ML20023D558

From kanterella
Jump to navigation Jump to search
RO 83-029/0:on 830422,50-meter Wind Direction Reading Did Not Agree w/10-meter Reading.Caused by Incorrectly Wired New Sensors Located in Design Change Package 82-502.Wiring Diagram Corrected
ML20023D558
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 05/09/1983
From: Mcgaughy J
MISSISSIPPI POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
AECM-83-0273, AECM-83-273, RO-83-029-0, RO-83-29, NUDOCS 8305200604
Download: ML20023D558 (1)


Text

MISSISSIPPI POWER & LIGHT COMPANY Helping Build Mississippi P. O . BOX 1640, J AC K SO N, MIS SIS SlP PI 3 9 65 May 9, 1983

  • 3 ic JAMES P. McGAUGHY, JR.

v c a ns. .. , h g.

Office of Inspection and Enforcement in -

U.S. Nuclear Regulatory Commission Region II h**

C 7,

101 Marietta St., N.W., Suite 2900 #

7 Atlanta, Georgia 30303 N Attention: Mr. J. P. O'Reilly, Regional Administrator

Dear Mr. O'Reilly:

SUBJECT:

Grand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-13 File: 0260/L-835.0 Special Report 83-029/0 - Wind Direction Sensors Incorrectly Wired AECM-83/0273 On April 22, 1983, maintenance personnel noted that the 50 meter wind direction reading did not agree with the 10 meter reading while the wind vanes were pointing in the same direction. Maintenance personnel investigating found that Design Change Package 82-502 which installed new sensors had incorrectly wired the system such that east and west direction readings were in error.

A Change Notice was issued to the DCP which corrected the wiring diagram.

The change was made and the system was restored on May 3, 1983. This is submitted as a Special Report as required by T.S.3.3.7.3.a and pursuant to Technical Specification 6.9.2.

Yours truly,

~

JPM:rg h 7 A /7 %2/ 4 cc: Mr. J. B. Richard Mr. R. B. McGehee d$ Mr. T. B. Conner ogn. Mr. G. B. Taylor h8t)

Mr. Richard C. DeYoung, Director Office of Inspection & Enforcement M

o:s U. S. Nuclear Regulatory Commission - M

$@ Washington, D. C. 20555 '

X o ca 'CY[NN; .

7 Document Control Desk

@@ U. S. Nuclear Regulatory Commission #

CDo.fD Washington, D. C. 20555 bgg Member Middle South Utilities System i