Ack Receipt of Informing NRC of Actions Taken to Correct Violations Noted in Insp Rept 50-333/86-11
ML20214K729
Person / Time
Site: FitzPatrick 
Issue date: 11/25/1986
From: Ebneter S
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Radford Converse
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
References
NUDOCS 8612020437
Download: ML20214K729 (2)


Text

e.

..

Y NOV 2 5 EliS y

Docket No. 50-333 Power Authority of the State of New York James A. FitzPatrick Nuclear Power Plant ATTN: Mr. Radford J. Converse Resident Manager P. O. Box 41 Lycoming, New York 13093 Gentlemen:

Subject:

Inspection No. 86-11 This refers to your letter dated September 8,1986, in response to our letter dated August 8, 1986.

Thank you for informing us of the corrective and preventive actions documented in your letter. These actions will be examined during a future inspection of your licensed program.

Your cooperation with us is appreciated.

Sincerely, Original Signed Ey:

Lee H. Bettenhousen Stewart D. Ebneter, Director Division of Reactor Safety cc:

J. P. Bayne, First Executive Vice President and Chief Operations Officer A. Klausmann, Vice President - Quality Assurance and Reliability R. L. Patch, Quality Assurance Superintendent George M. Wilverding, Chairman, Safety Review Committee Gerald C. Goldstein, Assistant General Counsel NRC Licensing Project Manager Dept. of Public Service, State of New York Public Document Room (PDR)

local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector State of New York 8612O20437 861125 PDR ADOCK 05000333 G

PDR OFFICIAL RECORD COPY IR FITZ 86-11 - 0001.0.0 11/03/86

\\

\\

1'7CD\\

(

.

. _.

.

.

- -.

-.

.

-

.

--.

.

.

.

New York Power Authority

.i k

I bec w/ encl:

Region I Docket Room (with concurrences)

Management Assistant, DRMA (w/o enc 1)

Section Chief, DRP Robert J. Bores, DRSS

>

!

b

'

RI:DRS N

RI:DRS W. Oliveira/fi L. Bettenhausen 1$/g86 1 9 86

'

0FFICIAL RECORD COPY IR FITZ 86-11 - 0002.0.0 11/03/86

,

,

,,..,-,-

,,-,

,

-

, - -,, --- -


- -, - - - - - - -,

-

- - -

-

F

.

Jf rm,3 A FatsPetreck

.

Cuclear Power Plant

.

'

PO Boa 41 Lycomog. New York 13093

^

315 342 3840 Radford J. Converse

-

" " * " ' " ' " * "

  1. > NewYorkPbwer 4# Authority September 8, 1986 JAFP 86-0747 United States Nuclear Regulatory Commission Region I 631 Park Avenue Kina. of Prussia, PA 19406 Attention: Stewart D. Ebneter, Director Division of Reactor Safety Subject:

JAMES A. FITZPATRICK NUCLEAR POWER PLANT DOCKET NO. 50-333 INSPECTION 86-11 Gentlemen:

In accordance with the provisions of 10 CFR 2.201, we are submitting our response to Appendix A Notice Of Violation transmitted by your letter dated August 08, 1986, as received by the undersigned on August 14, 1986. This refers to the inspection conducted by Mr. William Oliveira of your office on July 14-18, 1986, at the James A. FitzPatrick Nuclear

'

Power Plant.

A)

NOTICE OF VIOLATION As a result of the inspection conducted on July 14-18, 1986, and in accordance with the NRC Enforcement Policy (10 CFR 2.

Appendix C), the following violation was identified:

10 CFR 50 Appendix B, Criterion XIII states:

"Meacures shall be established to control..... storage.....and preservation of material and equipment...to prevent damage or i

deterioration......"

l Paragraph 6.4.2 of ANSI N45.2.2-1972, committed to by the

,

licensee in FSAR Chapter 17, Appendix 17.2.B. requires the

" Care of Items" in storage, including periodic rotation of shafts or rotating equipment and other in-storage maintenance requirements specified by the manufacturer.

,

r

__

To: United Stetso Nucloor R2gulat.ory Commission Sspt. 8, 1986

.

Attcntion: Stcw;rt D. Ebneter, Dircctor JAFP 86-0747

-

-

Subject: JAMES A. FITZPATRICK NUCLEAR POWER PLANT Pcgo -2-DOCKET NO. 50-333 INSPECTION NO. 86-11

.

i Contrary to the above as of July 18, 1986 the licensee's measures for the care of items in storage was inadequate as evidenced by the following examples:

1.

The shafts of safety related Residual Heat Removal System Pumps procured under Purchase Order (PO) 84-2595 and stored since April 1984 were not rotated on monthly basis as specified by the manufacturer.

2.

Safety related cylinders procured under PO 83-1491 and stored since November 1983 were not lubricated and cycled as specified by the manufacturer.

B)

RESPONSE TO NOTICE OF VIOLATION The Power Authority agrees with this finding:

The fundamental cause of this violation is the lack of a fully implemented, comprehensive in-storage maintenance program.

Specifically, although an engineering evaluation and interim procedure had been implemented in response to a prior inspection finding (NRC Inspection 84-11), that action had only addressed stock warehouse inventory spara parts and components. What was not addressed were those direct turnover purchases stored for use in the "near future". The largest category of concern are those components purchased for future modifications.

The short term corrective action for this violation will be to upgrade the interim procedure by December 1, 1986 to address direct turnover purchases. This interim procedure establishes minimum test requirements for selected components to ensure that material which could be deficient as a result of improper storage, is not installed in plant systems.

The permanent corrective action will be as follows:

1)

Develop a storage maintenance administrative program by March 30, 1987. This program will establish certain minimum generic maintenance requirements and will specify how vendor reconunendations are to be evaluated and incorporated into the progra To:

United States Nucisar Reguletory Commission Szpt. 8, 1986

.,_

Attentian: Stew:rt D. Ebnetcr, Dircctor JAFP 85-0747

-

'

Subjcct: JAMES A. FITZPATRICK NUCLEAR POWER PLANT P go -3-

.

,

DOCKET NO. 50-333 INSPECTION NO. 86-11

.

t 2)

Upon completion of the administrative program, i

implementation will be as follows:

a)

For new purchases, implement immediately.

b)

For existing material in stock, perform an initial review of Category 1 components and implement the defined generic maintenance requirements. This will be done by July 30, 1987.

c)

Perform a systematic review and evaluation of Category 1 material presently in inventory to identify and define the total storage maintenance requirements.

In particular, specific vendor reconumendations will be evaluated at this time.

This activity will be conducted in conjunction with the overall systematic component review effort which is part of the ongoing maintenance program upgrade.

,

The effort to identify and define storage maintenance requirements will begin in the second quarter of 1987. The Authority estimates completior.

in early 1989 for safety and non-safety related components. Initial priority will be with the safety related components and spare parts.

Very truly yours,

/

4%,< <,,<,/,W

'

RADFORD J. CONVERSE RJC:WF:fah CC: RMS for Headquarters Distribution: WPO W. Fernandez R. Baker P. LoTempio R. Ramstad R. Patch

'

V. Walz J. Flaherty NRC Resident Inspector NRCI 86-11 File Doctunent Control Center CERTIFIED MAIL - RETURN RECEIPT REQUESTED