H.B. Robinson (34.40° N, 80.16° E), Control Point Hazard SA (g)

AFE 0.5 Hz AFE 1 Hz AFE 2.5 Hz AFE 5 Hz AFE 10 Hz AFE 25 Hz AFE 100 Hz 0.001000 8.752996e-03 1.447373e-02 2.099687e-02 2.213417e-02 2.233530e-02 2.210435e-02 2.087071e-02 0.001122 8.749623e-03 1.447363e-02 2.099673e-02 2.213417e-02 2.233526e-02 2.210435e-02 2.087071e-02 0.001259 8.574026e-03 1.446923e-02 2.099622e-02 2.213417e-02 2.233507e-02 2.210435e-02 2.087071e-02 0.001413 8.237725e-03 1.441793e-02 2.099461e-02 2.213415e-02 2.233431e-02 2.210435e-02 2.087071e-02 0.001585 7.829460e-03 1.424912e-02 2.098998e-02 2.213398e-02 2.233186e-02 2.210435e-02 2.087071e-02 0.001778 7.411577e-03 1.399124e-02 2.097826e-02 2.213297e-02 2.232515e-02 2.210432e-02 2.087071e-02 0.001995 7.013886e-03 1.366362e-02 2.095210e-02 2.212808e-02 2.230810e-02 2.210304e-02 2.087055e-02 0.002239 6.636731e-03 1.326255e-02 2.089965e-02 2.211026e-02 2.226671e-02 2.208362e-02 2.086688e-02 0.002512 6.277383e-03 1.280688e-02 2.080372e-02 2.206202e-02 2.218261e-02 2.198927e-02 2.083348e-02 0.002818 5.933491e-03 1.231823e-02 2.064293e-02 2.196400e-02 2.204914e-02 2.181292e-02 2.068699e-02 0.003162 5.601857e-03 1.180290e-02 2.039926e-02 2.180825e-02 2.187011e-02 2.158905e-02 2.035245e-02 0.003548 5.280146e-03 1.125870e-02 2.006790e-02 2.159861e-02 2.164820e-02 2.132456e-02 1.989384e-02 0.003981 4.965485e-03 1.068853e-02 1.965742e-02 2.133867e-02 2.138197e-02 2.101401e-02 1.937193e-02 0.004467 4.656031e-03 1.010372e-02 1.917993e-02 2.102762e-02 2.106795e-02 2.065404e-02 1.879363e-02 0.005012 4.349879e-03 9.518593e-03 1.864423e-02 2.066342e-02 2.070244e-02 2.024227e-02 1.815971e-02 0.005623 4.046127e-03 8.944354e-03 1.805613e-02 2.024423e-02 2.028229e-02 1.977652e-02 1.747420e-02 0.006310 3.744378e-03 8.386964e-03 1.742059e-02 1.976837e-02 1.980532e-02 1.925587e-02 1.674196e-02 0.007079 3.445051e-03 7.848648e-03 1.674255e-02 1.923467e-02 1.927090e-02 1.868158e-02 1.596871e-02 0.007943 3.149535e-03 7.329656e-03 1.602720e-02 1.864301e-02 1.867999e-02 1.805682e-02 1.516224e-02 0.008913 2.860909e-03 6.829611e-03 1.527997e-02 1.799468e-02 1.803514e-02 1.738591e-02 1.433182e-02 0.010000 2.584892e-03 6.347884e-03 1.450659e-02 1.729245e-02 1.734050e-02 1.667479e-02 1.348743e-02 0.011220 2.321390e-03 5.883917e-03 1.371306e-02 1.654069e-02 1.660173e-02 1.593022e-02 1.263882e-02 0.012589 2.071624e-03 5.437321e-03 1.290562e-02 1.574546e-02 1.582590e-02 1.516024e-02 1.179587e-02 0.014125 1.835411e-03 5.007890e-03 1.209082e-02 1.491446e-02 1.502117e-02 1.437309e-02 1.096746e-02 0.015849 1.614231e-03 4.595719e-03 1.127547e-02 1.405676e-02 1.419645e-02 1.357731e-02 1.016196e-02 0.017783 1.409239e-03 4.201396e-03 1.046657e-02 1.318245e-02 1.336094e-02 1.278085e-02 9.386129e-03 0.019953 1.220200e-03 3.826405e-03 9.671172e-03 1.230217e-02 1.252381e-02 1.199126e-02 8.645629e-03 0.022387 1.047110e-03 3.471377e-03 8.896183e-03 1.142663e-02 1.169380e-02 1.121525e-02 7.944323e-03 0.025119 8.908011e-04 3.136105e-03 8.148121e-03 1.056607e-02 1.087890e-02 1.045865e-02 7.284047e-03 0.028184 7.517148e-04 2.821127e-03 7.432849e-03 9.729797e-03 1.008604e-02 9.726040e-03 6.657059e-03 0.031623 6.290155e-04 2.526631e-03 6.755301e-03 8.925778e-03 9.320927e-03 9.017680e-03 6.032148e-03 0.035481 5.220036e-04 2.252310e-03 6.119249e-03 8.160375e-03 8.587793e-03 8.303045e-03 5.401395e-03 0.039811 4.296439e-04 1.997984e-03 5.527161e-03 7.438138e-03 7.889203e-03 7.552365e-03 4.805491e-03 0.044668 3.508698e-04 1.763562e-03 4.980144e-03 6.761502e-03 7.224684e-03 6.814048e-03 4.263147e-03 0.050119 2.842308e-04 1.548713e-03 4.477988e-03 6.130341e-03 6.589090e-03 6.122694e-03 3.772300e-03 0.056234 2.284184e-04 1.352859e-03 4.019287e-03 5.542033e-03 5.979206e-03 5.484373e-03 3.326845e-03 0.063096 1.821045e-04 1.175321e-03 3.601641e-03 4.993413e-03 5.400184e-03 4.897283e-03 2.920982e-03 0.070795 1.440945e-04 1.015261e-03 3.221913e-03 4.483558e-03 4.858796e-03 4.358455e-03 2.550176e-03 0.079433 1.131913e-04 8.718322e-04 2.876531e-03 4.013339e-03 4.357959e-03 3.864471e-03 2.211080e-03 0.089125 8.828443e-05 7.441730e-04 2.561864e-03 3.582361e-03 3.896933e-03 3.411827e-03 1.901674e-03 0.100000 6.839692e-05 6.312951e-04 2.274586e-03 3.188162e-03 3.473158e-03 2.997256e-03 1.619957e-03 0.112202 5.268530e-05 5.321711e-04 2.011888e-03 2.827535e-03 3.083646e-03 2.617840e-03 1.359775e-03 0.125893 4.039094e-05 4.457733e-04 1.771483e-03 2.497412e-03 2.725597e-03 2.270519e-03 1.117119e-03 0.141254 3.084840e-05 3.710297e-04 1.551517e-03 2.195063e-03 2.396602e-03 1.952789e-03 8.967460e-04 0.158489 2.347718e-05 3.068077e-04 1.350457e-03 1.918089e-03 2.094531e-03 1.664423e-03 7.069231e-04

0.177828 1.782660e-05 2.519773e-04 1.167026e-03 1.664397e-03 1.817152e-03 1.404531e-03 5.482419e-04 0.199526 1.351576e-05 2.054480e-04 1.000210e-03 1.432265e-03 1.562641e-03 1.173507e-03 4.174624e-04 0.223872 1.024361e-05 1.661993e-04 8.492770e-04 1.220491e-03 1.330555e-03 9.706000e-04 3.120963e-04 0.251189 7.766797e-06 1.333021e-04 7.137362e-04 1.028490e-03 1.120605e-03 7.938965e-04 2.292200e-04 0.281838 5.892584e-06 1.059597e-04 5.931908e-04 8.561323e-04 9.320545e-04 6.414230e-04 1.657034e-04 0.316228 4.473001e-06 8.346228e-05 4.871931e-04 7.033686e-04 7.645772e-04 5.108721e-04 1.179849e-04 0.354813 3.395790e-06 6.513303e-05 3.951721e-04 5.699014e-04 6.179069e-04 4.012124e-04 8.258634e-05 0.398107 2.576927e-06 5.031855e-05 3.164074e-04 4.550951e-04 4.913119e-04 3.106631e-04 5.675637e-05 0.446684 1.954234e-06 3.842793e-05 2.499975e-04 3.580402e-04 3.842403e-04 2.372177e-04 3.829410e-05 0.501187 1.480534e-06 2.896150e-05 1.948434e-04 2.775535e-04 2.959658e-04 1.788330e-04 2.537855e-05 0.562341 1.120842e-06 2.151273e-05 1.496991e-04 2.120931e-04 2.246243e-04 1.331015e-04 1.659737e-05 0.630957 8.487933e-07 1.575592e-05 1.132764e-04 1.597794e-04 1.678399e-04 9.761368e-05 1.066771e-05 0.707946 6.435465e-07 1.140804e-05 8.433991e-05 1.185946e-04 1.233650e-04 7.033805e-05 6.745472e-06 0.794328 4.886880e-07 8.193929e-06 6.174466e-05 8.661957e-05 8.913481e-05 4.987346e-05 4.202741e-06 0.891251 3.716140e-07 5.850924e-06 4.443502e-05 6.217866e-05 6.324762e-05 3.479449e-05 2.572303e-06 1.000000 2.827745e-07 4.152423e-06 3.144044e-05 4.386184e-05 4.403599e-05 2.381346e-05 1.542512e-06 1.122019 2.150054e-07 2.923393e-06 2.188010e-05 3.045203e-05 3.006124e-05 1.597975e-05 9.058182e-07 1.258925 1.631500e-07 2.039456e-06 1.497806e-05 2.085394e-05 2.009610e-05 1.049945e-05 5.196670e-07 1.412538 1.234683e-07 1.412643e-06 1.007944e-05 1.410207e-05 1.315644e-05 6.730539e-06 2.909951e-07 1.584893 9.313281e-08 9.759606e-07 6.658080e-06 9.409352e-06 8.455967e-06 4.202196e-06 1.578682e-07 1.778279 6.991620e-08 6.751666e-07 4.312188e-06 6.181446e-06 5.346683e-06 2.558422e-06 8.184510e-08 1.995262 5.215384e-08 4.673845e-07 2.740167e-06 3.988016e-06 3.325018e-06 1.517736e-06 4.024036e-08 2.238721 3.861229e-08 3.221254e-07 1.712308e-06 2.521783e-06 2.031394e-06 8.727472e-07 1.872737e-08 2.511886 2.833893e-08 2.200982e-07 1.055298e-06 1.562516e-06 1.217150e-06 4.829077e-07 8.060216e-09 2.818383 2.059538e-08 1.492787e-07 6.429683e-07 9.500576e-07 7.114502e-07 2.552085e-07 3.043746e-09 3.162278 1.481606e-08 1.011158e-07 3.875104e-07 5.677751e-07 4.011371e-07 1.273275e-07 8.887860e-10 3.548134 1.055835e-08 6.882973e-08 2.306851e-07 3.333767e-07 2.155373e-07 5.874388e-08 1.502358e-10 3.981072 7.461598e-09 4.720266e-08 1.353528e-07 1.917318e-07 1.098622e-07 2.436770e-08 1.063061e-11 4.466836 5.232156e-09 3.255350e-08 7.823774e-08 1.074983e-07 5.294692e-08 8.819439e-09 2.548474e-13 5.011872 3.639225e-09 2.247256e-08 4.466367e-08 5.845334e-08 2.356240e-08 2.710102e-09 1.855635e-15 5.623413 2.675563e-09 1.650633e-08 2.948881e-08 3.690561e-08 1.327557e-08 1.427197e-09 9.278186e-16 6.309573 1.711901e-09 1.054011e-08 1.431396e-08 1.535789e-08 2.988745e-09 1.442911e-10 2.275952e-21 H.B. Robinson (34.40° N, 80.16° E), Response Spectra Frequency (Hz)

UHRS 1E-4 (g)

GMRS (g)

UHRS 1E-5 (g) 0.500000 0.084126 0.111331 0.226125 0.561009 0.099062 0.135079 0.276421 0.629463 0.117567 0.163926 0.337325 0.706269 0.142342 0.200989 0.414900 0.792447 0.176339 0.249280 0.514735 0.889140 0.225756 0.307913 0.630138 0.997631 0.288413 0.367279 0.738844 1.000000 0.289820 0.368553 0.741146 1.122019 0.362173 0.450194 0.900186 1.258925 0.428140 0.521492 1.037466 1.412538 0.488196 0.582372 1.152559 1.584893 0.541695 0.638691 1.260335

1.778279 0.582866 0.673785 1.323031 1.995262 0.613211 0.699157 1.368129 2.238721 0.639487 0.715556 1.393663 2.500000 0.662416 0.729694 1.415644 2.805046 0.685088 0.750345 1.453619 3.147313 0.713733 0.778107 1.505658 3.531344 0.746725 0.808646 1.562137 3.962233 0.766654 0.822937 1.586242 4.445698 0.765914 0.820399 1.580509 4.988156 0.753599 0.808278 1.557675 5.000000 0.753356 0.808005 1.557142 5.610092 0.726717 0.775097 1.491642 6.294627 0.708176 0.754638 1.451940 7.062688 0.712693 0.753158 1.446083 7.924466 0.718660 0.758689 1.456329 8.891397 0.743886 0.776962 1.487423 9.976312 0.762121 0.792899 1.516447 10.000000 0.762613 0.793297 1.517154 11.220185 0.757984 0.799483 1.534290 12.589254 0.745254 0.787720 1.512514 14.125375 0.718637 0.756245 1.450479 15.848932 0.695981 0.733904 1.408350 17.782794 0.669800 0.709184 1.362301 19.952623 0.645646 0.683531 1.312985 22.387211 0.625325 0.663371 1.274912 25.000000 0.599569 0.631639 1.211819 28.050461 0.569344 0.596755 1.143437 31.473135 0.541325 0.568991 1.091008 35.313439 0.516308 0.538068 1.029509 39.622330 0.489502 0.507650 0.970125 44.456985 0.469866 0.483799 0.922887 49.881558 0.449697 0.459853 0.875699 55.968028 0.431410 0.439147 0.835316 62.797161 0.414206 0.419992 0.798102 70.459573 0.398617 0.402643 0.764403 79.056942 0.382964 0.385932 0.732252 88.703347 0.367962 0.370699 0.703294 99.526793 0.355226 0.358293 0.679959 100.000000 0.333566 0.337620 0.641285