CNL-16-150, Revised Response to Requests for Additional Information Proposed Technical Specifications Change TS-505 - Request for License Amendment - Extended Power Uprate - Supplement 31

From kanterella
(Redirected from ML16267A374)
Jump to navigation Jump to search

Revised Response to Requests for Additional Information Proposed Technical Specifications Change TS-505 - Request for License Amendment - Extended Power Uprate - Supplement 31
ML16267A374
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 09/21/2016
From: James Shea
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
Shared Package
ML16267A373 List:
References
CNL-16-150
Download: ML16267A374 (41)


Text

Proprietary Information and Critical Energy Infrastructure Information Withhold from Public Disclosure Under 10 CFR 2.390 This letter is decontrolled when separated from Enclosures 3 and 4 Tennessee Valley Authority, 1101 Market Street, Chattanooga, Tennessee 37402 CNL-16-150 September 21, 2016 10 CFR 50.90 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2, and 3 Renewed Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296

Subject:

Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU) - Supplement 31, Revised Responses to Requests for Additional Information

References:

1. Letter from TVA to NRC, CNL-15-169, Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU), dated September 21, 2015 (ML15282A152)
2. Letter from NRC to TVA, Browns Ferry Nuclear Plant, Units 1, 2, and 3 -

Request for Additional Information Related to License Amendment Request Regarding Extended Power Uprate (CAC Nos. MF6741, MF6742, and MF6743), dated January 28, 2016 (ML16020A111)

3. Letter from NRC to TVA, Browns Ferry Nuclear Plant, Units 1, 2, and 3 -

Request for Additional Information Related to License Amendment Request Regarding Extended Power Uprate (CAC Nos. MF6741, MF6742, and MF6743), dated May 6, 2016 (ML16119A440)

4. Letter from TVA to NRC, CNL-16-023, Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU) - Supplement 4, Responses to Requests for Additional Information, dated February 16, 2016 (ML16049A248)

U.S. Nuclear Regulatory Commission CNL-16-150 Page 2 September 21, 2016

5. Letter from TVA to NRC, CNL-16-091, Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU) - Supplement 18, Responses to Requests for Additional Information and Updates Associated with Interconnection System Impact Study Modifications, dated May 27, 2016 (ML16197A563)
6. Letter from TVA to NRC, CNL-16-093, Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU) - Supplement 19, Responses to Requests for Additional Information, dated June 17, 2016 (ML16169A332)

By the Reference 1 letter, Tennessee Valley Authority (TVA) submitted a license amendment request (LAR) for the Extended Power Uprate (EPU) of Browns Ferry Nuclear Plant (BFN) Units 1, 2 and 3. The proposed LAR modifies the renewed operating licenses to increase the maximum authorized core thermal power level from the current licensed thermal power of 3458 megawatts to 3952 megawatts. The Reference 2 and 3 letters provided Nuclear Regulatory Commission (NRC) Requests for Additional Information (RAIs) related to electrical systems.

to this letter provides revisions to the responses for NRC RAIs EEEB-RAIs 2, 6, 18, and 21 provided in the References 4 and 6 letters. These revisions to the responses to NRC RAIs EEEB-RAIs 2, 6, 18, and 21 are as a result of additional reviews. The revisions to the responses to NRC RAIs EEEB-RAIs 2, 6, 18, and 21, included in Enclosure 1 to this letter, supersede and replace the previous submitted RAI responses.

to this letter provides a revision to the Insert to Power Uprate Safety Analysis Report (PUSAR) (NEDC-33860P, Revision 0) Section 2.5.1.2.2, which was provided in Enclosures 8 and 9 of the Reference 5 letter. The Insert to PUSAR Section 2.5.1.2.2 addresses the impact of the main generator excitation system upgrade included in the interconnection System Impact Study. The revision to this Insert is the result of additional reviews. The Insert in Enclosure 2 to this letter supersedes and replaces the Insert to PUSAR Section 2.5.1.2.2 submitted in Enclosures 8 and 9 of the Reference 5 letter.

to this letter provides Revision 2 of the interconnection System Impact Study (SIS) and Enclosure 4 to this letter provides Revision 3 of the BFN EPU Transmission System Stability Evaluation. These revisions to the interconnection SIS and the BFN EPU Transmission System Stability Study are the result of additional reviews. Enclosures 3 and 4 to this letter supersede and replace the interconnection SIS and the BFN EPU Transmission System Stability Study submitted in Enclosures 1 and 2, respectively, of the Reference 5 letter. Enclosures 3 and 4 contain critical energy infrastructure information that is considered sensitive, unclassified (non-safeguard) information. As a result, TVA requests that Enclosures 3 and 4 be withheld from public disclosure in accordance with the provisions of 10 CFR 2.390(d)(1).

U.S. Nuclear Regulatory Commission CNL-16-150 Page 3 September 21, 2016 TVA has reviewed the information supporting a finding of no significant hazards consideration and the environmental consideration provided to the NRC in the Reference 1 letter. The supplemental information provided in this submittal does not affect the bases for concluding that the proposed license amendment does not involve a significant hazards consideration. In addition, the supplemental information in this submittal does not affect the bases for concluding that neither an environmental impact statement nor an environmental assessment needs to be prepared in connection with the proposed license amendment.

Additionally, in accordance with 10 CFR 50.91 (b)(1 ), TVA is sending a copy of this letter, without the critical energy infrastructure information, to the Alabama State Department of Public Health.

There are no new regulatory commitments associated with this submittal. If there are any questions or if additional information is needed, please contact Edward D. Schrull at (423) 751-3850.

I declare under penalty of perjury that the foregoing is true and correct. Executed on the 21st day of September 2016.

Respectfully, J. W. Shea Vice President, Nuclear Licensing

Enclosures:

cc:

1. Revised Responses to NRC Requests for Additional Information EEEB-RAI 2 (Revision 1), EEEB-RAI 6 (Revision 1), EEEB-RAI 18 (Revision 1), and EEEB-RAI 1 (Revision 1)
2. Power Uprate Safety Analysis Report Section 2.5.1.2.2 Insert (Revision 1)
3. Interconnection System Impact Study, Revision 2: Browns Ferry Nuclear Plant Extended Power Uprate (Critical Energy Infrastructure Information)
4. BFN EPU LAR, Attachment 43, Transmission System Stability Evaluation, Revision 3 (Critical Energy Infrastructure Information)

NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant State Health Officer, Alabama Department of Public Health (w/o Enclosures 3 and 4)

ENCLOSURE 1 Revised Responses to NRC Requests for Additional Information EEEB RAI 2 (Revision 1), EEEB-RAI 6 (Revision 1), EEEB RAI 18 (Revision 1), and EEEB-RAI 21 (Revision 1)

ENCLOSURE 1 E11

EEEB-RAI 2 In Section 2.3.3.1 of Attachment 7, Safety Analysis Report for Browns Ferry Nuclear Plant Units 1, 2, and 3 Extended Power Uprate, the licensee states:

The larger condensate pump motors (1,250 horsepower (hp)), CBP motors (3,000 hp) and reactor recirculation pump motors (8,657 hp) do not change the conclusions of the current Browns Ferry degraded voltage analysis. The analysis encompasses the safety-related 4.16 kV [kilovolts] buses and is independent of voltage profiles for the balance of plant buses [BOP].

Provide a summary of the degraded voltage analysis corresponding to post-EPU conditions.

Also, provide single line diagram(s) showing the safety-related 4.16 kV buses with its connected loads and power sources and the BOP buses with its connected loads and power sources.

TVA Response (Revision 1):

I.

EPU Impact The Class 1E onsite distribution system degraded voltage relays were determined to be adequate for operation at pre-EPU conditions. BFN developed and validated the relay settings based on the equipment ratings and the expected load profile of the safety-related equipment in response to a design basis accident. No EPU modifications are made to safety-related equipment so the ratings are unchanged. Due to the fact that this is a constant pressure power uprate, no increase in flow, pressure, or mission time is required of any AC powered ECCS equipment and therefore, the amount of power required to perform safety-related functions (pump and valve loads) is not increased with EPU and the load profile is unchanged. As such, the degraded voltage analysis currently in place at BFN still applies at EPU conditions.

Furthermore, an analysis shows that the onsite electrical voltage levels and the degraded voltage settings are adequate at EPU conditions.

II.

Degraded Voltage Protection Description In the normal station electrical lineup, the Unit Station Service Transformers (USSTs) 1A, 1B, 2A, 2B, 3A, and 3B are fed from their respective unit generator or from the 500kV switchyard and supply power to operational loads on 4kV Unit Boards 1A, 1B, 1C, 2A, 2B, 2C, 3A, 3B, and 3C. The 4kV Shutdown Boards are fed in the following manner:

USST Unit Board Shutdown Bus Shutdown Board 1B 1A 1

A and B 2B 2A 2

C and D 3B 3A none 3EA and 3EB 3B 3B none 3EC and 3ED USSTs 1B, 2B, and 3B are equipped with automatic Load Tap Changers (LTCs) on the primary winding that can change the voltage by one step every 1.1 seconds. Each step is a change in voltage of 1.25% over a plus or minus 10% range.

ENCLOSURE 1 E12

In case the USST 1B, 2B, or 3B cannot maintain adequate voltage, each Shutdown Board is provided with degraded voltage (DV) protection. The following is a description of the DV protection scheme for 4kV Shutdown Board A. This same scheme is typical for the remaining 4kV Shutdown Boards. The times stated are nominal. The actual setpoints for the timers and the DV values have been determined by analyses and are consistent with the Browns Ferry Nuclear Plant (BFN) Final Safety Analysis Report accident analyses. The three DV relays sense each of the three phase-to-phase voltages on the shutdown board potential transformer secondary windings. If two of the three relays sense a shutdown board voltage below the setpoint (3920V) for approximately 0.3 seconds, a time delay relay will initiate. The Degraded Voltage Relay is set to actuate when the steady state voltage drops below 3920V and resets when the voltage recovers to greater than 3962V. Due to inaccuracy of the relay, dropout may occur at any voltage between 3940V and 3899V and reset at any voltage between 3941V and 3983V. To ensure that the relay resets, the voltage must recover to at least 3983V or 95.75% of 4160V. If a DV situation exists for approximately four seconds, the emergency diesel generator will start. If the relay is actuated but the voltage at the board recovers within 6.9 seconds, the relay will reset and the board will not transfer to the emergency diesel generator. If a DV situation exists for 6.9 seconds, time delay relays will pickup and initiate 4kV Shutdown Board A power system isolation, load shedding, and eventual closing of the emergency diesel generator breaker when the diesel is up to normal speed and voltage. This initiation is inhibited if the emergency diesel generator breaker 1818 or inter-tie breaker 1824 is closed. A time delay pickup relay (1.3 seconds) allows time for shutdown board power system isolation and subsequent voltage decay before the emergency diesel generator breaker 1818 close signal is issued.

III.

Acceptance Criteria/Bases A.

Acceptable Voltage Ranges for Boards 4kV Switchgear 480V Switchgear 480V MCCs3 Max: 4400V2 508V2 508V2 Min: 3983V1 440V2 432V2,4

1. This is the reset voltage of the degraded voltage relay.
2. Per American National Standards Institute (ANSI) C84.1, 1995, Voltage Ratings for Electric Power Systems, Voltage Range B.
3. The Diesel Auxiliary boards are considered MCCs.
4. In order to maintain acceptable control circuit voltages, the minimum acceptable voltage is 451V for Reactor Motor Operated Valve (RMOV) Board 2D and 439V for RMOV Board 2E.

B.

Acceptable Operating Voltage Ranges Running Motors 4kV 480V*

460V*

440V*

Max: 4400V 528V 506V 484V Min: 3600V 432V 414V 396V Static Loads (non-lighting loads)

Max: 528V Min: 432V (Inverters, battery chargers, electronic controls, lighting) 416V (All other static loads.)

  • National Electrical Manufacturers Association (NEMA) MG 1 Section 12.45 requires that motors shall operate with variation in voltage up to plus or minus 10% of rated voltage.

ENCLOSURE 1 E13

C Minimum Voltage for Starting Motors Using Static Motor Analysis:

4kV Motors 460V Air Compressors 460 V Motors and MOVs U1 MOVs 3200V (80%)*

368V (80%)* 391V (85%)*

414V (90%)*

  • Percentages are based on 4000V and 460V rated motor voltage. For motors other than 460V, the same percentages are applicable.

The minimum motor voltages are based on the following:

Class 1E motors up to 30 horsepower, NEMA Type B, provide 150 percent starting torque at full voltage which corresponds to close to 100 percent torque at 80 percent voltage. For loads, such as fans, as the speed increases, so does the torque requirement. Other loads, such as positive-displacement compressors, start unloaded and do not require a large starting torque from the drive motors.

In addition, the electrical industry accepts a starting voltage of 80 percent of rated voltage at the terminals of the NEMA Type B motors. For Unit 1 motor operated valves (MOVs), 90% of rated voltage is considered.

IV.

Analysis The ability of the required equipment (boards and their loads) to perform their intended functions in the DV condition has been analyzed. For this analysis, the DV Dropout voltage is 3900V.

This is the minimum Technical Specification value. The DV Reset value is 3983V.

1.

Effect on Safety-Related Boards Board voltages were calculated using Electrical Transient Analyzer Program (ETAP), the power systems analysis software used by BFN, assuming a shutdown board voltage of 3900V and worst case LOCA loading at t=60 seconds. If the ETAP calculated voltage did not meet the minimum required voltage from Acceptance Criteria/BasesSection II.A, then the board voltages were calculated again at 3983V shutdown board voltage and worst case LOCA loading at t=60 seconds. This case assumes that the DV reset voltage has been met. In this case, all of the board voltages met the minimum required voltages from Acceptance Criteria/BasesSection II.A. All of the safety-related boards would be able to perform their intended function at the DV condition. The results are summarized in Table 1.

2.

Effect on Safety-Related Board Loads

a.

440/460/480V Motor and Non-Generic Letter (GL) 89-10 Motor Operated Valves (MOVs) Starting Voltage With a shutdown board voltage of 3983V, all motors that are safety-related and required to mitigate the accident, had adequate starting voltages in accordance with Acceptance Criteria/BasesSection II.C and would be able to perform their intended function at the DV condition. The results are summarized in Table 2.

ENCLOSURE 1 E14

b.

460V Motor Running Voltage With a shutdown board voltage of 3900V, all motors had adequate running voltages in accordance with Acceptance Criteria/Bases section II.B and would be able to perform their intended function at the DV condition.

c.

440/480V Motor Running Voltage With a shutdown board voltage of 3900V, all non-standard voltage, safety-related motors had adequate running voltages in accordance with Acceptance Criteria/BasesSection II.B and would be able to perform their intended function at the DV condition.

d.

Static Loads With a shutdown board voltage of 3983V, all static loads required for safe operation have adequate voltage in accordance with Acceptance Criteria/BasesSection II.B and would be able to perform their intended function at the DV condition.

e.

GL 89-10 MOV Starting Voltages With a shutdown board voltage of 3983V, all of the GL-89-10 MOVs had adequate starting voltages in accordance with Acceptance Criteria/BasesSection II.C or were otherwise individually analyzed to show that they would be able to perform their intended function at the DV condition. The results are summarized in Table 3.

f.

4kV Shutdown Boards (SD BDs) A, B, C, and D Voltage vs. Time Graphs Voltage vs. Time Graphs for the 4kV SD BDs A, B, C, and D with a 495kV starting yard voltage, a LOCA on Unit 1, and offsite power available, for the first 60+ seconds of the event, are provided in Figures EEEB-RAI 2-1 through 2-4.

ENCLOSURE 1 E15

V.

Single Line Diagrams Single line diagrams 0-15E500-1 and 3-15E500-3, showing the safety-related 4.16kV buses with their power sources and the Balance of Plant (BOP) 4.16kV buses with their power sources, are were provided in response to EEEB-RAI 18. The response to EEB-RAI 18 was submitted to NRC in letter from TVA to NRC, CNL-16-093, Proposed Technical Specifications (TS) Change TS-505 - Request for License Amendments - Extended Power Uprate (EPU) -

Supplement 19, Responses to Requests for Additional Information, dated June 17, 2016 (ML16169A332). The connected loads, for each of the buses listed below, are shown on the drawing referenced beside each bus.

Safety-Related 4.16kV Buses 4kV SHUTDOWN BUS 1 4kV SHUTDOWN BUS 2 4kV SHUTDOWN BD A (0-45E724-1) 4kV SHUTDOWN BD B (0-45E724-2) 4kV SHUTDOWN BD C (0-45E724-3) 4kV SHUTDOWN BD D (0-45E724-4) 4kV SHUTDOWN BD 3EA (3-45E724-6) 4kV SHUTDOWN BD 3EB (3-45E724-7) 4kV SHUTDOWN BD 3EC (3-45E724-8) 4kV SHUTDOWN BD 3ED (3-45E724-9)

BOP 4.16kV Buses 4kV START BUS 1A 4kV START BUS 1B 4kV START BUS 2A 4kV START BUS 2B 4kV UNIT BD 1A (1-45E721) 4kV UNIT BD 1B (1-45E721) 4kV UNIT BD 1C (1-45E721) 4kV UNIT BD 2A (2-45E721) 4kV UNIT BD 2B (2-45E721) 4kV UNIT BD 2C (2-45E721) 4kV UNIT BD 3A (3-45E721) 4kV UNIT BD 3B (3-45E721) 4kV UNIT BD 3C (3-45E721) 4kV COMMON BD A (0-15E500-2) 4kV COMMON BD B (0-15E500-2)

ENCLOSURE 1 E16

Table 1 Board Voltage Summary Board Name Board Voltage (Volts)

Operation @ 3900V t=60 Sec Loading Board Voltage (Volts)

Operation @ 3983V t=60Sec Loading Minimum Acceptable Board Voltage (Volts) 1 4kV SHUTDOWN BD A 3900 3983 3983 2

4kV SHUTDOWN BD B 3900 3983 3983 3

4kV SHUTDOWN BD C 3900 3983 3983 4

4kV SHUTDOWN BD D 3900 3983 3983 5

4kV SHUTDOWN BD 3EA 3900 3983 3983 6

4kV SHUTDOWN BD 3EB 3900 3983 3983 7

4kV SHUTDOWN BD 3EC 3900 3983 3983 8

4kV SHUTDOWN BD 3ED 3900 3983 3983 9

Control Bay Vent Bd A 442 453 432 10 Control Bay Vent Bd B 439 449 432 11 Diesel Auxiliary Bd A 442 452 432 12 Diesel Auxiliary Bd B 445 455 432 13 Shutdown Bd 1A 446 456 440 14 Shutdown Bd 1B 448 458 440 15 Shutdown Bd 2A 445 455 440 16 Shutdown Bd 2B 450 460 440 17 Shutdown Bd 3A 447 457 440 18 Shutdown Bd 3B 443 453 440 19 RMOV Bd 1A 444 455 432 20 RMOV Bd 1B 446 456 432 21 RMOV Bd 1C 446 457 432 22 RMOV Bd 2A 443 454 432 23 RMOV Bd 2B 446 456 432 24 RMOV Bd 2C 448 458 432 25 RMOV Bd 2D 445 455 451 26 RMOV Bd 2E 450 460 439 27 RMOV Bd 3A 444 455 432 28 RMOV Bd 3B 436 447 432 29 RMOV Bd 3C 441 452 432 30 RMOV Bd 3D 447 457 432 31 RMOV Bd 3E 443 453 432 32 Diesel Auxiliary Bd 3EA 444 455 432 33 Diesel Auxiliary Bd 3EB 437 448 432 34 Standby Gas Treatment Bd 445 455 440 35 HVAC Bd B 440 450 440

ENCLOSURE 1 E17

Table 1 Board Voltage Summary (continued)

Shading In Table 1 indicates boards at less than required minimum voltage with the shutdown boards at 3900V.

With operation at the DV dropout setting of 3900V, the 4kV Shutdown Boards and the RMOV Board 2D are less than the minimum acceptable voltage listed in Acceptance Criteria/BasesSection II.A. However, all boards meet the requirements with operation at the DV reset voltage of 3983V. Operation between 3900V and 3983V for the allowed time delay ensures that power is available for starting required equipment without risking damage to that equipment.

ENCLOSURE 1 E18

Table 2 440/460/480V Motor and Non-GL 89-10 MOV Starting Voltage Summary at Degraded Voltage (DV) Reset (3983V)

Load ID

%VST @ 3983V (480V Base)

Voltage @ 3983V (Volts)

Load Justification 183-6D 81.04 389 See below All motors that are safety related and required to mitigate the accident, had adequate starting voltages in accordance with Acceptance Criteria/BasesSection II.C, except the motor for Load ID 183-6D. 183-6D is the 3A Air Handling Unit (AHU) that provides cooling to the Electrical Board Room 3A/3B. The 3A AHU is a normal operating load. The load has been verified to be a NEMA B Design motor and NEMA MG 1-12.38 shows that the 20 horsepower motor, rated at 1800 RPM, produces 150 percent locked rotor torque. Because the torque developed in a motor is proportional to the square of the voltage, a voltage of 84.56% (81.04% @ 480V =

84.56% @ 460V) will produce approximately 107.3% torque. Therefore, the DV is acceptable per the acceptance criteria in accordance with Acceptance Criteria/BasesSection II.C.

ENCLOSURE 1 E19

Table 3 GL 89-10 MOV Starting Voltages LoadID Description Minimum Required Voltage (Volts)

%StartingVoltage 480VBase)@

DegradedVoltage Reset(3983V)

MOV Terminal Voltage (Volts)

LoadJustification 1911E 1FCV7550 414 85.70 411 Evaluatedat405V 2818C 2FCV7448 414 83.82 398 Evaluatedat391V 2823E 2FCV6879 414 83.20 399 Evaluatedat378V 38112E 3FCV7458 414 85.71 411 Evaluatedat411V Shading In Table 3 indicates boards at less than required minimum voltage with the shutdown boards at 3983V.

All of the GL 89-10 MOVs had adequate starting voltage, in accordance with Acceptance Criteria/BasesSection II.C, with the above four exceptions. Each of these valves was then analyzed individually at the DV level stated in the Load Justification column. Calculations were performed to determine the thrust developed by each of the operators at the stated voltages.

These developed thrusts were then compared to the thrust required for the valves to perform their intended functions. In all four cases, the developed thrust was greater than the required thrust and therefore these four valves will perform their intended functions at the stated degraded voltages.

ENCLOSURE 1 E110

Figure EEEB-RAI 2-1, MOTOR STARTING ANALYSIS - SD BD A BUS VOLTAGE

140-19 RHR 110 100 90 80 70 0

10 20 30 40 50 60 70 Vbus (% of Bus Nominal kV)

ENCLOSURE 1 E111

Figure EEEB-RAI 2-2, MOTOR STARTING ANALYSIS - SD BD B BUS VOLTAGE 150-17 RHR 110 100 90 80 70 0

10 20 30 40 50 60 70 Vbus (% of Bus Nominal kV)

ENCLOSURE 1 E112

Figure EEEB-RAI 2-3, MOTOR STARTING ANALYSIS - SD BD C BUS VOLTAGE 260-17 RHR 110 105 100 95 90 85 0

10 20 30 40 50 60 70 Vbus (% of Bus Nominal kV)

ENCLOSURE 1 E113

Figure EEEB-RAI 2-4, MOTOR STARTING ANALYSIS - SD BD D BUS VOLTAGE 270-16 RHR 110 105 100 95 90 85 0

10 20 30 40 50 60 70 Vbus (% of Bus Nominal kV)

ENCLOSURE 1 E114

EEEB-RAI 6 On page 2-130 of Attachment 7 of the LAR, in the BFN Current Licensing Basis section, the licensee stated that the BFN EQ program for electrical equipment is described in the BFN Updated Final Safety Analysis Report (UFSAR), Section 8.9, Safety Systems Independence Criteria and Bases for Electrical Cable Installation. However, Section 8.9 of the UFSAR does not contain the description of the BFN EQ program.

Provide the current licensing basis (include the history) for the BFN EQ of electrical equipment, and a mark-up of the UFSARs relevant sections showing the requested information.

TVA Response (Revision 1):

The Environmental Qualification (EQ) of Electrical Equipment for the Browns Ferry Nuclear Plant (BFN) is described in Section 7.1.6 of the UFSAR. Corrected mark-ups of the affected page of the PUSAR (proprietary and non-proprietary) are provided in Enclosures 2 and 3, respectively. The first paragraph in the BFN Current Licensing Basis section of the Power Uprate Safety Analysis Report (Attachments 6 and 7 of the BFN EPU LAR) section 2.3.1 is revised to read, The Browns Ferry program for environmental qualification of electrical equipment is described in Browns Ferry UFSAR Section 7.1.6, Environmental Qualification of Electrical Equipment. The current licensing basis (including the history) for the BFN EQ of electrical equipment in provided in the attached mark-up (Attachment 1) of the proposed change to Section 7.1.6 of the BFN UFSAR.

ENCLOSURE 1 E115

EEEB-RAI 18 On page 2-140 of Attachment 7 of the LAR, the licensee stated that equipment are operated at or below the nameplate ratings in both normal and emergency conditions at the EPU power level. Table 2.3-7 shows that the nameplate rating of the condensate booster pumps (CBPs) in all three units is 3,000 horsepower (hp), but the maximum transient load on the CBPs assuming a trip of one out of three CBPs or condensate pumps (CPs) is 3,720 brake hp. This shows that the CBPs are overloaded during the transient, and thus are operated above the nameplate ratings.

a.

Identify the balance of plant buses/boards that power the CPs and CBPs, and provide the worst case loading of these buses/boards and margin available at CLTP and EPU conditions. Also, provide a copy of all the Single Line Diagrams listed on page E5-5 provided in response to EEEB-RAI-2.

b.

Provide a summary of relay settings to show that CBPs and their associated boards remain adequately protected during transient loading. Also, provide a duration of the transient loading.

TVA Response (Revision 1):

The overload condition for the condensate booster pumps (CBP) shown in Table 2.3-7 of of the Extended Power Uprate (EPU) License Amendment Request (LAR) are from system hydraulic analyses for each Browns Ferry Nuclear Plant (BFN) units that were designed to maximize the loading of the BFN Unit boards. The electrical buses that supply power to the condensate pump (CP) and CBP motors also are the normal supply for the safety-related shutdown buses. In the event of a loss of coolant accident (LOCA) or high energy line break, the electrical load flow analyses assume that the CP and CBP flow can potentially increase such that the brake horsepower requirements of the pumps will exceed the motor ratings. As a result, the maximum horsepower is computed at the maximum possible flow across CPs and CBPs. These maximum loads were then input into the BFN electrical load flow analyses for the determination of the maximum bus loads, adequacy of degraded voltage settings (See the TVA response to EEEB-RAI 2), motor terminal voltages, and short circuit analyses where a LOCA without loss of offsite power is postulated to occur after a trip of a CBP.

In order to maximize the brake horsepower (BHP) loading of the CBPs, the hydraulic analyses for the CBP trip allowed the two remaining CBP to either go into runout flow conditions or to operate with no net positive suction head (NPSH) margin. These analysis conditions are very conservative versus the actual CBP BHP results upon a trip of a CBP at EPU power levels from an initial 3/3/3 CP/CBP/feedwater pump running configuration. The maximum CBP BHP upon trip of a CBP at EPU rated thermal power is 3,377 hp. While this power demand is above the CBP motor nameplate rating of 3,000 hp, it is within the 1.15 service factor (SF) rating of the motor (3,450 hp). Upon a trip of a CBP, the BFN operators would perform increased monitoring of the CBP motor parameters and a load reduction would be initiated to prevent exceeding the pump motor winding temperature alarm of 266°F.

ENCLOSURE 1 E116

a. The balance of plant (BOP) boards that power the condensate pumps (CP) and CBPs are shown in Table EEEB-RAI 18-1. The requested drawings identified in the TVA response to EEEB-RAI 2 are provided in Attachment 2 of this RAI response.

Table EEEB-RAI 18-1 Pump Motors Board 1A CP and 1A CBP Unit Board 1A 1B CP and 1B CBP Unit Board 1B 1C CP and 1C CBP Unit Board 1C 2A CP and 2A CBP Unit Board 2A 2B CP and 2B CBP Unit Board 2B 2C CP and 2C CBP Unit Board 2C 3A CP and 3A CBP Unit Board 3A 3B CP and 3B CBP Unit Board 3B 3C CP and 3C CBP Unit Board 3C The worst case loading for the BFN Unit Boards is shown in Table EEEB-RAI 18-2. The Unit Board loads in Table EEEB-RAI 18-2 represents the highest individual board load for all load flow analysis conditions that include normal and alternate feeds to the 4KV unit boards, 4KV shutdown boards, 480V shutdown boards and 480V RMOV boards. The limiting load flow analyses assume a trip of a CBP in one BFN unit followed by LOCA without loss of off-site power. This worst case loading condition is applicable to BFN current licensed thermal power (CLTP) and EPU conditions. The hydraulic analyses that determined the maximum CBP and CP loadings are independent of the plant initial power level because the analyses artificially placed the remaining CP and CBP in runout conditions and/or set the pumps into conditions of zero NPSH margin. These analysis conditions are characteristics of the pumps and the condensate/feedwater piping and not the initial plant power level. In addition, the CP and CBP upgrades were performed for Unit 1 prior to Unit 1 restart.

Previous load flow analyses prior to Unit 1 restart considered Unit 1 in a shutdown and defueled condition, i.e., there was no loading on the Unit 1 unit boards 1A, 1B, and 1C.

Therefore, there is no direct comparison analysis between CLTP and EPU power for the limiting load flows. The CBP and CP upgrades have been field implemented at all three BFN units where the last implementation was the CBP upgrade for BFN Unit 3 in the Spring 2016 refueling outage.

ENCLOSURE 1 E117

Table EEEB-RAI 18-2 Unit Board Maximum LOCA Loads (amps)

Board rating (amps)

Margin to Board Rating (%)

1A 1992 2000 0.4 1B 1992 2000 0.4 1C 935 1200 22.1 2A 1990 2000 0.5 2B 1997 2000 0.1 2C 895 1200 25.4 3A 1952 2000 2.4 3B 1975 2000 1.3 3C 898 1200 25.2

b. Motor breaker relay settings for the upgraded CPs and CBPs, as well as the Unit Board normal and alternate feeder breakers are shown in Table EEEB-RAI 18-3.

Summary information concerning the calculation of the CBP relay settings and coordination with the feeder breakers is as follows:

The below data is for the 3000 hp CBP motors. All BFN Unit 1, 2, and 3 CBP motors are identical.

HP Power Factor Efficiency Rated Voltage Full Load Amps Locked Rotor Current (LRC)

LRC Time (cold) 3000 0.907 0.958 4000 Volts 372 amperes 2325 amperes 9 seconds The following are requirements for the breaker relay settings:

The service factor of the CBP motors is 1.15. The device 51 (time overcurrent (OC) relay) is set to protect against overload conditions, and its minimum pickup (overcurrent tap setting) should not exceed 125% of full load current.

Device 50 (instantaneous overcurrent relay) is set to actuate between 150% and 200%

of motor locked-rotor current at 100% of rated voltage The time dial is set to provide an operating time to allow the motor start and protect the motor against locked rotor condition and running overload.

The high drop out is set between 130 and 200% of motor full load current.

Coordination curves between the motor breaker settings and the bus (Unit board) feeder breakers are drawn.

ENCLOSURE 1 E118

The following is a summary computation of the CBP breaker relay settings:

A. Inputs Device: 50/51 Type of relay: 121AC66K8A Current transformer (CT) Ratio: 500/5 = 100 B. Current Tap Setting (OC Tap Setting)

Set at approximately 125% of full load current OC Tap setting = (1.25 x 372)/100 = 4.65 amp Set at 4.5 amp (121% of full load current)

C. Normal Dropout Instantaneous (Norm. Inst.)

Set at approximately 200% of locked rotor current (LRC)

Norm. Inst. = (2 x 2325)/100 = 46.5 amp Set at 46.5 (200% of locked rotor current)

D. High Drop Out Instantaneous (High D.O. Inst.)

Set between 130% and 200% of load current (1.3 x 372)/100 = 4.84 (2 x 372)/100 = 7.44 Set at 7.0 (188% of full load current)

E. Time Dial Set the time dial at 1.0 to protect the motor and allow the motor to start.

The coordination curves, Figures EEEB-RAI 18-2, 18-3, and 18-4, show that the settings are acceptable.

Figure EEEB-RAI 18-1 provides a schematic of the normal and alternate board feeds and the CBP motor feed.

Figure EEEB-RAI 18-2 coordination curve is applicable to CBP 1A, 1B, 2A, 2B, 3A, and 3B.

Figure EEEB-RAI 18-3 coordination curve is applicable to CBP 1C, 2C, and 3C.

ENCLOSURE 1 E119

Figure EEEB-RAI 18-4 coordination curve is applicable to all CBPs. Observation of Figure EEEB-RAI 18-4 shows that a 124% overload of a CBP, the BHP associated with the limiting CBP BHP used as input into the limiting electrical load flow analysis, would result in a trip of the CBP in approximately 40 seconds. The BFN load flow analysis does not credit any tripping of the running CBP during the 65 second duration of the LOCA load flow analysis.

The total transient loading duration for the 4KV Unit Boards supplying power to the CBPs, as well as the 4KV shutdown boards and 480V boards, is 61 seconds during the worst-case LOCA loading condition. At 61 seconds following the LOCA initiation, all large accident loads such as residual heat removal, core spray and residual heat removal service water pumps that are brought on line at discrete time sequences will have been loaded onto the plant electrical boards and all motor operated valves will have started and stroked to their required configuration. The BFN LOCA load flow analysis is run for a duration of 65 seconds to ensure that a steady state load flow is achieved. Therefore, the analyzed transient duration for the BFN electrical load flow analyses is 65 seconds.

The following drawings listed in the TVA response to EEEB-RAI 2 are provided in.

4kV SHUTDOWN BD A (0-45E724-1) 4kV SHUTDOWN BD B (0-45E724-2) 4kV SHUTDOWN BD C (0-45E724-3) 4kV SHUTDOWN BD D (0-45E724-4) 4kV SHUTDOWN BD 3EA (3-45E724-6) 4kV SHUTDOWN BD 3EB (3-45E724-7) 4kV SHUTDOWN BD 3EC (3-45E724-8) 4kV SHUTDOWN BD 3ED (3-45E724-9) 4kV UNIT BD 1A (1-45E721) 4kV UNIT BD 1B (1-45E721) 4kV UNIT BD 1C (1-45E721) 4kV UNIT BD 2A (2-45E721) 4kV UNIT BD 2B (2-45E721) 4kV UNIT BD 2C (2-45E721) 4kV UNIT BD 3A (3-45E721) 4kV UNIT BD 3B (3-45E721) 4kV UNIT BD 3C (3-45E721) 4kV COMMON BD A (0-15E500-2) 4kV COMMON BD B (0-15E500-2)

Key Diagram of Standby Auxiliary Power System (0-15E500-1)

Key Diagram of Normal & Standby Auxiliary Power System (3-15E500-3)

ENCLOSURE 1 E120

Table EEEB-RAI 18-3 CP, CBP, and Unit Board Feeder Breaker Information at EPU Unit Board Equipment Breaker Size (Amps)

CT Ratio Over-current Tap (Setting)

Over-current Trip Setting (Amps)

Over-current Time Delay (Setting) 1A Norm Feed Bkr 1112 2000 400 8.0 3200 7.7 1A Unit Start Bkr 1424 2000 400 8.0 3200 7.7 1A CP Bkr 1A 1200 40 5.0 200 4.0 1A CBP Bkr 1A 1200 100 4.5 450 1.0 1B Norm Feed Bkr 1114 2000 400 8.0 3200 7.7 1B Unit Start Bkr 1524 2000 400 8.0 3200 7.7 1B CP Bkr 1B 1200 40 5.0 200 4.0 1B CBP Bkr 1B 1200 100 4.5 450 1.0 1C Norm Feed Bkr 1116 1200 300 10.0 450 3000 6.0 1C Unit Start Bkr 1532 1200 300 10.0 3000 6.0 1C CP Bkr 1C 1200 40 5.0 200 4.0 1C CBP Bkr 1C 1200 100 4.5 450 1.0 2A Norm Feed Bkr 1212 2000 400 8.0 3200 7.7 2A Unit Start Bkr 1428 2000 400 8.0 3200 7.7 2A CP Bkr 2A 1200 40 5.0 200 4.0 2A CBP Bkr 2A 1200 100 4.5 450 1.0 2B Norm Feed Bkr 1214 2000 400 8.0 3200 7.7 2B Unit Start Bkr 1526 2000 400 8.0 3200 7.7 2B CP Bkr 2B 1200 40 5.0 200 4.0 2B CBP Bkr 2B 1200 100 4.5 450 1.0 2C Norm Feed Bkr 1216 1200 300 10.0 3000 6.0 2C Unit Start Bkr 1426 1200 300 10.0 3000 6.0 2C CP Bkr 2C 1200 40 5.0 200 4.0

ENCLOSURE 1 E121

Unit Board Equipment Breaker Size (Amps)

CT Ratio Over-current Tap (Setting)

Over-current Trip Setting (Amps)

Over-current Time Delay (Setting) 2C CBP Bkr 2C 1200 100 4.5 450 1.0 3A Norm Feed Bkr 1312 2000 400 8.0 3200 7.7 3A Unit Start Bkr 1432 2000 400 8.0 3200 7.7 3A CP Bkr 3A 1200 40 5.0 200 4.0 3A CBP Bkr 3A 1200 100 4.5 450 1.0 3B Norm Feed Bkr 1314 2000 400 8.0 3200 7.7 3B Unit Start Bkr 1528 2000 400 8.0 3200 7.7 3B CP Bkr 3B 1200 40 5.0 200 4.0 3B CBP Bkr 3B 1200 100 4.5 450 1.0 3C Norm Feed Bkr 1316 1200 300 10.0 3000 6.0 3C Unit Start Bkr 1434 1200 300 10.0 3000 6.0 3C CP Bkr 3C 1200 40 5.0 200 4.0 3C CBP Bkr 3C 1200 100 4.5 450 1.0

ENCLOSURE 1

E122 Figure EEEB-RAI 18-1 (This figure is applicable to all Unit 1, 2, and 3 4KV Unit Boards)

ENCLOSURE 1

E123 Figure EEEB-RAI 18-2 (This figure is applicable to CBP 1A, 2A, 3A, 1B, 2B and 3B)

ENCLOSURE 1

E124 Figure EEEB-RAI 18-3 (This figure is applicable to CBP 1C, 2C, and 3C)

ENCLOSURE 1

E125 Figure EEEB-RAI 18-4 EEEB-RAI 21

ENCLOSURE 1

E126 On page 2-143 of Attachment 7 of the LAR, the licensee states:

The results of the battery sizing calculation for the LOCA/LOOP [loss of offsite power]

analysis scenario show that the existing batteries have adequate voltage at the end of the duty cycle. It also shows all required DC devices are within their design voltage range.

Provide a summary of the battery (identify the batteries) sizing calculation, including assumptions, voltages and margin, for the LOCA/LOOP scenario corresponding to EPU conditions.

TVA Response (Revision 1):

The summary of the battery sizing calculation for the LOCA/LOOP scenario corresponding to EPU conditions is as follows.

1.0 PURPOSE 1.1 Perform the DC load study for all three units on 250V DC unit batteries 1, 2 and 3 to verify that the size of the existing batteries is adequate during a DBA on one unit and spurious DBA on another unit (Loss of Coolant Accident (LOCA) and Loss of Offsite Power (LOOP)) with one battery system out of service and the safe shutdown and cooldown of the remaining non-DBA unit.

1.2 Establish the voltage profile for each battery duty cycle to determine the minimum available voltage at the terminals of each unit battery, battery boards, Reactor Motor Operated Valve (RMOV) boards, and Shutdown Boards for each case of study and verify that these calculated voltages are higher than the bus voltage used to perform control circuit voltage drop (CCVD) calculations.

ENCLOSURE 1

E127 2.0 SYSTEM DESCRIPTION The existing 250V DC system at BFN serves the three unit plant with a continuous source of DC power to both safety-related and non-safety related loads. It also provides power for unit control functions, operative power for unit control loads, control power for 4kV and 480V switchgear, common plant and transmission system control functions, and drive power for motor loads.

2.1 The 250V DC Power System at BFN has two sub-systems.

2.1.a The 250V DC plant system consists of three unit batteries 1, 2, and 3 and their associated battery chargers and distribution boards. These batteries supply all the required safety related loads.

Three station batteries 4, 5 and 6 and their associated battery chargers and distribution boards supply loads that are not essential to safe shutdown and cooldown of the units and are therefore not discussed further.

Each unit battery is a 120 cell lead-acid battery of C&D make, type LCUN-33. They have a one-minute rating of 2080 amps and an 8-hour discharge rating of 2320 ampere-hours. Both ratings are based on a battery terminal voltage of 210V (at 77°F) at end of discharge (1.75V/Cell).

The three unit batteries are for three units and feed Class 1E battery boards 1, 2, and 3.

These three unit batteries have all the engineered safeguards loads for the three units distributed among them so that redundant systems on each unit have separate normal and alternate power supplies, each capable of providing sufficient power for engineered safeguard loads. Safety-related DC Motor Operated Valve (MOV) boards have power supplies from two different batteries designated as normal and alternate power supply.

All transfers from normal to alternate sources are performed manually.

2.1.b 250V DC control power supply system consists of five shutdown batteries (SB) SB-A, B, C, D and 3EB and their associated battery chargers and distribution boards. This system supplies control power to 4160V Shutdown Boards A, B, C, D and 3EB and 480 Shutdown Boards 1A, 1B, 2A, and 2B.

Each shutdown board battery is a 120 cell lead-acid battery of C&D make, type KCR*11.

They have a one-minute discharge rating of 500 amperes and an 8-hour discharge rating of 410 ampere-hours. Both ratings are based on a battery terminal voltage of 210V (at 77°F).

3.0 ACCEPTANCE CRITERIA 3.1 Battery Sizing - The batteries cells must contain more positive plates than the number of positive plates required as calculated by the ETAP program.

3.2 Battery Capacity - The capacity of the battery shall be considered adequate for minimum required battery terminal voltage of 210.0V (1.75V/Cell). However, higher minimum voltage at the battery terminals shall be maintained for maintaining the minimum voltages for various boards in order to have adequate voltage at the control devices

ENCLOSURE 1

E128 evaluated in control circuit voltage drop calculations. (See Section 3.3) The batterys duty cycle is 30 minutes.

3.3 Minimum Board Voltages - The minimum available voltages necessary at the end devices are calculated by the ETAP using actual minimum voltage at the upstream buses of the end devices. The following minimum voltages have been used at the 250V DC boards to perform control circuit voltage drop calculations and therefore these minimum voltages must be maintained:

4kV Shutdown Board A 206.0V 4kV Shutdown Board B 207.5V 4kV Shutdown Board C 208.0V 4kV Shutdown Board D 207.5V 4kV Shutdown Board 3EA, 3EB, 3EC, 3ED 204.5V 480V Shutdown Board 1A, 1B, 2A, 2B, 3A, 3B 202.0V 250V RMOV Board 2A 210.0V 250V RMOV Boards 2C and 2B 210.0V 250V RMOV Boards 3A, 3B and 3C 210.0V 250V RMOV Boards 1A, 1B and 1C 210.0V 4.0 ANALYSIS 4.1 The 250V DC load study calculation is performed using the TVA verified ETAP software, Version 5.0.3.

4.2 The worst case loading condition for the batteries, based on the operation of valves, pumps, etc., is used in the 30 minute battery duty cycle. Both HPCI and RCIC systems will automatically start at time t=0 seconds for the Units in the real, as well as spurious, DBA events. Even though HPCI and RCIC do not start simultaneously, loading is considered at t=0 seconds for conservatism. The HPCI and RCIC systems for the unit, which will not be in a DBA event, will initiate after 25 seconds of the battery duty cycle.

Even though Unit 1 is not in a DBA event, the applied loads at 25 seconds are considered to be the LOCA loads. Units 2 and 3 loads are initiated at 0 seconds in the battery duty cycle and Unit 1 at 25 seconds. The worst load peak is at 0 seconds due to Units 2 and 3 transient loads. This worst case loading is considered for the entire minute. Therefore, any combination of DBA and non-DBA events configuration (for e.g., "U1 in LOCA, U2 in spurious LOCA and U3 in normal cold shutdown" or "U3 in LOCA, U1 in spurious LOCA and U2 in normal cold shutdown mode") will be enveloped by the analyzed configuration of U2 in LOCA, U3 in Spurious LOCA and U1 in normal cold shutdown mode. Hence, separate battery loading evaluation has not been performed for different combination of DBA events between the units.

Also, the minimum available voltage at the end devices will be the same as computed with these DBA events, because ETAP performs voltage drop computations with the minimum calculated voltage during the entire first minute. The voltage drop computation has been performed with actual cable data for all units which have been input in the ETAP. Therefore, the minimum available voltages will be the same in different combinations of DBA events between units.

ENCLOSURE 1

E129 4.3 Battery load is calculated to verify the adequacy of the 250V DC system to perform its design functions. Unit batteries are required to carry the accident load with one battery out of service. Also, any one shutdown battery may be removed from service. The 250V DC distribution system provides alternate feeds to all loads to allow one battery to be removed from service. Considering combination of each unit battery with no unit batteries out of service and with each battery out of service one at a time results in the following cases of study.

Establish 30 minute duty cycles for Battery Board #1 with:

Case 1: Shutdown Battery C* out of service.

Case 2: Unit Battery 2 out of service.

Case 3: Unit Battery 3 out of service.

Establish 30 minute duty cycles for Battery Board #2 with:

Case 4: Unit Shutdown Battery A* out of service.

Case 5: Unit Battery 1 out of service.

Case 6: Unit Battery 3 out of service.

Establish 30 minute duty cycles for Battery Board #3 with Case 7: Shutdown Battery D* out of service.

Case 8: Unit Battery 1 out of service.

Case 9: Unit Battery 2 out of service.

  • For consideration of shutdown batteries out of service, only the worst case load on each unit battery is calculated.

Unit batteries 1, 2 and 3 supply all safety related loads and station batteries 4, 5 and 6 supply all non-safety related loads. Only loads for the following board/panel equipment can be transferred between the unit and station batteries.

  • Electrical Distribution Circuit Breaker Panel 9-24 (From BB4 (Norm) to BB2 (Alt))

The ETAP has been modeled as showing the alternate breakers as closed. The alternate breakers would normally only be closed if unit battery 4 were out of service.

Modeling the alternate breakers as closed is conservative and eliminates the need to run a special case for each unit battery 1, 2 and 3, with unit battery 4 out of service.

4.4 The total load on each battery board for each of the three cases of study is compiled and the battery duty cycle is established for all cases. Battery sizing calculations, to determine the required number of positive plates, are then performed for each case using ETAP. The battery voltage profile is also determined for each battery duty cycle for every case using the same ETAP model.

4.5 The following cell sizing correction factors are used in this calculation.

1.11 - Temperature correction for 60°F.

1.25 - Compensating for aging factor for 80% of rated capacity at the end life.

1.02 - Design Margin (BFN being an operational plant, minimum 2% Design Margin is used).

4.6 The DC buses are considered to have negligible resistance and inductance. The inductance of cables is not considered in the calculations.

ENCLOSURE 1

E130 4.7 The impedance of circuit breakers and fused disconnect switches is considered to be negligible.

4.8 Battery internal cell resistance used is 0.01416 Ohms (0.000118 Ohms/Cell x 120 Cells).

4.9 Battery initial voltage used in "ETAP" at t=0 seconds is considered to be Battery Open Cell voltage of 2.055V/Cell (246.6V) for battery load flow and battery discharge calculations.

4.10 Initiation of HPCI and RCIC valves are analyzed for the entire duty cycle. For conservative battery loading, the "ON & OFF" cycling of the valves has been considered to initiate at the beginning of each time interval. This will result in conservative battery loading since the loads are stacked on the top of each other.

4.11 The operating stroke times for all Units MOVs, required to operate during a DBA event, is less than or equal to one minute. However, all stroke times are entered into ETAP as one minute for conservatism.

4.12 Control loads such as indicating lights in spare cubicles of switchgear are negligible and are not considered.

4.13 All motor starting loads are modeled as constant resistance. The load current for constant resistance loads is adjusted by ETAP based on available battery voltage. This is conservative.

4.14 All safety-related control operations shall be automatic for the first 10 minutes after a loss of off-site power and/or any other accident condition.

4.15 The full load current for the MOVs is normally based on 20% running torque. As per Limitorque Corp., the MOV motor should be adequate to accommodate a running torque of 10% to 25% of the seating force (torque). Hence a full load (running) current corresponding to 25% running torque will be used. The increase in 5% running torque is equivalent to 20% increase of the rated full load current and these values are used in the ETAP calculation. This will also result in conservative battery loading.

4.16 The pump motors are assumed to reach rated speed within five seconds. This assumption in the battery load duty cycle that the DC pump motor inrush current lasts for five seconds is conservative based on the following:

DC pump motors have the reduced voltage starting circuit. The reduced voltage starting resistance in the motor armature circuit cuts out after 2 seconds. The timer is typically chosen such that the motor will be close to, or equal to, full speed (free running) before the starting resistor is cut out. This means by two seconds, there is sufficient counter emf generated in the motor such that the current won't be excessive when the starting resistor is removed from the circuit. The remaining acceleration time to full speed will be negligible. Therefore, the maximum duration of inrush current will be two seconds.

4.17 HPCI Gland Seal condensate pump is cycling on and off and is considered as a cyclic load. Also the HPCI auxiliary oil pump is considered to run continuously during the 30-minute duty cycle. This represents conservative loading for the auxiliary oil pump.

ENCLOSURE 1

E131 4.18 Continuous 4.0 ampere margin is added to each of the following boards during each step of the thirty minute duty cycle to account for the effects of the incorporation of future design changes into this calculation and is conservative.

Battery Board 1, 2 and 3 250V RMOV Board 1A, 1 B and 1C 250V RMOV Board 2A, 2B and 2C 250V RMOV Board 3A, 3B and 3C 4.19 A continuous design margin of 5.0 amps has been added to each 4kV shutdown board DC distribution panel for the entire 30 minute battery duty cycle. This margin is included to account for the effects of the incorporation of future design changes into this calculation and is conservative.

5.0 RESULTS 5.1 Battery Sizing Table 5.1 Unit Batteries - Sizing Battery/Case Number of Positive Plates Calculated Number of Positive Plates Supplied Positive Plate Margin

(%)

UNIT BATTERY 1, CASE 1 11.83 16 26.1 UNIT BATTERY 1, CASE 2 7.44 16 53.5 UNIT BATTERY 1, CASE 3 8.83 16 44.8 UNIT BATTERY 2, CASE 4 11.75 16 26.6 UNIT BATTERY 2, CASE 5 10.11 16 36.8 UNIT BATTERY 2, CASE 6 10.22 16 36.1 UNIT BATTERY 3, CASE 7 11.42 16 28.6 UNIT BATTERY 3, CASE 8 6.85 16 57.2 UNIT BATTERY 3, CASE 9 11.04 16 31.0

ENCLOSURE 1

E132 Table 5.2 Shutdown Batteries - Sizing Shutdown Battery Number of Positive Plates Calculated Number of Positive Plates Supplied Positive Plate Margin

(%)

SB-A 2.37 5

52.6 SB-B 3.00 5

40.0 SB-C 3.00 5

40.0 SB-D 3.00 5

40.0 SB-3EB 3.00 5

40.0 Unit batteries 1, 2, and 3 and Shutdown Batteries SB-A, B, C, D, 3EB are adequately sized as the number of positive plates supplied in the cells exceeds the number of positive plates required by ETAP calculation.

ENCLOSURE 1

E133 5.2 Battery Capacity Table 5.3 Unit Batteries - Capacity Battery/Case Minimum Voltage (Volts) (0-30 minutes)

Required Minimum Voltage (Volts)

Voltage Margin

(%)

UNIT BATTERY 1, CASE 1 221.91 210.00 32.5 UNIT BATTERY 1, CASE 2 227.24 210.00 47.1 UNIT BATTERY 1, CASE 3 225.06 210.00 41.1 UNIT BATTERY 2, CASE 4 222.05 210.00 32.9 UNIT BATTERY 2, CASE 5 223.88 210.00 37.9 UNIT BATTERY 2, CASE 6 223.27 210.00 36.3 UNIT BATTERY 3, CASE 7 222.25 210.00 33.5 UNIT BATTERY 3, CASE 8 228.03 210.00 49.3 UNIT BATTERY 3, CASE 9 222.34 210.00 33.7 Table 5.4 Shutdown Batteries - Capacity Shutdown Board Battery Minimum Voltage (Volts) (0-30 minutes)

Required Minimum Voltage (Volts)

Voltage Margin

(%)

SB-A1 SB-B SB-C SB-D SB-3EB 225.06 210.00 41.1 1 Calculation was performed using the worst case profile for battery SB-A which bounds the load profiles of the other batteries.

Unit batteries 1, 2, and 3 and Shutdown Batteries SB-A, B, C, D, 3EB have adequate capacity as the minimum voltages, calculated by ETAP, were all greater than the required minimum voltage of 210.0V (1.75V/Cell). However, higher minimum voltage at the battery terminals shall be required for maintaining the minimum voltages for various boards in order to have adequate voltage at the control devices evaluated in control circuit voltage drop calculations. (See Results Section 5.3 - Minimum Board Voltages.)

ENCLOSURE 1

E134 5.3 Minimum Board Voltages Table 5.5 Unit Batteries - Minimum Board Voltages Shutdown Board ID Minimum Acceptable Bus Voltage (Volts) 250V DC BUS VOLTAGE NORMAL SOURCE1 ALTERNATE SOURCE1 Minimum (Volts)

Margin

(%)

Minimum (Volts)

Margin

(%)

4kV SHUTDOWN BD 3EA 204.5 219.44 35.5 221.97 43.8 4kV SHUTDOWN BD 3EC 204.5 219.13 38.3 215.81 41.5 4kV SHUTDOWN BD 3ED 204.5 221.19 34.8 220.62 26.9 4kV BUS TIE BD 204.5 221.32 39.6 222.92 38.3 480V SHUTDOWN BD 3A 202.0 215.48 30.2 222.86 46.8 480V SHUTDOWN BD 3B 202.0 217.35 34.4 217.35 34.4 RMOV BOARD 1A 210.0 218.81 24.1 See Footnote 2

N/A RMOV BOARD 1B 210.0 221.12 30.4 See Footnote 2

N/A RMOV BOARD 1C 210.0 220.81 29.5 See Footnote 2

N/A RMOV BOARD 2A 210.0 217.60 20.8 See Footnote 2

N/A RMOV BOARD 2B 210.0 220.58 28.9 See Footnote 2

N/A RMOV BOARD 2C 210.0 220.91 29.8 See Footnote 2

N/A RMOV BOARD 3A 210.0 218.40 23.0 See Footnote 2

N/A RMOV BOARD 3B 210.0 220.21 27.9 See Footnote 2

N/A RMOV BOARD 3C 210.0 219.96 27.2 See Footnote 2

N/A 1

The three unit batteries, batteries 1, 2, and 3 have all the engineered safeguards loads for the three units distributed among them so that redundant systems on each unit have separate normal and alternate supplies.

2 RMOV Board voltages calculated for the alternate source are not available. However, the minimum voltages for every load fed from the RMOV Boards were calculated and all met their minimum acceptable voltages. Therefore, by definition, it follows that the RMOV Board voltages also met their minimum acceptable voltages.

ENCLOSURE 1

E135 Table 5.6 Shutdown Batteries - Minimum Board Voltages Shutdown Board ID Minimum Acceptable Bus Voltage (Volts) 250V DC BUS VOLTAGE NORMAL SOURCE1 ALTERNATE SOURCE1 Minimum (Volts)

Margin

(%)

Minimum (Volts)

Margin

(%)

4kV SHUTDOWN BD A 206.0 220.61 36.0 220.28 35.2 4kV SHUTDOWN BD B 207.5 220.61 33.5 217.17 24.7 4kV SHUTDOWN BD C 208.0 220.61 32.7 212.09 10.6 4kV SHUTDOWN BD D 207.5 220.61 33.5 221.30 35.3 4kV SHUTDOWN BD 3EB 204.5 220.61 38.3 215.27 25.6 480V SHUTDOWN BD 1A 202.0 207.84 13.1 216.40 32.3 480V SHUTDOWN BD 1B 202.0 207.84 13.1 225.67 53.1 480V SHUTDOWN BD 2A 202.0 207.84 13.1 209.72 17.3 480V SHUTDOWN BD 2B 202.0 207.84 13.1 225.67 53.1 1 The three unit batteries, batteries 1, 2, and 3 have all the engineered safeguards loads for the three units distributed among them so that redundant systems on each unit have separate normal and alternate supplies.

Unit batteries 1, 2, and 3 and Shutdown Batteries SB-A, B, C, D, 3EB provide adequate voltages to all boards as the calculated voltages supplied, from the normal source and the alternate source to each board, are greater than the minimum voltages, required to ensure the most limiting load on each board, functions properly.

6.0 CONCLUSION

The 250V DC system has sufficient battery (Unit and Shutdown) capacity, at EPU conditions, to power the necessary loads during a LOOP/LOCA event and maintain adequate voltage levels to all required DC equipment during the 30 minute duty cycle.

ENCLOSURE 2 Power Uprate Safety Analysis Report Section 2.5.1.2.2 Insert (Revision 1)

Insert 1 (Revision 1)

The main generator excitation systems, that existed on all three units, were GE Alterrex Excitation systems. The energy for excitation of the generator field is derived from the turbine using a self-excited shaft driven alternator. The output of the alternator is rectified by a set of water cooled stationary diode bridges mounted in the doghouse of the generator. The resultant DC voltage is supplied to the generator field via brushes and collector rings. In 2011 and 2012, TVA replaced the voltage regulators in the Alterrex Excitation systems with new ABB Unitrol 5000 voltage regulators. The Interconnection System Impact Study (SIS), performed for BFN at EPU conditions, determined that main generator stability issues exist for a 3-phase fault on one of several BFN transmission lines coincident certain transmission lines already out of service (N-1-1 event.). The present excitation system cannot raise the field voltage fast enough and high enough to prevent the main generator from becoming unstable. To address the transient stability issue, BFN will install a new shunt-fed, static excitation system on each of the three units. The new excitation system will provide the field current directly to the brushes and collector rings eliminating the need for the rotating Alterrex exciter and the stationary diodes.

Additional computer simulations of the N-1-1 event for the SIS, with this new excitation system modeled, have shown that the generators remain stable. As the new excitation system requires a higher DC field voltage, the insulating material in the rotors will need to be evaluated as acceptable or replaced. If the rotors must be changed, e.g., insulating material replaced, the design change process will ensure that the modifications will not have an adverse effect on GDC 17 compliance, generator stability, short circuit analysis acceptance criteria compliance, and reliability and availability of the offsite transmission system. When conditions exist, that make generator instabilities possible during an N-1-1 event, administrative controls will be implemented to limit unit output whenever certain transmission lines are out of service. Once the excitation systems are replaced on all three units, the administrative controls will no longer be necessary. Use of administrative controls to prevent transient instabilities, prior to the excitation systems being installed, is allowed by North American Reliability Council (NERC) standards.