Similar Documents at Surry |
---|
Category:SAFETY EVALUATION REPORT--LICENSING & RELATED ISSUES
MONTHYEARML18152B3371999-09-24024 September 1999 SER Accepting Third 10-year Interval Inservice Insp Plan Request for Relief SR-026 for Surry Power Station Unit 2 ML18152B3631999-08-23023 August 1999 Safety Evaluation Supporting Eddy Current Techniques Used by VEPCO to Determine Depth of Degradation Evident in Units SG Tubing & VEPCO Approach for Dispositioning Tubes with Avb Wear Indications ML18152B3831999-08-23023 August 1999 Safety Evaluation Granting Relief Request from ASME Section XI Requirements for Containment Insp ML18152B3841999-08-23023 August 1999 Safety Evaluation Granting Relief Request from ASME Section Xa Requirements for Containment Insp ML20196J4781999-07-0101 July 1999 Safety Evaluation Supporting Amends 221 & 221 to Licenses DPR-32 & DPR-37,respectively ML20195D3571999-06-0707 June 1999 Safety Evaluation Supporting Amends 220 & 220 to Licenses DPR-32 & DPR-37,respectively ML18152B6481999-04-14014 April 1999 Safety Evaluation Supporting Relief Requests IWE-2,4.5.6 & IWL-2 to Licenses DPR-32 & DPR-37 Respectively ML18152B6451999-04-13013 April 1999 SER Accepting Util Reactor Pressure Vessel Fluence Methodology for Surry Power Stations,Units 1 & 2 & North Anna Power Station,Units 1 & 2 Subject to Listed Limitations ML20207L8081999-03-12012 March 1999 Safety Evaluation Supporting Amends 219 & 219 to Licenses DPR-32 & DPR-37 ML18152B5381999-02-16016 February 1999 SER Accepting Third 10-year Interval Inservice Insp Request for Relief for Surry Power Station,Unit 1.Staff Concludes That Licensee Proposed Alternative Will Provide Acceptable Level of Quality & Safety.Technical Ltr Rept Also Encl ML18152B5861998-12-18018 December 1998 SER Approving Request Relief Related to Inservice Testing Program at Surry Power Station Unit 1 ML18152B5901998-12-16016 December 1998 Safety Evaluation Authorizing Request to Use Code Case N-577 as Alternative to Requirements of ASME Code Section XI for Surry Power Station,Unit 1 ML20198F9221998-12-16016 December 1998 Safety Evaluation Supporting Amends 217 & 217 to Licenses DPR-32 & DPR-37,respectively ML20151U7261998-09-0303 September 1998 Safety Evaluation Approving Exemption from Certain 10CFR20 Requirements Re Use of self-contained Breathing Apparatus with Enriched Oxygen in Subatmospheric Containments at SPS ML20237E9721998-08-26026 August 1998 Safety Evaluation Supporting Amends 216 & 216 to Licenses DPR-32 & DPR-37,respectively ML20236R2111998-07-15015 July 1998 SER Related to Request for Revised Exemption from 10CFR70.24(a) for Surry Power Station,Units 1 & 2 ML20249B8191998-06-19019 June 1998 Safety Evaluation Supporting Amends 215 & 215 to Licenses DPR-32 & DPR-37,respectively ML20249B8261998-06-19019 June 1998 Safety Evaluation Supporting Amends 214 & 214 to Licenses DPR-32 & DPR-37,respectively ML20248M0911998-06-11011 June 1998 Safety Evaluation Supporting Amends 213 & 213 to Licenses DPR-32 & DPR-37,respectively ML18152B8011998-05-0404 May 1998 Safety Evaluation Granting Third 10-year Interval Inservice Insp Plan Request for Relief SR-19 for Surry Power Station, Unit 1 ML18152B7881998-04-28028 April 1998 SER Accepting Request for Relief from ASME Code Requirements - Deferral of Repair to RHR Sys Piping ML18153A3011998-04-20020 April 1998 Safety Evaluation Denying Licensee Assessment of Reactor Vessel Structural Integrity ML20217P9941998-04-0707 April 1998 Safety Evaluation Granting Licensee Third 10-yr Inservice Insp Program Relief Requests SR-018 - Sr-024 ML18153A3841997-12-0303 December 1997 Safety Evaluation Accepting Licensee Structural Integrity & Operability Assessments ML20202B8751997-11-24024 November 1997 Safety Evaluation Denying Licensee Request for Exemption from Section III.G.2.f of App R to 10CFR50.Staff Concluded That Use of Combustible Radiant Energy Heat Shields Inside Containment at Surry & North Anna Unacceptable ML18153A4011997-11-24024 November 1997 Safety Evaluation Accepting Licensee Proposed Alternative to Perform Visual Exam of Reactor Vessel Closure Head Nuts in Lieu of Surface Exam ML18153A4471997-10-0101 October 1997 Safety Evaluation Re Relief from Implementation of 10CFR50.55a Requirements for Surry Power Station,Units 1 & 2 & North Anna Power Station,Units 1 & 2 ML20217P0951997-08-21021 August 1997 Safety Evaluation Accepting Licensee ,As Suppl by 970324 Request for Exemption from Requirements of 10CFR70.24(a) Re Criticality Monitors as Pertaining to Unirradiated Fuel & Other Forms of Special Nuclear Matls ML20149D8361997-07-15015 July 1997 Safety Evaluation Supporting Amends 211 & 211 to Licenses DPR-32 & DPR-37,respectively ML18153A1271997-04-11011 April 1997 Safety Evaluation Accepting Third 10-yr ISI Interval Requests for Relief Sr-14 - SR-17 for Plant,Unit 2 ML18153A0511996-08-30030 August 1996 SE Granting Third 10-yr Interval ISI Program Plan Requests for Relief SR-009 Through SR-017,subj to Requirement for Relief Request SR-014 ML20117M4281996-06-0707 June 1996 Safety Evaluation Supporting Amends 210 & 210 to Licenses DPR-32 & DPR-37 ML20108B3661996-04-29029 April 1996 Safety Evaluation Supporting Amends 209 & 209 to Licenses DPR-32 & DPR-37,respectively ML20107K0081996-04-18018 April 1996 Safety Evaluation Supporting Amends 208 & 208 to Licenses DPR-32 & DPR-37,respectively ML18153A6091996-04-16016 April 1996 Safety Evaluation Authorizing Third 10-yr Interval ISI Program Plan Requests for Relief to Use Code Cases N-522 & N-535 at Plant,Per 10CFR50.55a(a)(3)(i) ML20099M0071995-12-28028 December 1995 Safety Evaluation Supporting Amends 207 & 207 to Licenses DPR-32 & DPR-37,respectively ML18153A5631995-12-19019 December 1995 SER Recommending That Relief Requests SR-22 Through SR-26, Be Granted,Per 10CFR50.55a(g)(6)(i) ML18153A5541995-12-13013 December 1995 Safety Evaluation Accepting Change to Emergency Plan Augmentation Goals of Selected Responders from 30 Minutes to 45 Minutes for Plant ML20092G7381995-09-14014 September 1995 Safety Evaluation Supporting Amends 205 & 205 to Licenses DPR-32 & DPR-37 ML20092A3131995-09-0101 September 1995 Safety Evaluation Supporting Amend 204 to Licenses DPR-32 & DPR-37 ML18153A7511995-08-30030 August 1995 Safety Evaluation Granting Third 10-yr Interval Inservice Insp Program Plan,Rev 0 & Associated Requests for Relief ML20087B5731995-08-0303 August 1995 Safety Evaluation Supporting Amends 203 & 203 to Licenses DPR-32 & DPR-37,respectively ML20087A1791995-07-27027 July 1995 Safety Evaluation Supporting Amends 202 & 202 to Licenses DPR-32 & DPR-37,respectively ML18153A7261995-07-19019 July 1995 Safety Evaluation Re Third 10-yr Interval Inservice Insp Program Update & Associated Requests for Relief ML18153A7101995-07-19019 July 1995 Safety Evaluation Granting Requests for Relief RR-2,RR-6, RR-7,RR-8,RR-11,SR-002,SR-003,SR-004 & SR-006 ML20086J7611995-07-11011 July 1995 Safety Evaluation Supporting Amends 201 & 201 to Licenses DPR-32 & DPR-37,respectively ML18153A6951995-07-0606 July 1995 SER Denying Proposed Revisions to Decrease Effectiveness of Currently Approved Emergency Plan for Each Site ML20086E3221995-06-29029 June 1995 Safety Evaluation Supporting Amends 200 & 200 to Licenses DPR-32 & DPR-37,respectively ML18153A8511995-06-0808 June 1995 Safety Evaluation Granting Third Interval Inservice Insp Program Relief Requests from ASME Code Section XI for Plant, Unit 1 & 2 ML20091R3121995-05-31031 May 1995 Safety Evaluation Supporting Amend 199 to Licenses DPR-32 & DPR-37,respectively 1999-09-24
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML18152A2811999-10-12012 October 1999 Technical Basis for Elimination of Nozzle Inner Radius Insps (for Nozzles Other than Reactor Vessel),Technical Basis for ASME Section XI Code Case N-619 05000281/LER-1999-004-02, :on 981109,EDG Was Inoperable Longer than Allowed by TS Due to Governor Compensation Valve.Root Cause Evaluation Being Performed to Determine How Compensation Valve Became Closed1999-10-0101 October 1999
- on 981109,EDG Was Inoperable Longer than Allowed by TS Due to Governor Compensation Valve.Root Cause Evaluation Being Performed to Determine How Compensation Valve Became Closed
ML18152B3531999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Surry Power Station,Units 1 & 2.With ML18152B3371999-09-24024 September 1999 SER Accepting Third 10-year Interval Inservice Insp Plan Request for Relief SR-026 for Surry Power Station Unit 2 ML18152B6651999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Surry Power Station Units 1 & 2.With 05000280/LER-1999-006, :on 990802,determined That Plant Was Outside of App R Design Basis Due to Fire Barrier Deficiencies. Caused by Original Plant Design Deficiencies.Fire Watches Were Established & Mods Have Been Completed.With1999-08-27027 August 1999
- on 990802,determined That Plant Was Outside of App R Design Basis Due to Fire Barrier Deficiencies. Caused by Original Plant Design Deficiencies.Fire Watches Were Established & Mods Have Been Completed.With
05000280/LER-1999-005-01, :on 990731,effluent Radiation Monitors Were Declared Inoperable.Caused by Degraded Heat Trace Circuits for Monitors Sample Suction Line.Degraded Heat Trace Circuit Was Replaced & Addl Heat Trace Is Being Installed1999-08-27027 August 1999
- on 990731,effluent Radiation Monitors Were Declared Inoperable.Caused by Degraded Heat Trace Circuits for Monitors Sample Suction Line.Degraded Heat Trace Circuit Was Replaced & Addl Heat Trace Is Being Installed
ML18152B3841999-08-23023 August 1999 Safety Evaluation Granting Relief Request from ASME Section Xa Requirements for Containment Insp ML18152B3631999-08-23023 August 1999 Safety Evaluation Supporting Eddy Current Techniques Used by VEPCO to Determine Depth of Degradation Evident in Units SG Tubing & VEPCO Approach for Dispositioning Tubes with Avb Wear Indications ML18152B3831999-08-23023 August 1999 Safety Evaluation Granting Relief Request from ASME Section XI Requirements for Containment Insp 05000280/LER-1999-004-01, :on 990714,TS Violation Due to non-safety Related Fans Effect on CR Boundary Was Noted.Cause of Event Has Not Yet Been Determined.Cable Spreading Room Doors Were Operned to Reduce Pressure in Rooms1999-08-13013 August 1999
- on 990714,TS Violation Due to non-safety Related Fans Effect on CR Boundary Was Noted.Cause of Event Has Not Yet Been Determined.Cable Spreading Room Doors Were Operned to Reduce Pressure in Rooms
ML18151A3981999-08-13013 August 1999 SPS Unit 2 ISI Summary Rept for 1999 Refueling Outage ML18152B3791999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Surry Power Station,Units 1 & 2.With 05000281/LER-1999-003-02, :on 990705,auto Reactor Trip on Low Coolant Flow,Occurred.Caused by Loop Stop Valve Failure.Approved RCE Recommendations,Designed to Prevent Recurrence of Similar Event Will Be Implemented Through CAP1999-07-30030 July 1999
- on 990705,auto Reactor Trip on Low Coolant Flow,Occurred.Caused by Loop Stop Valve Failure.Approved RCE Recommendations,Designed to Prevent Recurrence of Similar Event Will Be Implemented Through CAP
ML20196J4781999-07-0101 July 1999 Safety Evaluation Supporting Amends 221 & 221 to Licenses DPR-32 & DPR-37,respectively ML18152B3911999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Surry Power Station,Units 1 & 2.With ML20195D3571999-06-0707 June 1999 Safety Evaluation Supporting Amends 220 & 220 to Licenses DPR-32 & DPR-37,respectively ML20195E2401999-05-31031 May 1999 Rev 2 to COLR for SPS Unit 2 Cycle 16 Pattern Ag ML18152B4341999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Surry Power Station,Units 1 & 2.With 05000281/LER-1999-002-02, :on 990425,MSSVs Tested Out of Tolerance for as Found Setpoint.Caused by Minor Setpoint Drift.No Immediate Action Required.Deviation Rept Submitted for Each Valve.With1999-05-18018 May 1999
- on 990425,MSSVs Tested Out of Tolerance for as Found Setpoint.Caused by Minor Setpoint Drift.No Immediate Action Required.Deviation Rept Submitted for Each Valve.With
ML18152B4161999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Surry Power Station Units 1 & 2.With 05000280/LER-1999-003-01, :on 990331,potential Loss of Charging Pumps Was Noted.Caused by Main CR Fire.Station Deviation Was Issued on 990331.With1999-04-28028 April 1999
- on 990331,potential Loss of Charging Pumps Was Noted.Caused by Main CR Fire.Station Deviation Was Issued on 990331.With
ML18152B6481999-04-14014 April 1999 Safety Evaluation Supporting Relief Requests IWE-2,4.5.6 & IWL-2 to Licenses DPR-32 & DPR-37 Respectively ML18152B6451999-04-13013 April 1999 SER Accepting Util Reactor Pressure Vessel Fluence Methodology for Surry Power Stations,Units 1 & 2 & North Anna Power Station,Units 1 & 2 Subject to Listed Limitations 05000281/LER-1999-001-02, :on 990301,RPS Relay Not Placed in Trip Resulted in Violation of TS 3.7.Caused by Lack of Procedural Guidance.Developed New Procedure to Provide More Explicit Instructions for Placing Stop Valve in Relay Trip1999-03-31031 March 1999
- on 990301,RPS Relay Not Placed in Trip Resulted in Violation of TS 3.7.Caused by Lack of Procedural Guidance.Developed New Procedure to Provide More Explicit Instructions for Placing Stop Valve in Relay Trip
ML18152B6511999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Surry Power Station Units 1 & 2 05000280/LER-1999-002-01, :on 990301,prematurely Released Fire Watches Resulted in Violation of TS 3.21.B.7.Caused by Inadequate Procedure.Procedure for Opening & Sealing Fire Stops Was Revised on 9902121999-03-29029 March 1999
- on 990301,prematurely Released Fire Watches Resulted in Violation of TS 3.21.B.7.Caused by Inadequate Procedure.Procedure for Opening & Sealing Fire Stops Was Revised on 990212
05000280/LER-1998-013, :on 981122,turbine/reactor Tripped on High Due to Short Circuit in Summator for MSL C Loop Channel III Flow Transmitter.Replaced 1-MS-FT1494 Summator & Module Repair Procedure Revised.With 9903190 Ltr1999-03-19019 March 1999
- on 981122,turbine/reactor Tripped on High Due to Short Circuit in Summator for MSL C Loop Channel III Flow Transmitter.Replaced 1-MS-FT1494 Summator & Module Repair Procedure Revised.With 9903190 Ltr
ML20207L8081999-03-12012 March 1999 Safety Evaluation Supporting Amends 219 & 219 to Licenses DPR-32 & DPR-37 ML18152B7331999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Surry Power Station,Units 1 & 2.With ML18152B5381999-02-16016 February 1999 SER Accepting Third 10-year Interval Inservice Insp Request for Relief for Surry Power Station,Unit 1.Staff Concludes That Licensee Proposed Alternative Will Provide Acceptable Level of Quality & Safety.Technical Ltr Rept Also Encl ML18152B5421999-01-31031 January 1999 Monthly Operating Repts for Jan 1999 for Surry Power Station,Units 1 & 2.With ML18151A3031999-01-29029 January 1999 ISI Summary Rept for 1998 Refueling Outage,Including Form NIS-1, Owners Rept for ISIs & Form NIS-2, Owners Rept for Repairs & Replacements 05000280/LER-1999-001, :on 981222,auxiliary Feedwater Pipe Support Missed Surveillance.Caused by Personnel Error.Station Deviation Rept Was Submitted.Two Supports in Question Received Required Code Insp & Were Found Acceptable1999-01-21021 January 1999
- on 981222,auxiliary Feedwater Pipe Support Missed Surveillance.Caused by Personnel Error.Station Deviation Rept Was Submitted.Two Supports in Question Received Required Code Insp & Were Found Acceptable
ML18152B6011998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Surry Power Station,Units 1 & 2.With ML18152B5861998-12-18018 December 1998 SER Approving Request Relief Related to Inservice Testing Program at Surry Power Station Unit 1 ML20198F9221998-12-16016 December 1998 Safety Evaluation Supporting Amends 217 & 217 to Licenses DPR-32 & DPR-37,respectively 05000280/LER-1998-014, :on 981126,manual Reactor Trip in Response to Main Feedwater Regulating Valve Failure Occurred.Caused by Dislocation of Retaining Clip in Positioner.Control Room Operators Placed Unit in Safe,Shutdown Condition1998-12-16016 December 1998
- on 981126,manual Reactor Trip in Response to Main Feedwater Regulating Valve Failure Occurred.Caused by Dislocation of Retaining Clip in Positioner.Control Room Operators Placed Unit in Safe,Shutdown Condition
ML18152B5901998-12-16016 December 1998 Safety Evaluation Authorizing Request to Use Code Case N-577 as Alternative to Requirements of ASME Code Section XI for Surry Power Station,Unit 1 ML18152B7121998-12-0404 December 1998 LER 98-S01-00:on 981105,noted Failure to Deactivate Station Access Badge.Caused by Human Error.Licensee Will Now Deactivate Station Badges Before Clearance Is Revoked & Process for Badge Deactivations Have Been Strengthened 05000280/LER-1998-012, :on 981102,noted That EDGs Were Concurrently Inoperable.Caused by Required Testing Per TS 3.16.B.1.a.2. Redundant EDG Was Returned to Svc within Two Hour Period, Following Satisfactory Testing.With1998-12-0101 December 1998
- on 981102,noted That EDGs Were Concurrently Inoperable.Caused by Required Testing Per TS 3.16.B.1.a.2. Redundant EDG Was Returned to Svc within Two Hour Period, Following Satisfactory Testing.With
ML18152B7081998-11-30030 November 1998 Rev 0 to COLR for Surry 1 Cycle 16,Pattern Un ML18152B5721998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Surry Power Station,Units 1 & 2.With ML18152B6241998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Surry Power Station Units 1 & 2.With ML18152B6881998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Surry Power Station Units 1 & 2.With ML20151U7261998-09-0303 September 1998 Safety Evaluation Approving Exemption from Certain 10CFR20 Requirements Re Use of self-contained Breathing Apparatus with Enriched Oxygen in Subatmospheric Containments at SPS ML18153A3271998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Surry Power Station,Units 1 & 2 ML20237E9721998-08-26026 August 1998 Safety Evaluation Supporting Amends 216 & 216 to Licenses DPR-32 & DPR-37,respectively ML18153A3161998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Surry Power Station Units 1 & 2 05000280/LER-1998-010, :on 980715,low Intake Canal Level Instrument Channel I Was Declared Inoperable to Allow Testing of Intake Canal Level Probe 1-CW-LE-102.Subject Probe Was Cleaned by Diver,Tested & Channel I Was Returned to Operable Status1998-07-31031 July 1998
- on 980715,low Intake Canal Level Instrument Channel I Was Declared Inoperable to Allow Testing of Intake Canal Level Probe 1-CW-LE-102.Subject Probe Was Cleaned by Diver,Tested & Channel I Was Returned to Operable Status
1999-09-30
[Table view] |
Text
p f. Egg UNITED STATES g
,j NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 2065H001 n% *****/
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 221 TO FACILITY OPERATING LICENSE NO. DPR-32 AND AMENDMENT NO. 221 TO FACILITY OPERATING LICENSE NO. DPR-37 VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION. UNIT NOS.1 AND 2 DOCKET NOS. 50-280 AND 50-281
1.0 INTRODUCTION
By letter dated February 16,1999, Virginia Electric and Power Company (the licensee) submitted for staff review and approval a proposed Technical Specifications (TS) change
'egarding inspection requirements for the reactor coolant pump (RCP) flywheels. This issue as addressed in the Westinghouse topical report, WCAP-14535A, " Topical Report on Reactor Joolant Pump Flywheel Inspection Elimination," which was approved by the United States Nuclear Regulatory Commission (USNRC) with certain conditions. These conditions are specified in the safety evaluation report (SER) dated September 12,1996, for WCAP-14535A.
The licensee intended to apply this topical report to Surry Units 1 and 2 and change their RCP
)
flywheels inspection intervals in accordance with the conclusion of the SER on WCAP-14535A.
]
The function of the RCP in the reactor coolant system (RCS) of a pressurized water reactor (PWR) plant is to maintain an adequate cooling flow rate by circulating a large volume of primary coolant water at high temperature and pressure through the RCS. A concern over overspeed of the RCP and its potential for failure led to the issuance of Regulatory Guide (RG) 1.14 in 1971. Since then, all licensees for PWR plants, with very few exceptions, have adopted the guidelines of RG 1.14 to conduct their RCP flywheel examinations. These requirements are normally specified in the individual plant's TS as is the case for Surry Units 1 and 2.
2.0 EVALUATION in the SER on Westinghouse topical report WCAP-14535A, the staff stated that the evaluation methodology for RCP flywheels in WCAP-14535A is appropriate and the criteria are in
)
accordance with the design criteria of RG 1.14. In addition, the staff specified:
(1) Licensees who plan to submit a plant-specific application of this topical report for flywheels made of SA 533 B material need to confirm that their flywheels are made of l
l SA 533 8 material. Further, licensees having Group-15 flywheels need to demonstrate that the material properties of their A516 material are equivalent to i
SA 533 8 material, and its reference temperature, RTa, is less than 30"F.
Enclosure 9907070301 990701 PDR ADOCK 05000200 P
PDR 1
l
4 e
2 (2) Licensees who plan to submit a plant-specific application of this topical report for their flywheels not made of SA 533 B or A516 material need to either demonstrate that their flywheel material properties are bounded by those of SA 533 B material, or provide the minimum specified ultimate tensile stress, S, the fracture toughness, K, and the o
g reference temperature, RTuot, for that material. For the latter, the licensees should employ these material-specific properties, and use the methodology in the topical report, as extended in the two responses to the staff's request for additional information, to provide an assessment to justify a change in inspection schedules for their plants.
(3) Licensees meeting either (1) or (2) above should either conduct a qualified in-place ultrasonic testing (UT) examination of the volume from the inner bore of the flywheel to the circle of one-half the outer radius or conduct a surface examination (MT and/or PT) of exposed surfaces defined by the volume of the disassembled flywheels once every 10 years. The staff considers this 10-year inspection requirement not burdensome when the flywheel inspection is conducted during scheduled inservice inspection or RCP motor maintenance. This would provide an appropriato level of defense in depth.
Further, the staff required:
Licensees with Group-10 flywheels need to confirm in the near term that their flywheels have an adequate shrink fit of the flywheel at the maximum overspeed.
The licensee confirmed in its submittal that the flywheels for Surry Units 1 and 2 are made of SA 533 B material. Hence, only (1) and (3) apply. The staff further verified that the flywheels for Surry Units 1 and 2 do not belong to either Group 10 or Group 15 flywheels, for which j
additional analyses need to be performed. Therefore, the plant-specific applicability of WCAP-14535A to Surry Units 1 and 2 has been established, and the 10-year inspection requirement with details specified in (3) is acceptable.
The staff has determined that the analysis in the Westinghouse topical report WCAP-14535A is applicable to Surry Units 1 and 2. Hence, the staff accepts the licensee's proposed changes, i.e.,10-year inspection intervals for RCP flywheels, in accordance with (3) above, to TS 4.2, Augmented Inspections, Table 4.2-1, item 1.3, for both units.
3.0 STATE CONSULTATION
I in accordance with the Commission's regulations, the Virginia State official was notified of the proposed issuance of the amendments. The State official had no comment.
4.0 ENVIRONMENTAL CONSIDERATION
These amendments change a requirement with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 and change a surveillance requirement. The NRC staff has determined that the amendments involve no significant increase in the amounts and no significant change in the types of any effluents that I
I 1
s 3-may be released offsite, and that there is no significant increase in individual'or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding
. that these amendments involve no significant hazards consideration and there has been no public comment on such finding (64 FR 24204). Accordingly, these amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of these amendments;
5.0 CONCLUSION
- The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the'public will not be endangered by
- operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of these amendments will not be inimical to the common defense and security or to the health and safety of the public.
Principal Contributor S. Sheng
. Date: July 1,1999 i
4 i
s
i-
- .. w.
l l
l l
DATED:
Julv 1.1999 AMENDMENT NO. 221 TO FACILITv OPERATING LICENSE NO. DPR SURRY UNIT 1 AMENDMENT NO. 221 TO FACILITY OPERATING LICENSE NO. DPR SURRY UNIT 2 I
fOoolest FileJD PUBLIC PDil-1 R/F H. Berkow R. Emch E. Dunnington G. Edison OGC G. Hill (4), TWFN, 5/C/3 W. Beckner S.Sheng ACRS R. Hasg, Ril e-mail R. Scholl-SE only i
i l
l l
1
_