MONTHYEARML21111A0372021-05-0303 May 2021 Inspection Manual Chapter 0375 Recommendation for Callaway Plant Project stage: Request ML21123A2622021-05-0303 May 2021 Presentation Information for Planned Pre-Application Meeting (Closed Meeting), Non-Proprietary (Redacted) Version for Closed Meeting Project stage: Meeting ML21125A4262021-05-0505 May 2021 Partially Closed Pre-Application Teleconference with Union Electric Company to Discuss Approval to Insert Framatome'S Gaia Fuel Assemblies in Their Core in Reload Quantities for the Callaway Plant, Unit No. 1 Project stage: Meeting ML21130A6842021-05-10010 May 2021 Partially Closed Pre-Application Teleconference with Union Electric Company to Discuss Approval to Insert Framatome'S Gaia Fuel Assemblies in Their Core in Reload Quantities for the Callaway Plant, Unit No. 1 Project stage: Meeting ML21126A2322021-05-14014 May 2021 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML21168A0022021-07-0101 July 2021 Summary of Partially Closed Pre-Application Teleconference with Union Electric Company Regarding Approval to Insert Framatome'S Gaia Fuel Assemblies in Their Core in Reload Quantities for Callaway Plant, Unit No. 1 Project stage: Meeting 2021-05-03
[Table View] |
|
---|
Category:Memoranda
MONTHYEARML22147A0932022-06-0606 June 2022 2021 Annual Assessment Public Meeting Summary ML22034A3932022-02-16016 February 2022 Calendar Year 2021 Security Baseline Completion Memo ML21216A2002021-08-11011 August 2021 Summary of Public Webinar with Ameren Missouri to Discuss the Nuclear Regulatory Commission 2020 Annual Assessment of Callaway Plant Docket No. 50-483 ML21111A0372021-05-0303 May 2021 Inspection Manual Chapter 0375 Recommendation for Callaway Plant ML18173A0082018-06-20020 June 2018 Cancelling Numerous Inspection Report Numbers ML17170A3202017-06-20020 June 2017 Safety Evaluation Input - for Ameren Missouri Request to Amend Callaway Plant, Unit 1, Technical Specification 5.6.5, Core Operating Limits Report - ML16197A0102016-08-22022 August 2016 Staff Observations of Testing for Generic Safety Issue 191 During a June 28 to June 30, 2016 Trip to the Alden Test Facility for Performance Contracting Inc. Strainer Tests ML16091A1522016-03-31031 March 2016 Request to Review and Update Guidance in National Fire Protection Association (NFPA) 805 Frequently Asked Question (FAQ) 07-0040 ML15139A4842015-06-0202 June 2015 Staff Review of Callaway Plant Unit 1 Physical Security Plan Revision 12 for the Verification of ASM (EA-13-237) Incorporation (TAC No. L25009) ML14310A8362015-02-0909 February 2015 NRC Staff Evaluation of Final Rule for Continued Storage of Spent Nuclear Fuel for the License Renewal Environmental Review for Callaway, Unit 1 ML14177A5952014-07-0808 July 2014 Summary of Telephone Conference Call Held on February 12, 2014, Between the U.S. Nuclear Regulatory Commission and Union Electric Company (Ameren Missouri), Concerning Requests for Additional Information Pertaining to the Callaway Plant, Un ML14183A0212014-07-0101 July 2014 License Renewal Application ML14121A5532014-06-18018 June 2014 November 25, 2013, Summary of Telephone Conference Call Held Between NRC and Union Electric Co., (Ameren Missouri), Concerning Requests for Additional Information Pertaining to Callaway, Unit 1, License Renewal Application ML14121A1062014-05-12012 May 2014 Advisory Committee on Reactor Safeguards Review of the Callaway Nuclear Plant License Renewal Application - Safety Evaluation Report ML14112A2762014-05-0707 May 2014 Summary of Public Meetings to Discuss Draft Supplement 51 to the Generic Environmental Impact Statement for License Renewal of Nuclear Plants Regarding Callaway Plant, Unit 1 ML14104A8932014-04-23023 April 2014 U.S. Nuclear Regulatory Commission Staff'S Spot- Check Review of Ameren Missouri'S 100 Percent Ownership Interest in Callaway Energy Center, Docket No. 50-483, on April 8, 2014- Finding of No Potential Issue ML14087A2102014-04-0808 April 2014 Summary of 3/25/14 Verbal Relief Telephone Conference, Relief Request I3R-16, Temporary Non-Code Repair of the Train a Component Cooling Water Heat Exchanger to Control ESW Leakage, Third 10-Year Inservice Inspection Interval ML14035A5752014-03-25025 March 2014 January 28, 2014, Summary of Telephone Conference Call Held Between NRC and Union Electric Company (Ameren Missouri), Pertaining to the Callaway Plant Unit 1, LRA ML13246A3072013-09-0909 September 2013 Memorandum to File - Verbal Authorization of Relief Request PR-07, Testing Frequency for Pumps and Valves, Third 10-year Inservice Testing Interval ML13126A3202013-05-0707 May 2013 Summary of Telephone Conference, Verbal Authorization of Relief Request I3R-14. Proposed Alternative to ASME Code Requirements for Leakage Testing of RPV Head Flange Leakoff Lines, Third 10-Year ISI Interval. ML13059A8002013-03-11011 March 2013 Summary of Telephone Call Held on 11/5/12, Between NRC and Union Electric Company, Regarding Request for Clarification of Responses to the SAMA RAI Concerning Callaway Plant, Unit 1, LRA ML12298A4282012-10-26026 October 2012 Notice of Preapplication Meeting with Union Electric Company to Discuss Callaway Plant, Unit 1, License Amendment Request to Change Licensing Basis and Analysis of Integrated Head Assembly Consistent with Regulatory Guide 1.61 Revision 1 ML12292A1212012-10-22022 October 2012 Updated ETE Quarterly Report for Q4 2012 ML12262A3112012-10-0202 October 2012 Summary of Telephone Conference Call Held on September 14, 2012, Between NRC and Union Electric Company, Concerning the SAMA RAI for the Callaway Plant, Unit 1, LRA ML12234A5232012-08-24024 August 2012 Quarterly Report of Activity Related to Updated Evacuation Time Estimates ML12227A3472012-08-14014 August 2012 8/29/2012 Notice of Preapplication Meeting with Union Electric Company to Discuss Request for New Technical Specification Related to Class 1E Electrical Equipment Air Conditioning System at Callaway Plant, Unit 1 ML12227A3492012-08-14014 August 2012 8/29/2012 Notice of Preapplication Meeting with Union Electric Company to Discuss Request to Revise Technical Specification 3.7.9, Ultimate Heat Sink SR 3.7.9.1 and 3.7.9.2 at Callaway Plant, Unit 1 ML12167A5082012-06-15015 June 2012 Letter to the Honorable Jeannette Mott Oxford Related to the 10/21/2003, Shutdown at Callaway Plant ML1211502472012-05-0303 May 2012 Memo to File, Verbal Authorization, Relief Request VR-01 from Requirements of ASME OM Code Mandatory Appendix I, One-time Extension Replacement of Main Steam Isolation Valve Actuator Rupture Disks ML12089A0992012-04-11011 April 2012 Summary of Public Scoping Meetings Conducted Related to the Review of the Callaway Plant, Unit 1 License Renewal Application ML12041A4792012-02-24024 February 2012 03/14/2012-Notice of Forthcoming Meeting to Discuss the License Renewal Process and Environmental Scoping for Callaway Plant, Unit 1 ML12027A0202012-01-27027 January 2012 Acceptance of License Renewal Application, Callaway Plant Unit 1 ML1200300872011-12-29029 December 2011 Forthcoming Meeting with Petitioner Requesting Action Under 10 CFR 2.206 Regarding Blocking P-4/Low Tavg Feedwater Isolation Signal at Callaway Plant, Unit 1 ML1136304032011-12-29029 December 2011 Correction Notice of Forthcoming Meeting with Petitioner Requesting Action Under 10 CFR 2.206 ML1131200872011-11-16016 November 2011 Verbal Authorization Memorandum, Relief Request 13R-13, Alternative to Requirements for Performance of Second Successive Exam of C Cold Leg Safe-End to Elbow Weld, Third 10-Year Inservice Inspection ML11192A2362011-07-12012 July 2011 Notice of Closed Meeting with Callaway to Discuss Lessons Learned from the Recent Triennial Force-On-Force Exercise at the Callaway Nuclear Power Plant IR 05000483/20110072011-06-27027 June 2011 IR 05000483-11-007, on 03/21-05/13/11, Callaway Plant, Special Inspection for Turbine-driven Auxiliary Feedwater Pump Bearing Degradation ML1113202252011-05-12012 May 2011 Notice of Preapplication Meeting with Union Electric Company to Discuss Callaway Plant, Unit 1's Amendment Request to Adopt Risk-informed, Performance-Based Alternative Described in National Fire Protection Association Standard (NFPA) 805 ML1136103072011-05-0404 May 2011 CW-2011-06-Public Forms ML1109501212011-04-0505 April 2011 Notice of Meeting to Discuss NRC Reactor Oversight Process Annual Assessment of Callaway Plant ML1104001662011-02-22022 February 2011 Summary of Meeting with Union Electric Company to Discuss Licensee'S Planned Responses to Staff Requests for Additional Information Callaway Plant'S Request to Revise TS 3.3.2, ESFAS Instrumentation Functions ML1101204702011-01-12012 January 2011 Notice of Meeting with Union Electric Company to Discuss Licensee'S Planned Responses to Staff Requests for Additional Information Callaway Plant'S Request to Revise TS 3.3.2, ESFAS Instrumentation Functions ML1030202792010-11-0505 November 2010 Notice of Meeting with Union Electric Company to Discuss Licensee'S Planned Responses to Staff Requests for Additional Information Related to Callaway Plant'S Request to Revise TS 3.3.2, ESFAS Instrumentation Functions ML11363A1132010-08-0505 August 2010 Memo from M. Markley, NRR to M. Kotzalas, EDO on G20100476/EDATS: OEDO-2010-0609 - Briefing Package for Drop-In Visit by Union Electric Company Official with NRC Staff on August 13, 2010, for Callaway Plant ML1009105332010-04-0505 April 2010 U.S. Nuclear Regulatory Commission Staff Review of the Department of Homeland Security Consultation Reports ML0929300152009-10-20020 October 2009 Revised Notice of Meeting with Union Electric Company and Wolf Creek Nuclear Operating Company to Discuss NRC Requests for Additional Information on Generic Letter 2004-02 ML0928003162009-10-16016 October 2009 Notice of Meeting with Union Electric Company and Wolf Creek Nuclear Operating Company to Discuss NRC Requests for Additional Information on Generic Letter 2004-02 Sent 7/31/0209 and 8/27/2009, Respectively ML0924605592009-09-0404 September 2009 Notice of Meeting with Union Electric Company to Discuss a Proposed Risk Informed Change to Callaway, Unit 1, Technical Specifications ML0920306202009-07-31031 July 2009 Notice of Forthcoming Conference Call with Union Electric Company and Wolf Creek Nuclear Operating Company Re Draft Requests for Additional Information on Generic Letter 2004-02 for Callaway Plant and Wolf Creek Creek Generating Station ML0916801682009-06-17017 June 2009 Charter for Special Inspection Involving the Failure of the Turbine Driven Auxiliary Feedwater Pump to Start at the Callaway Plant 2022-06-06
[Table view] |
Text
May 3, 2021 MEMORANDUM TO: Scott A. Morris, Regional Administrator THRU: Ryan E. Lantz, Acting Director /RA/
Division of Reactor Projects FROM: Neil F. OKeefe, Chief /RA/
Project Branch B Division of Reactor Projects
SUBJECT:
INSPECTION MANUAL CHAPTER 0375 RECOMMENDATION FOR CALLAWAY PLANT Pursuant to Inspection Manual Chapter (IMC) 0375, Implementation of the Reactor Oversight Process at Reactor Facilities in an Extended Shutdown Condition for Reasons Not Related to Performance, this memorandum documents the Reactor Projects Branch B recommendation on implementation of the provisions of IMC 0375 for the Callaway Plant extended shutdown.
The Callaway Plant experienced a reactor trip on December 24, 2020, due to a main generator fault. The fault resulted in damage to the non-safety main generator and associated support systems that necessitated an extended outage to complete repairs. The expected duration of the outage is sufficiently long to consider implementing IMC 0375. The IMC 0375 allows the Regional Administrator significant flexibility in deciding whether and how to implement the guidance. Branch B has reviewed IMC 0375 and discussed the guidance it contains with the Inspection Program Assessment Branch, which owns the guidance. While a formal cause evaluation has not yet been completed, the licensee provided a briefing on their discovery information concerning the damage and developed the expected outage work scope sufficiently to support the present decision-making for oversight. The following recommendation was developed based on the information available.
Recommendation: The benefits of implementing all or parts of IMC 0375 are limited in this case. Specifically, there is no plant condition or safety performance issue that would drive the need to establish additional regulatory oversight or complex inspection planning. Therefore, Branch B recommends using the flexibilities available within the Reactor Oversight Process (ROP) baseline inspection program with special attention to documenting regulatory decisions, monitoring ROP performance Indicators that may become invalid, and consideration of monitoring of restart readiness of operators.
CONTACT: Neil OKeefe, DRP/B 817-917-5646.
S. Morris 2 The following factors support this recommendation:
- The cause of the shutdown appears to be directly related to recent work within the main generator and is not applicable to any other plant equipment. The extent of condition for the damage was limited to the non-safety main generator and its support systems.
Therefore, there is no need to develop an inspection plant to ensure adequate discovery.
- There were no safety performance issues or equipment concerns, either prior to the event or associated with the event, that necessitate further regulatory consideration or monitoring of corrective action effectiveness to ensure adequate safety prior to returning to operation.
- The ability to perform baseline inspections or safety assessments is not expected to be affected by the nature or the expected duration of the outage.
- Reactor Projects Branch B plans to work with the Operations Branch to consider whether to implement additional oversight prior to the unit restart based on operator proficiency following an extended outage. A recommendation will be provided and documented at that time.
- The Be Risk Smart process was used to evaluate potential risks and risk management options. Choosing to not implement IMC 0375 is a low risk option that can be managed using normal processes.
Further recommendations on regional oversight of the Callaway Plant will be provided when the licensee is ready for restart following the extended outage.
John D. Digitally signed by John D.
Monninger Action: Approve / Disapprove Monninger Date: 2021.05.10 20:08:00
-05'00' Scott A. Morris Date Regional Administrator
ML21111A037 SUNSI Review ADAMS: Non-Publicly Available Non-Sensitive Keyword:
By: DLP Yes No Publicly Available Sensitive NRC-002 OFFICE SPE:DRP/B C:DRP/B AD:DRP NAME DProulx NOKeefe RLantz SIGNATURE /RA/ /RA/ /RA/
DATE 03/29/21 04/21/21 04/21/21