FENOC FirstEnergy Nuclear Operating Company Mark A. Manoleras 724-682-5101 Director Site Engineering Fax: 724-682-1840 July 11,2008 L-08-225 10 CFR 54 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001

SUBJECT:

Beaver Valley Power Station, Unit Nos. 1 and 2 BV-1 Docket No. 50-334, License No. DPR-66 BV-2 Docket No. 50-412, License No. NPF-73 Reply to Request for Additional Information for the Review of the Beaver Valley Power Station, Units 1 and 2, License Renewal Application (TAC Nos. MD6593 and MD6594) and License Renewal Application Amendment No. 16 Reference 1 provided the FirstEnergy Nuclear Operating Company (FENOC) License Renewal Application (LRA) for the Beaver Valley Power Station (BVPS). During a telephone conference call with the U.S. Nuclear Regulatory Commission (NRC) on July 1, 2008, NRC requested additional information from FENOC regarding the BVPS license renewal integrated plant assessment in Section B.2.5 of the BVPS LRA.

The Attachment provides the FENOC reply to the U.S. Nuclear Regulatory Commission request for additional information. The Enclosure provides Amendment No. 16 to the BVPS License Renewal Application.

There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Clifford I. Custer, Fleet License Renewal Project Manager, at 724-682-7139.

I declare under penalty of perjury that the foregoing is true and correct. Executed on July i/

,2008.

Sincerely, Mark A. Manoleras

I Beaver Valley Power Station, Unit Nos. 1 and 2 L-08-225 Page 2

References:

1.

FENOC Letter L-07-113, "License Renewal Application," August 27, 2007.

Attachment:

Reply to Request for Additional Information Regarding Beaver Valley Power Station, Units 1 and 2, License Renewal Application, Section B.2.5

Enclosure:

Amendment No. 16 to the BVPS License Renewal Application cc:

Mr. K. L. Howard, NRC DLR Project Manager Mr. S. J. Collins, NRC Region I Administrator cc:

w/o Attachment or Enclosure Mr. B. E. Holian, NRC DLR Director Mr. D. L. Werkheiser, NRC Senior Resident Inspector Ms. N. S. Morgan, NRC DORL Project Manager Mr. D. J. Allard, PA BRP/DEP Director Mr. L. E. Ryan, PA BRP/DEP

ATTACHMENT L-08-225 Reply to Request for Additional Information Regarding Beaver Valley Power Station, Units 1 and 2, License Renewal Application, Section 2.5 Page 1 of 1 Section 2.5 Question RAI 2.5-1 Clarify the description of the electrical scoping boundary in LRA Section 2.5 to include the first breaker as described in ISG 2008-01.

RESPONSE RAI 2.5-1 FENOC intended the electrical scoping boundary description for recovery of offsite power following station blackout to include the first breaker within the Switchyard. LRA Section 2.5 is revised to clarify that the first breakers in the Switchyard (breakers 92 and 83 for Unit 1, and breakers 85 and 94 for Unit 2) are included in the scope of license renewal.

See the Enclosure to this letter for the revision to the BVPS LRA.

ENCLOSURE Beaver Valley Power Station (BVPS), Unit Nos. 1 and 2 Letter L-08-225 Amendment No. 16 to the BVPS License Renewal Application Page 1 of 2 License Renewal Application Sections Affected Section 2.5 The Enclosure identifies the correction by Affected License Renewal Application (LRA)

Section, LRA Page No., and Affected Paragraph and Sentence. The count for the affected paragraph, sentence, bullet, etc. starts at the beginning of the affected Section or at the top of the affected page, as appropriate. Below each section the reason for the change is identified, and the sentence affected is printed in italics with deleted text finedeou and added text underlined.

I Enclosure L-08-225 Page 2 of 2 Affected Paragraph Affected LRA Section LRA Page No.

and Sentence Section 2.5 Page 2.5-2 "Evaluation Boundaries" Section, 2 nd Paragraph LRA, Section 2.5, "Scoping and Screening Results: Electrical and Instrumentation and Controls Systems," page 2.5-2, subsection titled "Evaluation Boundaries," is revised to clarify that the first breakers in the Switchyard (breakers 92 and 83 for Unit 1, and breakers 85 and 94 for Unit 2) are included in the scope of license renewal. Section 2.5, page 2.5-2, section titled "Evaluation Boundaries," 2 nd paragraph, is revised to read:

"For BVPS, recovery of offsite power following station blackout is dependent upon medium-voltage insulated cable, Switchyard bus, breakers, transmission conductors, and high voltage insulators that connect the plant electrical distribution system to the offsite AC power source via the station service transformers. The supply of offsite power to the plant electrical distribution system is within the scope of License Renewal from and including the first breakers in the switchyard (breakers 92 and 83 for Unit 1, and breakers 85 and 94 for Unit 2) from the plant electrical distribution system, as shown on Figures 2.5-1 and 2.5-2. Switchyard bus, transmission conductors, high-voltage insulators, and connections connecting Switchyard breakers and station service transformers are subject to aging management review. Medium-voltage cables and connections, connecting station service transformers and nonsafety buses are subject to aging management review. Medium-voltage cables and connections connecting nonsafety buses to the safety buses are subject to aging management review."