Perry, Attached is a page from the PNPS FSAR on Fire Hose Station testing.

Bryan Ford 1.;-.

C.

cAtemp\\GWJ00001.TMP Page 1 1 Wc:.

M P.Pag 1

4 Mail Envelope Properties (45BF801D.D3B : 9: 52539)

Subject:

Creation Date From:

Created By:

FSAR Excerpt 1/30/2007 12:27:43 PM "Ford, Bryan" <BFord@entergy.com>

BFord@entergy.corn Recipients nrc.gov OWGWPO01.HQGWDO01 PHB 1 (Perry Buckberg)

Post Office OWGWPO0 I.HQGWD01 Route nrc.gov Files MESSAGE ScanOO.PDF Mime.822 Options Expiration Date:

Priority:

ReplyRequested::

Return Notification:

Concealed

Subject:

Security:

Size 89 48057 68244 Date & Time 1/30/2007 12:27:43 PM None Standard No None..

iv No Standard Junk Mail Handling Evaluation Results Message is eligible for Junk Mail handling This message was not classified as Junk Mail Junk Mail settings when this message was delivered Junk Mail handling disabled by User Junk Mail handling disabled by Administrator

ýJunk List is not enabled Junk Mail using personal address books is not enabled Block List is not enabled

PNPS-FSAR 10.8.4.5.2 Fire Hose Stations Surveillance Requirements

(

Each interior fire hose station shall be verified to be operable:

1.

At least once per month by visual inspection of the station to assure that the hose and nozzle are properly installed.

(Exception -

Once per cycle for those in Locked High Radiation Areas).

2.

At least once per cycle by remnoving the hose for inspection, replacing any degraded coupling gaskets, and reracking.

3.

At least once per two fuel cycles (approximately 4

years) by partially opening each hose station valve to verify valve operability and no obstruction.

(Partial flow test).

4.

By conducting a hydrostatic test of each hose every three years.

a.

at a pressure 50 psig greater than the maximum available pressure at that hose station.,

or

b.

at the applicable service test pressure as listed in Table 8-3 of the "Standard for

Care, Maintenance of Fire Hose including Connection and Nozzles."

NFPA No. 1962-1979, or

c.

by replacing each nontested hose with a new or..

used hose which has been hydrostaticaliyiese e n

accordance with the pressures sQecified in a or' b above.