Technical Specifications, Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for the Diesel Fuel Oil Testing Programs Using the Consolidated Line Item Improvement Process
ML071500232
Person / Time
Site: Fermi DTE Energy icon.png
Issue date: 04/12/2007
From:
NRC/NRR/ADRO/DORL/LPLIII-2
To:
Thorpe-Kavanaugh, Meghan, NRR 415-5735
Shared Package
ML070720027 List:
References
TAC MD3691
Download: ML071500232 (2)


Text

Programs and Manuals 5.5 5.5 Programs and Manuals (continued) 5.5.8 EXplosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures containedin the Main Condenser offgas treatment system, and the quantity of radioactivity contained in temporary outdoor storage tanks.

The program shall include:

a.

A limit of

  • 4% by volume for concentration of hydrogen in the main condenser offgas treatment system and a surveillance program to ensure the limit is maintained.
b.

A surveillance program to ensure that the quantity of radioactivity contained in any outdoor liquid radwaste tank that is not surrounded by liners, dikes, or walls, capable of holding the tank's contents and that does not have tank overflows and surrounding area drains connected to the liquid radwaste treatment system is e 10 curies, excluding tritium and dissolved or entrained noble gases.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

5.5.9 Emergency Diesel Generator Fuel Oil Testing Program An emergency diesel generator fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established.

The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards.

The purpose of the program is to establish the following:

a.

Acceptability of new fuel oil for use prior to addition to storage tanks by determining that the fuel oil has:

1.

an API gravity or an absolute specific gravity within I Illll ts,

2.

a flash point and kinematic viscosity within limits for ASTM 2D fuel oil, and

3.

a clear and bright appearance with proper color or a water and sediment content within limits; (continued)

FERMI UNIT 2 5.0-15 Amendment No. 1$4174

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Emergency Diesel Generator Fuel Oil Testing Program (continued)

b.

Within 31 days following addition of new fuel oil to storage tanks, verify that the properties of the new fuel oil, other than those addressed in a., above, are within limits for ASTM 2D fuel oil; and

c.

Total particulate concentration of the fuel oil is

  • 10 mg/l when tested every 31 days.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Emergency Diesel Generator Fuel Oil Testing Program testing frequencies.

5.5.10 Technical Specifications (TS) Bases Control Program This program provides a means for processing changes to the Bases of these Technical Specifications.

a.

Changes to the Bases of the TS'shall be made under appropriate administrative controls and reviews.

b.

Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

1.

a change in the TS incorporated in the license; or

2.

a change to the UFSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.

c.

The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the UFSAR.

d.

Proposed changes that meet the criteria of Specification 5.5.10b above shall be reviewed and approved by the NRC prior to implementation.

Changes to the Bases implemented without prior NDr approvmal shallbe pronidda

+to tka NRD on a

frequency consistent with 10 CFR 50.71(e).

(continued)