Palo Verde (33.39° N, 112.86° E), Control Point Hazard SA (g)

AFE 0.5 Hz AFE 1 Hz AFE 2.5 Hz AFE 5 Hz AFE 10 Hz AFE 20 Hz AFE 100 Hz 0.000001 1.600000e+00 1.600000e+00 1.600000e+00 1.600000e+00 1.600000e+00 1.600000e+00 1.600000e+00 0.000500 3.800000e-01 1.050000e+00 1.210000e+00 1.050000e+00 7.860000e-01 7.330000e-01 7.740000e-01 0.001000 2.250000e-01 7.170000e-01 8.900000e-01 7.560000e-01 5.160000e-01 4.680000e-01 4.810000e-01 0.005000 3.310000e-02 1.990000e-01 2.430000e-01 2.020000e-01 1.140000e-01 1.000000e-01 9.180000e-02 0.010000 9.050000e-03 8.830000e-02 1.070000e-01 8.770000e-02 4.530000e-02 3.980000e-02 3.310000e-02 0.015000 3.710000e-03 4.850000e-02 5.950000e-02 4.850000e-02 2.420000e-02 2.120000e-02 1.630000e-02 0.030000 6.730000e-04 1.370000e-02 1.740000e-02 1.480000e-02 7.350000e-03 6.230000e-03 4.180000e-03 0.050000 1.730000e-04 4.540000e-03 6.000000e-03 5.630000e-03 2.900000e-03 2.290000e-03 1.420000e-03 0.075000 5.790000e-05 1.730000e-03 2.400000e-03 2.540000e-03 1.360000e-03 9.880000e-04 5.940000e-04 0.100000 2.690000e-05 8.390000e-04 1.230000e-03 1.430000e-03 7.880000e-04 5.320000e-04 3.200000e-04 0.150000 9.340000e-06 2.930000e-04 4.770000e-04 6.370000e-04 3.580000e-04 2.170000e-04 1.330000e-04 0.300000 1.630000e-06 4.780000e-05 9.750000e-05 1.570000e-04 8.340000e-05 4.100000e-05 2.690000e-05 0.500000 4.480000e-07 1.300000e-05 3.080000e-05 5.290000e-05 2.320000e-05 9.510000e-06 6.530000e-06 0.750000 1.550000e-07 4.580000e-06 1.200000e-05 1.980000e-05 6.730000e-06 2.340000e-06 1.690000e-06 1.000000 7.070000e-08 2.110000e-06 5.850000e-06 8.810000e-06 2.400000e-06 7.480000e-07 5.630000e-07 1.500000 2.220000e-08 6.400000e-07 1.900000e-06 2.240000e-06 4.460000e-07 1.230000e-07 1.000000e-07 3.000000 2.600000e-09 6.070000e-08 1.880000e-07 1.060000e-07 1.470000e-08 3.460000e-09 3.380000e-09 5.000000 4.610000e-10 8.430000e-09 2.520000e-08 6.520000e-09 8.700000e-10 1.710000e-10 1.900000e-10 7.500000 1.050000e-10 1.540000e-09 4.360000e-09 5.330000e-10 8.230000e-11 1.230000e-11 1.490000e-11 10.000000 3.480000e-11 4.280000e-10 1.160000e-09 7.700000e-11 1.490000e-11 1.670000e-12 2.120000e-12 Palo Verde (33.39° N, 112.86° E), Response Spectra Frequency (Hz)

UHRS 1E-4 (g)

GMRS (g)

UHRS 1E-5 (g)

UHRS 1E-6 (g) 100.000 0.1700 0.2140 0.4290 0.8600 90.000 0.1690 0.2140 0.4300 0.8630 80.000 0.1690 0.2140 0.4300 0.8660 70.000 0.1680 0.2140 0.4310 0.8690 60.000 0.1680 0.2150 0.4330 0.8730 50.000 0.1680 0.2160 0.4350 0.8780 40.000 0.1700 0.2180 0.4390 0.8860 35.000 0.1720 0.2200 0.4430 0.8910 30.000 0.1770 0.2240 0.4500 0.8980 25.000 0.1870 0.2320 0.4640 0.9110 20.000 0.2070 0.2480 0.4910 0.9300 15.000 0.2270 0.2680 0.5290 1.0100 12.500 0.2490 0.2940 0.5810 1.0900 10.000 0.2750 0.3320 0.6590 1.2300 9.000 0.2860 0.3470 0.6890 1.2800 8.000 0.3020 0.3660 0.7270 1.3400 7.000 0.3220 0.3940 0.7840 1.4300 6.000 0.3480 0.4320 0.8640 1.5900 5.000 0.3710 0.4750 0.9560 1.8000 4.000 0.3750 0.4930 0.9990 1.9600

3.500 0.3630 0.4870 0.9920 2.0200 3.000 0.3370 0.4530 0.9230 1.9800 2.500 0.2970 0.3960 0.8060 1.8200 2.000 0.2650 0.3390 0.6820 1.7200 1.500 0.2800 0.3370 0.6680 1.4800 1.250 0.2910 0.3490 0.6920 1.4000 1.000 0.2260 0.2770 0.5530 1.2900 0.900 0.1910 0.2390 0.4790 1.1700 0.800 0.1540 0.1960 0.3930 0.9970 0.700 0.1180 0.1500 0.3020 0.7820 0.600 0.0861 0.1070 0.2140 0.5580 0.500 0.0613 0.0736 0.1460 0.3640 0.400 0.0490 0.0589 0.1170 0.2910 0.350 0.0429 0.0515 0.1020 0.2550 0.300 0.0368 0.0442 0.0876 0.2180 0.250 0.0307 0.0368 0.0730 0.1820 0.200 0.0245 0.0295 0.0584 0.1460 0.150 0.0184 0.0221 0.0438 0.1090 0.125 0.0153 0.0184 0.0365 0.0910 0.100 0.0123 0.0147 0.0292 0.0728