Summer (34.30° N, 81.32° E), Control Point Hazard SA (g)

AFE 0.5 Hz AFE 1 Hz AFE 2.5 Hz AFE 5 Hz AFE 10 Hz AFE 25 Hz AFE 100 Hz 0.001000 1.067699e-02 1.782023e-02 2.560430e-02 2.690781e-02 2.713233e-02 2.685359e-02 2.542270e-02 0.001122 1.008503e-02 1.694379e-02 2.509690e-02 2.665681e-02 2.694817e-02 2.661710e-02 2.489234e-02 0.001259 9.509951e-03 1.608945e-02 2.459455e-02 2.640684e-02 2.676400e-02 2.637987e-02 2.436536e-02 0.001413 8.964554e-03 1.524246e-02 2.402902e-02 2.610476e-02 2.653623e-02 2.609539e-02 2.377222e-02 0.001585 8.447184e-03 1.440337e-02 2.340075e-02 2.574954e-02 2.626357e-02 2.576236e-02 2.311356e-02 0.001778 7.955414e-03 1.358208e-02 2.270963e-02 2.533155e-02 2.593557e-02 2.537225e-02 2.238958e-02 0.001995 7.488159e-03 1.278033e-02 2.196260e-02 2.485510e-02 2.555535e-02 2.492847e-02 2.160772e-02 0.002239 7.041227e-03 1.200461e-02 2.116228e-02 2.431170e-02 2.511286e-02 2.442367e-02 2.077113e-02 0.002512 6.613633e-03 1.125419e-02 2.031147e-02 2.370238e-02 2.460835e-02 2.385842e-02 1.988317e-02 0.002818 6.200210e-03 1.053250e-02 1.941699e-02 2.302239e-02 2.403500e-02 2.322953e-02 1.895243e-02 0.003162 5.800968e-03 9.839355e-03 1.848594e-02 2.227777e-02 2.339756e-02 2.254198e-02 1.798668e-02 0.003548 5.410703e-03 9.174625e-03 1.752692e-02 2.146743e-02 2.269316e-02 2.179699e-02 1.699822e-02 0.003981 5.030072e-03 8.537698e-03 1.654564e-02 2.059747e-02 2.192669e-02 2.099946e-02 1.599310e-02 0.004467 4.655170e-03 7.925854e-03 1.555193e-02 1.967201e-02 2.110105e-02 2.015609e-02 1.498693e-02 0.005012 4.287226e-03 7.338738e-03 1.455078e-02 1.869774e-02 2.022174e-02 1.927204e-02 1.398421e-02 0.005623 3.924798e-03 6.772633e-03 1.355251e-02 1.768481e-02 1.929773e-02 1.835880e-02 1.300127e-02 0.006310 3.569664e-03 6.227869e-03 1.256165e-02 1.664058e-02 1.833532e-02 1.742166e-02 1.204081e-02 0.007079 3.223058e-03 5.701539e-03 1.158872e-02 1.558046e-02 1.734789e-02 1.647432e-02 1.111651e-02 0.007943 2.886570e-03 5.194300e-03 1.063668e-02 1.451044e-02 1.634080e-02 1.552080e-02 1.022865e-02 0.008913 2.563771e-03 4.705761e-03 9.717118e-03 1.344990e-02 1.533028e-02 1.457488e-02 9.386656e-03 0.010000 2.255901e-03 4.237010e-03 8.831751e-03 1.240351e-02 1.432103e-02 1.363970e-02 8.589280e-03 0.011220 1.967239e-03 3.789981e-03 7.991680e-03 1.139002e-02 1.332840e-02 1.272627e-02 7.855734e-03 0.012589 1.697898e-03 3.365307e-03 7.196301e-03 1.041110e-02 1.235510e-02 1.183615e-02 7.156805e-03 0.014125 1.452106e-03 2.967084e-03 6.455288e-03 9.482631e-03 1.141484e-02 1.097791e-02 6.502367e-03 0.015849 1.228308e-03 2.594328e-03 5.765189e-03 8.602510e-03 1.050725e-02 1.015186e-02 5.891354e-03 0.017783 1.029330e-03 2.250998e-03 5.131165e-03 7.780046e-03 9.641646e-03 9.362170e-03 5.322951e-03 0.019953 8.533435e-04 1.936494e-03 4.549914e-03 7.013200e-03 8.818466e-03 8.609103e-03 4.795239e-03 0.022387 7.011857e-04 1.653146e-03 4.021577e-03 6.304533e-03 8.042104e-03 7.894844e-03 4.305915e-03 0.025119 5.698570e-04 1.398266e-03 3.541389e-03 5.649635e-03 7.310175e-03 7.217738e-03 3.852710e-03 0.028184 4.590822e-04 1.173043e-03 3.106819e-03 5.047224e-03 6.624226e-03 6.578718e-03 3.435058e-03 0.031623 3.659362e-04 9.747768e-04 2.714144e-03 4.493882e-03 5.982547e-03 5.976866e-03 3.052280e-03 0.035481 2.893224e-04 8.033830e-04 2.359981e-03 3.986319e-03 5.384521e-03 5.412114e-03 2.703369e-03 0.039811 2.264247e-04 6.555607e-04 2.041015e-03 3.521319e-03 4.827928e-03 4.882977e-03 2.385363e-03 0.044668 1.758959e-04 5.304712e-04 1.754707e-03 3.095846e-03 4.311538e-03 4.389197e-03 2.096885e-03 0.050119 1.353419e-04 4.248246e-04 1.498166e-03 2.707128e-03 3.833123e-03 3.929086e-03 1.834858e-03 0.056234 1.034599e-04 3.374148e-04 1.270078e-03 2.353420e-03 3.391759e-03 3.502548e-03 1.598428e-03 0.063096 7.842044e-05 2.652075e-04 1.067765e-03 2.032269e-03 2.985340e-03 3.107842e-03 1.387946e-03 0.070795 5.912640e-05 2.068087e-04 8.906116e-04 1.743108e-03 2.613493e-03 2.745000e-03 1.199731e-03 0.079433 4.426738e-05 1.596358e-04 7.358108e-04 1.483303e-03 2.273895e-03 2.412034e-03 1.032182e-03 0.089125 3.302004e-05 1.223571e-04 6.029044e-04 1.252991e-03 1.966763e-03 2.109118e-03 8.841707e-04 0.100000 2.450915e-05 9.293132e-05 4.890617e-04 1.049335e-03 1.689618e-03 1.834171e-03 7.541160e-04 0.112202 1.815993e-05 7.018478e-05 3.935062e-04 8.722865e-04 1.442651e-03 1.587184e-03 6.405460e-04 0.125893 1.342422e-05 5.261340e-05 3.134362e-04 7.186773e-04 1.223007e-03 1.365563e-03 5.420297e-04 0.141254 9.927274e-06 3.929959e-05 2.478185e-04 5.880782e-04 1.030719e-03 1.168442e-03 4.569275e-04 0.158489 7.345635e-06 2.921257e-05 1.940697e-04 4.771107e-04 8.624879e-04 9.941980e-04 3.832819e-04

0.177828 5.448011e-06 2.168456e-05 1.509770e-04 3.847152e-04 7.177235e-04 8.420033e-04 3.199500e-04 0.199526 4.052775e-06 1.606880e-05 1.165070e-04 3.079636e-04 5.934741e-04 7.095249e-04 2.661607e-04 0.223872 3.024892e-06 1.191696e-05 8.945389e-05 2.453573e-04 4.884901e-04 5.954763e-04 2.206383e-04 0.251189 2.267927e-06 8.847747e-06 6.822399e-05 1.942975e-04 3.998108e-04 4.974600e-04 1.822743e-04 0.281838 1.706046e-06 6.583547e-06 5.183753e-05 1.532993e-04 3.259699e-04 4.139819e-04 1.500361e-04 0.316228 1.288807e-06 4.913019e-06 3.920061e-05 1.204145e-04 2.645633e-04 3.431249e-04 1.230310e-04 0.354813 9.754922e-07 3.674714e-06 2.957622e-05 9.433772e-05 2.140811e-04 2.834875e-04 1.004107e-04 0.398107 7.401971e-07 2.756761e-06 2.224740e-05 7.366508e-05 1.725992e-04 2.333753e-04 8.154502e-05 0.446684 5.615907e-07 2.070327e-06 1.671137e-05 5.739839e-05 1.387980e-04 1.915481e-04 6.593452e-05 0.501187 4.260032e-07 1.556988e-06 1.252963e-05 4.459975e-05 1.112619e-04 1.566810e-04 5.306661e-05 0.562341 3.223941e-07 1.169851e-06 9.382673e-06 3.457223e-05 8.895301e-05 1.277600e-04 4.247612e-05 0.630957 2.432317e-07 8.778829e-07 7.014625e-06 2.671705e-05 7.088404e-05 1.038057e-04 3.380134e-05 0.707946 1.827230e-07 6.567362e-07 5.234287e-06 2.058082e-05 5.630304e-05 8.405139e-05 2.673828e-05 0.794328 1.364968e-07 4.892491e-07 3.895836e-06 1.578798e-05 4.453938e-05 6.777523e-05 2.101033e-05 0.891251 1.013576e-07 3.626250e-07 2.890221e-06 1.205801e-05 3.508399e-05 5.442087e-05 1.639060e-05 1.000000 7.466692e-08 2.669462e-07 2.134844e-06 9.156594e-06 2.748811e-05 4.347830e-05 1.268606e-05 1.122019 5.460552e-08 1.951943e-07 1.569019e-06 6.913119e-06 2.141758e-05 3.455430e-05 9.736413e-06 1.258925 3.954023e-08 1.414249e-07 1.145341e-06 5.179419e-06 1.656944e-05 2.728742e-05 7.407732e-06 1.412538 2.839678e-08 1.016568e-07 8.304379e-07 3.852925e-06 1.273055e-05 2.140951e-05 5.582882e-06 1.584893 2.015658e-08 7.225322e-08 5.963646e-07 2.838034e-06 9.691208e-06 1.666137e-05 4.163098e-06 1.778279 1.417112e-08 5.087974e-08 4.244573e-07 2.071825e-06 7.312821e-06 1.285833e-05 3.069672e-06 1.995262 9.834230e-09 3.537156e-08 2.984853e-07 1.494706e-06 5.456286e-06 9.823385e-06 2.236558e-06 2.238721 6.752894e-09 2.433154e-08 2.076605e-07 1.066981e-06 4.027787e-06 7.427067e-06 1.608608e-06 2.511886 4.564897e-09 1.647659e-08 1.422104e-07 7.501368e-07 2.929400e-06 5.539733e-06 1.141152e-06 2.818383 3.044865e-09 1.100800e-08 9.601137e-08 5.199779e-07 2.099741e-06 4.072723e-06 7.972516e-07 3.162278 1.991165e-09 7.208991e-09 6.347687e-08 3.531810e-07 1.474652e-06 2.937561e-06 5.474753e-07 3.548134 1.277640e-09 4.631402e-09 4.111163e-08 2.349652e-07 1.013225e-06 2.072778e-06 3.687094e-07 3.981072 7.952589e-10 2.885340e-09 2.577103e-08 1.513359e-07 6.733602e-07 1.417592e-06 2.427293e-07 4.466836 4.831276e-10 1.754378e-09 1.576058e-08 9.491271e-08 4.347639e-07 9.401376e-07 1.554001e-07 5.011872 2.811590e-10 1.021831e-09 9.228293e-09 5.684545e-08 2.672628e-07 5.948192e-07 9.636739e-08 5.623413 1.734349e-10 6.306177e-10 5.703913e-09 3.532714e-08 1.670680e-07 3.794636e-07 6.415495e-08 6.309573 6.571081e-11 2.394048e-10 2.179533e-09 1.380884e-08 6.687324e-08 1.641080e-07 3.194251e-08 Summer (34.30° N, 81.32° E), Response Spectra Frequency (Hz)

UHRS 1E-4 (g)

GMRS (g)

UHRS 1E-5 (g) 0.500000 0.057034 0.070536 0.140861 0.561009 0.063415 0.079204 0.158560 0.629463 0.069969 0.087568 0.175394 0.706269 0.076579 0.095713 0.191646 0.792447 0.083275 0.103754 0.207582 0.889140 0.090061 0.111766 0.223390 0.997631 0.096837 0.119796 0.239250 1.000000 0.096978 0.119962 0.239577 1.122019 0.110439 0.141384 0.284792 1.258925 0.124540 0.161587 0.326583 1.412538 0.139070 0.180945 0.365962 1.584893 0.153743 0.199710 0.403750

1.778279 0.168578 0.218158 0.440631 1.995262 0.183553 0.236443 0.477012 2.238721 0.198654 0.254725 0.513306 2.500000 0.213261 0.272346 0.548257 2.805046 0.232173 0.304049 0.615938 3.147313 0.252368 0.336411 0.684527 3.531344 0.273788 0.369290 0.753645 3.962233 0.296396 0.402670 0.823247 4.445698 0.320210 0.436632 0.893503 4.988156 0.345190 0.470933 0.963817 5.000000 0.345719 0.471649 0.965282 5.610092 0.370216 0.514616 1.058161 6.294627 0.397125 0.559505 1.154341 7.062688 0.426373 0.606088 1.253238 7.924466 0.458100 0.654066 1.353936 8.891397 0.492204 0.703621 1.456963 9.976312 0.528695 0.754577 1.561848 10.000000 0.529474 0.755650 1.564051 11.220185 0.539896 0.774813 1.605942 12.589254 0.551644 0.795774 1.651518 14.125375 0.564834 0.818937 1.701743 15.848932 0.579558 0.844611 1.757348 17.782794 0.596815 0.873592 1.819644 19.952623 0.618157 0.908131 1.893309 22.387211 0.643942 0.949015 1.980116 25.000000 0.658385 0.970152 2.024140 28.050461 0.672741 0.991632 2.069126 31.473135 0.685976 1.011985 2.112035 35.313439 0.697093 1.030220 2.151052 39.622330 0.703947 1.043391 2.180141 44.456985 0.709365 1.054139 2.204020 49.881558 0.705597 1.051172 2.199195 55.968028 0.684258 1.021410 2.137993 62.797161 0.644409 0.963178 2.016759 70.459573 0.587183 0.877506 1.837300 79.056942 0.520277 0.776818 1.626115 88.703347 0.452067 0.674060 1.410533 99.526793 0.393336 0.585344 1.224289 100.000000 0.355619 0.530042 1.109055