LER 89-032-00:on 891228 & 900105,HPCS Sys Declared Inoperable Due to Inoperability of Div 3 Battery.Caused by Low Pilot Cell Voltage,Cell W/Slow Electrolyte Leak & Blown Power Fuse.Fuse & Hydromotor Pump replaced.W/900119 Ltr
ML19354E096
Person / Time
Site: Perry FirstEnergy icon.png
Issue date: 01/19/1990
From: Hegrat H, Kaplan A
CLEVELAND ELECTRIC ILLUMINATING CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LER-89-032, LER-89-32, PY-CEI-NRR-1123, NUDOCS 9001250368
Download: ML19354E096 (5)


Text

>

' N 6 . l THE CLEVELAND ELECTRIC ILLUMINATING COMPANY j P.O. DOX 97 e PERRY OHC 440s1 W TELEPHONE G18) 2664737 9 ADDRESS-10 MNTER ROAD  !

FROM CLEVELAND: 4 4 1300 3 TELEX: 24160s ';

ANSWERBACK: CEtPRYO  ;

Al Kaplan Serving The Best location in the Nation PERRY NUCLEAR POWER PLANT  ;

ver catsain ,

NUCtl AR GHOUP . }

Jsuuary 19, 1990 l

'PY-CEI/NRR-1123 L' l k

i t

U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555 Perry Nuclear Power Plant  !

Docket No. 50-440 l LER 89-032  !

Dear Sirs i

. .  ?

Enclosed is Licensee Event Report 89-032 for the Perry Nuclear Power Plant. l r

e Very truly yours,.

5' Al Kaplan

~

Vice President .

Nuclear Croup AK/njc Enclosure LER 89032 ,

ect T. Colburn NRC Resident inspector +

.i U.S. Nuclear: Regulatory Commission  !

799 Roosevelt Road >

I Clen Ellyn, Illinois 60137 4 l

[ lli :

0

i gcyoawm u.stvC5 mm muutont Commism04 ,,,,,,,,,,,,,,,,,,,,, ,

...l t.

sees C t te0 m S ms 8 m*Am

. LICENSEE EVENT REPORT (LER) g . mate.4 N43, 6 ,a g g l y sg.t. ;60,, tg 8 g at0vtavoav coaswistione twa PAPIstupORK natHawotO,N.

mtDUCil0N DC 20b64.1 AND pn0JtC (31h0410 08FICE 10 os ua4ActestNT AND suDGEt,manniseGt0N.DC 20603.

' AC.Lity swhast til DOCati neuestta m raus .I Parry Nuclear Power Plant. Unit I o is 10 l0 t o p l4 l C 1 loFl0 14  ;

'"" " Division 3 Battery Low Electrolyte Temperature Cause High Pressure Core Spray Svarem Innnerability iv4Nt oats e ita Nuessen e nerontoave m ovata eaCitatits sNvoLvso ni i h00NtM DAY Yt&M VtAR (' b MONtM OAV Te&R I AC84'T ' awls DOCEtt NWW94 Rill ol51010lcl l l >

~ -

ll 2 2l 2 8 9 8l 9 0l3 l 2 0l 0 0ll ll9 9l 0 c isto ic ioi l l '

,,,,A,,,,, im... ., .v itt ,v u.ctoT 6..ous.s= c.o,i.C.. pC - .. - ,nu

==4 = i n .a. n . .. .miH. nmi g'I0i i o _

n . inin.

[ u m in.

Z .mimi.,

[ n.,u.i n., n . in H.,

m me.immi mimm umi. .

_ogs.gg

.emi.H mai . 4>

M SteH1Hl.i te.736sH3Hei W.tStatWst.elHei M eteHt Hei M.734sHtiMi .0.t31sHfHai LIC48 848 CONT ACT P0a YMtB LOR 613)

.elut TE LtPM044 NUhtttR Amta CODE H2nry L. Hegrat, Compliance Engineer. Extension 6855 2 ll 16 215l9l -13l713l7 Cowan o=8 tml eon aaC# CO-omN, eaitual meCnino m t=s neon om Caust tv8ttu Cour0 Nth? "M $C- m{oy,v,'j,8 Cavat 8vstt u C0 esp 04 TNT "$$'glE' "fo m k' X 9I FlUi l Gi I8 i 7 3 N i i i l i i X 19 M Tl cut l Fl l l 3l 0 N l l l l l l l

.v u=Nm u, c 5.et8o n.1 .0c - ... ,s..c SUSMtSSION Yt8 fifF.. e.m.asse IMfrtfD $US.stMs0N 0d ffs 40 l l l aset. act to ,. . .. ,a . . ,, aN . -, . , o.,

On December 22, 1989, and on January 5, 1990, Unit 2 Division 3 battery electrolyte temperature was discovered to be below Technical Specification limits. Because Unit 1 Division 3 battery was inoperable due to maintenance being performed, Plant Technical Specifications required the High Pressure Core Spray (HPCS) system to be declared inoperable. Operators took actions to raise battery room temperature and declared the HPCS system operable when battery electrolyte temperatures returned to acceptable levela.

The cause of the December 22, 1989 event was Equipment Failure, specifically, a blown fuse in the battery room ventilation duct heater circuitry. Loss of the heater combined with the low heat load in the Unit 2 Division 3 battery room result'ed in the b:ttery electrolyte temperature decrease. The January 5, 1990 event was caused by a temperature control valve malfunction which allowed excess cooling water to the b:ttery room ventilation system at a time when cooling water was not desired. This also resulted in the decrease of battery electrolyte temperature.

To prevent recurrence, the blown fuse for the ventilation duct heater was replaced and the heater checked to ensure proper operation. The temperature control valve actuator hydromotor pump was replaced and the valve checked for proper operation. Additionally, operators revised the plant equipment round procedure to include checking battery room temperature once per shift, and a design change proposal to install low temperature clarm instrumentation for the battery rooms is presently being evaluated. As part of the established requalification training program, all plant licensed operators will be inst ructed on the lessons lentned f rom thin event.

DeRC f enn 30 (640,

e I

g,. ..,u=.....u..

. .u .r i UCENSEE EVENT REPORT (LER) M'i'?Ju"JR.7,",o"'C'4T,,' *f'f,ll To',"J",,'!  !

TEXT CONTINUATION f ".'.".M'.",'#,3*.f##'*d!,'e?'/MQ' Oc73 '

M, 0

an"Aas40sastNT Aeso puOo

  • D ACeut, seasst su 00cettt Nue64. m g,. asunset. p.s Paet (31 ,

"^a " t'X."

"tfat Perry Nuclear Power Plant, Unit 1 0l5l0l0l0l4l4l0 8l9 --

01312 --

0l0 012 0F 'O 14 run u . --.m.aac =-antw nn  ;

I On December 22, 1989, and on January 5, 1990, the High Pressure Core Spray [BG)

(HPCS) system was declared inoperable due to the inoperability of the associated -

Division 3 battery [EJ). At the time of both events, the plant was in Operational Condition 1 (Power Operation) at approximately 100 percent of rated ,

thermal power with the Reactor Pressure Vessel [RPV) at saturated conditions at I

approximately 1000 psig. The Unit 1 Division 3 battery [BTRY) was inoperable due to a low pilot cell voltage and a cell with a slow electrolyte leak.

On December 22, 1989, at 1027, Unit 2 Division 3 battery electrolyte temperature i was discovered to be approximately 69 degrees Fahrenheit (F). In accordance with ,

Technical Specification action requirements associated with D.C. electrical power sources, operators declared High Pressure Core Spray (HPCS) system and the Division 3 Diesel Generator inoperable and initiated troubleshooting efforts to determine the cause of the low temperature. Maintenance troubleshooting revealed -

a blown power fuse [FU) in a heater circuit for the MCC, Switchgear, and Miscellaneous Electrical Equipment Areas HVAC system [VI). The fuse was replaced and HPCS/ Division 3 operability was declared on December 23, 1989 at 0445, after the battery electrolyte tempeneture increased above 72 degrees F. All action statements of associated Technical Specifications were satisfied.

On January 5, 1990, at 0241, train "B" of the battery room ventilation system was shifted to recirculation mode due to Unit 2 Division 3 battery room temperature decreasing to 73 degrees F. The ventilation system shift was ineffective due to a malfunctioning temperature control valve [TCV) which, unknown to operators, was the initial cause of the decrease in battery room temperature. The temperature control valve remained closed approximately 50 percent instead of 100 percent as it was supposed to. The failure of the temperature control valve to completely close allowed cooling water to continue flowing to the ventilation system cooler while temperature conditions required cooling flow to be secured. As a result, the Unit 2 Division 3 battery room temperature continued to drop instead of increase as was intended. At approximately 1010, the Unit 2 Division 3 battery room temperature was discovered to be below 72 degrees F and the battery electrolyte temperature was also below 72 degrees F. Operators declared the HPCS system inoperable at that time. At 1024 operators shifted the battery room ventilation system to train "A" in recirculation mode which caused battery room temperature to increase. On January 5, 1990 at approximately 2130 Unit 2 Division 3 battery electrolyte temperature had risen to 72.9 degrees F and battery room temperature had risen to 76 degrees F. Operators then declared Unit 2 Division 3 battery, Diviaton 3 diesel s generator and HPCS system operable. ,

The cause of the December 22, 1989 event was equipment failure, specifically, a blown power fuse in the ventilation duct neater circuitry. The loss of the heater combined with the low heat load in the Unit 2 Division 3 battery room resulted in the battery electrolyte temperature decreasing below the Technical Specification limit. The absence of a battery room low temperature alarm to alert operators to low temperature conditions is: considered to be a contributing 5 factor.

II.C 7em 3RRA 16401

i

- . ...- s .m== ,,,,,,,,,,,,,,,,,,,,,,  !

UCENSEE EVENT REPORT (LER) No'1".'. *.'"..'".9" "*.TL",",T%.#'fX &"J."i1 TEXT CONTINUATION  %""#,'?IA "'.*.*."*,2.n'"f'." !T.c"'/MU".' "',EN! I

  • oh, '

b"k" wo o "aa f 2."

"'J.it t

Perry Nuclear Power Plant. Unit I ol5l0l0l0l4l4lo gl g --

ol3l2 -- ojo ol3 0F nlt i un w . < -. -= == a muinm  !

The cause of the January 5, 1990 event was equipment malfunction. A temperature '

control valve in the Control Complex Chilled Water (KH] (CCCW) system did not close completely when its control signal required full closure. Although operators were aware of decreasing Unit 2 Division 3 battery room temperature and took action to shift to the recirculation mode which should have prevented exceeding the Technical Specification limit for electrolyte temperature, the ,

valve malfunction resulted in continued cooling of the Unit 2 Division 3 battery ,

room. Again the absence of a battery room low temperature alarm to alert ,

operators to low temperature conditions is considered to be a contributing factor as this would have provided more time to evaluate system conditions and take corrective action. >

The objective of the Division 3,125-volt de power system is to provide a 5

continuous and independent 125-volt de source of control and motive power as  ;

required for HPCS system logic, HPCS diesel generator control and protection, and ,

all Division 3 related 125-volt de control. Upon loss of these control power t systems, the HPCS system is required by Technical Specification to be declared inoperable. '

i The HPCS system pumps water through a peripheral spray ring sparger mounted above ,

the reactor core. Coolant is supplied over the entire range of system operation t

pressures. The primary purpose of HPCS is to maintain reactor vessel inventory i

, after small breaks which do not depressurize the reactor vessel. HPCS also  ;

provides spray cooling heat transfer during leaks in which core uncovery is.

l l calculated. During the periods of time the HPCS system was declared inoperable, l the Automatic Depressurization System and Low Pressure Core Spray, as well as the  ;

l Low Pressure Coolant injection Systems were operable ensuring adequate core ,

cooling as described in Chapter 15 of the Updated Safety Analysis Report. ]

Additionally, although the batteries were required to be declared inoperable, the ,

HPCS system was not removed from service and would have automatically initiated i if required. Engineering calculations indicate that the Unit 2 Division 3  ;

battery would perform its intended function with electrolyte temperature as low i

as 65 degrees F. Therefore, these events are not considered to be safety '

significant. '

(

One other previous event involving low battery electrolyte temperature was l documented by LER 87-008. A faulty thermostat had caused Division 1 battery l electrolyte temperature to be less than 72 degrees F. The Division 1 battery room thermostat was replaced. Additionally, to address a delay by maintenance personnel in notifying the control room of their findings, maintenance personnel I were counseled to ensure prompt notification of the Unit Supervisor if Technical  ;

Specification acceptance criteria is exceeded. These corrective actions could not have prevented the December 22, 1989 and January 5, 1990 events.

l l

wic emm mu m4.i 1

__ _ _. __ , - - ,,. , . , 1 - - , .r-

=_ _ - _ _ - . - . - _ - - -

4,..- - ,,,,,,,,, ,,,,,,, ,,,,,,,,

. ......... l UCENSEE EVENT REPORT (LER) *V7,,^.,%',,u"og';',l',",o"'50**1,'%'f'"? T,",.1"'s TEXT CONTINUAT60N W'.",.'#16,'"nMf,f"f'1!!,'e'"','!2 Mit.i o" '1" *

'.* oft.o*'!a"f'?"J.*J5 e

U;' 741Tf!

M?.li Of MAen&Gthat est aseD SuDGif.h ASNI880 TON.DC 30603.

Iaceksty esaast 414 DOCE4, sepesten its Llt 8sphEDER tel PAtt 4D

"** " O' .,

11 '.' ' "?J.*.O i Perry Nuclear Power Plant. 11n i t 1 0 l5 l0 l0 le 14 I 410 819 -

0 l 312 -

Ol0 0l4 0F 0 14 rexto . = m necsei amewnn To prevent recurrence, on December 23, 1989, the blown power fuse for the battery room ventilation duct heater circuit was replaced and voltage and current readings were taken to ensure the heater was working as designed. On January 12, 1990, the CCCW temperature control valve actuator hydromotor pump was replaced due to internal leakage, and subsequently the temperature control vt,1ve was ,

tested satisfactorily in the system. Additionally, operators revised the plant i equipment round procedure to include checking battery room temperatures once per  :

l shift. Finally, a previously submitted design change proposal to install low l temperature alarm instrumentation for the battery-room is presently being evaluated. As part of the established requalification training program, all '

plant licensed operators will be instructed on the lessons learned from this event.

Energy Induwtry Identification System Codes are identified in the text as [XX]. t t

T h

I L

l E

4 E

  1. f8lC Peein 3BBA 16 001

-, - - -. _ _ .. __