ML030770796

From kanterella
Jump to navigation Jump to search

Technical Specification Pages to Amendment 133 to License NPF-47
ML030770796
Person / Time
Site: River Bend 
(NPF-047)
Issue date: 03/14/2003
From: Michael Webb
NRC/NRR/DLPM/LPD4
To: Hinnenkamp P
Entergy Operations
References
TAC MB5093
Download: ML030770796 (7)


Text

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.8 1.9 SR 3.8.1.10 NOTE "1.

This Surveillance shall not be performed in MODE 1 or 2. (Not applicable to DG 1C)

However, credit may be taken for unplanned events that satisfy this SR.

2.

If performed with DG synchronized with offsite power, it shall be performed at a power factor

< 0.9 Verify each DG rejects a load greater than or equal to its associated single largest post accident load and following load rejection, the engine speed is maintained less than nominal plus 75% of the difference between nominal speed and the overspeed trip setpoint or 15% above nominal, whichever is lower.

NOTE This Surveillance shall not be performed in MODE 1 or 2. (Not applicable to DG 1C) However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor< 0.9 does not trip and voltage is maintained < 4784 V for DG 1A and DG 1 B and < 5400 V for DG IC during and following a load rejection of a load > 3030 kW and

< 3130 kW for DGs 1A and 1B and;> 2500 kW and

< 2600 kW for DG 1C.

FREQUENCY 4

18 months 4

18 months (continued)

Amendment No. 84 424, 133 I

I RIVER BEND 3.8-8

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.11 NOTES

1.

All DG starts may be preceded by an engine prelube period.

2.

This Surveillance shall not be performed in MODE 1, 2, or 3. (Not applicable to DG 1C)

However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated loss of offsite power signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses for Divisions I and II; and

c.

DG auto-starts from standby condition and:

1.

energizes permanently connected loads in

< 10 seconds for DG 1A and DG 1B and

< 13 seconds for DG IC,

2.

energizes auto-connected shutdown loads,

3.

maintains steady state voltage

> 3740 V and5 <4580 V,

4.

maintains steady state frequency > 58.8 Hz and5 <61.2 Hz, and

5.

supplies permanently connected and auto-connected shutdown loads for

> 5 minutes.

Amendment No. 84-42-I, 133 18 months (continued)

RIVER BEND 3.8-9

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.12 NOTES

1.

All DG starts may be preceded by an engine prelube period.

2.

This Surveillance shall not be performed in MODE 1 or2. (Not applicable to DG 1C)

However, credit may be taken for unplanned events that satisfy this SR.

Verify on an actual or simulated Emergency Core 18 months Cooling System (ECCS) initiation signal each DG auto-starts from standby condition and:

a For DG IC during the auto-start maintains voltage < 5400 V and frequency < 66.75 Hz;

b.

In:< 10 seconds for DG 1A and DG 1B and

< 13 seconds for DG 1C after auto-start and during tests, achieves voltage Ž: 3740 V and

< 4580 V;

c.

In <10 seconds for DG 1A and DG 1B and

< 13 seconds for DG 1C after auto-start and during tests, achieves frequency > 58.8 Hz and

< 61.2 Hz; and

d.

Operates for > 5 minutes.

(continued)

Amendment No.084 424, 133 RIVER BEND 3.8-10

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.8.1.13 SR 3.8.1.14 NOTE This Surveillance shall not be performed in MODE 1,2, or 3. (Not applicable to DG 1C)

However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG's automatic trips are bypassed on an actual or simulated ECCS initiation signal except

a.

Engine overspeed; and

b.

Generator differential current.

NOTES

1.

Momentary transients outside the load and power factor ranges do not invalidate this test.

2.

Credit may be taken for unplanned events that satisfy this SR.

Verify each DG operating at a power factor _ 0.9, operates for > 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

a.

For DG lA and DG 1B loaded > 3030 kW and <3130 kW, and

b.

For DG 1C:

1.

For Ž! 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> loaded;> 2750 kWand

_< 2850 kW, and

2.

For the remaining hours of the test loaded > 2500 kW and* 2600 kW.

Amendment No. 841-4 4.24, 133 FREQUENCY 18 months 18 months (continued)

I RIVER BEND 3.8-11

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.8.1.15 SR 3.8.1.16 NOTES

1.

This Surveillance shall be performed w*ithin 5 minutes of shuttin9 down the DG after the DG has operated > 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> loaded > 3000 kW and

_<3100 kWfor DG 1Aand DG 1B, and 2t 2500 kW and _2600 for DG 1C, or operating temperatures have stabilized, which ever is longer.

Momentary transients outside of the load range do not invalidate this test.

2.

All DG starts may be preceded by an engine prelube period.

Verify each DG starts and achieves, in < 10 seconds for DG 1A and DG 1B and _13 seconds for DG 1C, voltage > 3740 V and < 4580 V and frequency

> 58.8 Hz and < 61.2 Hz.

NOTE This Surveillance shall not be performed in MODE 1, 2, or 3. (Not applicable to DG 1 C) However, credit may be taken for unplanned events that satisfy this SR.

Verify each DG:

a.

Synchronizes with offsite power source while loaded with emergency loads upon a simulated restoration of offsite power;

b.

Transfers loads to offsite power source; and

c.

Returns to ready-to-load operation.

FREQUENCY 18 months 4

18 months (continued)

Amendment No. 84 41-24, 133 I

RIVER BEND 3.8-12

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE SR 3.8.1.17 NOTE This Surveillance shall not be performed in MODE 1, 2, or 3. (Not applicable to DG 1C) However, credit may be taken for unplanned events that satisfy this SR.

Verify, with a DG operating in test mode and connected to its bus, an actual or simulated ECCS initiation signal overrides the test mode by:

a.

Returning DG to ready-to-load operation; and

b.

Automatically energizing the emergency loads from offsite power.

FREQUENCY 18 months SR 3.8.1.18 NOTE This Surveillance shall not be performed in MODE 1, 2, or 3. (Not applicable to DG 1C) However, credit may be taken for unplanned events that satisfy this SR.

Verify sequence time is within +/- 10% of design for 18 months each load sequencer timer.

(continued)

Amendment No. 84 95 4-24, 133 I

I RIVER BEND 3.8-13

AC Sources-Operating 3.8.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.8.1.19 NOTES

1.

All DG starts may be preceded by an engine prelube period.

2.

This Surveillance shall not be performed in MODE 1, 2, or 3. (Not applicable to DG I C)

However, credit may be taken for unplanned events that satisfy this SR.

Verify, on an actual or simulated loss of offsite power 18 months signal in conjunction with an actual or simulated ECCS initiation signal:

a.

De-energization of emergency buses;

b.

Load shedding from emergency buses for Divisions I and II; and

c.

DG auto-starts from standby condition and:

1.

energizes permanently connected loads in

_< 10 seconds for DG 1A and DG 1B and

< 13 seconds for DG 1C.

2.

energizes auto-connected emergency

loads,
3.

achieves steady state voltage > 3740 V and

< 4580 V,

4.

achieves steady state frequency 2 58.8 Hz and <61.2 Hz, and

5.

supplies permanently connected and auto-connected emergency loads for S5 minutes.

(continued)

Amendment No. 84 424, 133 RIVER BEND 3.8-14