PAM Instrumentation 3.3.3.1 SURVEILLANCE REQUIREMENTS Thee sappyoachFunct-------NOTi These SRs; apply to each Function in Table 3.3.3 SURVEILLANCE FREQUENCY SR 3.3.3.1.1 Perform CHANNEL CHECK.
31 days SR 3.3.3.1.2 Deleted SR 3.3.3.1.3 Perform CHANNEL CALIBRATION.
18 months Il RIVER BEND 3.3-21 Amendment No. 9,142
PAM Instrumentation 3.3.3.1 Table 3.3.3.1-1 (page 1 of 1)
Post Accident Monitoring Instrumentation REQUIRED CHANNELS FUNCTION
- 1. Reactor Steam Dome Pressure
- 2. Reactor Vessel Water Level - Wide Range
- 3. Reactor Vessel Water Level - Fuel Zone
- 4. Suppression Pool Water Level
- 5. Suppression Pool Sector Water Temperature
- 6. Drywell Pressure
- 7. Primary Containment Pressure
- 8. Drywell Area Radiation
- 9. Primary Containment Area Radiation
- 10. Deleted 1 1. Deleted
- 12. Penetration Flow Path, Automatic PCIV Position 2
2 2
2 2(a) 2 2
2 2
CONDITIONS REFERENCED FROM REQUIRED ACTION D.1 E
E E
E E
E E
F F
I I
2 per penetration flow path (b)(c)
E (a)
(b)
(c)
Monitoring each of two sectors.
Not required for isolation valves whose associated penetration flow path is isolated.
Only one position indication channel is required for penetration flow paths with only one control room indication channel.
RIVER BEND 3.3-22 Amendment No. 81 95,142