i

/.eue:va%

UNITED STATES 9

N NUCLEAR REGULATORY COMMISSION

/'

3

.E REGION 11 f

101 MARIETTA ST N.W.. SUITE 3100 o

Y

[

ATLANTA. G EORGIA 30303 e

August 25, 1982 MEMORANDUM FOR: Chief, Vendor Inspection Branch, Region IV FROM:

R. C. Lewis, Director, Division of Project and Resident Programs

SUBJECT:

CONSTRUCTION DEFICIENCY REPORT - CONFIRMATION OF TELECON (AITS N0. F02700273 )

Enclosed is a 10/CFR 50.55(e)/10 CFR 21 report received from Mississippi Power & Light Co.

This appears to be a generic problem. Would you please followup on the generic aspects of the problem with the AE/ Vendor? Should you have additional questions, we will be glad to discuss them with you.

[ C.

)

R. C. Lewis

Enclosure:

as stated cc:

J. Olshinski, RII Director, DPRP, RI Director, DPRP, RIII Di rector. DRRP8EP, RV B. Heishman, IE 8612120229 861203 PDR FOIA ELLISS6-656 PDR CONTACT:

R. Rutthpr (242-5584 )

D/A?

9 I~

.AW W

i:

6, ei,;:e.

- ' A li Y Id I'0' 1 Ri til!! ! !

Ofil t Augus,t 25, 1982 f Ai.!! 1iY 7,011! IT ij tg Iit: oR Li'i.;;J pu,10N,ft,1, AL Ilu 4 i

Grand Gulf 1 & 2 Licensee 8/24 Unqualified Material Used in Governor Drive Followup per MC 2512 DN:

50-416 & 417 Coupling of Delaval Diesel Generator (DG).

and 251 Transamerica Delaval notified the NRC by REGION IV NOTIFIED letter dated 6/23/82 that the Governor Drive O k p il Couplings for Delaval Diesel Generators were fabricated using isopreme.

Isopreme is not qualified for the high temperature oil atmo-ys sphere encountered in this application and g fail causing the DG to trip. MP&L was notified of this defect 8/23. Couplings were manufactured i

by the Koppers Company.

e-

% 4 1

.- -