Forwards Engineering Assessment Turbine Bldg Fire Area IE Ja Fitzpatrick Nuclear Power Plant, to Support App R Exemption for area-wide Detection in Turbine Bldg
ML20091C244
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 07/31/1991
From: Radford Converse
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20091C245 List:
References
JAFP-91-0455, JAFP-91-455, NUDOCS 9108060104
Download: ML20091C244 (2)


Text

. . _ _ _ . - - _ - _ - _ _ _ _ _ _ - _ - _ _ _ _ - _ - - _ - - _ _ _ _ - _ _ _ - - - _ _ - _ _ . _ _ _ _ _ - - - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - .

s:

James A. nl:Patrich

. Nuclear Power Plant P o 00: 41

- Lycoming. New Ytuk 13093 315 342 3840

  1. > NewYorkPower tv Authority "" 2 % o" * "

July 31, 1991 JAPP-91-0455 United States Nuclear Regulatory Commission Document Control Desk Mail' Station Pl-137 Washington, D.C. 20555

Subject:

J AMES A. FITZPATRICK NUCLEAR POWER PLANT DOCKET NO. 50-333 APPENDIX R TO 10 CFR 50 EXEMPTION REQUEST FOR AREA WIDE DETECTION IN THE TURBINE BUILDING -

Dear Sirs:

In accordance with the provisions of 10 CFR 50.12, the New York Power Authority requests exemption from the requirements of Sections III.G.3 of Appendix R to 10 CFR 50 as they apply to the James A. FitzPatrick Nuclear Power Plant. The exemption request concerns fire detection in the Turbine Building.

Turbine Buildina Area (Fire Zone 1Et <

Section III.G.3.b of Appendix R to 10 CFR 50 requires " fire detection and a fixed fire suppression system ... in the area, room,_or zone under consideration" where electrical circuits

" associated" with alternative or dedicated shutdown could prevent operation of equipment required for hot shutdown. "

The Authority has recently determined that a fire-in either the FitzPatrick Control Room or Turbine Building could prevent operation of the East and West Electric Bay Ventilation Unit Cooler Fans because of circuits " associated" with these fans.

Equirment required for safe shutdown in the electrical bays may ovt-beat and become inoperable if the fans do not operate.

Modifications have been installed to assure that these fans will operate. However, a fire detection system-is not currently installed "in the area, roon, or zone under consideration".

As an interim compensatory measure, the Authority will post a continuous fire watch in the area. Individuals standing fire watch will be trained how to use a portable fire extinguisher.

The Authority requests exemption from the requirements of Section III.G.3 of Appendix R to 10 CFR 50 to the extent that a fire detection system is required-within the turbine building.

910GO60104 910731 h PDR ADOCK 05000333 t F PDR '

(

.- .- .- - . . - -. = .. . - , . . . - .

4 UNITED STATES NUCLEAR REGULATORY COMMISSION July 31, 1991 Document Control Desk JAFP-91-o455 Docket No. 50-333 Page 2 of 2 A detailed description, engineering assessment and technical justification for this exemption request is included in Attachment I.

If you have any questions, regarding either of these exemption requests, please contact Mr. J. A. Gray, Jr.

Very,t'r 19 yours, g// /

_/ h &(.A v "

RAD 70 D J. CONVERSE RESIDENT MANAGER RJC JE:mac Attachment cc: U.S. Nuclear Regulatory Commission Region 1 475 Allendale Road King of Prussia, PA 19406 Office of Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 136 Lycoming, NY 13093 Mr. Brian C. McCabe Project Directorate I-1 Director of Reactor Projects - I/II U.S. Nuclear Regulatory Commission Mail Stop 14 B2 Washington, D.C. 20555