Responds to Violations Noted in Insp Repts 50-335/89-23 & 50-389/89-23.Corrective actions:resin-fill Funnels Removed, Gasketed Flanges Installed & Metal Trench Covers Replaced
ML17223A436
Person / Time
Site: Saint Lucie  NextEra Energy icon.png
Issue date: 12/13/1989
From: GOLDBERG J H
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-89-440, NUDOCS 8912200314
Download: ML17223A436 (8)


Text

gCCELZRATEDKFZR1BUTIO>DEMONSTRATIO>~ST~MREGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)DISTRIBUTIONCODE:IEOIDCOPIESRECEIVED:LTRjENCLSIZE:TITLE:General(50Dkt)-InspRept/NoticeofViolationesponseNOTES:g(g$RECIPIENTIDCODE/NAMEPD2-2PDCOPIESLTTRENCL11RECIPIENTIDCODE/NAMENORRIS,JCOPIESLTTRENCL11'CCESSIONNBR:8912200314DOC.DATE:89/12/13NOTARIZED:NOFACIL:50-335St.LuciePlant,Unit1,FloridaPower&LightCo.50-389St.LuciePlant,Unit2,FloridaPower&LightCo.UTH.NAMEAUTHORAFFILIATIONOLDBERG,J.H.FloridaPower&LightCo.RECIP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)

SUBJECT: RespondstoviolationsnotedduringinspofLicensesDPR-57&NPF-16.DOCKET0500033505000389INTERNAL:ACRSAEOD/DEIIBDEDRONRR/DET/DZR8H3NRR/DOEADIR11NRR/DREP/PRPB11NRR/DST/DIRSE2NUDOCS-ABSTRACTOGC/HDS2RESMORZSSEAUPDEXTERNAL:LPDRNSIC22111111112~211111111AEODAEOD/TPADNRRSHANKMAN,SNRR/DLPQ/LPEB10NRR/DREP/PEPB9DNRR/DRIS/DIRNRR/PMAS/ILRB120RMAN,JREGFIL'2RGN2FILE01NRCPDR1111111111111111111111DTOTAL."NUMBEROF,CGPZES.REQUIRED:LTTR27ENCL27 f

P.O.Box14000,JunoBeach,FL334080420APLL-89-44010CFR2.201U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555Gentlemen:Re:St.LucieUnits1and2DocketNos.50-335and50-389InspectionReport.89-23Re1toaNoticeofViolation'IFloridaPower&LightCompanyhasreviewedthesubjectinspectionreport,andpursuanttotheprovisionsof10CFR2.201,theresponseisattached.BasedonadiscussionwithNRCRegionIIStafftheresponsedatewasrevisedtoDecember13,1989.Verytrulyyours,IJ'J>~J.H.GoldbergExecutiveVicePresidentJHG/JRH/rhAttachmentcc:StewartD.Ebneter,RegionalAdministrator,RegionII,USNRCSeniorResidentInspector,USNRC,St.LuciePlant8p122003i48~1~>3PDRADOCKC5000335GPNU

L-89-440AttachmentVIOLATIONA.Unit1TechnicalSpecification6.8.l.a.requiresthatwrittenproceduresshallbeestablished,implemented,andmaintained,'coveringtheactivitiesrecommendedinAppendix"A"ofRegulatoryGuide1.33,revision2,February1978.Appendix"A",paragraph7.a.,recommendsproceduresfortheliquidradioactivewastesystemincluding"demineralizing".Appendix"A"paragraph3.n.,recommendsproceduresforthechemicalandvolumecontrolsystem,whichcontainssomeoftheionexchangersaddressedinthesubjectprocedure.Thesewereimplementedin-partonsitebyoperatingprocedureOP1-0520020,RadioactiveResinReplacement,whichprovidedinstructionsforresinreplacementonvariousionexchangers,includingthe1Dwasteionexchanger.Contrarytotheabove,onAugust20,1989,thelicenseefailedtoimplementtheaboveprocedure.Theprocedurewassignedasbeingcompletefor.the1Dwasteionexchanger;however,theresinfillfunnelwasleftinstalledontheresinfillisolationvalveflangeandexposedtotheweatheruntilSeptember8,1989,whenitwasdiscoveredbyanNRCinspector.Thefillisolationvalve,whichwasapotentialunmonitoredradioactivereleasepoint,islocatedinashallowtrenchontheauxiliarybuildingroof.Thisfillstation,asshownbydiagramsintheFinalSafetyAnalysesReport,wouldnormallybesealedafterresinfillingbyaboltedandgasketedblankflangeandwouldalsobeprotectedbyaboltedmetaltrenchcover.Subsequentprocedurereviewshowedthattheprocedurewasalsoinadequatelyestablished.Itdidnotadequatelyaddressfunnelinstallation/removal;blankflangeremoval,temporarystorage,orreinstallation;stowageinstructionsforthepotentiallycontaminatedfunnel;nordiditprovideadequatemanagementcontrolofdepartmentalinterfacesduringtheprocess.RESPONSEA:1~FloridaPower&Lightconcurswiththeviolation.2~Thecauseoftheviolationwaspersonnelerrorandinadequateprocedure.Theprocedurebeingimplementeddidnotprovidethespecificactionstobeaccomplishedwhenresinreplacementwascomplete.3~4~Theresinfillfunnelswereremoved,gasketedflangesinstalledandthemetaltrenchcoverswerereplaced.OperatingProcedures1-0520020and2-0520020willberevisedto'rovidetheinterdepartmentalcontrolsfortheinstallationandremovaloftheresinfillfunnelsandblankflanges.5.CorrectiveactionsarescheduledtobecompletedbyFebruary1,199 L-89-440AttachmentPg2VIOLATIONB:Units1and2TS6.8.1arequirethatwrittenproceduresshallbeestablished,implemented,andmaintainedcoveringtheactivitiesrecommendedinAppendix"A"ofRegulatoryGuide1.33,revision2,February1978.Appendix"A",paragraph9.aincludesproceduresformaintenanceofsafety-relatedequipment.Thisrequirementwasimplementedinpartbyprocedures1-M-0018and2M0018)MechanicalMaintenanceSafety-RelatedPreventiveMaintenance(PM).Program,thatimplementedPMrequirementsonthestrainersforthebearinglubricatingwaterfortheUnit1and2intakecoolingwater(ICW)pumps.Contrarytotheabove,thesubjectprocedureswereinadequatelyestablishedinthattheydidnotprovideappropriateinspectionguidanceconcerningself-cleaningstrainersandy-typestrainersinthebearinglubricatingwatersystemsfortheICWpumps.Theproceduresdidnotprovidestrainerinspectionacceptancecriteria,servicelimits,orrepairspecifications.Thelackofinspectionguidanceallowedachangeinstrainermeshsizetogounquestionedandexcessivedeteriorationofself-cleaningstrainerstobeunrecognized.ThechangeinstrainermeshsizewasamajorcontributortolAICWpumpbearingfailurescausedbyy-typestrainerblockage.RESPONSEB'loridaPower&Lightconcurswiththeviolation.2~Thecauseoftheviolationwasaninadequateprocedure.Theinspectionacceptance.criteria,servicelimits,andsparepartsinformationwerenotprovidedin'theICWpumpbearinglubricatingwatersystempreventativemaintenanceactivities.(PMfilenumbers153,154,155,and156forUnit1andPMfilenumbers00501,00502,00503,and00504forUnit2).TheseactivitiesarespecifiedintheMechanicalMaintenanceSafety-RelatedPreventive,MaintenanceProgramProcedures(1-M-0018and2-M-0018).3~Thepreventativemaintenance(PM)activitiesfortheICWpumpbearinglubricatingwatersystemspecifiedinprocedures1-M-0018and2-M-0018havebeen'evisedtoprovidetheinspectionacceptancecriteria,repairguidelinesandsparepartsinformatio L-89-440AttachmentPg34ThemaintenancedepartmentwillreviewarepresentativesampleofotherPMsinprocedures1-M-0018and2-M-0018todetermineif'heinspectionacceptancecriteria,repairguidelinesandsparepartsinformationareincluded..Basedon.theresultsofthisreviewthecorrectiveactionsspecifiedinitem,3abovewillbeexpandedtoincludeadditionalPMactivitiesaswarranted.ThisreviewisscheduledtobecompletedbyJanuary31,1990.5.Item3abovewascompletedonOctober30,198 P