CNL-15-252, License Amendment Request and Request for Deviation from 10 CFR 50, Appendix R in Support of Closure of Generic Safety Issue 191 (WBN-TS-16-01)
| ML16054A585 | |
| Person / Time | |
|---|---|
| Site: | Watts Bar |
| Issue date: | 02/23/2016 |
| From: | James Shea Tennessee Valley Authority |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| CNL-15-252, TAC MC4730, WBN-TS-16-01 | |
| Download: ML16054A585 (23) | |
Text
Tennessee Valley Authority, 1101 Market Street, Chattanooga, Tennessee 37402 CNL-15-252 February 23, 2016 U.S. Nuclear Regulatory Commission ATTN : Document Control Desk Washington, D.C. 20555-0001 Watts Bar Nuclear Plant, Unit 1 Facility Operating License NPF-90 NRC Docket No. 50-390 10 CFR 50.90 10 CFR 50 Appendix R
Subject:
Watts Bar Nuclear Plant Unit 1 License Amendment Request and Request for Deviation from 10 CFR 50 Appendix R in Support of Closure of Generic Safety Issue 191 (WBN-TS-16-01)
References:
- 1. TVA letter to NRC, CNL-15-009, "Watts Bar Nuclear Plant Unit 1 -
Resolution of Generic Safety Issue 191," dated April 17, 2015 (ML15111A065)
- 2. NRC letter to TVA, "Watts Bar Nuclear Plant, Unit 1, Closeout of Generic Letter 2004-02, 'Potential Impact of Debris Blockage on Emergency Recirculation During Design Basis Accidents at Pressurized-Water Reactors' (TAC No. MC4730)," dated September 17, 2015(ML15191A183)
In accordance with the provisions of Title 10 of the Code of Federal Regulations (10 CFR) 50.90, "Application for amendment of license, construction permit, or early site permit", the Tennessee Valley Authority (TVA) is submitting a request for an amendment to Facility Operating License (OL) No. NPF-90 for the Watts Bar Nuclear Plant (WBN), Unit 1.
This license amendment requests Nuclear Regulatory Commission (NRC) approval, pursuant to OL Condition 2.F, for the enclosed revision to the WBN Dual Unit Fire Protection Report (FPR). Specifically, this license amendment requests NRC approval of a deviation from the separation requirements of 10 CFR Part 50 Appendix R, Section 111.G.2.d, as documented in Section 9.5.1 of the updated Safety Analysis Report (USAR), regarding two cables and conduits located inside WBN, Unit 1. The 10 CFR 50 Appendix R, Section 111.G.2.d requires "Separation of cables and equipment and associated non-safety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards."
This deviation request is in support of the resolution of Generic Safety Issue (GSI) 191. TVA submitted a plan to address fibrous material in the WBN Unit 1 containment (Reference 1 ),
which was accepted by the NRC in Reference 2.
U.S. Nuclear Regulatory Commission CNL-15-252 Page 2 February 23, 2016 For those two cables/conduits, TVA has conducted a fire hazard analysis that provides the basis for the deviation to the 20-foot separation requirements of Appendix R, Section 111.G.2.d.
The enclosure to this letter provides a description of the proposed changes, technical evaluation of the proposed changes, regulatory evaluation, and a discussion of environmental considerations. Attachment 1 to the enclosure provides the existing WBN Unit 1 OL Condition 2.F marked-up to show the proposed change. Attachment 2 to the enclosure provides the existing WBN Unit 1 OL Condition 2.F retyped to show the proposed change.
The proposed new Part VII, Section 2.9.22 to the Dual Unit FPR is provided in Attachment 3 to the enclosure along with the revised deviation table from Part VII, Section 2.9.0 of the FPR.
TVA has determined that there are no significant hazards considerations associated with the proposed change and that the license amendment qualifies for a categorical exclusion from environmental review pursuant to the provisions of 10 CFR 51.22(c)(9). Additionally, in accordance with 10 CFR 50.91(b)(1), TVA is sending a copy of this letter and enclosures to the Tennessee State Department of Public Health.
TVA requests approval of this license amendment prior to the WBN Unit 1 Cycle 14 refueling outage, currently scheduled to start March 20, 2017. TVA requests that this license amendment be implemented within 30 days of issuance.
The WBN Plant Operations Review Committee and the TVA Nuclear Safety Review Board have reviewed this proposed change and determined that operation of WBN Unit 1 in accordance with the proposed change will not endanger the health and safety of the public.
No new regulatory commitments are associated with this letter. If you have any questions or comments, please contact Gordon Arent at (423) 365-2004.
I declare under penalty of perjury that the foregoing is true and correct. Executed on the 23rd day of February 2016.
Enclosure:
Evaluation of the Proposed Change to Operating License Condition 2. F cc (Enclosure):
NRC Regional Administrator - Region II NRC Senior Resident Inspector - Watts Bar Nuclear Plant Unit 1 NRR Project Manager - Watts Bar Nuclear Plant Director, Division of Radiological Health - Tennessee State Department of Environment and Conservation
CNL-15-252 E-1 of 21 ENCLOSURE EVALUATION OF PROPOSED CHANGE TO OPERATING LICENSE CONDITION 2.F
SUBJECT:
WATTS BAR NUCLEAR PLANT UNIT 1 LICENSE AMENDMENT REQUEST AND REQUEST FOR DEVIATION FROM 10 CFR 50 APPENDIX R IN SUPPORT OF CLOSURE OF GENERIC SAFETY ISSUE 191 (WBN-TS-16-01)
- 1.
SUMMARY
DESCRIPTION
- 2. DETAILED DESCRIPTION
- 3. TECHNICAL EVALUATION
- 4. REGULATORY EVALUATION 4.1. Applicable Regulatory Requirements/Criteria 4.2. Precedent 4.3. Significant Hazards Consideration 4.4. Conclusion
- 5. ENVIRONMENTAL CONSIDERATION
- 6. REFERENCES ATTACHMENTS
- 1. Proposed Change to Operating License Condition 2.F (Mark-Up) for WBN Unit 1
- 2. Proposed Change to Operating License Condition 2.F (Final Typed) for WBN Unit 1
- 3. Proposed Revision to the Watts Bar Dual Unit Fire Protection Report and Appendix R Deviation Request
CNL-15-252 E-2 of 21
- 1.
SUMMARY
DESCRIPTION Title 10 of the Code of Federal Regulations (10 CFR) 50 Appendix R,Section III.G.2 provides physical separation criteria applicable to fire areas where cables or equipment of redundant trains of systems necessary to achieve and maintain hot shutdown are located in the same fire area. Compliance with these criteria is one means of ensuring that one of the redundant trains is free of fire damage as required by 10 CFR 50 Appendix R, Section III.G.1. The 10 CFR 50 Appendix R, Section III.G.2.d requires Separation of cables and equipment and associated non-safety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustibles or fire hazards.
Tennessee Valley Authority (TVA) is requesting Nuclear Regulatory Commission (NRC) approval, pursuant to Watts Bar Nuclear Plant (WBN) Unit 1 Operating License (OL) Condition 2.F, to make changes to the WBN Dual Unit Fire Protection Report (FPR) as described in the WBN Updated Safety Analysis Report (USAR). Specifically, TVA requests a deviation from the physical separation criteria of 10 CFR 50 Appendix R, Section III.G.2 for the rooms listed in Table 1. The rooms listed in the Table 1 demonstrate compliance with 10 CFR 50 Appendix R, Section III.G.1 by a fire hazards analysis (FHA) with no operator manual actions (OMAs),
electrical raceway fire barrier systems (ERFBS), or radiant energy shields (RES).
Table 1 Room Locations Section of the WBN Dual Unit Fire Protection Report (FPR)
Room Number 2.9.22 RI-1, RI-2, RI-3, RI-4 The specific items that do not meet the 20-foot separation criteria are cables associated with Loop 1 hot and cold leg temperature elements and with the reactor pressure vessel (RPV) head vent valves.
TVA shall implement and maintain in effect all provisions of the approved fire protection program as described in the Fire Protection Report for the facility, as approved in Appendix FF Section 3.5 of Supplement 18 and Supplement 29 of the SER (NUREG-0847) subject to the following provision:
TVA may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
The proposed amendment would revise WBN Unit 1 OL Condition 2.F as follows:
TVA shall implement and maintain in effect all provisions of the approved fire protection program as described in the Fire Protection Report for the facility, as
CNL-15-252 E-3 of 21 approved in Appendix FF Section 3.5 of Supplement 18 and Supplement 29 of the SER (NUREG-0847) and in Amendment No. ZZZ subject to the following provision:
TVA may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
2.2 Need for Proposed Changes As part of the resolution of Generic Safety Issue (GSI) 191, TVA submitted a plan to address fibrous material in the WBN Unit 1 containment (Reference 1), which was accepted by the NRC in Reference 2. To address in-vessel effects, the amount of fiber allowed to transport into the active fuel region must be very low.
To satisfy GSI 191 requirements, Minnesota Mining and Manufacturing (3M) fire protection mat (M20C) will need to be removed from five separate conduits inside the WBN Unit 1 containment crane wall. The 3M fire protection mat is currently used as an RES to satisfy 10 CFR 50 Appendix R requirements. To remove the 3M RES and continue to satisfy 10 CFR 50 Appendix R requirements, each associated conduit would need to be re-routed such that it is separated by a minimum of 20 feet horizontally with no intervening combustibles from another channel providing the same function inside the containment crane wall. With this separation, no fire barrier material, and thus no fibrous material, would be required inside the crane wall.
Of the five conduits described above, TVA has determined that three can be rerouted to comply with Appendix R requirements. The remaining two conduits have been analyzed and found to remain functional with the 3M RES removed, based on a detailed FHA. This FHA supports a deviation from the requirements of 10 CFR 50 Appendix R Section III.G.2 similar to one approved for WBN Unit 2 in Section 2.9.21 of the FPR. Therefore, TVA is requesting NRC approval of a deviation from 10 CFR 50 Appendix R Section III.G.2. The FHA is provided in to the enclosure.
- 3. TECHNICAL EVALUATION The FHA has been performed for the rooms listed in Table 1. The FHA was performed in accordance with the guidelines of Generic Letter (GL) 86-10, Implementation of Fire Protection Requirements. When a barrier is identified as a rated fire barrier, the penetrations through that barrier are rated for the barrier and are maintained by appropriate engineering design and maintenance programs (e.g., fire doors, fire dampers, penetration seal programs
[FPR Part II, References 4.2.48, 4.2.44, 4.2.49, 4.2.34, 4.2.35, and 4.2.67]). The combustible loading information is derived from the combustible loading calculation (FPR Part II, Reference 4.2.10) and the fire rated barriers are documented on the fire protection compartmentation drawings (FPR Part II, Reference 4.2.39).
CNL-15-252 E-4 of 21 Defense in Depth The concept of defense-in-depth, described in 10 CFR 50 Appendix R, is applied to fire protection in fire areas important to safety, with the following three objectives:
- 1.
Prevent fires from starting The area of the plant in question (i.e., inside the crane wall below the operating deck of the reactor building) has a low combustible loading. A leak collection system is provided for the reactor coolant pumps (RCPs), which is the main source of combustibles, to collect any leakage and route it such that the potential for a fire is low. Additionally, for those items that are combustible, there are no associated ignition sources. Accordingly, there is a low likelihood of a fire starting.
- 2.
Detect rapidly, control, and extinguish promptly those fires that do occur For the area inside the crane wall, thermal detectors are provided for the RCPs, which annunciate in the control room. Hose stations are provided inside the containment crane wall to support manual fire fighting by the fire brigade.
- 3.
Provide protection of structures, systems and components (SSC) important to safety so that a fire that is not promptly extinguished by fire suppression activities will not prevent the safe shutdown of the plant.
As described in Attachment 3, if a fire were to occur, at least one train of safe shutdown equipment would remain functional to support safe shutdown. This is provided by existing barriers, low combustible loading, and equipment separation.
- 4. REGULATORY EVALUATION 4.1. Applicable Regulatory Requirements/Criteria 10 CFR 50 Appendix R Section III.G.2 specifies a number of means of ensuring that one train of required equipment is free from damage in the event of a fire. TVA requests a deviation from one the those means, specifically 10 CFR 50 Appendix R Section III.G.2.f which states:
Separation of cables and equipment and associated non-safety circuits of redundant trains by a noncombustible radiant energy shield.
TVA has performed an FHA that demonstrates that without an RES for the cables identified above, at least one train of required safe shutdown equipment will remain functional in the event of a fire.
4.2. Precedent The NRC has approved a similar deviation request for WBN Unit 2 in the Dual Unit FPR Section VII, subsection 2.9.21 (NUREG-0847, Supplement 29).
CNL-15-252 E-5 of 21 4.3. Significant Hazards Consideration The proposed change will revise the Watts Nar Nuclear Plant (WBN) Unit 1 Operating License Condition 2.F. This license condition is associated with fire protection and defines the basis for the NRCs approval of the WBN Fire Protection Program that is applicable for the operation of WBN Unit 1. Operating License Condition 2.F is being updated to reflect the enclosed deviation.
TVA has evaluated whether or not a significant hazards consideration is involved with the proposed amendment by focusing on the three standards set forth in 10 CFR 50.92, "Issuance of amendment," as discussed below:
- 1.
Does the proposed amendment involve a significant increase in the probability or consequences of an accident previously evaluated?
Response: No.
A fire hazards analysis was performed for the areas under the scope of this amendment. This fire hazards analysis demonstrates that one train of safe shutdown equipment will remain functional in the event of an Appendix R fire, even though a radiant energy shield will not be provided for two raceway containing safe shutdown circuits.
Therefore, the proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2.
Does the proposed amendment create the possibility of a new or different kind of accident from any accident previously evaluated?
Response: No.
A fire hazards analysis was performed for the areas under the scope of this amendment. This fire hazards analysis demonstrates that one train of safe shutdown equipment will remain functional in the event of an Appendix R fire, even though a radiant energy shield will not be provided for two raceway containing safe shutdown circuits. Based on this, the proposed amendment will not alter the requirements or function for systems required during accident conditions.
Therefore, the proposed change does not create the possibility of a new or different kind of accident from any accident previously evaluated.
- 3.
Does the proposed amendment involve a significant reduction in a margin of safety?
Response: No.
CNL-15-252 E-6 of 21 A fire hazards analysis was performed for the areas under the scope of this amendment. This fire hazards analysis demonstrates that one train of safe shutdown equipment will remain functional in the event of an Appendix R fire, even though a radiant energy shield will not be provided for two raceway containing safe shutdown circuits.
Therefore, the proposed change does not involve a significant reduction in a margin of safety.
Based on the above, TVA concludes that the proposed amendment does not involve a significant hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a finding of "no significant hazards consideration" is justified.
4.4 Conclusions In conclusion, based on the considerations discussed above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commissions regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
5.0 ENVIRONMENTAL CONSIDERATION
A review has determined that the proposed amendment would not change a requirement with respect to installation or use of a facility component located within the restricted area, as defined in 10 CFR 20, or would change an inspection or surveillance requirement. The proposed amendment does not involve (i) a significant hazards consideration, (ii) a significant change in the types or significant increase in the amounts of any effluents that may be released offsite, or (iii) a significant increase in individual or cumulative occupational radiation exposure.
Accordingly, the proposed amendment meets the eligibility criterion for categorical exclusion set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the proposed amendment.
6.0 REFERENCES
- 1.
TVA letter to NRC, CNL-15-009, Watts Bar Nuclear Plant Unit 1 - Resolution of Generic Safety Issue 191, dated April 17, 2015 (ML15111A065)
- 2.
NRC letter to TVA, Watts Bar Nuclear Plant, Unit 1, Closeout of Generic Letter 2004-02, Potential Impact of Debris Blockage on Emergency Recirculation During Design Basis Accidents at Pressurized-Water Reactors (TAC No. MC4730), dated September 17, 2015 (ML15191A183)
CNL-15-252 E-7 of 21 Proposed Change to Operating License Condition 2.F (Mark-Up) for WBN Unit 1 (For the following mark-up, deletions are shown as strikethrough text and additions are shown as bold text.)
CNL-15-252 E-8 of 21 5a F.
TVA shall implement and maintain in effect all provisions of the approved fire protection program as described in the Fire Protection Report for the facility, as approved in Appendix FF Section 3.5 of Supplement 18 and Supplement 29 of the SER (NUREG-0847) and in Amendment No. ZZZ subject to the following provision:
TVA may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
G.
Deleted H.
The licensee shall have and maintain financial protection of such types and in such amounts as the Commission shall require in accordance with Section 170 of the Atomic Energy Act of 1954, as amended, to cover public liability claims.
Amendment 87 88 90 105 ZZZ
CNL-15-252 E-9 of 21 Proposed Change to Operating License Condition 2.F (Final Typed) for WBN Unit 1
CNL-15-252 E-10 of 21 5a F.
TVA shall implement and maintain in effect all provisions of the approved fire protection program as described in the Fire Protection Report for the facility, as approved in Appendix FF Section 3.5 of Supplement 18 and Supplement 29 of the SER (NUREG-0847) and in Amendment No. ZZZ subject to the following provision:
TVA may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
G.
Deleted H.
The licensee shall have and maintain financial protection of such types and in such amounts as the Commission shall require in accordance with Section 170 of the Atomic Energy Act of 1954, as amended, to cover public liability claims.
Amendment 87 88 90 105 ZZZ
CNL-15-252 E-11 of 21 Proposed Revision to the Watts Bar Dual Unit Fire Protection Report and Appendix R Deviation Request
CNL-15-252 E-12 of 21 2.9.22 RI - Unit 1 Reactor Building Inside Crane Wall [RI-1 (0° to 90°), RI-2 (90° to 180°), RI-3 (180° to 270°), RI-4 (270° to 360°)]
2.9.22.1 Description of Condition This area of the Unit 1 Reactor Building is the part of fire area 61 (see Part III, Table 3-3 for room listing) that is inside the Crane Wall and is analyzed in analysis volumes AV-92H, AV-92J, AV-92K and AV-92L. Fire area 61 is considered a III.G.2 area. The Fire Safe Shutdown (FSSD) analysis of this room, based on the assumption that all the cables and equipment in the room failed due to postulated fire damage, relied on physical separation and radiant energy shields (RES) to protect cables and achieve III.G.2 cable separation and included an Operator Manual Action (OMA). The following OMA and radiant energy shields were credited to ensure fire safe shutdown.
- a. Open Residual Heat Removal (RHR) isolation valve via hand wheel in preparation to transition to cold shutdown.
- b. Protect Reactor Coolant Pump (RCP) loop 1 and 3 hot and cold leg temperature monitoring cables with radiant energy shields.
- c. Protect pressurizer Power Operated Relief Valve (PORV) cable with radiant energy shields.
- d. Protect Reactor Head Vent isolation and throttle valves cables with radiant energy shields.
The RES is 3M M20C which is a fibrous material with a stainless steel foil backing that poses some concern for reactor building sump filter blockage. Therefore, for conservatism, this material is being removed from that portion of the Unit 1 Reactor Building inside the Crane Wall. This area is designated as RI and the fire safe shutdown analysis is documented in Part VI of the Fire Protection Report.
Appendix R, section III.G.1 states:
Fire protection features shall be provided for structures, systems, and components important to safe shutdown. These features shall be capable of limiting fire damage so that:
- a. One train of systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergency control station(s) is free of fire damage; and
- b. Systems necessary to achieve and maintain cold shutdown from either the control room or emergency control station(s) can be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
A fire hazards analysis (Section 2.9.22.2) of each of the analysis volumes of RI determined that equipment required for fire safe shutdown are adequately separated from each other in accordance with III.G.2.d criteria, except in quadrant RI-2. In this quadrant some of the circuits for redundant equipment are routed in conduits that are not adequately separated from each other (e.g., hot and cold leg temperature instrumentation) and are protected with radiant energy shields in accordance with III.G.2.f. As described below, the fire hazards analysis determined there is no credible ignition source or concentration of combustibles in the vicinity of these
CNL-15-252 E-13 of 21 conduits that could cause fire damage to these circuits. Therefore, at least one train of systems necessary to achieve and maintain hot shutdown conditions would not be damaged by any credible postulated fire. Because there is no credible fire that could damage these circuits routed in conduit, the radiant energy shields are not necessary and can be removed to eliminate this potential sump filter blockage concern.
2.9.22.2 Fire Hazards Analysis 2.9.22.2.a Room Description The area of the Unit 1 Reactor Building inside the Crane Wall is designated as RI and is separated from adjacent areas of the Unit 1 Reactor Building by reinforced concrete barriers that are 30 to 48-inches thick. These barriers are not assigned a fire resistance rating and contain electrical and mechanical penetrations that are not provided with fire rated seals/closures. The room has a floor area of 3,656-ft2 and a ceiling height of 40-feet to 51-feet.
This area is divided into four quadrants (RI-1, RI-2, RI-3 and RI-4), each of these contains an RCP and associated steam generator.
2.9.22.2.b Fire Load The combustible loading for RI is Low with the RCP lubricating oil being most of the combustible load. The remainder of the in situ combustible load consists of insulation on cables in trays and small quantities of plastics associated with small control panels, telephones and junction boxes. There is a Steam Generator (SG), an RCP and a Control Rod Drive Mechanism (CRDM) cooler located in each quadrant. Each RCP is provided with an oil collection system (per Appendix R,Section III.O - See FPR Part VII, Section 2.8) and detection and automatic suppression. A postulated fire on an RCP would be detected by the detection system which would activate the suppression system and alarm in the Main Control Room.
A CRDM cooler unit consists of a plenum, three air cooling coils and two vane axial fans and their motors. Each unit is designed to seismic category I(L) criteria. A postulated fire in a CRDM cooler unit would be very small and contained within the unit. Therefore, the lack of combustibles associated with the unit provides assurance that no components outside the unit would be damaged.
None of the other combustible materials in RI are associated with an ignition source. The ignition sources in the area are insignificant, (Motor Operated Valve [MOV] motors are not considered ignition sources - see 2.9.0 above) and would not propagate beyond themselves, except the RCPs. The only credible ignition sources are the RCPs, which in addition to being provided with Section III.O oil collection systems, are protected by suppression and detection systems. In addition, a standpipe in each RI quadrant is available for fire brigade use. The RCP oil collection system and automatic suppression for each RCP prevent an RCP from being a significant hazard and the lack of credible ignition sources and the small amounts of in situ combustibles provides assurance that no credible fire in one quadrant of RI would propagate into another quadrant of RI. There is no credible fire in RI that could propagate from RI into an adjacent area of the Unit 1 Reactor Building.
CNL-15-252 E-14 of 21 2.9.22.2.c Control of Combustibles and Ignition Sources NPG-SPP-18.4.7, Control of Transient Combustibles and NPG-SPP-18.4.8, Control of Ignition Sources (Hot Work), define the fire preventive measures to preclude introduction of significant quantities of combustible material or ignition sources into RI. Compensatory measures must be implemented when transient combustibles or ignition sources are brought into a room due to work activities. Access to the room is from Reactor Instrument Room (RIR) via a ladder down to the area outside the Crane Wall (RO) and through the Crane Wall into RI.
When Unit 1 is operating, access to the reactor building is strictly controlled. Prior to returning the unit to operation, transient material that might have been brought into the room is removed.
The lack of in situ combustible material and ignition sources and the controls for transient combustibles and ignition sources in combination provide assurance that no credible exposure fire would occur in RI that could damage components in the room or propagate into an adjacent room or from one quadrant of RI into an adjacent quadrant. Based on this, no credible fire can cause the plant to enter the fire safe shutdown procedure.
2.9.22.2.d Adjacent Rooms Accumulator Room 1 (RA1) is separated from RI-1 by a 36 to 48 inch thick reinforced concrete wall. Conduit, instrumentation lines and mechanical piping penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RA1 is low and is comprised of small quantities of lubricant in valves, expansion joint material and small quantities of plastics associated with electrical control panels, junction boxes and telephones.
The lack of credible ignition sources and concentrations of in situ combustibles provides assurance that no credible fire in RA1 could propagate into RI-1 through the unprotected penetrations.
Accumulator Room 2 (RA2) is separated from RI-2 by a 36 to 48 inch thick reinforced concrete wall. Conduit, instrumentation lines and mechanical piping penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RA2 is low and is comprised of small quantities of lubricant in valves, and small quantities of plastics associated with electrical control panels, junction boxes, and telephones. The lack of credible ignition sources and concentrations of in situ combustibles provides assurance that no credible fire in RA2 could propagate into RI-2 through the unprotected penetrations.
Accumulator Room 3 (RA3) is separated from RI-3 by a 36 to 48 inch thick reinforced concrete wall. Conduit, instrumentation lines and mechanical piping penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RA3 is low and is comprised of small quantities of lubricant in valves, and small quantities of plastics associated with electrical control panels, junction boxes, cable insulation, and telephones. The lack of credible ignition sources and concentrations of in situ combustibles provides assurance that no credible fire in RA3 could propagate into RI-3 through the unprotected penetrations.
Accumulator Room 4 (RA4) is separated from RI-4 by a 36 to 48 inch thick reinforced concrete wall. Conduit, instrumentation lines and mechanical piping penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RA4 is low and is comprised of small quantities of lubricant in valves and small quantities of plastics associated with electrical control panels, junction boxes, flex conduit, and telephones. The lack of credible ignition sources and concentrations of in situ combustibles provides assurance that no credible fire in RA4 could propagate into RI-4 through the unprotected penetrations.
CNL-15-252 E-15 of 21 Fan Room 1 (RF1) is separated from RI-1 and RI-4 by a 36 inch thick reinforced concrete wall.
Conduit, instrumentation lines, mechanical piping and ventilation openings penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RF1 is insignificant and is comprised of small quantities of lubricant in valves, and small quantities of plastics associated with electrical control panels, junction boxes, and telephones. Transient combustibles are not considered since the access to RF1 is strictly controlled during unit operation and any transient material brought in during an outage is removed prior to unit startup. Therefore, due to the insignificant combustible load and lack of credible ignition sources, there is no credible fire in RF1 that could propagate into RI-1 or RI-4 or from RI-1 or RI-4 into RF1.
Fan Room 2 (RF2) is separated from RI-2 and RI-3 by a 36 inch thick reinforced concrete wall.
Conduit, instrumentation lines, mechanical piping and ventilation openings penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RF2 is insignificant and is comprised of small quantities of lubricant in valves, and small quantities of plastics associated with electrical control panels, junction boxes, and telephones. Transient combustibles are not considered since the access to RF2 is strictly controlled during unit operation and any transient material brought in during an outage is removed prior to unit startup. Therefore, due to the insignificant combustible load and lack of credible ignition sources, there is no credible fire in RF2 that could propagate into RI-2 or RI-3 or from RI-2 or RI-3 into RF2.
The Unit 1 Reactor Building Instrument Room (RIR) is separated from RI-1 and RI-2 by a 36 inch thick reinforced concrete wall. Conduit, instrumentation lines and mechanical piping penetrate the wall and are not provided with fire rated penetration seals. The in situ combustible load in RIR is insignificant and is due to small quantities of lubricant in valves, and small quantities of plastics associated with electrical control panels, terminal/junction boxes/assemblies, and telephones. Transient combustibles are not considered since the access to RIR is strictly controlled during unit operation and any transient material brought in during an outage is removed prior to unit startup. Therefore, due to the insignificant combustible load and lack of credible ignition sources, there is no credible fire in RIR that could propagate into RI-1 or RI-2 or from RI-1 or RI-2 into RIR.
RO is separated from RI by 36 to 48 inch thick non-fire rated reinforced concrete Crane wall.
The Crane Wall contains electrical and mechanical openings that are not provided with fire rated seals/closures. There is a personnel access opening through RO from RO-3 into RI-3.
The in situ combustible load in RO is low of which the expansion joint seal material accounts for 86% of the load and small quantities of lubricant in valves and small quantities of plastics associated with electrical control panels, terminal/junction boxes/collectors, and telephones.
Only the edge of the expansion joint seal is exposed, the rest is between concrete walls. The lack of exposed in situ combustibles and credible ignition sources provides assurance that no credible fire in RO could propagate into RI via this personnel access opening or these penetrations. Access to the reactor building is strictly controlled during operation and transient material brought into the reactor building for outage work is removed prior to start-up; therefore, there is no fire hazard from transient material. Therefore there is no credible fire in RO that could propagate into RI or from RI into RO.
CNL-15-252 E-16 of 21 Upper Containment (RU) is separated from RI by a 24 inch thick reinforced concrete floor.
Conduit, instrumentation lines and mechanical piping penetrate the floor and are not provided with fire rated penetration seals or closures. The in situ combustible load in RU is moderate and is due to small quantities of foam insulation, lubricant in valves, the crane and small quantities of plastics associated with electrical control panels, junction boxes, and cranes. Due to the lack of credible ignition sources and insignificant concentrations of in situ combustibles, there is no credible fire in RU could propagate into RI or from RI into RU.
Due to the lack of significant concentrations of in situ combustible material and credible ignition sources and the controls for transient combustibles and ignition sources, no credible exposure fire would occur that could propagate from RI into an adjacent room or from an adjacent room into RI.
2.9.22.3 System Evaluation 2.9.22.3.a Redundant Components in the Room Protected with Radiant Energy Shield The RI is made up of four quadrants (RI-1, RI-2, RI-3 and RI-4) with an RCP and an SG and associated components in each. Any two SGs provide adequate decay heat removal capability.
Each SG has one RCS hot leg (Thot) and one cold leg (Tcold) temperature indication. The cables associated with these indicators for SG#1 are routed in RI-1 and RI-2. The cables for SG#2 are routed in RI-2. The cables for SG#3 are routed in RI-3. The cables for SG#4 are routed in RI-4. For a fire in quadrant RI-1 or RI-4, SG#2 and SG#3 are credited. For a fire in quadrant RI-3, SG#1 and SG#4 are credited. For a fire in quadrant RI-2, SG#3 and SG#4 are credited. The cables for SG#3 RCS Thot and Tcold are located within RI-3 and are at least 7 feet and 11 inches from the RI-2 quadrant. The lack of credible ignition sources and combustible material in the route of these circuits provides assurance that a fire in quadrant RI-2 would not fail SG#3 hot leg and cold leg temperature indication. Additionally for a fire on the boundary between RI-2 and RI-3 the cables associated with SG#1 RCS hot leg and cold leg are horizontally separated from SG#3 hot leg and cold leg temperature by at least 17 feet and 11 inches such that a fire affecting SG#3 would not also affect SG#1. Since only two sets of SG temperature indications are required this meets the requirements for fire safe shutdown.
Therefore, neither operator manual actions nor radiant energy shields are needed to provide adequate SG Thot and Tcold indication in the control room.
The water level in each SG is monitored by three narrow range level transmitters and one wide range level transmitter. Additionally two flow indicators monitor the auxiliary feedwater (FW) flow to each SG. The flow indicators, transmitters, cables and sense lines are not located in reactor building. The level transmitters for SG#1 and SG#4 (south side) are located in RF1 and the level transmitters for SG#2 and SG#3 (north side) are located in RF2. For a fire in quadrant RI-1 or RI-4, SG#2 and SG#3 are credited. The cable for SG#2 Narrow Range (NR) level transmitter (1-LT-3-52) and SG#3 NR level transmitter (1-LT-3-94) are located in RF2 and the sense lines associated with the level transmitters are routed in the north portion of RI (RI-2 & RI-3) and will not be affected by a fire in the south portion of RI (RI-1 or RI-4). For a fire in quadrant RI-3, SG#1 and SG#4 are credited. The cable for SG#1 NR level transmitter (1-LT-3-38) and SG#4 NR level transmitter (1-LT-3-106) are located in RF1 and sense lines associated with the level transmitter are routed in the south portion of RI (RI-1 & RI-4) and will
CNL-15-252 E-17 of 21 not be affected by a fire in quadrant RI-3. For a fire in RI-2, SG#3 and SG#4 are credited. The cable for SG#3 NR level transmitter (1-LT-3-94) is located in RF2 and the sense line is routed in quadrant RI-3 (approximately AZ 200) and will not be affected by a fire in quadrant RI-2.
The cable for SG#4 NR level transmitter (1-LT-3-106) is located in RF1 and sense line associated with the level transmitter is routed in the south portion of RI and will not be affected by a fire in quadrant RI-2. Since level indication in the control room is assured for two SGs, this meets the fire safe shutdown requirements without the need for operator manual actions or radiant energy shields. In addition, based on the minimal fire hazards described in 2.9.22.2, there is no credible fire in RI that could adversely impact the level indication for the credited steam generators.
The pressurizer spray valves are normally closed and fail closed on loss of signal or air. The modulating signal cable from each pressurizer spray valve is routed in conduit through RI. One spray valve cable is routed by itself in dedicated conduit. The only failure that could spuriously open the other spray valve is a double cable-to-cable hot short (plus-to-plus and minus-to-minus) without grounding between two twisted shielded pair instrument cables in conduit. The fire hazards analysis (2.9.22.2) concludes that due to the minimal combustible load and no ignition sources such a failure is not credible. In addition, if the spray valves could spuriously open, the main control room operator trips the RCPs to stop flow through the spray valves.
Therefore, there is no need for operator manual actions or radiant energy shields for closure of the pressurizer spray valves.
Each RCP seal leakoff valve and its cables are located in the quadrant with its associated RCP. The valves are air operated, normally open, solenoid controlled valves that fail open on loss of air or 125v DC electrical power and their fire safe shutdown desired position is open.
The only fire induced failure that could energize the solenoid to close one of these valves would be a cable-to-cable hot short to cables with thermoset insulation. There is insignificant in situ combustible loading and no credible ignition sources in the room (see 2.9.22.2).
Therefore, there is no fire hazard that could damage circuits and spuriously energize each RCP seal leakoff valve. For additional defense in depth, even if a postulated fire could cause the valve to spuriously close, the operator would close the reactor building nonessential control air header isolation valve and open the header dump solenoid valves from the main control room, thereby reducing the control air header pressure which would open the valve. Therefore, there is no need for operator manual actions or radiant energy shields to assure each RCP seal leakoff valves remain open.
Redundant channel source range neutron detector and indication cables are routed in RI. The cables are horizontally separated in excess of 20 feet (10 CFR 50 Appendix R, Section III.G.2.d). Therefore, even if there could be a fire of sufficient magnitude to damage one channel, the other channel could not be damaged based on physical separation.
For Top of Pressurizer Cavity: The train A and train B PORVs and their associated block valves are located on top of the pressurizer in RI. The train A cables and train B cables are routed in separate conduits in opposite directions away from the pressurizer. Fire damage to a PORV or its cables at the top of the pressurizer could disable the valve, but would not spuriously open the valve. The head vent valves whose cables are routed in conduit greater than 17 feet outside of the pressurizer cavity or outside of RI are operable to depressurize the RCS if needed. Based on the minimal fire loading and no credible ignition sources near the pressurizer, concurrent fire damage to the PORVs and their associated block valves and the
CNL-15-252 E-18 of 21 head vent valve cables is not considered credible. In addition, power is removed from the head vent valve circuits during normal plant operation to prevent spuriously opening of the PORVs.
For Outside of Pressurizer Cavity: The only potential PORV spurious operation outside the pressurizer cavity is for the Train A PORV. Train A PORV cable 1V1207A (with thermoset insulation) and RCS letdown control valve energized cable 1V4426A (with thermoset insulation) are installed in 1-JB-293-6347-A and conduit 1VC4057A that are located within 20 feet of the pressurizer cavity and provide a potential for hot short source which could spuriously open the PORV. Based on the minimal fire loading and no credible ignition sources outside the pressurizer cavity and the thermoset insulation on both the source and target cables, spurious opening of the Train A PORV is not considered credible.
Both RCS normal letdown flow control valves and associated cables are located in RI-2.
These are normally open air operated valves that fail closed on loss of air or 125vdc electrical power. The desired position for FSSD is closed. There is no fire hazard that could damage circuits and spuriously energize both valve circuits. For additional defense in depth, if both valves are assumed to fail to close, the operator will isolate and depressurize the Unit 1 reactor building non-essential control air header from the main control room, thereby causing the valves to close. Operator manual actions or radiant energy shields are not needed to provide normal letdown.
The pressurizer level transmitter sense lines originate near the top of the pressurizer and travel to the RIR. The sense lines from the tap on the pressurizer to the bellows (located outside of the pressurizer enclosure) consist of two parts. The parts are rigid tubing and flex hose (for thermal expansion/contraction). The flex hose is American Society of Mechanical Engineers (ASME)Section III, class 2 flex hose assembly metal bellows. The rigid tubing is ASME Section III, class 2, schedule 160 welded stainless steel. The sense lines have horizontal separation at the taps in excess of four feet and they are located more than forty feet above the floor. Based on the minimal fire loading and no credible ignition sources near the pressurizer, the design of the instrument sense lines utilizing only non-combustible material, the separation between the sense lines and the large distance from the floor of the pressurizer enclosure, fire damage to the sense lines is not considered credible. Operator manual actions or radiant energy shields are not needed for fire safe shutdown.
One CRDM is located in each of the four quadrants along with a temperature control damper and a temperature control valve to regulate the amount of cooling provided by the cooler.
Containment cooling is also provided by the four lower compartment coolers (LCCs) located in RF1 and RF2. Three LCCs alone or two LCCs and two CRDMS provide adequate containment cooling. The CRDMs and two out of four LCCs temperature sensing element (thermocouple) cables are routed in RI. Based on the limited fire hazard (2.9.22.2) there is no credible fire that could damage these temperatures sensing cables. Even if they could be damaged, the most likely failure mode is a conductor to conductor short within the 2-conductor thermocouple extension wire cable which creates a new thermocouple junction in a hot environment resulting in a higher cooling demand and the valve opens as desired. In quadrant RI-1, LCC 1B-B and CRDM 1B-B along with LCC 1C-A and CRDM 1C-A whose temperature sensing element cables are routed in RI-1 provides the needed containment cooling. In quadrant RI-2 either three LCCs or two LCCs and two CRDMs will provide the containment cooling since the cable for LCC 1A-A is separated from the cable for CRDM 1C-A by greater than 10 feet. In quadrant RI-3 LCCs 1A-A and 1B-B along with LCC 1CA, whose temperature sensing element cable is routed in RI-3, provides the needed containment cooling. In quadrant RI-4, LCC 1A-A and 1B-B along with LCC 1C-A, whose temperature sensing element cable is
CNL-15-252 E-19 of 21 routed in RI-4, provides the needed containment cooling. Operator manual actions or radiant energy shields are not needed to provide fire safe shutdown.
Each train of the Auxiliary Control Air System (ACAS) supplies one component (pressurizer spray valve) located in RI. These two ACAS air users are horizontally separated by at least 8 feet. Based on the limited fire hazard (2.9.22.2) there is no credible fire that could damage both ACAS headers. At least one train of ACAS is available. Even with the loss of an ACAS header the pressurizer spray valve would fail closed, which is the FSSD desired position. A failure of an ACAS header inside the reactor building can be isolated by closing their containment isolation valves from the main control room and thereby ensuring the ACAS is available to operate equipment in the auxiliary building. Operator manual actions or radiant energy shields are not needed to provide fire safe shutdown.
2.9.22.3.b FSSD Components with Redundant FSSD Components in an Adjacent Room within the Same Analysis Volume The RHR system piping is isolated from the RCS by two opposite train motor operated isolation valves in series. Each of the isolation valves has a by-pass valve of the opposite train. One set (main isolation valve and its opposite train by-pass valve) of RHR isolation valves are located in RI-4 and its redundant set is located in RA4. Cables for the train A main isolation valve and its train B by-pass valve are routed in separate conduits through RI. The valves of one set must remain closed to achieve and maintain hot shutdown. This is ensured by removing power from the valves in both trains during normal plant operation. For RHR operation (cold shutdown) one valve of each set must be opened. The performance of an OMA (2.9.20.1.a) is credited in the FSSD analysis to manually open one of the valves in RI-4 before containment became uninhabitable due to reactor coolant accumulation resulting from letdown through the PORV. As discussed in the fire hazard analysis (2.9.22.2), the combustible loading and ignition sources in RI are insufficient to create fire damage that results in entry into the fire safe shutdown procedures. Therefore, the OMA to open one of the RHR isolation valves is not necessary.
2.9.22.3.c Other FSSD Components in the Room Room RI contains FSSD cables associated with FSSD equipment relied upon for fires in other areas of the plant (i.e., equipment and cables not credited for a fire in Room RI). The following cables are routed in conduit.
Reactor building sump level transmitter cable (input to RHR to sump isolation valve circuits)
Turbine Driven Auxiliary Feedwater SG #2 and #4 level transmitter cables Pressurizer heater cables Reactor coolant pump motor cables Reactor coolant system hot leg temperature auxiliary control room cables Although no fire induced failures are expected due to the insignificant fire hazards in RI, postulated failure of the not-credited FSSD cables has been evaluated to assess its effect on plant operation. Failure of these FSSD cables is detected and mitigated by normal plant procedures and would not prevent a fire safe shutdown.
CNL-15-252 E-20 of 21 2.9.22.4 Conclusion There is insignificant threat from transient combustibles, in situ combustible material, or credible ignition sources in Unit 1 RI. A credible fire would not cause loss of the station control air system, or damage equipment/cables and prevent FSSD for a fire in RI. There is no fire hazard in RI that necessitates any OMA or warrants protecting electrical raceways (conduits and junction boxes) with radiant energy shields. TVA concludes that a deviation from the prescriptive separation criteria of III.G.2 is acceptable because the intent of III.G.1 is assured by a fire hazards analysis.
CNL-15-252 E-21 of 21 PART VII - DEVIATIONS AND EVALUATIONS DEVIATION - For the purpose of addressing operator manual actions (OMAs), electrical raceway fire barrier systems (ERFBS) and radiant energy shields (RES), the rooms listed in the following table demonstrate compliance with the intent of Section III.G.1 by a fire hazards analysis with no OMA, ERFBS or RES in lieu of the prescriptive separation criteria described in Section III.G.2.
SECTION ROOM NUMBER 2.9.1 692.0-A29 & 692.0-A30 2.9.2 729.0-A1 & 737.0-A6 2.9.3 729.0-A2 2.9.4 729.0-A6 2.9.5 729.0-A10 2.9.6 729.0-A11 & 737.0-A10 2.9.7 729.0-A12 2.9.8 729.0-A13 2.9.9 729.0-A15 & 763.5-A2 2.9.10 757.0-A13 2.9.11 757.0-A14 2.9.12 757.0-A15 2.9.13 2RIR 2.9.14 2RA1 2.9.15 2RA2 2.9.16 2RA3 2.9.17 2RA4 2.9.18 2RF1 2.9.19 2RF2 2.9.20 2RI (2RI-1, 2, 3, 4) 2.9.21 2RO (2RO-1, 2, 3, 4) 2.9.22 RI-1, RI-2, RI-3, RI-4 JUSTIFICATION - A fire hazards analysis (FHA) as documented below has been performed for each of the rooms listed in the above table and is provided here for NRC review and approval. The FHA has been performed in accordance with the guidelines of GL 86-10. When a barrier is identified as a rated fire barrier, the penetrations through that barrier are rated for the barrier and are maintained by appropriate engineering design and maintenance programs (e.g. fire doors, fire dampers, and penetration seal programs [Part II, Reference 4.2.48, 4.2.44, 4.2.49, 4.2.34, 4.2.35, and 4.2.67]). The combustible loading information is derived from the Combustible Loading calculation (Part II, Reference 4.2.10) and the fire rated barriers are documented on the Fire Protection Compartmentation drawings (Part II, Reference 4.2.39).
VII-21