|
---|
Category:REPORTABLE OCCURRENCE REPORT (SEE ALSO AO
MONTHYEARML20045D3011993-06-18018 June 1993 Special Rept 93-002:on 930521,invalid Failure of Sdg 12 Occurred Due to False High Jacket Water Temp Signal, Generated by Faulty Jacket Water Temp Switch.Faulty Switch Replaced ML20044H0761993-06-0202 June 1993 Special Rept 93-001:on 930504,trip Signal Occurred During Performance of Monthly Functional Test for Standby DG 11. Caused by Inadequate Work Instructions.Surveillance Procedure Will Be Revised to Address Probe Magnetic Bars ML20042G8711990-05-0808 May 1990 Ro:On 900412,groundwater Level Reading Taken from Dewatering Well 8 Exceeded 109 Ft Mean Sea Level Design Basis.Caused by Incorrect Level Sensor Probe Setting.Probe Adjusted Using New Setpoint Data to Cycle Dewatering Well at 108.4 Ft ML19354E6851990-01-17017 January 1990 Special Rept 89-009-00:on 891218,diesel Generator 11 Failed. Potential Transformer Fuse Holders Found Loose.No Obvious Cause of Event Identified.Diesel Retested Satisfactorily W/O Recurrence of Original Incident ML19325E3561989-10-24024 October 1989 Special Rept 89-008-0:on 891010,instrument Channel Inoperable for More than 72 H.Caused by Turbine Bldg Exhaust Accident Range Monitor Declared Inoperable After Sample Flow Calculations Could Not Be Completed Due to Leaking Valve ML20024F4781983-08-29029 August 1983 RO 83-072/0:on 830729,30 & 0814-16,control Room Air Temp Exceeded Tech Spec Limit.Caused by Lack of Operating Control Room HVAC Subsystems & Low Freon in Subsystem B, Respectively.No Corrective Action Stated ML20024D0431983-07-27027 July 1983 RO 83-059/0:on 830620,fire-rated Doors OC412 & OC712 to Reactor Protection Sys Motor Generator Set Rooms Blocked Open to Aid Room Ventilation.Fire Watch Established.Expected Restoration Date of Doors Is 830731 ML20024C3311983-06-27027 June 1983 RO 83-052/0:on 830523,listed Fire Rated Penetrations Opened to Implement Design Change Packages.Hourly Fire Watches Established & Will Be Maintained Until Penetrations Resealed by 830801 ML20024C2611983-06-27027 June 1983 Updated RO 83-027/1:on 830321,during Seismic Monitoring Sys Functional Test,Operation of Chart Recorders & Spectrum Analyzers Unacceptable.Caused by Faulty Circuit Card.Card Replaced.Sys Restored on 830519 ML20024C3321983-06-24024 June 1983 RO 83-050/0:on 830519,floor Penetration CE-37G in Control Bldg Upper Cable Room Opened to Rework Cable Tray Hanger. Fire Watch Established Until Penetration Sealed on 830603. Seven-day Limiting Condition for Operation Exceeded ML20024C2761983-06-24024 June 1983 RO 83-049/0:on 830526,halon Bottle 2 in Panel P936 Discharged Until Empty.Hourly Fire Watch Established Pending Bottle Replacement.Limiting Condition for Operation to Be Maintained.Next Rept Will Be Submitted by 830731 ML20024C1151983-06-22022 June 1983 RO 83-047/0:on 830508 & 11,fire Protection Halon Sys for Two Control Room Back Panels Failed Surveillances.Caused by Inability to Meet Tolerance Specified for Full Charge Pressure.Surveillance Procedure Revised ML20023D5581983-05-0909 May 1983 RO 83-029/0:on 830422,50-meter Wind Direction Reading Did Not Agree w/10-meter Reading.Caused by Incorrectly Wired New Sensors Located in Design Change Package 82-502.Wiring Diagram Corrected ML20023B6381983-04-28028 April 1983 RO 83-025/0:on 830322,fire Rated Penetrations Opened to Implement Design Change Packages.Hourly Fire Watches Established within 1 H & Will Be Maintained for Duration of Planned Maint Activities.Work to Be Completed by 830610 ML20023B5021983-04-28028 April 1983 RO 83-026/0:on 830327,security Access Card Reader to Fire Door 1A318,Elevation 166 Ft,In Auxiliary Bldg Malfunctioned. Caused by Fire Door Blocked to Allow Personnel Access.Card Reader Reworked & Returned to Svc 830405 ML20028A5311982-11-10010 November 1982 Ro:On 820813,Channel a Tripped & HPCS Initiated on False Low Level Signal.Caused by Failure to Follow Procedures.On 820814,HPCS Initiated by True Low Reactor Water Level Signal from B21-N073 L&R.Procedures Developed to Correct Problems 1993-06-02
[Table view] Category:LER)
MONTHYEARML20045D3011993-06-18018 June 1993 Special Rept 93-002:on 930521,invalid Failure of Sdg 12 Occurred Due to False High Jacket Water Temp Signal, Generated by Faulty Jacket Water Temp Switch.Faulty Switch Replaced ML20044H0761993-06-0202 June 1993 Special Rept 93-001:on 930504,trip Signal Occurred During Performance of Monthly Functional Test for Standby DG 11. Caused by Inadequate Work Instructions.Surveillance Procedure Will Be Revised to Address Probe Magnetic Bars ML20042G8711990-05-0808 May 1990 Ro:On 900412,groundwater Level Reading Taken from Dewatering Well 8 Exceeded 109 Ft Mean Sea Level Design Basis.Caused by Incorrect Level Sensor Probe Setting.Probe Adjusted Using New Setpoint Data to Cycle Dewatering Well at 108.4 Ft ML19354E6851990-01-17017 January 1990 Special Rept 89-009-00:on 891218,diesel Generator 11 Failed. Potential Transformer Fuse Holders Found Loose.No Obvious Cause of Event Identified.Diesel Retested Satisfactorily W/O Recurrence of Original Incident ML19325E3561989-10-24024 October 1989 Special Rept 89-008-0:on 891010,instrument Channel Inoperable for More than 72 H.Caused by Turbine Bldg Exhaust Accident Range Monitor Declared Inoperable After Sample Flow Calculations Could Not Be Completed Due to Leaking Valve ML20024F4781983-08-29029 August 1983 RO 83-072/0:on 830729,30 & 0814-16,control Room Air Temp Exceeded Tech Spec Limit.Caused by Lack of Operating Control Room HVAC Subsystems & Low Freon in Subsystem B, Respectively.No Corrective Action Stated ML20024D0431983-07-27027 July 1983 RO 83-059/0:on 830620,fire-rated Doors OC412 & OC712 to Reactor Protection Sys Motor Generator Set Rooms Blocked Open to Aid Room Ventilation.Fire Watch Established.Expected Restoration Date of Doors Is 830731 ML20024C3311983-06-27027 June 1983 RO 83-052/0:on 830523,listed Fire Rated Penetrations Opened to Implement Design Change Packages.Hourly Fire Watches Established & Will Be Maintained Until Penetrations Resealed by 830801 ML20024C2611983-06-27027 June 1983 Updated RO 83-027/1:on 830321,during Seismic Monitoring Sys Functional Test,Operation of Chart Recorders & Spectrum Analyzers Unacceptable.Caused by Faulty Circuit Card.Card Replaced.Sys Restored on 830519 ML20024C3321983-06-24024 June 1983 RO 83-050/0:on 830519,floor Penetration CE-37G in Control Bldg Upper Cable Room Opened to Rework Cable Tray Hanger. Fire Watch Established Until Penetration Sealed on 830603. Seven-day Limiting Condition for Operation Exceeded ML20024C2761983-06-24024 June 1983 RO 83-049/0:on 830526,halon Bottle 2 in Panel P936 Discharged Until Empty.Hourly Fire Watch Established Pending Bottle Replacement.Limiting Condition for Operation to Be Maintained.Next Rept Will Be Submitted by 830731 ML20024C1151983-06-22022 June 1983 RO 83-047/0:on 830508 & 11,fire Protection Halon Sys for Two Control Room Back Panels Failed Surveillances.Caused by Inability to Meet Tolerance Specified for Full Charge Pressure.Surveillance Procedure Revised ML20023D5581983-05-0909 May 1983 RO 83-029/0:on 830422,50-meter Wind Direction Reading Did Not Agree w/10-meter Reading.Caused by Incorrectly Wired New Sensors Located in Design Change Package 82-502.Wiring Diagram Corrected ML20023B6381983-04-28028 April 1983 RO 83-025/0:on 830322,fire Rated Penetrations Opened to Implement Design Change Packages.Hourly Fire Watches Established within 1 H & Will Be Maintained for Duration of Planned Maint Activities.Work to Be Completed by 830610 ML20023B5021983-04-28028 April 1983 RO 83-026/0:on 830327,security Access Card Reader to Fire Door 1A318,Elevation 166 Ft,In Auxiliary Bldg Malfunctioned. Caused by Fire Door Blocked to Allow Personnel Access.Card Reader Reworked & Returned to Svc 830405 ML20028A5311982-11-10010 November 1982 Ro:On 820813,Channel a Tripped & HPCS Initiated on False Low Level Signal.Caused by Failure to Follow Procedures.On 820814,HPCS Initiated by True Low Reactor Water Level Signal from B21-N073 L&R.Procedures Developed to Correct Problems 1993-06-02
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217F9921999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Grand Gulf Nuclear Station,Unit 1.With ML20212F5641999-09-23023 September 1999 SER Concluding That All of ampacity-related Concerns Have Been Resolved & Licensee Provided Adequate Technical Basis to Assure That All of Thermo-Lag Fire Barrier Encl Cables Operating within Acceptable Ampacity Limits ML20211Q3171999-09-0909 September 1999 Safety Evaluation Accepting BWROG Rept, Prediction of Onset of Fission Gas Release from Fuel in Generic BWR, Dtd July 1996 ML20216E4881999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Grand Gulf Nuclear Station.With ML20211A6921999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Grand Gulf Nuclear Station,Unit 1.With ML20209J1961999-07-12012 July 1999 Special Rept 99-001:on 990528,smoke Detectors Failed to Alarm During Performance of Routine Channel Functional Testing.Applicable TRM Interim Compensatory Measure of Establishing Roving Hourly Fire Patrol Was Implemented ML20196K4981999-07-0101 July 1999 Safety Evaluation Authorizing PRR-E12-01,PRR-E21-01, PRR-P75-01,PRR-P81-01,VRR-B21-01,VRR-B21-02,VRR-E38-01 & VRR-E51-01.Concludes That Alternatives Proposed by EOI Acceptable ML20209G0691999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Grand Gulf Nuclear Station,Unit 1.With ML20196A1161999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Grand Gulf Nuclear Station.With ML20206Q4831999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Grand Gulf Nuclear Station Unit 1.With ML20206J1201999-04-30030 April 1999 Redacted ME-98-001-00, Pressure Locking & Thermal Binding Test Program on Two Gate Valves with Limitorque Actuators ML18016A9011999-04-12012 April 1999 Part 21 Rept Re Defect in Component of DSRV-16-4,Enterprise DG Sys.Caused by Potential Problem with Connecting Rod Assemblies Built Since 1986,that Have Been Converted to Use Prestressed Fasteners.Affected Rods Should Be Inspected ML20205P8771999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Grand Gulf Nuclear Station,Unit 1.With ML20207M9231999-03-12012 March 1999 Amended Part 21 Rept Re Cooper-Bessemer Ksv EDG Power Piston Failure.Total of 198 or More Pistons Have Been Measured at Seven Different Sites.All Potentially Defective Pistons Have Been Removed from Svc Based on Encl Results ML20207K5141999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Grand Gulf Nuclear Station,Unit 1.With ML20206T7991999-01-31031 January 1999 Iodine Revolatizitation in Grand Gulf Loca ML20207A8301998-12-31031 December 1998 1998 Annual Operating Rept for Ggns,Unit 1 ML20206R9501998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Grand Gulf Nuclear Station,Unit 1.With ML20206D7721998-12-31031 December 1998 South Mississippi Electric Power Association 1998 Annual Rept ML20198E2481998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Grand Gulf Nuclear Station,Unit 1.With ML20195F4121998-11-13013 November 1998 Rev 16 to GGNS-TOP-1A, Operational QA Manual (Oqam) ML20195C4841998-11-0606 November 1998 SER Accepting QA Program Change to Consolidate Four Existing QA Programs for Arkansas Nuclear One,Grand Gulf Nuclear Station,River Bend Station & Waterford 3 Steam Electric Station Into Single QA Program ML20195C2791998-11-0505 November 1998 BWR Feedwater Nozzle Inservice Insp Summary Rept for GGNS, NUREG-0619-00006 ML20195F4801998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Grand Gulf Nuclear Station,Unit 1.With ML20155C1351998-10-26026 October 1998 Rev B to Entergy QA Program Manual ML20154K2391998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Grand Gulf Nuclear Station Unit 1.With ML20155F1961998-09-0101 September 1998 Engineering Rept for Evaluation of BWR CR Drive Mounting Flange Cap Screw ML20153B2161998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Grand Gulf Nuclear Station,Unit 1.With ML20237B6661998-07-31031 July 1998 Monthly Operating Rept for Jul 1998 for Grand Gulf Nuclear Station,Unit 1 ML20236R0231998-06-30030 June 1998 Monthly Operating Rept for June 1998 for Grand Gulf Nuclear Station,Unit 1 ML20155J0811998-05-31031 May 1998 10CFR50.59 SE for Period Jan 1997 - May 1998 ML20249B1251998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Grand Gulf Nuclear Station,Unit 1 ML20248B6261998-05-11011 May 1998 Rev 6 to Grand Gulf Nuclear Station COLR Safety-Related ML20217Q6701998-05-0606 May 1998 SER Approving Proposed Postponement of Beginning Augmented Exam Requirements of 10CFR50.55a(g)(6)(ii)(A)(2) at Grand Gulf for Circumferential Shell Welds for Two Operating Cycles ML20206J1271998-04-30030 April 1998 Pressure Locking Thrust Evaluation Methodology for Flexible Wedge Gate Valves ML20247F3591998-04-30030 April 1998 Monthly Operating Rept for Apr 1998 for Grand Gulf Nuclear Plant,Unit 1 ML20217M8951998-04-30030 April 1998 QA Program Manual ML20217P8281998-04-0707 April 1998 Safety Evaluation Accepting Relief Authorization for Alternative to Requirements of ASME Section Xi,Subarticle IWA-5250 Bolting Exam for Plants,Per 10CFR50.55a(a)(3)(i) ML20217P0381998-04-0606 April 1998 Safety Evaluation Supporting Amend 135 to License NPF-29 ML20217A0291998-03-31031 March 1998 Monthly Operating Rept for Mar 1998 for Grand Gulf Nuclear Sation,Unit 1 ML20216J4211998-03-18018 March 1998 SER Approving Alternative to Insp of Reactor Pressure Vessel Circumferential Welds for Grand Gulf Nuclear Station ML20216J2021998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Grand Gulf Nuclear Station,Unit 1 ML20203A2891998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Grand Gulf Nuclear Station ML20247B4111997-12-31031 December 1997 1997 Annual Financial Rept for South Mississippi Electric Power Association ML20203H9741997-12-31031 December 1997 1997 Annual Operating Rept, for Ggns,Unit 1 ML20198P1121997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Grand Gulf Nuclear Station,Unit 1 ML20203B5581997-12-0404 December 1997 Special Rept 97-003:on 971111,valid Failure of Div 2 EDG Occurred,Due to Jacket Water Leak.Failure Reported,Per Plant Technical Requirements Manual Section 7.7.2.2 ML20203K4031997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Grand Gulf Nuclear Station,Unit 1 ML20199H3711997-11-19019 November 1997 SER Accepting Approving Request Relief from Requirements of Section XI, Rule for Inservice Insp of NPP Components, of ASME for Current or New 10-year Inservice Insp Interval IAW 50.55(a)(3)(i) of 10CFR50 ML20199F3431997-11-18018 November 1997 SER Accepting Rev 15 of Operational Quality Assurance Manual for Grand Gulf Nuclear Station,Unit 1 1999-09-09
[Table view] |
Text
.i' lA
- t . .
0 , u i f A? " '~!1
/SWem. Energy:':-
s v.i - ca.,ov
.PO Box 750 .
- nori oeso,. us saiso ,
. , . : lol cot 437 6809 ili William T, cottle' we nose ,
g 'May 8,71990- **>= owees <
- j. : ' '
f .U.S.' ' Nuclear- Regulatory Connission 'g Mail-Station P1-13e
,WashingtonE D.C. .~20555; ;
Attentionse Document Control Desk i' q
'1 Gentlemen: ' N
SUBJECT:
. Grand-Gulf Nuclear Station
' Unit 1-DocketINo. 50-416:
License No.'NPF-29: 4
.High. Groundwater Elevation : '
AECM-90/0083-On April 12,E1990, a groundwater l level reading takenlfrom-dewatering; we'll-8 ' indicated 109.4 feet Mean . Sea ;I.evel1(MSL): which exceeded the 109.0 feet MSL design basis ( ' The' level-. increase was; apparently1 due' to an' incorrect ll level' sensor probe' setting'.. The probe has been properly-adjusted:using new- J
-setpoint data to cycle the dewatering well pump on at'108.4 feet MSL:and off'
~
)
at 106.5 MSL. :
A previous occurrence of:high groundwater level: elevation reported by O letter. dated April 16, 1990/(AECM 90/0062) required' temporary replacement ofi d I
a level sensor cable.- The temporary cable was replacedJon April-.20,L 1990-with an original equipment-type cable and the.well was restored 1to normal;
]j service. The. occurrence of high= groundwater elevation 11s. reported as- j
- l. requested by your letter dated August'19, 1985 (MAEC 85/0284). l.
l 'An engineering study was performed'.in'1985 to-determine thel sensitivity of Grand Gulf Nuclear Station (GGNS)' Unit'l buildings to'a. maximum i
groundwater elevation of 114.5 feet MSL. The study. concluded that the 'l i
i- structural integrity of the Unit 1 buildings would not be: impaired. :This:
information was previously submitted by letter dated February 14, 1985-(AECM-85/0035). . - - -
7 i j Yours truly,-
I, d i, WTC:cg ep Q l 1f i
- i l ' r}
-l GRDWATEL/SCMPFLR I ;
900516D208 900508- 3 -
PDR S
ADOCK 05000416 PDC:~
' M =- -
-g j
y.;
eV
- 'E
> m .
AECM-90/0083i
~
', c: Pagv2 i s
- j. ..
cci- Mr. D. C.Lilintr.
J
'Mr. T.'H.=Cloninger' r
-Mr..R. B. McGehoo, I '
Hr. N._S. Reynolds-L M r. 11. - In Thomas-l.
Mr. II. ;0. ' : Christensen- <
1 L
v, lHreStewartD.Ebneter.
U.S. Nuclear. Regulatory Commission-l-- .Reglon~II ; s. -
l 4
, ;101 Marietta St.,-N.E ,7 Suite-2900'-
1
" Atlanta, Georgia 30.323:
..r
- Hr. L. L. Kintner, Project Manager
' Office'of Nuclear-Reactor Regulation
~
U.S. Nuclear Regulatory Commission _
Mail Stol i14B20-L Washington',;D.C, 20555 l.
L-1;
, j e:
(-
' y I
I s..
3,c t-e
. .n l ls
- 1 E
GRDWATEL/SCMPFLR - 2 i
,1 4 ,
- 5) t l'
-' ' l , :. i + m