Safety Evaluation & Statement of Staff Positions Relative to Emergency Power Sys for Operating Reactors
ML19337A632
Person / Time
Site: Rancho Seco
Issue date: 09/22/1980
From:
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To:
Shared Package
ML19337A628 List:
References
PROC-800922, TAC-10968, NUDOCS 8009290356
Download: ML19337A632 (3)


Text

-

<+

O Enclosure II SACRAMENTO MUNICIPAL UTILITY DISTRICT RANCHO SECO NUCLEAR GENERATING STATION, UNIT NO. 1 RESPONSE TO:

NUCLEAR REGULATORY COMMISSION REQUEST FOR INFORMATION REGARDING ENCLOSURE 1 0F NRC TO SMUD LETTER DATED JUNE 3, 1977 TITLED SAFETY EVALUATION AND STATEMENT OF STAFF POSITIONS RELATIVE TO THE EMERGENCY POWER SYSTEMS FOR OPERATING REACTORS Issued: July 19, 1977 Revision 1: August 1, 1980 Revision 2: September 22, 1980 8009290 356 g

ATTACHMENT 1 4.

SURVEILLANCE STANDARDS 4.1 OPERATIONAL SAFETY REVIEW TABLE 4.1-1 INSTRUMENT SURVEILLANCE REQUIREMENTS Add item 48 to Table 4.1-1.

Channel Description Check Test Calibrate Remarks 48.

Voltage Protection S

Compare voltmeter readings a.

Undervoltage M

R b.

Overvoltage M

R c.

Time Delay M

R

,2 S = Each Shift M = Monthly R = Once during the refueling interval 4.6 EMERGENCY POWER SYSTEM PERIODIC TESTING Specification Substitute 4.6.2 with the following:

4.6.2 During each refueling interval, a test of the diesel generators and emergency start circuits shall be performed to verify that these emergency power sources and associated equipment are operable by:

A.

Simulating a loss of offsite power in conjunction with a safety injection actuation signal, and:

1)

Verifying deenergization of the nuclear services buses and operation of the load shedding circuitry.

2)

Verifying the diesel starts from ambient condition on the auto-start signal and energizes the nuclear services buses, and by verifying proper operation of the automatic load sequencing circuitry. The diesel generators will be operated for at least 5 minutes in this condition.

II-16 l

6 TABLE 3.7.1 VOLTAGE PROTECTION SYSTEM RELAY TRIP VALUES Trip Value Time Delay Undervoltage (Note 1) a.

Dropout 3771 1 38V 12s +- 1.2s 2

b.

75 percent of 4160V 3120 1 31V 1.9 1 0.2s c.

Complete loss 0

1.5 1 0.2s Overvoltage 4580 1 46V 3.0 1 0.3s 2

y Notel. - The relay voltage values shown have been converted by the PT ratio (40:1) for review convenience.

C d>

l

-