MONTHYEARML24292A1832024-10-30030 October 2024 Summary of Meeting with Tennessee Valley Authority, October 16, 2024, to Discuss Proposed License Amendment Regarding Implementation of an Online Monitoring Methodology ML24269A0062024-10-0303 October 2024 Correction to Summary of August 19, 2024, Meeting with Tennessee Valley Authority Regarding a Proposed Supplement to the TVA Nuclear Quality Assurance Plan ML24262A0602024-09-23023 September 2024 Summary of August 19, 2024, Meeting with Tennessee Valley Authority Regarding a Proposed Supplement to the Tennessee Valley Authority Nuclear Quality Assurance Plan ML24228A2652024-08-20020 August 2024 Summary of Public Pre-Submittal Meeting with Tennessee Valley Authority Regarding a Future Sequoyah Nuclear Plant and Watts Bar Nuclear Plant LAR Related to TS 3.5.2. ECCS - Operating ML24221A0132024-08-19019 August 2024 July 10, 2024, Summary of Meeting with Tennessee Valley Authority Regarding a Proposed Change to the Tennessee Valley Authority Nuclear Quality Assurance Plan ML24173A2122024-06-27027 June 2024 Summary of Public Meeting with Tennessee Valley Authority to Discuss a Proposed License Amendment Request Regarding Adoption of TSTF-276-A, Revision 2 to Clarify Requirements for Diesel Generator Testing ML24158A3002024-06-11011 June 2024 Summary of May 6, 2024, Public Meeting with Tennessee Valley Authority to Discuss the Potential for a License Amendment Request Regarding the Control Room Envelope and Selective Use of an Alternative Source Term ML24089A0712024-04-0101 April 2024 3/20/24 & 3/27/24 2023 TVA Public Annual Assessment Meeting Summary ML24057A0582024-02-27027 February 2024 Summary of February 15, 2024, Public Meeting with Tennessee Valley Authority Regarding Proposed License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML24008A1592024-01-18018 January 2024 Summary of December 13, 2023, Meeting with Tennessee Valley Authority Regarding a Proposed Change to the Tennessee Valley Authority Nuclear Quality Assurance Plan ML23304A0682023-11-0606 November 2023 Summary of October 24, 2023, Public Mtg W/Tennessee Valley Authority Regarding Proposed License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2, and Sequoyah Nuclear Plant, Units 1 and 2 to Revise Function 5, Turbine Trip and F ML23265A1512023-09-28028 September 2023 Summary of September 12, 2023, Partially Closed Meeting with Tennessee Valley Authority to Discuss Proposed License Amendment Request ML23198A3102023-07-20020 July 2023 July 10, 2023, Summary of Public Meeting with Tennessee Valley Authority Regarding Proposed License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML23142A2132023-05-22022 May 2023 Public Meeting Summary - 2022 Annual Assessment Meetings for Browns Ferry, Sequoyah and Watts Bar Nuclear Plants ML23068A1532023-03-16016 March 2023 Summary of February 22, 2023, Meeting with Tennessee Valley Authority Regarding Proposed License Amendment Request to Increase Allowable Number of Tritium Producing Burnable Absorber Rods at Watts Bar Nuclear Plant, Units 1 and 2 ML23055A4562023-03-0909 March 2023 Summary of February 15, 2023, Public Meeting with Tennessee Valley Authority Regarding Proposed Expedited License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML22329A1382022-12-0505 December 2022 Summary of Meeting with Tennessee Valley Authority Related to Planned Alternative Request WBN-2-ISI-01 for Watts Bar Nuclear Plant, Unit 2 ML22168A1642022-06-27027 June 2022 Summary of June 9, 2022, Meeting with TVA Regarding a Proposed License Amendment Request Related to Low Temperature Overpressure System and Cold Overpressure Mitigation System for Sequoyah and Watts Bar Nuclear Plants ML22104A2252022-04-20020 April 2022 Summary of Meeting with Tennessee Valley Authority Regarding a Proposed Exemption Request for Watts Bar Nuclear Plant, Unit 2 ML22109A0042022-04-20020 April 2022 Summary of Meeting with Tennessee Valley Authority Regarding a Proposed Alternative Request Related to Testing of the Motor-Driven Auxiliary Feedwater Pumps at Sequoyah and Watts Bar Nuclear Plants ML22108A1842022-04-18018 April 2022 TVA 2021 Annual Assessment Public Meeting Summary ML22042B3262022-02-14014 February 2022 Summary of February 8, 2022, Meeting with Tennessee Valley Authority Regarding a Proposed License Amendment Request to Revise the Allowable Value for Trip of Turbine-Driven Main Feedwater Pump at Watts Bar Nuclear Plant, Unit 1 ML22025A3112022-02-0909 February 2022 Summary of January 19, 2022, Meeting with Tennessee Valley Authority Regarding a Proposed Schedule for Development of a License Amendment Request for Increased Tritium Production ML21349A3642022-01-0404 January 2022 Summary of December 14, 2021, Teleconference with Tennessee Valley Authority Regarding a Proposed Change to the Capsule Withdrawal Schedule for Watts Bar Nuclear Plant, Unit 2 ML21279A0902021-11-0303 November 2021 Summary of Conference Calls Regarding the Fall 2021, Mid-Cycle Steam Generator Tube Inspections ML21291A0092021-11-0303 November 2021 Tennessee Valley Authority Fleet - Summary of October 13, 2021, Teleconference with Tennessee Valley Authority to Discuss Planned License Amendment Requests Related to the Emergency Action Level Scheme ML21253A0872021-09-15015 September 2021 Summary of August 19, 2021, Partially Closed Meeting with Tennessee Valley Authority to Discuss Mid-Cycle Outage Contingencies for Watts Bar Nuclear Plant, Unit 2 ML21245A4252021-09-15015 September 2021 Summary of August 19, 2021, Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Request Related to the Watts Bar Nuclear Plant, Units 1 and 2 ML21165A1482021-06-30030 June 2021 Summary of Closed Meeting with Tennessee Valley Authority to Discuss Planned Requests for Exemption from Certain Requirements of 10 CFR Part 37 ML21137A0022021-05-17017 May 2021 Public Meeting Summary - Browns Ferry, Sequoyah and Watts Bar Nuclear Plants, Docket Nos. 50-259, 50-260, 50-296, 50-327, 50-328, 50-390, and 50-391, Meeting Number 20210392 ML21120A2192021-05-0404 May 2021 April 28,2021, Summary of Meeting with Tennessee Valley Authority Related to a Planned License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2, to Remove from Technical Specifications Redundant Units of Measurement for Control ML21099A2072021-04-13013 April 2021 Summary of April 7, 2021, Meeting with Tennessee Valley Authority Related to a Planned Relief Request from ASME Code Testing Requirements ML21060B0532021-03-0303 March 2021 Summary of February 11, 2021, Meeting with Tennessee Valley Authority Related to a Planned License Amendment Request for Watts Bar Nuclear Plant, Unit 2, to Apply a Temperature Adjusted Steam Generator Tube Flaw Growth Rate Methodology ML21033A5952021-02-23023 February 2021 Summary of Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Requests Related to the Watts Bar Nuclear Plant, Unit 2 Steam Generator Replacement ML20351A4212021-01-19019 January 2021 Summary of Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Requests Related to the Watts Bar, Unit 2, Steam Generator Replacement ML20357A0092021-01-19019 January 2021 Summary of December 17, 2020, Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Request Related to Use of Alternate Probability of Detection at Watts Bar Nuclear Plant, Unit 2 ML20351A2192021-01-11011 January 2021 Summary of Conference Calls Regarding the Fall 2020 Steam Generator Tube Inspections ML20337A0402020-12-15015 December 2020 Summary of November 17, 2020, Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Request for Technical Specification 5.9.9, Steam Generator Tube Inspection Report ML20323A0662020-11-27027 November 2020 Summary of October 28, 2020, Teleconference with Tennessee Valley Authority Regarding Planned License Amendment Request for Technical Specification Surveillance Requirement 3.6.15.4, Shield Building ML20244A1892020-09-11011 September 2020 Summary of Teleconference Call with Tennessee Valley Authority Regarding a Proposed Change to the Containment Leakage Rate Testing Program ML20233A8352020-08-25025 August 2020 Summary of August 11, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML20213C7112020-08-25025 August 2020 Summary of July 28, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned Alternative Request for Watts Bar Nuclear Plant, Unit 1 ML20175A8012020-08-11011 August 2020 Summary of June 23, 2020, Public Meeting with Tennessee Valley Authority to Discuss a Planned License Amendment ML20211L8222020-08-10010 August 2020 Summary of Teleconference Call with the Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Unit 1 ML20150A4162020-06-24024 June 2020 Summary of May 28, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Unit 1 ML20153A3622020-06-22022 June 2020 Summary of May 27, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML20135H2702020-05-28028 May 2020 Summary of May 5, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 ML20143A1692020-05-28028 May 2020 Summary of May 14, 2020, Teleconference Call with Tennessee Valley Authority Regarding a Planned License Amendment Request for Watts Bar Nuclear Plant, Unit 2 ML20127H8412020-05-0606 May 2020 Public Meeting Summary - Browns Ferry, Sequoyah and Watts Bar Nuclear Plant, Meeting No. 20200384 ML20034F5232020-02-12012 February 2020 Summary of Meeting with Tennessee Valley Authority Regarding Planned License Amendment Request for Watts Bar Nuclear Plant, Units 1 and 2 2024-09-23
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 December 3, 2014 APPLICANT: Tennessee Valley Authority FACILITY: Watts Bar Nuclear Power Plant, Unit 2
SUBJECT:
SUMMARY
OF NOVEMBER 12,2014, MEETING WITH TENNESSEE VALLEY AUTHORITY REGARDING THE WATTS BAR NUCLEAR PLANT, UNIT 2 OPERATING LICENSE APPLICATION (FIRE PROTECTION)
On November 12, 2014, a Category 1 public teleconference was held between the U.S. Nuclear Regulatory Commission (NRC) staff and representatives of the Tennessee Valley Authority (TVA). The purpose of this meeting was for TVA and the NRC staff to discuss staff questions related to TVA's draft "As-Constructed Fire Protection Report" (the Report). TVA plans to submit the final version of the Report in November 2014. The NRC staff and TVA discussed draft versions of this report at four previous meetings as well. At this meeting, the discussion focused on clarification questions the staff had related to certain text in the Report that appeared contradictory to NRC staff. The meeting notice and agenda, dated October 22, 2014, is available in the Agencywide Documents Access and Management System at Accession No. ML14297A373. A list of attendees is provided as Enclosure 1. TVA had no formal presentation materials at this meeting.
The list of staff questions is provided as Enclosure 2. The NRC staff and TVA went through each of the staff's five questions listed in Enclosure 2. The focus of the clarification was related to how recall times should be incorporated into the calculations of times for operator manual actions necessary to safely shut down the plant in the event of a fire that could damage safety-related plant equipment. Currently, the NRC believes that the assistant unit operators (AUOs) are in the control room once equipment damage starts and, therefore, recall time need not be included in the calculations. However, closer examination of the Report revealed certain statements that called this assumption into question. The NRC noticed an area of the report that seemed to indicate that operators would recall the AUOs AFTER they had received confirmation of a fire and, therefore, potentially AFTER equipment damage had begun. TVA stated that they would examine this situation more closely to see if it is feasible and clarify any areas that may be confusing in their current form. Any modifications to the Report based on the staff's questions will be submitted as part of the final version of the Report.
Members of the public were not in attendance and, therefore, no public comments or Public Meeting Feedback Forms were received at this meeting.
No regulatory decisions were made as a part of this meeting.
Please direct any inquiries to me at 301-415-2048, or by email to Justin.poole@nrc.gov.
Justin C. Poole, Senior Project Manager Watts Bar Special Projects Branch Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-391
Enclosures:
- 1. Meeting Attendance List
- 2. Staff Questions Related to the As-Constructed Fire Protection Report cc w/enclosures: Distribution via Listserv
MEETING ATTENDANCE LIST Applicant: Tennessee Valley Authority Plant: Watts Bar Nuclear Plant. Unit 2
Subject:
Fire Protection (WBN, Unit 2) Date: November 12, 2014 Location: Teleconference Time: 9:00 a.m. - 10:00 a.m.
NAME TITLE ORGANIZATION Sr. Project Manager Watts NRC/NRR/DORUWatts Bar Special Justin Poole Bar Unit 2 Projects Branch NRC/NRR/DRA/Fire Protection Dan Frumkin Fire Protection Engineer Branch NRC/NRRIDORUWatts Bar Special Anthony Minarik Project Manager Projects Branch NRC/NRRIDRA/Fire Protection Charles Moulton Fire Protection Engineer Branch Director of Licensing, Gordon Arent Tennessee Valley Authority (TVA)
Watts Bar Bill Crouch Fire Protection Engineer TVA Charlie Brush Fire Protection Engineer EPM (TVA Contractor)
Engineering/Licensing Tom Morgan TVA Support Engineering/Licensing Mark Marinak TVA Support Enclosure 1
STAFF QUESTIONS RELATED TO THE AS-CONSTRUCTED FIRE PROTECTION REPORT TO BE DISCUSSED AT NOVEMBER 12, 2014, PUBLIC MEETING As-Constructed Fire Protection Report (FPR) Part V, Section 2.2.2, states that, "Upon detection of a fire either automatically or via observation, the main control room recalls Assistant Unit Operators (AUOs) to the assembly location from their normal duties in various plant locations."
FPR Part V, Section 2.2, Safe Shutdown Procedures, includes "notify the Appendix R AUOs to report to the control room," as the fifth step, of which the first step is "initiate fire alarm."
- 1) Clarify if "initiate fire alarm," is the actuation of detection equipment (similar to 2.2.2) or if initiation of fire alarm includes judgment or actions on the part of the control room staff.
- 2) If recall of AUOs is not immediate upon detection, describe the actions taken prior to, "initiate fire alarm."
- 3) If recall of AOUs is not immediate upon detection, describe any delays between the "early warning provided by the smoke detection system" and the reactor trip that would delay the AUOs from being recalled.
- 4) If there is a delay as described in the item above, provide a description of how that delay is considered in the timing for operator manual actions, specifically how that delay is accounted for in the 100% margin described in 2.1.2, Acceptance Criteria, and the evaluation of Required for Safe Shutdown Operator Manual Actions, Section 8.3 of Part VII.
- 5) If the AOUs will be recalled upon actuation of a fire detection system (similar to 2.2.2),
describe whether any procedures need to be revised to reflect this.
Enclosure 2
Members of the public were not in attendance and, therefore, no public comments or Public Meeting Feedback Forms were received at this meeting.
No regulatory decisions were made as a part of this meeting.
Please direct any inquiries to me at 301-415-2048, or by email to Justin.poole@nrc.gov.
IRA!
Justin C. Poole, Senior Project Manager Watts Bar Special Projects Branch Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-391
Enclosures:
- 1. Meeting Attendance List
- 2. Staff Questions Related to the As-Constructed Fire Protection Report cc w/enclosures: Distribution via Listserv DISTRIBUTION:
PUBLIC RidsNrrPMWattsBar2 Resource RidsNrrDorl Resource LPWB Reading RidsNrrLABCiayton LRonewicz, NRR Rlyengar, EDO RidsAcrsAcnw_MaiiCTR Resource RidsRgn2MaiiCenter Resource TWertz, NRR RidsNrrDoriLp_WB Resource DFrumkin, NRR AMinarik, NRR AWilson, Rll JDion, NRR CMoulton, NRR RidsNrrDraAfpb Resource OLopez, Rll RidsNrrPMWattsBar2 Resource ADAM SAccession No.: M eetin_g_ Not1ce: