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 121 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.410E-04 0.058 1.000 8.431E-05 0.175 3.000 6.099E-05 0.292 5.000 3.725E-05 0.584 10.000 2.386E-05 0.876 15.000 1.695E-05 1.168 20.000 1.287E-05 1.459 25.000 1.021E-05 1.751 30.000 8.375E-06 2.043 35.000 7.053E-06 2.335 40.000 6.043E-06 2.627 45.000 5.250E-06 2.919 50.000 4.612E-06 3.211 55.000 4.090E-06 3.503 60.000 3.656E-06 3.794 65.000 3.385E-06 4.086 70.000 3.163E-06 4.378 75.000 4.221E-05 0.5 8.57 ANNUAL AVERAGE = 5.34E-07 3 to ULNRC-06696 Page 406 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 122 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.011 1.964 2.360 4.392 5.599 5.980 7.567 9.496 11.211 12.672 0.04487 0.08716 0.10475 0.19497 0.24853 0.26545 0.33593 0.42156 0.49768 0.56252 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 12.862 13.942 14.069 16.038 16.041 17.438 19.915 21.503 22.455 22.519 0.57098 0.61891 0.62454 0.71194 0.71209 0.77411 0.88406 0.95455 0.99684 0.99965 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.773 25.631 26.012 30.331 30.902 38.841 40.937 43.096 43.477 49.002 1.01093 1.13780 1.15472 1.34643 1.37180 1.72421 1.81725 1.91310 1.93002 2.17530 5.568E-06 4.541E-06 3.596E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 49.066 62.530 75.295 75.358 84.123 84.250 87.743 87.997 89.267 91.172 2.17812 2.77580 3.34248 3.34530 3.73436 3.74000 3.89506 3.90634 3.96272 4.04730 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 93.522 93.586 94.602 95.300 95.364 96.189 97.142 97.587 97.650 98.158 4.15161 4.15443 4.19954 4.23055 4.23337 4.27002 4.31231 4.33205 4.33487 4.35742 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 407 of 456 98.349 98.603 98.857 99.619 99.873 100.000 4.36588 4.37716 4.38843 4.42227 4.43354 4.43918 3 to ULNRC-06696 Page 408 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 123 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.649E-04 0.044 1.000 9.905E-05 0.133 3.000 7.585E-05 0.222 5.000 4.891E-05 0.444 10.000 3.301E-05 0.666 15.000 2.255E-05 0.888 20.000 1.673E-05 1.110 25.000 1.302E-05 1.332 30.000 1.049E-05 1.554 35.000 8.690E-06 1.776 40.000 7.422E-06 1.998 45.000 6.430E-06 2.220 50.000 5.636E-06 2.442 55.000 4.988E-06 2.664 60.000 4.451E-06 2.885 65.000 4.000E-06 3.107 70.000 3.617E-06 3.329 75.000 3.251E-06 3.551 80.000 4.519E-05 0.5 11.26 ANNUAL AVERAGE = 5.11E-07 3 to ULNRC-06696 Page 409 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 124 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 1.116 1.762 2.369 4.593 5.668 6.314 8.752 10.852 13.076 14.151 0.04389 0.06926 0.09314 0.18054 0.22283 0.24820 0.34406 0.42663 0.51402 0.55631 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 14.223 15.801 16.374 19.817 19.822 21.041 23.694 25.057 26.204 26.491 0.55913 0.62116 0.64371 0.77904 0.77922 0.82715 0.93146 0.98503 1.03014 1.04142 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 29.360 29.934 35.671 36.962 45.424 48.006 49.727 50.229 54.604 54.819 1.15419 1.17674 1.40228 1.45303 1.78571 1.88720 1.95486 1.97460 2.14658 2.15503 4.541E-06 4.176E-06 3.898E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 69.736 69.951 70.023 81.139 86.446 88.167 88.812 90.390 90.892 93.402 2.74144 2.74990 2.75272 3.18971 3.39834 3.46600 3.49137 3.55340 3.57313 3.67181 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 94.621 94.693 95.267 95.410 95.554 96.701 98.207 98.566 98.637 98.781 3.71974 3.72256 3.74511 3.75075 3.75639 3.80150 3.86070 3.87480 3.87762 3.88326 1.611E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 410 of 456 98.996 99.426 99.570 99.928 100.000 3.89171 3.90863 3.91427 3.92836 3.93118 3 to ULNRC-06696 Page 411 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 125 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph BACK EXTRAPOLATION FOR 1 PERCENTILE.
PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.727E-04 0.039 1.000 1.020E-04 0.118 3.000 7.838E-05 0.197 5.000 5.312E-05 0.393 10.000 3.976E-05 0.590 15.000 2.980E-05 0.786 20.000 2.109E-05 0.983 25.000 1.640E-05 1.179 30.000 1.319E-05 1.376 35.000 1.089E-05 1.572 40.000 9.161E-06 1.769 45.000 7.805E-06 1.966 50.000 6.732E-06 2.162 55.000 5.871E-06 2.359 60.000 5.167E-06 2.555 65.000 4.585E-06 2.752 70.000 4.096E-06 2.948 75.000 3.682E-06 3.145 80.000 3.139E-06 3.342 85.000 4.611E-05 0.5 12.72 ANNUAL AVERAGE = 5.05E-07 3 to ULNRC-06696 Page 412 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 126 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WSW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.660 1.542 2.198 3.642 4.364 5.408 6.130 8.509 10.355 10.836 0.02318 0.05419 0.07720 0.12795 0.15332 0.18997 0.21535 0.29893 0.36378 0.38069 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 12.602 13.083 16.935 16.941 18.546 21.756 23.200 24.404 24.805 28.096 0.44272 0.45963 0.59496 0.59514 0.65153 0.76430 0.81505 0.85734 0.87143 0.98702 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 4.541E-06 3.596E-06 29.139 35.639 36.121 43.584 46.954 49.121 49.362 55.862 72.956 83.789 1.02368 1.25204 1.26895 1.53115 1.64956 1.72568 1.73413 1.96250 2.56300 2.94361 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 87.722 87.802 89.166 89.728 90.450 92.777 94.623 95.506 95.666 95.827 3.08175 3.08457 3.13250 3.15223 3.17761 3.25937 3.32421 3.35522 3.36086 3.36650 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 95.907 96.790 98.074 98.876 99.037 99.197 99.438 99.519 99.679 99.920 3.36932 3.40033 3.44544 3.47363 3.47927 3.48491 3.49337 3.49619 3.50183 3.51028 8.057E-08 3 to ULNRC-06696 Page 413 of 456 100.000 3.51310 3 to ULNRC-06696 Page 414 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 127 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.398E-04 0.035 1.000 8.921E-05 0.105 3.000 6.898E-05 0.176 5.000 4.631E-05 0.351 10.000 3.349E-05 0.527 15.000 2.500E-05 0.703 20.000 1.905E-05 0.878 25.000 1.509E-05 1.054 30.000 1.234E-05 1.230 35.000 1.033E-05 1.405 40.000 8.806E-06 1.581 45.000 7.641E-06 1.757 50.000 6.720E-06 1.932 55.000 5.966E-06 2.108 60.000 5.341E-06 2.284 65.000 4.814E-06 2.459 70.000 4.336E-06 2.635 75.000 3.890E-06 2.810 80.000 3.499E-05 0.5 14.23 ANNUAL AVERAGE = 4.20E-07 3 to ULNRC-06696 Page 415 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 128 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
W SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.532 1.334 1.963 3.245 3.645 4.446 5.007 7.469 9.792 9.952 0.01874 0.04693 0.06908 0.11419 0.12828 0.15647 0.17621 0.26285 0.34461 0.35025 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 10.032 11.955 12.676 15.800 15.805 17.808 20.051 21.012 21.974 22.054 0.35307 0.42073 0.44611 0.55606 0.55623 0.62671 0.70565 0.73948 0.77331 0.77613 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 22.214 25.338 25.979 33.509 34.070 44.644 48.089 51.854 52.495 58.103 0.78177 0.89172 0.91428 1.17929 1.19902 1.57117 1.69240 1.82491 1.84746 2.04481 4.541E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 7.796E-07 74.846 85.981 90.787 90.868 92.390 93.030 93.351 95.193 96.475 97.036 2.63404 3.02592 3.19508 3.19790 3.25146 3.27402 3.28529 3.35014 3.39525 3.41498 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 97.196 97.276 97.356 97.677 98.398 99.039 99.119 99.199 99.840 100.000 3.42062 3.42344 3.42626 3.43754 3.46291 3.48546 3.48828 3.49110 3.51366 3.51929 3 to ULNRC-06696 Page 416 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 129 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.302E-04 0.035 1.000 8.475E-05 0.106 3.000 6.553E-05 0.176 5.000 4.458E-05 0.352 10.000 3.163E-05 0.528 15.000 2.275E-05 0.704 20.000 1.776E-05 0.880 25.000 1.444E-05 1.056 30.000 1.208E-05 1.232 35.000 1.031E-05 1.408 40.000 8.955E-06 1.584 45.000 3.315E-05 0.5 14.21 ANNUAL AVERAGE = 4.04E-07 3 to ULNRC-06696 Page 417 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 130 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
WNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.455 1.240 1.846 2.752 3.176 4.143 4.626 6.965 9.201 9.322 0.02120 0.05786 0.08608 0.12837 0.14810 0.19321 0.21577 0.32484 0.42915 0.43479 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 1.520E-05 10.773 11.257 14.461 14.465 15.795 18.575 19.482 20.570 20.752 24.318 0.50245 0.52500 0.67443 0.67463 0.73666 0.86634 0.90863 0.95938 0.96784 1.13418 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 24.802 32.479 33.204 43.299 46.321 50.251 51.097 57.444 57.867 74.914 1.15673 1.51478 1.54861 2.01943 2.16040 2.34365 2.38312 2.67914 2.69888 3.49392 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 1.026E-06 9.744E-07 7.796E-07 85.492 91.174 91.235 92.202 92.504 92.746 94.318 94.378 95.648 96.675 3.98729 4.25230 4.25512 4.30023 4.31433 4.32561 4.39891 4.40173 4.46093 4.50886 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.209E-07 9.669E-08 8.057E-08 97.038 97.098 97.884 98.549 98.972 99.093 99.154 99.396 99.577 100.000 4.52577 4.52859 4.56524 4.59626 4.61599 4.62163 4.62445 4.63573 4.64418 4.66392 3 to ULNRC-06696 Page 418 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 131 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.226E-04 0.047 1.000 7.884E-05 0.140 3.000 6.173E-05 0.233 5.000 4.216E-05 0.466 10.000 2.901E-05 0.700 15.000 2.101E-05 0.933 20.000 1.662E-05 1.166 25.000 1.364E-05 1.399 30.000 1.150E-05 1.632 35.000 9.895E-06 1.866 40.000 8.625E-06 2.099 45.000 7.587E-06 2.332 50.000 6.743E-06 2.565 55.000 6.045E-06 2.798 60.000 5.459E-06 3.032 65.000 4.962E-06 3.265 70.000 4.532E-06 3.498 75.000 4.046E-06 3.731 80.000 3.633E-06 3.964 85.000 3.964E-05 0.5 10.72 ANNUAL AVERAGE = 5.12E-07 3 to ULNRC-06696 Page 419 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 132 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 1.078 1.748 2.927 3.272 3.933 4.709 7.213 9.168 9.714 0.04931 0.10570 0.17148 0.28707 0.32091 0.38575 0.46187 0.70753 0.89924 0.95281 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 9.887 11.956 12.244 16.268 16.271 17.392 21.617 24.290 25.526 25.555 0.96972 1.17271 1.20090 1.59560 1.59591 1.70586 2.12030 2.38249 2.50372 2.50654 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 25.584 29.866 29.924 30.499 39.898 40.473 53.810 55.764 59.673 60.420 2.50936 2.92943 2.93507 2.99146 3.91336 3.96975 5.27790 5.46961 5.85303 5.92633 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 65.307 65.451 78.989 79.046 86.347 88.445 88.589 88.905 89.106 89.135 6.40561 6.41971 7.74759 7.75323 8.46933 8.67513 8.68923 8.72024 8.73998 8.74279 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 91.981 93.878 94.424 94.510 94.568 95.602 96.723 97.126 97.183 97.586 9.02190 9.20798 9.26154 9.27000 9.27564 9.37713 9.48709 9.52656 9.53219 9.57166 1.604E-07 1.209E-07 9.669E-08 8.057E-08 3 to ULNRC-06696 Page 420 of 456 97.614 98.965 99.713 100.000 9.57448 9.70699 9.78029 9.80848 3 to ULNRC-06696 Page 421 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 133 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.268E-04 0.098 1.000 8.108E-05 0.294 3.000 6.272E-05 0.490 5.000 4.274E-05 0.981 10.000 3.209E-05 1.471 15.000 2.457E-05 1.962 20.000 1.939E-05 2.452 25.000 1.584E-05 2.943 30.000 1.329E-05 3.433 35.000 1.138E-05 3.923 40.000 1.040E-05 4.414 45.000 9.578E-06 4.904 50.000 8.700E-06 5.395 55.000 7.477E-06 5.885 60.000 6.487E-06 6.376 65.000 5.675E-06 6.866 70.000 5.000E-06 7.356 75.000 4.393E-06 7.847 80.000 3.749E-06 8.337 85.000 6.210E-05 0.5 5.10 ANNUAL AVERAGE = 1.15E-06 3 to ULNRC-06696 Page 422 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 134 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNW SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.676 1.073 1.374 2.698 3.514 3.868 5.192 6.069 6.886 8.630 0.08630 0.13704 0.17547 0.34463 0.44894 0.49405 0.66321 0.77534 0.87965 1.10237 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.219E-05 1.937E-05 11.212 11.830 12.602 12.735 14.699 14.700 15.428 20.482 20.505 32.643 1.43223 1.51117 1.60984 1.62676 1.87768 1.87786 1.97089 2.61651 2.61933 4.16993 1.824E-05 1.775E-05 1.666E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.626E-06 9.035E-06 33.040 33.062 35.181 36.351 36.395 36.638 40.610 40.897 40.919 54.867 4.22068 4.22350 4.49415 4.64357 4.64921 4.68022 5.18770 5.22435 5.22716 7.00895 8.308E-06 7.700E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 55.750 55.772 63.055 65.990 69.213 70.360 77.952 78.460 83.955 83.999 7.12172 7.12454 8.05491 8.42987 8.84149 8.98809 9.95792 10.02277 10.72477 10.73041 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.299E-06 9.744E-07 8.553E-07 7.796E-07 84.021 87.089 87.155 88.524 89.098 89.782 91.900 93.556 93.578 94.196 10.73323 11.12511 11.13356 11.30836 11.38166 11.46906 11.73971 11.95116 11.95398 12.03292 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 3 to ULNRC-06696 Page 423 of 456 94.460 94.549 94.747 95.829 95.851 96.976 97.506 97.771 98.279 98.455 12.06675 12.07803 12.10340 12.24154 12.24436 12.38815 12.45581 12.48964 12.55449 12.57704 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 99.095 99.559 99.912 99.978 100.000 12.65880 12.71800 12.76311 12.77157 12.77439 3 to ULNRC-06696 Page 424 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 135 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.360E-04 0.128 1.000 7.806E-05 0.383 3.000 6.086E-05 0.639 5.000 4.236E-05 1.277 10.000 3.308E-05 1.916 15.000 2.736E-05 2.555 20.000 2.346E-05 3.194 25.000 2.060E-05 3.832 30.000 1.684E-05 4.471 35.000 1.404E-05 5.110 40.000 1.196E-05 5.748 45.000 1.032E-05 6.387 50.000 9.006E-06 7.026 55.000 8.009E-06 7.665 60.000 7.052E-06 8.303 65.000 6.869E-05 0.5 3.91 ANNUAL AVERAGE = 1.34E-06 3 to ULNRC-06696 Page 425 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 136 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
N SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.418 0.929 1.105 1.884 2.287 2.690 3.388 4.185 4.776 5.770 0.04389 0.09745 0.11591 0.19767 0.23996 0.28225 0.35555 0.43913 0.50116 0.60547 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 6.630 6.872 7.248 7.275 7.490 8.403 8.405 8.996 11.495 17.836 0.69569 0.72106 0.76053 0.76335 0.78591 0.88176 0.88195 0.94397 1.20616 1.87152 1.824E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.283E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 18.347 21.651 21.732 22.619 23.022 23.049 23.452 25.520 25.709 33.984 1.92508 2.27185 2.28031 2.37335 2.41564 2.41846 2.46075 2.67783 2.69757 3.56591 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 35.086 46.129 52.765 55.076 58.918 64.829 66.576 66.602 72.514 72.540 3.68150 4.84022 5.53658 5.77904 6.18220 6.80244 6.98570 6.98852 7.60876 7.61158 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 72.567 77.592 77.753 81.326 81.649 86.566 86.996 89.038 90.945 91.859 7.61440 8.14160 8.15852 8.53348 8.56732 9.08325 9.12835 9.34262 9.54279 9.63864 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 3 to ULNRC-06696 Page 426 of 456 92.719 92.826 93.605 94.841 94.895 95.755 96.507 97.501 97.958 98.307 9.72886 9.74014 9.82190 9.95158 9.95722 10.04744 10.12638 10.23069 10.27862 10.31527 1.283E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 98.442 98.710 99.301 99.624 99.973 100.000 10.32937 10.35756 10.41959 10.45342 10.49007 10.49289 3 to ULNRC-06696 Page 427 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 137 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.110E-04 0.105 1.000 6.346E-05 0.315 3.000 4.718E-05 0.525 5.000 2.983E-05 1.049 10.000 2.212E-05 1.574 15.000 1.773E-05 2.099 20.000 1.443E-05 2.623 25.000 1.196E-05 3.148 30.000 1.015E-05 3.673 35.000 8.777E-06 4.197 40.000 7.695E-06 4.722 45.000 6.891E-06 5.246 50.000 6.240E-06 5.771 55.000 4.855E-05 0.5 4.77 ANNUAL AVERAGE = 8.02E-07 3 to ULNRC-06696 Page 428 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 138 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NNE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.344 0.763 0.992 1.411 1.704 1.997 2.835 3.744 4.246 4.959 0.02318 0.05137 0.06678 0.09498 0.11471 0.13445 0.19083 0.25199 0.28582 0.33375 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 5.503 5.587 6.131 6.508 8.142 8.144 8.898 11.662 16.605 17.065 0.37040 0.37604 0.41269 0.43807 0.54802 0.54814 0.59889 0.78496 1.11764 1.14865 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 19.704 19.788 20.710 20.961 21.422 23.809 24.144 33.150 34.113 43.705 1.32626 1.33190 1.39393 1.41084 1.44186 1.60255 1.62511 2.23125 2.29610 2.94171 6.384E-06 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.596E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 48.019 50.533 52.501 59.329 59.999 68.208 73.947 73.989 77.046 77.717 3.23210 3.40126 3.53376 3.99331 4.03842 4.59100 4.97724 4.98006 5.18586 5.23097 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.898E-07 79.727 79.895 83.078 85.466 87.644 88.733 88.816 89.319 90.408 90.618 5.36630 5.37758 5.59184 5.75254 5.89914 5.97244 5.97808 6.01191 6.08522 6.09931 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 429 of 456 92.754 94.597 95.518 96.146 96.607 97.529 98.366 99.539 100.000 6.24310 6.36714 6.42917 6.47146 6.50247 6.56449 6.62088 6.69982 6.73083 3 to ULNRC-06696 Page 430 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 139 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.811E-05 0.067 1.000 5.510E-05 0.202 3.000 4.177E-05 0.337 5.000 2.726E-05 0.673 10.000 2.078E-05 1.010 15.000 1.645E-05 1.346 20.000 1.326E-05 1.683 25.000 1.106E-05 2.019 30.000 9.450E-06 2.356 35.000 8.221E-06 2.692 40.000 7.214E-06 3.029 45.000 6.316E-06 3.365 50.000 3.300E-05 0.5 7.43 ANNUAL AVERAGE = 4.90E-07 3 to ULNRC-06696 Page 431 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 140 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
NE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.368 0.718 0.980 1.881 2.182 2.532 3.083 4.531 5.382 6.033 0.02071 0.04045 0.05521 0.10596 0.12287 0.14261 0.17362 0.25517 0.30309 0.33975 3.977E-05 3.643E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 6.383 6.483 7.284 7.585 8.986 8.989 10.091 13.795 19.852 20.703 0.35948 0.36512 0.41023 0.42714 0.50608 0.50625 0.56827 0.77690 1.11803 1.16596 1.666E-05 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 22.105 22.255 24.008 24.558 28.062 28.663 37.975 39.576 47.136 49.489 1.24490 1.25336 1.35203 1.38304 1.58039 1.61422 2.13861 2.22883 2.65454 2.78705 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 53.093 53.694 62.254 62.404 62.454 70.414 70.514 75.821 75.921 78.874 2.99004 3.02387 3.50596 3.51442 3.51724 3.96551 3.97115 4.26999 4.27563 4.44197 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 79.425 81.177 81.327 83.430 85.683 87.285 87.985 88.035 88.186 89.487 4.47298 4.57165 4.58011 4.69852 4.82539 4.91561 4.95508 4.95790 4.96635 5.03965 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 1.209E-07 9.669E-08 3 to ULNRC-06696 Page 432 of 456 91.740 93.042 93.092 93.893 94.293 94.794 94.844 94.894 96.796 98.548 5.16652 5.23982 5.24264 5.28775 5.31031 5.33850 5.34132 5.34414 5.45127 5.54995 8.057E-08 6.043E-08 99.750 100.000 5.61761 5.63170 3 to ULNRC-06696 Page 433 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 141 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.084E-04 0.056 1.000 6.351E-05 0.169 3.000 4.737E-05 0.282 5.000 2.898E-05 0.563 10.000 2.189E-05 0.845 15.000 1.921E-05 1.126 20.000 1.489E-05 1.408 25.000 1.202E-05 1.690 30.000 9.984E-06 1.971 35.000 8.639E-06 2.253 40.000 7.795E-06 2.534 45.000 6.836E-06 2.816 50.000 5.826E-06 3.097 55.000 4.928E-06 3.379 60.000 4.214E-06 3.661 65.000 3.639E-06 3.942 70.000 3.070E-06 4.224 75.000 3.165E-05 0.5 8.88 ANNUAL AVERAGE = 4.68E-07 3 to ULNRC-06696 Page 434 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 142 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ENE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.477 1.160 1.580 2.490 2.944 3.248 3.930 6.451 8.119 8.422 0.01775 0.04313 0.05876 0.09259 0.10951 0.12078 0.14616 0.23993 0.30196 0.31324 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.498 9.863 10.393 12.516 12.519 13.808 16.082 18.963 20.934 21.389 0.31606 0.36680 0.38654 0.46548 0.46561 0.51353 0.59811 0.70525 0.77855 0.79546 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 21.616 24.800 24.952 26.089 32.078 32.684 42.690 44.207 50.650 53.076 0.80392 0.92233 0.92797 0.97026 1.19298 1.21554 1.58768 1.64407 1.88371 1.97392 6.231E-06 5.568E-06 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 56.715 57.018 65.963 66.342 66.418 72.937 73.089 77.865 77.940 80.442 2.10925 2.12053 2.45320 2.46730 2.47012 2.71258 2.71821 2.89583 2.89865 2.99169 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 81.124 83.323 83.626 85.824 87.795 87.871 88.856 89.615 89.690 90.069 3.01706 3.09882 3.11010 3.19185 3.26516 3.26798 3.30463 3.33282 3.33564 3.34973 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 3 to ULNRC-06696 Page 435 of 456 91.434 92.798 94.087 94.315 94.997 95.452 95.603 97.423 98.560 99.697 3.40048 3.45123 3.49916 3.50761 3.53299 3.54990 3.55554 3.62320 3.66549 3.70778 6.043E-08 100.000 3.71906 3 to ULNRC-06696 Page 436 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 143 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.216E-04 0.037 1.000 7.504E-05 0.112 3.000 5.829E-05 0.186 5.000 3.740E-05 0.372 10.000 2.540E-05 0.558 15.000 1.910E-05 0.744 20.000 1.540E-05 0.930 25.000 1.290E-05 1.116 30.000 1.106E-05 1.302 35.000 9.661E-06 1.488 40.000 8.529E-06 1.674 45.000 7.590E-06 1.860 50.000 6.550E-06 2.045 55.000 5.543E-06 2.231 60.000 4.684E-06 2.417 65.000 2.824E-05 0.5 13.44 ANNUAL AVERAGE = 3.74E-07 3 to ULNRC-06696 Page 437 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 144 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
E SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.274 0.599 0.899 1.494 1.764 2.521 2.900 4.699 6.105 6.430 0.01430 0.03122 0.04685 0.07786 0.09196 0.13143 0.15116 0.24494 0.31824 0.33516 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 6.538 7.241 7.674 8.701 8.704 10.110 11.949 13.842 14.762 15.086 0.34080 0.37745 0.40000 0.45357 0.45372 0.52702 0.62288 0.72155 0.76948 0.78640 1.662E-05 1.520E-05 1.453E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 15.194 17.412 17.466 18.115 21.414 21.793 31.636 33.475 41.642 44.455 0.79204 0.90763 0.91045 0.94428 1.11625 1.13599 1.64910 1.74495 2.17067 2.31727 6.231E-06 5.568E-06 5.197E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 50.079 51.107 51.161 60.464 60.680 67.603 67.657 74.310 74.418 79.177 2.61048 2.66404 2.66686 3.15178 3.16305 3.52392 3.52674 3.87351 3.87915 4.12725 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 79.989 83.829 84.207 86.316 88.155 89.075 89.724 89.778 90.048 91.076 4.16954 4.36971 4.38944 4.49940 4.59525 4.64318 4.67701 4.67983 4.69393 4.74749 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 438 of 456 92.428 93.780 94.267 94.646 94.916 94.970 96.484 98.053 99.351 99.946 4.81797 4.88846 4.91383 4.93356 4.94766 4.95048 5.02942 5.11118 5.17884 5.20985 3.937E-08 100.000 5.21267 3 to ULNRC-06696 Page 439 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 145 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 9.966E-05 0.052 1.000 6.272E-05 0.156 3.000 4.979E-05 0.261 5.000 2.741E-05 0.521 10.000 1.805E-05 0.782 15.000 1.393E-05 1.043 20.000 1.132E-05 1.303 25.000 9.513E-06 1.564 30.000 8.437E-06 1.824 35.000 7.695E-06 2.085 40.000 6.933E-06 2.346 45.000 6.241E-06 2.606 50.000 5.330E-06 2.867 55.000 4.601E-06 3.128 60.000 2.863E-05 0.5 9.59 ANNUAL AVERAGE = 4.16E-07 3 to ULNRC-06696 Page 440 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 146 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
ESE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.541 0.759 1.192 2.195 3.023 3.328 4.374 6.675 8.331 8.942 0.03501 0.04911 0.07712 0.14196 0.19553 0.21526 0.28292 0.43175 0.53888 0.57835 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.072 10.075 10.598 13.257 13.260 14.829 17.662 19.580 21.193 21.498 0.58681 0.65165 0.68548 0.85746 0.85765 0.95914 1.14239 1.26644 1.37076 1.39049 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 24.157 24.506 28.603 29.126 36.449 38.192 41.287 42.725 47.433 47.825 1.56247 1.58502 1.85003 1.88387 2.35751 2.47028 2.67045 2.76348 3.06797 3.09334 4.541E-06 3.596E-06 2.987E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 1.299E-06 9.744E-07 7.796E-07 58.940 69.140 76.724 81.344 82.172 84.831 84.875 86.880 88.667 89.539 3.81226 4.47197 4.96252 5.26137 5.31493 5.48691 5.48973 5.61942 5.73501 5.79139 6.496E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 1.611E-07 1.604E-07 1.209E-07 9.669E-08 90.323 90.759 91.457 93.069 94.028 94.682 95.162 95.380 96.600 98.649 5.84214 5.87033 5.91544 6.01975 6.08178 6.12407 6.15508 6.16918 6.24812 6.38062 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 441 of 456 99.913 100.000 6.46238 6.46802 3 to ULNRC-06696 Page 442 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 147 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.261E-04 0.065 1.000 7.611E-05 0.194 3.000 5.914E-05 0.323 5.000 3.878E-05 0.647 10.000 2.675E-05 0.970 15.000 1.956E-05 1.294 20.000 1.481E-05 1.617 25.000 1.170E-05 1.940 30.000 9.541E-06 2.264 35.000 7.953E-06 2.587 40.000 6.747E-06 2.911 45.000 5.808E-06 3.234 50.000 5.059E-06 3.557 55.000 4.451E-06 3.881 60.000 3.949E-06 4.204 65.000 3.518E-06 4.528 70.000 3.112E-06 4.851 75.000 4.720E-05 0.5 7.73 ANNUAL AVERAGE = 6.30E-07 3 to ULNRC-06696 Page 443 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 148 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.620 0.788 1.178 2.401 3.329 3.582 4.806 6.697 7.793 8.932 0.04142 0.05270 0.07875 0.16051 0.22254 0.23945 0.32121 0.44761 0.52091 0.59703 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.662E-05 9.691 10.619 11.125 13.909 13.912 15.220 18.847 20.450 21.842 21.969 0.64778 0.70980 0.74363 0.92971 0.92991 1.01730 1.25976 1.36690 1.45993 1.46839 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 23.993 24.626 29.898 30.447 38.123 39.810 42.679 43.480 47.360 47.740 1.60372 1.64600 1.99842 2.03507 2.54818 2.66095 2.85266 2.90622 3.16560 3.19097 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 1.536E-06 59.761 59.803 69.758 69.800 78.025 78.151 83.044 83.424 85.490 85.533 3.99447 3.99729 4.66264 4.66546 5.21522 5.22368 5.55071 5.57609 5.71423 5.71705 1.299E-06 9.744E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 87.051 88.991 89.793 90.468 90.510 90.974 91.691 93.462 94.812 95.192 5.81855 5.94823 6.00180 6.04691 6.04973 6.08074 6.12867 6.24708 6.33729 6.36267 1.611E-07 1.604E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 444 of 456 95.360 95.571 96.837 98.482 99.494 100.000 6.37394 6.38804 6.47262 6.58257 6.65023 6.68407 3 to ULNRC-06696 Page 445 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 149 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.314E-04 0.067 1.000 7.626E-05 0.201 3.000 5.811E-05 0.334 5.000 3.885E-05 0.668 10.000 2.818E-05 1.003 15.000 2.106E-05 1.337 20.000 1.586E-05 1.671 25.000 1.249E-05 2.005 30.000 1.016E-05 2.339 35.000 8.426E-06 2.674 40.000 7.085E-06 3.008 45.000 6.049E-06 3.342 50.000 5.229E-06 3.676 55.000 4.568E-06 4.010 60.000 4.027E-06 4.345 65.000 3.576E-06 4.679 70.000 3.191E-06 5.013 75.000 4.643E-05 0.5 7.48 ANNUAL AVERAGE = 6.53E-07 3 to ULNRC-06696 Page 446 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 150 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
SSE SECTOR BOUNDARY DISTANCE = 4023.0 METERS LATERAL PLUME MEANDER/BUILDING WAKE CREDIT ALLOWED AS A FUNCTION OF DOWNWIND DISTANCE.
MEANDER CREDIT IS FOR WINDSPEEDS LESS THAN 6 MPS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.503 0.932 1.140 1.783 2.298 2.684 3.970 5.257 6.501 7.745 0.03304 0.06123 0.07491 0.11720 0.15103 0.17640 0.26098 0.34559 0.42735 0.50911 3.977E-05 3.629E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 1.937E-05 1.824E-05 1.666E-05 8.174 8.345 8.645 9.546 9.548 10.106 12.207 15.681 16.582 16.796 0.53730 0.54858 0.56831 0.62752 0.62764 0.66429 0.80244 1.03080 1.09000 1.10410 1.662E-05 1.520E-05 1.246E-05 1.140E-05 9.969E-06 9.035E-06 8.308E-06 7.482E-06 6.384E-06 6.231E-06 16.925 18.726 18.898 22.629 22.972 31.893 33.137 37.168 38.112 41.586 1.11256 1.23097 1.24224 1.48752 1.51008 2.09649 2.17825 2.44326 2.50528 2.73365 5.568E-06 4.541E-06 4.176E-06 3.596E-06 3.341E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 1.920E-06 41.886 53.766 53.809 68.305 68.348 77.055 77.098 82.544 82.630 86.018 2.75338 3.53432 3.53714 4.49006 4.49288 5.06519 5.06801 5.42606 5.43170 5.65442 1.536E-06 1.299E-06 9.744E-07 7.796E-07 6.496E-07 4.872E-07 4.276E-07 3.207E-07 2.566E-07 2.138E-07 86.404 87.948 89.707 91.422 92.537 92.795 93.224 95.239 96.912 97.384 5.67980 5.78129 5.89688 6.00965 6.08295 6.09987 6.12806 6.26057 6.37052 6.40153 1.611E-07 1.604E-07 1.551E-07 1.209E-07 9.669E-08 8.057E-08 6.043E-08 3 to ULNRC-06696 Page 447 of 456 97.427 97.984 98.027 98.499 99.228 99.528 100.000 6.40435 6.44100 6.44382 6.47483 6.52276 6.54250 6.57351 3 to ULNRC-06696 Page 448 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 151 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.193E-04 0.066 1.000 6.899E-05 0.197 3.000 5.249E-05 0.329 5.000 3.206E-05 0.657 10.000 2.046E-05 0.986 15.000 1.501E-05 1.315 20.000 1.183E-05 1.643 25.000 9.676E-06 1.972 30.000 8.124E-06 2.301 35.000 6.955E-06 2.629 40.000 6.047E-06 2.958 45.000 5.323E-06 3.287 50.000 4.733E-06 3.615 55.000 4.244E-06 3.944 60.000 3.833E-06 4.273 65.000 3.464E-06 4.601 70.000 3.115E-06 4.930 75.000 4.146E-05 0.5 7.61 ANNUAL AVERAGE = 5.31E-07 3 to ULNRC-06696 Page 449 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 152 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
DIRECTION-INDEPENDENT (S.R.P 2.3.4) MODEL.
MINIMUM BOUNDARY DISTANCE = 4023.0 METERS.
BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
3.550E-04 2.367E-04 1.775E-04 1.540E-04 1.420E-04 1.183E-04 1.027E-04 8.875E-05 7.700E-05 6.681E-05 0.558 1.057 2.168 2.551 3.143 4.133 4.610 5.509 6.823 8.472 0.55822 1.05723 2.16803 2.55145 3.14350 4.13307 4.60953 5.50888 6.82267 8.47195 6.160E-05 5.916E-05 5.134E-05 4.454E-05 4.437E-05 3.850E-05 3.550E-05 3.341E-05 3.072E-05 2.673E-05 9.495 10.110 12.275 12.625 12.743 15.904 15.906 16.995 16.997 17.928 9.49535 10.10995 12.27516 12.62475 12.74316 15.90358 15.90640 16.99464 16.99746 17.92783 2.567E-05 2.227E-05 2.219E-05 2.048E-05 1.925E-05 1.775E-05 1.670E-05 1.540E-05 1.536E-05 1.283E-05 22.089 24.282 24.285 24.421 25.357 25.359 30.149 30.228 30.747 30.750 22.08909 24.28249 24.28531 24.42064 25.35664 25.35946 30.14942 30.22836 30.74711 30.74993 1.229E-05 1.114E-05 1.024E-05 9.626E-06 8.352E-06 7.700E-06 7.680E-06 6.681E-06 5.568E-06 5.197E-06 31.232 41.015 42.698 42.701 48.325 48.328 52.399 54.550 55.450 55.452 31.23202 41.01494 42.69805 42.70087 48.32534 48.32816 52.39920 54.55032 55.44967 55.45249 5.120E-06 4.176E-06 3.898E-06 3.840E-06 3.341E-06 3.118E-06 3.072E-06 2.599E-06 2.560E-06 1.949E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.581 84.669 85.134 66.17422 66.52383 66.53793 75.54835 75.57090 75.58500 81.49986 81.58162 84.66873 85.13391 1.920E-06 1.536E-06 1.299E-06 1.026E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 87.141 87.302 89.411 89.413 91.221 91.238 92.272 92.861 92.932 93.205 87.14124 87.30194 89.41076 89.41358 91.22075 91.23766 92.27234 92.86156 92.93204 93.20551 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 3 to ULNRC-06696 Page 450 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.245 97.482 97.496 97.513 94.13587 94.15842 95.51168 96.42796 96.44205 96.90723 97.24554 97.48236 97.49646 97.51337 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 3.937E-08 98.345 99.179 99.777 99.991 99.997 100.000 98.34506 99.17957 99.77725 99.99152 99.99715 99.99998 3 to ULNRC-06696 Page 451 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 153 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 2.675E-04 1.000 1.000 1.461E-04 3.000 3.000 1.038E-04 5.000 5.000 6.116E-05 10.000 10.000 4.117E-05 15.000 15.000 2.918E-05 20.000 20.000 2.180E-05 25.000 25.000 1.683E-05 30.000 30.000 1.386E-05 35.000 35.000 1.155E-05 40.000 40.000 9.853E-06 45.000 45.000 8.469E-06 50.000 50.000 7.279E-06 55.000 55.000 6.240E-06 60.000 60.000 5.321E-06 65.000 65.000 4.576E-06 70.000 70.000 3.910E-06 75.000 75.000 1.038E-04 5.0 5.00 3 to ULNRC-06696 Page 452 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 154 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE CALCULATIONS:
FIVE PERCENT OVERALL SITE LIMIT BUILDING WAKE CREDIT IS NOT INCLUDED.
CORRECTION FACTORS USED IN THE ANNUAL AVERAGE CALCULATIONS BELOW ARE PRINTED THE ORDERED VALUES OF CHI/Q AND THE FREQUENCY WITH WHICH THAT VALUE IS REACHED OR EXCEEDED.
THE TOP NUMBER IS THE CHI/Q.
THE MIDDLE NUMBER IS THE FREQUENCY NORMALIZED TO THIS SECTOR.
THE THIRD NUMBER IS THE FREQUENCY WITH RESPECT TO ALL TIME.
1.641E-04 1.094E-04 9.072E-05 8.207E-05 6.566E-05 6.048E-05 5.471E-05 4.560E-05 4.536E-05 4.104E-05 0.558 1.057 1.441 2.551 3.143 3.620 4.610 6.259 7.573 8.472 0.55822 1.05723 1.44065 2.55145 3.14350 3.61996 4.60953 6.25881 7.57260 8.47195 3.977E-05 3.643E-05 3.629E-05 3.285E-05 3.040E-05 3.024E-05 2.492E-05 2.280E-05 2.268E-05 2.219E-05 9.087 9.205 10.228 10.231 10.581 12.746 12.749 13.837 16.997 17.000 9.08655 9.20496 10.22836 10.23118 10.58077 12.74598 12.74880 13.83704 16.99746 17.00028 1.937E-05 1.824E-05 1.775E-05 1.666E-05 1.662E-05 1.520E-05 1.453E-05 1.283E-05 1.246E-05 1.140E-05 21.162 22.092 22.095 23.031 23.166 25.359 25.438 25.441 25.960 30.750 21.16154 22.09190 22.09472 23.03072 23.16603 25.35944 25.43838 25.44120 25.95995 30.74991 9.969E-06 9.626E-06 9.035E-06 8.308E-06 7.700E-06 7.482E-06 6.384E-06 6.231E-06 5.568E-06 5.197E-06 31.232 31.235 41.018 42.701 42.704 48.328 50.479 54.550 55.450 55.452 31.23201 31.23483 41.01775 42.70085 42.70367 48.32814 50.47926 54.55030 55.44965 55.45247 4.541E-06 4.176E-06 3.898E-06 3.596E-06 3.341E-06 3.118E-06 2.987E-06 2.599E-06 2.560E-06 1.949E-06 66.174 66.524 66.538 75.548 75.571 75.585 81.500 81.582 84.669 85.134 66.17419 66.52380 66.53792 75.54835 75.57092 75.58502 81.49989 81.58167 84.66878 85.13396 1.920E-06 1.536E-06 1.299E-06 1.026E-06 9.744E-07 8.553E-07 7.796E-07 6.496E-07 6.415E-07 4.872E-07 87.141 87.302 89.411 89.414 91.221 91.238 92.272 92.862 92.932 93.206 87.14131 87.30202 89.41084 89.41366 91.22083 91.23776 92.27245 92.86166 92.93217 93.20565 4.276E-07 3.898E-07 3.207E-07 2.566E-07 2.417E-07 2.138E-07 1.611E-07 1.604E-07 1.551E-07 1.283E-07 3 to ULNRC-06696 Page 453 of 456 94.136 94.158 95.512 96.428 96.442 96.907 97.246 97.482 97.497 97.513 94.13601 94.15857 95.51183 96.42812 96.44222 96.90741 97.24574 97.48257 97.49668 97.51360 1.209E-07 9.669E-08 8.057E-08 6.043E-08 4.834E-08 3.937E-08 98.345 99.180 99.777 99.992 99.997 100.000 98.34529 99.17982 99.77751 99.99179 99.99744 100.00026 3 to ULNRC-06696 Page 454 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 155 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph ERROR IN NORMAL TRANSFORMATION FOR A( 76)= 100.00026 PERCENT OF TIME CHI/Q IS EQUALED OR EXCEEDED CHI/Q WITH RESPECT TO WHEN THE WIND BLOWS SEC/CUBIC METER THE TOTAL TIME INTO THIS SECTOR ONLY 1.283E-04 1.000 1.000 7.634E-05 3.000 3.000 5.798E-05 5.000 5.000 3.694E-05 10.000 10.000 2.657E-05 15.000 15.000 2.046E-05 20.000 20.000 1.551E-05 25.000 25.000 1.288E-05 30.000 30.000 1.091E-05 35.000 35.000 9.322E-06 40.000 40.000 8.148E-06 45.000 45.000 7.176E-06 50.000 50.000 6.331E-06 55.000 55.000 5.574E-06 60.000 60.000 4.885E-06 65.000 65.000 4.251E-06 70.000 70.000 3.659E-06 75.000 75.000 3.140E-06 80.000 80.000 5.798E-05 5.0 5.00 3 to ULNRC-06696 Page 455 of 456 NAI PROGRAM : PAVAN-NAI V- 3.0 PAGE: 156 VERSION DATE: 07/30/2015 USNRC CODE PAVAN, REV 10/76, 8/79 RUN DATE: Tue May 09 11:01:07 2017 PLANT NAME : Callaway AST METEOROLOGICAL INSTRUMENTATION DATA PERIOD : 2013-2016 METD WIND SENSOR HEIGHT : 10.0 Meters TYPE OF RELEASE : Ground Level Release DELTA-T HEIGHTS : Delta-T from 10-60m SOURCE OF DATA : Meteorological Data JFD data from METD MJFREQ module - RWST COMMENTS : JFD and Calms by getmet.inp - Calms counted & entered for Wind Speeds < 0.5 mph LOW POPULATION ZONE BOUNDARY (LPZ)
BUILDING WAKE CREDIT IS NOT INCLUDED.
RELATIVE CONCENTRATION (X/Q) VALUES (SEC/CUBIC METER)
VERSUS HOURS PER YEAR MAX LPZ AVERAGING TIME 0-2 HR X/Q IS DOWNWIND DISTANCE EXCEEDED DOWNWIND SECTOR (METERS) 0-2 HOURS 0-8 HOURS 8-24 HOURS 1-4 DAYS 4-30 DAYS ANNUAL AVERAGE IN SECTOR SECTOR S 4023. 4.22E-05 2.05E-05 1.43E-05 6.52E-06 2.12E-06 5.34E-07 21.3 S SSW 4023. 4.52E-05 2.15E-05 1.49E-05 6.65E-06 2.10E-06 5.11E-07 321.2 SSW SW 4023. 4.61E-05 2.19E-05 1.51E-05 6.70E-06 2.10E-06 5.05E-07 21.9 SW WSW 4023. 3.50E-05 1.68E-05 1.17E-05 5.28E-06 1.69E-06 4.20E-07 15.5 WSW W 4023. 3.31E-05 1.60E-05 1.11E-05 5.04E-06 1.62E-06 4.04E-07 14.1 W WNW 4023. 3.96E-05 1.93E-05 1.35E-05 6.18E-06 2.01E-06 5.12E-07 16.4 WNW NW 4023. 6.21E-05 3.21E-05 2.31E-05 1.13E-05 4.04E-06 1.15E-06 35.9 NW NNW 4023. 6.87E-05 3.58E-05 2.59E-05 1.28E-05 4.62E-06 1.34E-06 43.7 NNW N 4023. 4.86E-05 2.46E-05 1.75E-05 8.41E-06 2.92E-06 8.02E-07 23.9 N NNE 4023. 3.30E-05 1.65E-05 1.16E-05 5.46E-06 1.85E-06 4.90E-07 11.8 NNE NE 4023. 3.17E-05 1.58E-05 1.11E-05 5.23E-06 1.77E-06 4.68E-07 12.8 NE ENE 4023. 2.82E-05 1.38E-05 9.66E-06 4.45E-06 1.46E-06 3.74E-07 11.7 ENE E 4023. 2.86E-05 1.42E-05 1.00E-05 4.69E-06 1.58E-06 4.16E-07 11.1 E ESE 4023. 4.72E-05 2.31E-05 1.62E-05 7.46E-06 2.45E-06 6.30E-07 21.0 ESE SE 4023. 4.64E-05 2.29E-05 1.61E-05 7.51E-06 2.50E-06 6.53E-07 21.4 SE SSE 4023. 4.15E-05 2.02E-05 1.41E-05 6.44E-06 2.10E-06 5.31E-07 17.4 SSE MAX X/Q 6.87E-05 3.58E-05 2.59E-05 1.28E-05 4.62E-06 TOTAL HOURS: 621.2 SRP 2.3.4 4023. 1.04E-04 5.05E-05 3.53E-05 1.62E-05 5.26E-06 1.34E-06 SITE LIMIT 5.80E-05 3.11E-05 2.28E-05 1.16E-05 4.38E-06 1.34E-06 THE FIVE-PERCENT-FOR-THE-ENTIRE-SITE X/Q IS LIMITING.
- NOTE**: VALUES ON THIS PAGE ARE APPROXIMATIONS ONLY.
CHECK THE REASONABLENESS OF THE ENVELOPES COMPUTED FOR THE 0-2 HOUR VALUES. FOR ANY FAULTY ENVELOPES, ADJUST THE ABOVE VALUES.
3 to ULNRC-06696 Page 456 of 456 END OF PAVAN CARD INPUT.
PAVAN-NAI VERSION- 3.0 EXECUTION TERMINATED.