Entergy Nuclear Northeast Entergy Nuclear Operations, Inc.

James A. Fitzpatrick NPP h Entergy RO. Box 110 Lycoming, NY 13093 Tel 315 349 6024 Fax 315 349 6480 T.A. Sullivan November 10, 2004 Site Vice President - JAF JAFP-04-0181 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

SUBJECT:

James A. FitzPatrick Nuclear Power Plant Docket No. 50-333 October 2004 Monthly Operating Report

Dear Sir:

Enclosed is the Monthly Operating Report (MOR) for the James A. FitzPatrick Nuclear Power Plant for the month of October 2004.

MOR data has been prepared and formatted using the INPO Consolidated Data Entry (CDE) submittal process.

Should you have any questions concerning this report, please direct them to Mr. Mick Baker, Thermal Performance Engineer, at (315) 349-6181.

Very truly yours, T. A. Sullivan TAS:MB:dr Enclosure C"

'-6.'

cc: Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406-1415 Office of the Resident Inspector James A. FitzPatrick Nuclear Power Plant U.S. Nuclear Regulatory Commission P.O. Box 136 Lycoming, NY 13093 Mr. Patrick Milano, Sr. Project Manager Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop MS-8-C2 Washington, DC 20555-0001 Mr. Ronald Toole ENN BWR SRC Operations Subcommittee Chairmnan 1282 Valley of Lakes Box R-10 Hazelton, PA 18202 Mr. Paul Eddy New York State Department of Public Service 3 Empire State Plaza Albany, NY 12223-1350 JENG JAFP Files RMS (JAF)

OPERATING DATA REPORT DOCKET NO. 50-333 UNIT NAME FitzPatrick I DATE November 10, 2004 COMPLETED BY Mick Baker TELEPHONE 315-349-6181 REPORTING PERIOD October 2004

1. Design Electrical Rating 816.00
2. Maximum Dependable Capacity (MWe-Net) 813.00 This Month Yr-to-Date Cumulative
3. Number of Hours the Reactor was Critical 200.87 6,623.75 196,528.25
4. Number of Hours Generator On-line 169.77 6,522.64 191,093.84
5. Reserve Shutdown Hours 0.00 0.00 0.00
6. Net Electrical Energy Generated (MWHrs) 122,108.00 5,206,157.00 143,111,921.00 UNIT SHUTDOWNS Type Method of No. Date F: Forced Duration Reason Shutting Cause & Corrective Action S: Scheduled (Hours) Down 2 Comments 2004-03 09/25/2004 S 574.00 C 4 Shut Down for Refuel Outage.

2004-04 10/25/2004 S 1.23 B 5 Generator was taken off-line to perform overspeed testing following a refueling outage.

SUMMARY

Reactor was shutdown for a refueling outage. The plant went online at 22:00 on October 24th for testing of the turbine. The plant went off-line to perform turbine overspeed testing at 02:56 on October 25th. The plant went back online at 04:10 on October 25th.

1 2 Reason: Method:

A Equipment Failure (Explain) 1 Manual B Maintenance or Test 2 Manual Trip/Scram C Refueling 3 Automatic Trip/Scram D Regulatory Restriction 4 Continuation E Operator Training & License Examination 5 Other (Explain)

F Administration G Operational Error (Explain)

H Other (Explain)