Information Notice 2012-03, Design Vulnerability in Electric Power System

From kanterella
(Redirected from Information Notice 2012-03)
Jump to navigation Jump to search
Design Vulnerability in Electric Power System
ML120480170
Person / Time
Issue date: 03/01/2012
From: Camper L, Laura Dudes, Mcginty T
NRC/FSME/DWMEP, Division of Construction Inspection and Operational Programs, Division of Policy and Rulemaking
To:
Beaulieu, D P, NRR/DPR, 415-3243
References
IN-12-003
Download: ML120480170 (7)


UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

OFFICE OF FEDERAL AND STATE MATERIALS AND

ENVIRONMENTAL MANAGEMENT PROGRAMS

OFFICE OF NEW REACTORS

WASHINGTON, DC 20555-0001 March 1, 2012 NRC INFORMATION NOTICE 2012-03: DESIGN VULNERABILITY IN ELECTRIC POWER

SYSTEM

ADDRESSEES

All holders of an operating license or construction permit for a nuclear power reactor under

Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Domestic Licensing of

Production and Utilization Facilities, including those who have been permanently ceased

operations and have spent fuel in storage in the spent fuel pool.

All holders of or applicants for a standard design certification, standard design approval, manufacturing license, or combined license issued under 10 CFR Part 52, Licenses, Certifications, and Approvals for Nuclear Power Plants.

PURPOSE

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice (IN) to inform

addressees of recent operating experience involving the loss of one of the three phases of the

offsite power circuit. The NRC expects that recipients will review the information for applicability

to their facilities and consider actions, as appropriate, to avoid similar problems. Suggestions

contained in this IN are not NRC requirements; therefore, no specific action or written response

is required.

DESCRIPTION OF CIRCUMSTANCES

Byron Station, Unit 2

System Description: The Byron Unit 2 electrical system consists of four nonsafety-related

6.9-kilovolt (kV) buses, two nonsafety-related 4.16-kV buses, and two 4.16-kV engineered

safety features (ESF) buses. The two 4.16-kV ESF buses and two of the nonsafety-related

6.9-kV station buses normally are supplied by one of the two station auxiliary transformers

(SATs) connected through one 345-kV offsite circuit. The remaining two nonsafety-related

6.9-kV station buses and two nonsafety-related 4.16-kV station buses normally are supplied by

one of two unit auxiliary transformers (UATs) when the main generator is online.

On January 30, 2012, Byron Station, Unit 2 experienced an automatic reactor trip from full

power because of an undervoltage condition on two 6.9-kV electrical buses that power reactor

coolant pumps (RCPs) B and C. A broken insulator stack for the phase C conductor on the

345-kV power circuit that supplies both SATs caused the undervoltage condition. This insulator

failure caused the phase C conductor to break off from the power line disconnect switch, resulting in a phase C open circuit. Although the break in the power line may have caused

phase C to ground, the 345-kV circuit does not have ground fault protection and the switchyard

breakers did not open.

After the reactor trip, the two 6.9-kV buses that power RCPs A and D, which were aligned to the

UATs, automatically transferred to the SATs, as designed. Because phase C was open

circuited, the flow of current on phases A and B increased and caused all four RCPs to trip on

phase overcurrent. With no RCPs functioning, control room operators performed a

natural-circulation cooldown.

Even though phase C was open circuited, the SATs continued to provide power to the 4.16-kV

ESF buses A and B because of a design vulnerability this event revealed. The open circuit

created an unbalanced voltage condition (loss of phase) on the two 6.9-kV nonsafety-related

RCP buses and the two 4.16-kV ESF buses. ESF loads remained energized momentarily, relying on equipment-protective devices to prevent damage from single phasing or an

overcurrent condition. The overload condition caused several safety-related loads to trip.

Approximately 8 minutes after the reactor trip, the control room operators diagnosed the loss of

phase C condition and manually tripped breakers to separate the unit buses from the offsite

power source. When the SAT feeder breakers to the two 4.16-kV ESF buses were opened, the

loss of ESF bus voltage caused the emergency diesel generators (EDGs) to automatically start

and restore power to the ESF buses. The licensee declared a Notice of Unusual Event based

on the loss of offsite power. The next day, the licensee completed the switchyard repairs, restored offsite power, and terminated the Notice of Unusual Event.

The licensee reviewed the event and identified design vulnerabilities in the protection scheme

for the 4.16-kV ESF buses. The loss-of-voltage relay protection scheme is designed with two

undervoltage relays on each of the two ESF buses. These relays are part of a two-out-of-two

trip logic based on the voltages being monitored between phases A-B and B-C of ESF buses.

Even though phase C was open circuited, the voltage between phases A-B was normal;

therefore, the trip logic was not satisfied. Because the conditions of the two-out-of-two trip logic

were not met, no protective trip signals were generated to automatically separate the ESF

buses from the offsite power source.

Beaver Valley Power Station, Unit 1

On November 27, 2007, during a nonroutine walkdown of the offsite switchyard to investigate

line voltage differences, the licensee discovered that the phase A conductor of a 138-kV offsite

power circuit the Beaver Valley Power Station Unit 1 had broken off in the switchyard. This

break occurred between the offsite feeder breaker and the line running onsite to the A train

system station service transformer (SSST) located inside the site security fence. The terminal

broke on the switchyard side of a revenue-metering current transformer/voltage transformer

installed in 2006 to track the stations power usage through this line. During normal power

operation, no appreciable current goes through this 138-kV line because the unit generator

normally powers the station buses (loads). The station declared the A train offsite power circuit

inoperable. The licensee subsequently determined that the break on the 138-kV phase A had

occurred 26 days earlier and, therefore, had not been restored within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> as required by

technical specifications.

The licensee determined that the root cause of this event was that site personnel did not fully

recognize the characteristics of the three-legged WYE-G/WYE-G WYE-G design of the

secondary core form transformer. As such, their surveillance procedure did not identify the open phase that rendered the offsite power line inoperable. The surveillance procedure

measured phase-to-phase voltage on the secondary side (plant side) of the SSST. With this

type of transformer, the two functioning phases will induce voltage to the open-circuited phase

such that phase-to-phase voltage measurements alone would not identify an open-circuited

phase in a lightly loaded power line.

This event is discussed in Beaver Valley Power Station Unit 1 Licensee Event Report

(LER) 50-334/2007-002, dated January 25, 2008, available on the NRCs public Web site

(Agencywide Documents Access and Management System (ADAMS)

Accession No. ML080280592).

James A. FitzPatrick Nuclear Power Plant and Nine Mile Point, Unit 1 On December 19, 2005, with the James A. FitzPatrick Nuclear Power Plant (JAF) and Nine Mile

Point, Unit 1 (NMP1) operating at 100 percent power, National Grid (the local grid operator)

notified the NMP1 control room (who subsequently informed the JAF control room) that it had

observed abnormal amperage readings (0 amps on phase A and 50 amps on phases B and C)

on the 115-kV offsite power lines and suggested that the readings might indicate an open

phase. The JAF operators walked down the JAF 115-kV switchyard and observed an open

circuit on phase A of Line 4, caused by a broken bus bar connector. The operators declared

Line 4 inoperable, removed it from service for repairs, and returned it to service the following

day.

An engineering evaluation of the NMP1, JAF, and National Grid data revealed that the bus bar

connector failure had existed, undetected, since November 29, 2005, and Line 4 had been out

of service for approximately 21 days. As a result, one redundant offsite power supply had

exceeded the technical specification allowed out-of-service time. The cause of the undetected

inoperability of Line 4 was inadequate control room indications and alarms at NMP1 and an

inadequate surveillance test at JAF. The JAF surveillance procedure records 115-kV bus

voltages and confirms power availability, via communication with National Grid, but does not

confirm that all three phases are intact by monitoring current flow in the 115-kV transmission

lines. NMP1 corrective actions included implementing a plant process computer alarm

modification for low amperage on any of the 3 phases of the offsite power lines. JAF corrective

actions included revising the surveillance procedure to also record Line 4 phase amperage.

This event is discussed in NMP1 LER 50-220/2005-04, dated February 17, 2006 (ADAMS

Accession No. ML060620519), and JAF LER 50-333/2005-06, dated February 13, 2006 (ADAMS Accession No. ML060610079).

BACKGROUND

General Design Criterion (GDC) 17, Electric Power Systems, of Appendix A, General Design

Criteria for Nuclear Power Plants, to 10 CFR Part 50, requires the following:

an onsite electric power system and an offsite electric power system with

adequate capacity and capability shall be provided to permit functioning of

structures, systems, and components important to safety.Electric power from

the transmission network to the onsite electric distribution system shall be

supplied by two physically independent circuits (not necessarily on separate

rights of way) designed and located so as to minimize to the extent practical the likelihood of their simultaneous failure under operating and postulated accident

and environmental conditions.

The criterion also requires onsite power systems to have with sufficient independence and

redundancy to perform their safety functions assuming a single failure.

For nuclear power plants not licensed in accordance with the GDCs in Appendix A to

10 CFR Part 50, the updated final safety analysis report provides the applicable design criteria.

These reports set forth criteria similar to GDC 17, which requires, among other things, that an

offsite electric power system be provided to permit the functioning of certain structures, systems, and components important to safety in the event of anticipated operational

occurrences and postulated accidents.

In 10 CFR 50.55a(h)(2), the NRC requires nuclear power plants with construction permits

issued after January 1, 1971, but before May 13, 1999, to have protection systems that meet

the requirements stated in either Institute of Electrical and Electronics Engineers (IEEE)

Standard 279, Criteria for Protection Systems for Nuclear Power Generating Stations, or IEEE

Standard 603-1991, Criteria for Safety Systems for Nuclear Power Generating Stations, and

the correction sheet dated January 30, 1995. For nuclear power plants with construction

permits issued before January 1, 1971, protection systems must be consistent with their

licensing basis or meet the requirements of IEEE Standard 603-1991 and the correction sheet

dated January 30, 1995. These IEEE standards state that the protection systems must

automatically initiate appropriate protective actions whenever a condition the system monitors

reaches a preset level. Once initiated, protective actions should be completed without manual

intervention to satisfy the applicable requirements of the IEEE standards.

IEEE Standard 279, Section 4.2, Single Failure Criterion, states that any single failure within

the protection system shall not prevent proper protective action at the system level when

required. Single failures include such events as open or short circuits.

Appendix A to 10 CFR Part 50 defines single failure as follows:

Single failure means an occurrence which results in the loss of capability of a

component to perform its intended safety functions. Multiple failures resulting

from a single occurrence are considered to be a single failure. Fluid and electric

systems are considered to be designed against an assumed single failure if

neither (1) a single failure of any active component (assuming passive

components function properly) nor (2) a single failure of a passive component

(assuming active components function properly), results in a loss of the capability

of the system to perform its safety functions.1

_____________________

1 Single failures of passive components in electric systems should be assumed in designing

against a single failure.

This footnote emphasizes that for electric systems, no distinction is made between failures of

active and passive components and all such failures must be considered in applying the single

failure criterion.

DISCUSSION

Licensees are required to have two operable circuits between the offsite transmission network

and the onsite Class 1E alternating current electrical power distribution system, as specified in

the technical specifications. Licensees are also generally required to verify correct breaker

alignment and indicated power availability for each required offsite circuit as specified in

technical specification surveillance requirements. The events at Beaver Valley, JAF, and

NMP1, described above, involved offsite power supply circuits that were rendered inoperable by

open-circuited phase and this condition went undetected several weeks because offsite power

was not aligned during normal operation and the surveillance procedures, which recorded

phase-to-phase voltage, did not identify the loss of the single phase.

At Byron, the loss of a single phase did not go undetected, because one of the offsite circuits

was feeding both safety-related buses and some nonsafety-related buses, but instead, it

initiated an electrical transient that resulted in a reactor trip and revealed a design vulnerability

in the protection scheme for the 4.16-kV ESF buses. Specifically, because only one relay

detected the degraded condition, the situation did not meet the conditions of the protection

schemes two-out-of-two logic. As a result, the protection scheme did not automatically

separate the plants safety-related buses from the degraded offsite source and did not start the

EDGs. The Byron Unit 2 licensing basis for the protection scheme for the 4.16-kV ESF buses is

currently under review by the NRC staff.

CONTACT

This IN requires no specific action or written response. Please direct any questions about this

matter to the technical contacts listed below or the appropriate Office of Nuclear Reactor

Regulation (NRR) project manager.

/RA/ /RA/

Laura A. Dudes, Director Timothy J. McGinty, Director

Division of Construction Inspection Division of Policy and Rulemaking

and Operational Programs Office of Nuclear Reactor Regulation

Office of New Reactors

/RA/

Larry W. Camper, Director

Division of Waste Management

and Environmental Protection

Office of Federal and State Materials

and Environmental Management

Technical Contacts: Roy Mathew, NRR Gurcharan Matharu, NRR

301-415-8324 301-415-4057 E-mail: Roy.Mathew@nrc.gov E-mail: Gurcharan.Matharu@nrc.gov

Mohammad Munir, RIII

630-829-9797 E-mail: Mohammad.Munir@nrc.gov

Note: NRC generic communications may be found on the NRC public Web site, http://www.nrc.gov, under NRC Library.

ML120480170 TAC ME7973 OFFICE NRR/DE/EEEB Tech Editor BC:NRR/DE/EEEB D:NRR/DE

NAME RMathew KAzariah-Kribbs JAndersen PHiland

DATE 2/28/12 e-mail 2/27/12 e-mail 2/24/12 e-mail 2/24/12 e-mail

OFFICE BC:RGN-III/DRS/OB LA:PGCB:NRR PM:PGCB:NRR BC:PGCB:NRR

NAME HPeterson CHawes DBeaulieu KMorganbutler

DATE 2/24/12 e-mail 2/29/12 e-mail 2/28/12 2/29/12 e-mail

OFFICE LA:PGCB:NRR FSME/DWMEP D:DCIP:NRO D:DPR:NRR

NAME CHawes LCamper KMcConnell for LDudes TMcGinty

OFFICE 2/29/12 e-mail 3/1/12 3/1/12 3/1/12