Page 1 of I Perry Buckberg - 12/12/2006 conference call record From:

Perry Buckberg To:

Doug Ellis Date:

12/13/2006 2:50:52 PM

Subject:

12/12/2006 conference call record CC:

Rajender Auluck

Doug, Please review the attached edited record from yesterday's phone conference and reply with comments or concurrence.
Thanks, Perry Buckberg Project Manager - Division of License Renewal phone: (301)415-1383 fax:

(301)415-3031 phbl@r

c. ov file ://C:\\temp\\GW }00001.HTM 12/29/2006

[OfoýVT 6IJ-VP Page I c:\\temp\\GW}OOOO1.TMP Page 1~

Mail Envelope Properties (4580599C.448:9: 8248)

Subject:

Creation Date From:

Created By:

12/12/2006 conference call record 12/13/2006 2:50:52 PM Perry Buckberg PHB 1 @nrc.gov Recipients entergy.com PM dellisI (Doug Ellis)

Action Transferred Date & Time 12/13/2006 2:51:28 nrc.gov OWGWPO01.HQGWDO01 PM RCA CC (Rajender Auluck)

Delivered 12/13/2006 2:50:52 Post Office Delivered Route entergy.com MI nrc.gov OWGWPOO I.HQGWDO01 12/13/2006 2:50:52 P1 Files Size MESSAGE 894

--TEXT.htm.

649 MeetingSummary Dec 12 2006 (PNPS).wpd PM Date & Time 12/13/2006 2:50:51 PM 12/13/2006 2:47:58

29722, Options Auto Delete:

Expiration Date:

Notify Recipients:

Priority:

ReplyRequested:

Return Notification:

Concealed

Subject:

Security:

To Be Delivered:

Status Tracking:

No None Yes Standard No None No Standard Immediate Delivered

LICENSEE:

Entergy Nuclear Operations, Inc.

FACILITY:

Pilgrim Nuclear Power Station

SUBJECT:

SUMMARY

OF CONFERENCE CALL ON DECEMBER 12, 2006 WITH ENTERGY NUCLEAR OPERATIONS, INC., REGARDING THE PILGRIM LICENSE RENEWAL APPLICATION (TAC NO. MC9669)

The U.S. Nuclear Regulatory Commission staff conducted a conference call with Entergy Nuclear Operations, Inc. (Entergy or the applicant) regarding the Pilgrim License Renewal Application (LRA) to discuss information sent to the NRC in response to requests for additional information (RAI) and to address other license renewal issues. The conference call was conducted on Tuesday December 12, 2006, between 12:30 p.m. and 1:30 p.m. at 11555 Rockville Pike, Rockville, MD 20852. The list of participants is shown in the enclosure. The following is a summary of the conference call.

The NRC Pilgrim Project Manager provided an introduction and began discussing the 9 subjects to be covered in the conference: NRC staff considers the response to Pilgrim RAI 2.3.3.9-8 incomplete; NRC staff feels RAI 2.4.3-1 trash racks and traveling screens require aging management programs; request Entergy justify the RAI 2.4.3-1 jib crane being considered out of scope of license renewal; concurrence that RAI 2.4.5-1 transmission towers are included in LRA Table 2.4-5; NRC staff requires the applicant to make.a commitment Atoý.

boiling Water reactor vessel and internals program (BWRVIP)-94 and BWRVIP-76; discuss;:the core shroud tie rod upper bracket material and repair; discuss the validity of using one timer inspections to assess reduction of fracture toughness in cast austenitic stainless steel (CASS) components and discuss RAI B.1.3-2 exception to NUREG 1800 AMP XI.M6. Discussionof RAI 2.3.3.9-8, resulted in the Entergy action to assess whether fire suppression systemshfor several transformers are within scope. Discussions regarding the trash racks, traveling screens and the jib crane resulted in an Entergy explanation as to why these components are considered out of scope. The discussion of the transmission towers resulted in the confirmation that the towers are represented in LRA table 2.4-5. Entergy stated that the commitment to BWRVIP-94 is reflected in Entergy procedure ENN-DC-135 and that a commitment to BWRVIP-76 will be addressed in a pending LRA amendment. Entergy explained that the core shroud tie rod upper bracket will be replaced in the April, 2007 Pilgrim re-fueling outage. Entergy took an action to research LRA inconsistencies regarding the inspection for reduction of fracture toughness of CASS piping and pump casings. Entergy stated that exception 1 to GALL AMP XI.M6 need not be deleted from the LRA as a result of discussions with the NRC staff during this conference call.

The applicant had an opportunity to comment on the meeting summary.

Perry Buckberg, Project Manager License Renewal Branch A Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-293

Enclosure:

List of Participants

cc w/encl: See next page C

1"'i*;
  • t t
  • " ~

LIST OF PARTICIPANTS FOR TELEPHONE CONFERENCE CALL TO DISCUSS THE PILGRIM NUCLEAR POWER STATION LICENSE RENEWAL APPLICATION December 12, 2006 PARTICI PANTS Perry Buckberg Raj Auluck Ganesh Cheruvenki Naeem lqbal James Davis Susan Lane Peter Wen Phil Quails James Medoff Doug Ellis Fred Mogolesko Alan Cox Ray Pace Abdolreza Ahrabli David Lach Steve Burke AFFILIATION U.S. Nuclear Regulatory Commission (NRC)

NRC NRC NRC NRC NRC NRC NRC NRC Entergy Nuclear Operations, Inc. (Entergy)

Entergy Entergy Entergy Entergy Entergy Entergy ENCLOSURE