IR 05000244/2010005

From kanterella
Jump to navigation Jump to search
IR 05000244-10-005, on 10/01/2010 - 12/31/2010, R. E. Ginna Nuclear Power Plant, Routine Integrated Inspection Report
ML110200327
Person / Time
Site: Ginna Constellation icon.png
Issue date: 01/20/2011
From: Hunegs G
Reactor Projects Branch 1
To: John Carlin
Constellation Energy Nuclear Group, Ginna
Hunegs G
References
IR-10-005
Download: ML110200327 (26)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION

REGION I

475 ALLENDALE ROAD KING OF PRUSSIA. PA 19406-1415 January 20, 2OII

SUBJECT:

R.E. GINNA NUCLEAR POWER PLANT - NRC INTEGRATED REPORT 05000244t201 0005

Dear Mr. Carlin:

on December 31 ,z)1},the u.s. Nuclear Regulatory commission (NRC) completed an integrated inspection report inspection at your R.E. binna Nuclear Power}lant. The enclosed 18,2011, with Mr' Eric documents the inspection results, which were discussed on January Larson and other members of your statf'

as they relate to safety and The inspection examined activities conducted under your license with the conditions of your license'

compliance with the commission's rules and regulations and activities, and interviewed The inspectors reviewed selected procedures a-nd records, observed personnel.

Based on the results of this inspection, no findings were identified'

a copy of this letter and its ln accordance with 1O CFR 2.390 of the NRC's "Rules of Practice,"

for P!q!t inspection in-11" enclosure, and your response (if any) will be available electronically (PARS) component of the NRC public Document Room or from the Fublicly Available Records from the NRC Web site at NRC's document rvrf11 tAoAMS). ADAMS is accessible (the Public Electronic Reading Room)'

Sincerely,

  • -L1 Go'rdon Hunegs, Projects Branch 1 Division of Reactor Projects Docket No. 50-244 License No. DPR-18 Enclosure: lnspection Report No. 0500024412010005 w/ Attachment: Supplemental Information

SUBJECT:

R.E. GINNA NUCLEAR POWER PLANT - NRC INTEGRATED INSPECTION REPORT 050002441201 0005

Dear M

SUMMARY OF FINDINGS

lR 0500024412010005;1010112010 - 1213112010; R.E. Ginna Nuclear Power Plant, LLC (Ginna), Routine Integrated Inspection Report.

The report covered a three-month period of inspection by resident inspectors and region-based inspectors. The NRC's program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, "Reactor Oversight Process," Revision 4, dated December 2006.

No findings were identified.

REPORT DETAILS

Summarv of Plant Status R.E. Ginna Nuclear Power Plant (Ginna) began the inspection period operating at full rated thermal power and operated at full power for the entire period.

REACTOR SAFETY

Gornerstones: Initiating Events, Mitigating Systems, and Barrier Integrity

1R01 Adverse Weather Protection (71111.01 - Two samples)

.1 Cold Weather Preparations

a.

lnsoection Scope The inspectors performed a review of the cold weather preparation program and implementing procedures at Ginna before the arrival of sustained periods of cold weather. The review assessed the effectiveness of Ginna's cold weather readiness program to ensure systems would remain functional and available during cold weather conditions as specified by technical specifications (TSs). The inspectors conducted discussions with control room operators to understand protective measures applicable to these systems. The inspectors performed field walkdowns of the systems per Ginna procedure O-22, "Cold Weather Walkdown Procedure," Revision 00601, to evaluate the material condition and functionality of the freeze protection equipment (e.9., heat tracing, instrumentation, and ventilation).

b.

Findinos No findings were identified.

.2 lmrninent Adverse Weather

a.

lnspection Scope On November 17, 2010, the National Weather Service issued a wind advisory with expected wind gusts up to 50 miles per hour. Operators entered ER-SC.1, "Adverse Weather Plan," Revision 01700, due to the adverse weather condition. The inspectors observed operator actions that were associated with the procedure and toured areas of the plant that could be adversely affected by high wind conditions. Areas of focus included the intake structure and station transformers.

b.

Findinqs No findings were identified.

1R04 Equipment Aliqnment

.1 Partial Svstem Walkdown (71111.04Q

- Three samples)a. lnspection Scope The inspectors reviewed the alignment of system valves and electrical breakers to ensure proper in-service or standby configurations as described in plant procedures, piping and instrument drawings (P&lDs), and the updated final safety analysis report (UFSAR). During the walkdown, the inspectors evaluated the material condition and general housekeeping of the system and adjacent spaces. The inspectors also verified that operators were following plant TSs and system operating procedures. The inspectors performed a partial walkdown of the following systems:

.

The electrical lineup for offsite power system circuit 7T when offsite power system 767 was out of service (OOS) for planned maintenance;

.

The'A'emergency diesel generator (EDG) when the 'B' EDG was OOS for planned maintenance; and

.

The 'A' train of the motor-driven auxiliary feedwater (MDAFW) system when the 'B' train of MDAFW was OOS for planned maintenance.

b. Findinqs No findings were identified.

.2 Complete Walkdown (71111.04S

- One sample)

a. Inspection Scope

The inspectors performed a detailed walkdown of the spent fuel pool (SFP) cooling system to identify any discrepancies between the existing equipment lineup and the specified lineup. The SFP cooling system was chosen because of its risk-significant function to remove decay heat from spent fuel assemblies. The inspectors verified proper system alignment as specified by TSs, UFSAR, plant procedures, and P&lDs.

Documentation associated with open maintenance requests and design issues were reviewed and included items tracked by plant engineering to assess their collective impact on system operation. In addition, the inspectors reviewed the associated corrective action database to verify that any equipment alignment problems were being identified and appropriately resolved.

b. Findinqs No findings were identified.

1R05 Fire Protection (711 11.05)

.1 Quarterlv lnspection (71111.05Q

- Five samples)

a. Inspection Scope

The inspectors performed walkdowns of fire areas to determine if there was adequate control of transient combustibles and ignition sources. The material condition of fire protection systems, equipment and features, and the material condition of fire barriers were inspected against Ginna's licensing basis and industry standards. In addition, the passive fire protection features were inspected including the ventilation system fire dampers, structural steelfire proofing, and electrical penetration seals. The following plant areas were inspected:

r Turbine Building Basement (Fire Zone TB-1);

.

Intermediate Building Clean Side Basement (Fire Zone IBN-1);

.

Intermediate Building Main Steam Header Floor (Fire Zone IBN-2);

.

Intermediate Building Clean Side Fan Floor (Fire Zone IBN-3); and

.

Intermediate Building Clean Side Top Floor (Fire Zone IBN-4).

b. Findinos No findings were identified.

1R06 Flood Protection Measures

.1 Internal Floodinq (71111.06

- One Sample)

a. Inspection Scope

The inspectors evaluated Ginna's internal flood protection measures for the intermediate building to verify that Ginna had implemented appropriate measures to reduce the possibility that this area could be damaged by internal flooding. This area was selected given its risk significance to internal flooding events as outlined in Ginna's probabilistic risk assessment (PRA). To perform this evaluation, the inspectors reviewed the UFSAR, integrated plant safety assessment, condition reports (CRs), plant change records, and various flooding analyses for equipment located in the areas of the concern. During the field walkdown, to the extent practicable, the condition of flood mitigation equipment was examined by inspectors.

b. Findinqs No findings were identified.

.2 Annual Review of Cables Located in Underqround BunKers/Manholes (71111.06

- One Sample)a.

lnspection Scope On October 21,2010, Ginna performed an inspection of cables located in manholes under work order (WO) C91028373 using procedure CNG-AM-1.01-1029, "Medium Voltage Cable Program," Revision 0000, The lnspectors viewed manholes number two, three, three east, and three west which contained offsite power circuits. The inspectors noted that the offsite power cables had previously been submerged and that Ginna had implemented a preventive maintenance (PM) program to pump out water that accumulated in the manholes. The inspectors verified by direct observation that the cables were not submerged in water. The inspectors observed that the offsite power supply splice in manhole number two appeared to be intact and that degraded or missing cable supports did not impact cable integrity.

b. Findings

No findings were identified.

1R1 1 Licensed Operator Requalification Proqran'l Q1111.11)

.1 Resident Inspector Quarterlv Review (71111.11Q

- One sample)

a. Inspection Scope

On November 3, 2010, the inspectors observed licensed operator simulator scenarios, E2ECA21-03, Revision 03, and E3ECA33-01, Revision 03. The inspectors reviewed the critical tasks associated with the scenarios, observed the operators' performances, and observed the post-evaluation critiques. The inspectors also reviewed and verified compliance with Ginna procedure OTG-2.2, "Simulator Examination Instructions,"

Revision 43.

b.

Findinqs No findings were identified.

,2 Biennial Review (71111.1 1B - One sample)lnspection Scope The following inspection activities were performed using NUREG-1021, "Operator Licensing Examination Standards for Power Reactors," Revision 9, Inspection Procedure (lP) 71 111.11, "Licensed Operator Requalification Program," Appendix A, "Checklist for Evaluating Facility Testing Material," and Appendix B, "Suggested Interview Topics."

The inspectors reviewed documentation of operating history since the last requalification program inspection. Documents reviewed included NRC inspection reports, licensee event reports, Ginna's corrective action program (CAP) documents, and the most recent NRC plant issues matrix. The inspectors also reviewed specific events from Ginna's CAP that involved human performance issues for licensed operators to ensure that operational events were not indicative of possible training deficiencies. The operating tests for weeks one, two, and three of the exam cycle were reviewed for quality and performance.

On December 12,2010, the results of the annual operating tests for the year 2010 were reviewed to determine if pass fail rates were consistent with the guidance of NUREG-1021 and NRC Manual Chapter 0609, Appendix l, "Operator Requalification Human Performance Significance Determination Process." The inspectors verified that:

e Crew pass rates were greater than 80 percent (pass rate was 85.7 percent);r lndividual pass rates on the dynamic simulator test were greater than 80 percent (pass rate was 100 percent); and

.

Individual pass rates on the job performance measures of the operating exam were greater than 80 percent (pass rate was 100 percent).

Observations were made of the dynamic simulator exams and job performance measures (JPMs) administered during the week of November 8, 2010. These observations included facility evaluations of crew and individual performance during the dynamic simulator exams and individual performance of five JPMs. Remediation plans for 14 crew/individual exam failures were reviewed to assess the effectiveness of the remedial training. A license activation was reviewed to ensure that license conditions and applicable program requirements were met. Operators, instructors, and training/operations management were interviewed for feedback on their training program and the quality of training received. Simulator performance and fidelity were reviewed for conformance to the reference plant control room. A sample of records for requalification training attendance, program feedback, reporting, and medical reports were reviewed for compliance with license conditions, including NRC regulations.

b. Findinqs No findings were identified.

1R12 Maintenance Effectiveness (71111.12Q -Two samples)

a. Inspection Scope

The inspectors evaluated work practices and follow-up corrective actions for selected systems, structures, and components (SSCs) for maintenance effectiveness. The inspectors reviewed the performance history of those SSCs and assessed extent-of-condition determinations for those issues with potential common cause or generic implications to evaluate the adequacy of corrective actions. The inspectors reviewed Ginna's problem identification and resolution actions for these issues to evaluate whether Ginna had appropriately monitored, evaluated, and dispositioned the issues in accordance with procedures and the requirements of 10 CFR Part 50.65, "Requirements for Monitoring the Effectiveness of Maintenance." ln addition, the inspectors reviewed I

selected SSC classifications, performance criteria, goals, and corrective actions that were taken or planned to verify whether the actions were reasonable and appropriate.

The following issuesisystems were reviewed:

.

SFP cooling system; and o Repetitive set point drift on temperature module 4048 as documented in CRs 2010-527 6, 201 0-5304, 2010-5459, 20 1 0-5538, and 20 1 0-57 41. Temperature module 4048 is an input into the over temperature delta 'T' reactor trip in the reactor protection system (RPS).

b. Findinqs No findings were identified.

1R13 Maintenance Risk Assessments and Emeroent Work Control (71111.13 - Four samples)

a. Inspection Scope

The inspectors evaluated the effectiveness of Ginna's maintenance risk assessments required by 10 CFR Part 50.65(a)(a). The inspectors discussed the use of Ginna's online risk monitoring software with control room operators and scheduling department personnel. The inspectors reviewed equipment tracking documentation and daily work schedules, and performed plant tours to verify that actual plant configuration matched the assessed configuration. Additionally, the inspectors verified that risk management actions, for both planned and emergent work, were consistent with those described in CNG-OP-4.01-1 000, "lntegrated Risk Management," Revision 00601.

Risk assessments for the following OOS SSCs were reviewed:

r Planned maintenance and testing of the turbine-driven auxiliary feedwater (TDAFW)pump and the'B' component cooling water (CCW) pump while circuitT6T was OOS (October 25,2010);o Emergent work on the 'B' MDAFW pump during scheduled maintenance on the 'A' MDAFW pump and bus 18 (November 5, 2010);o Planned maintenance and testing on the 'B' EDG and pressure transmitter 420 reactor coolant system (RCS) pressure loop 420 (week of November 8, 2010); and o Planned maintenance and testing on the TDAFW system and the'A' EDG (week of November 29,2010).

b. Findinss No findings were identified.

1R15 Operabilitv Evaluations (71111.15 - Five samples)

a. Inspection Scope

The inspectors reviewed operability evaluations and/or CRs in order to verify that the identified conditions did not adversely affect safety system operability or plant safety.

The evaluations were reviewed using criteria specified in NRC Regulatory lssue Summary 2A05-20, "Revision to Guidance formerly contained in NRC Generic Letter (GL) 91-18, Information to Licensees Regarding Two NRC Inspection Manual Sections on Resolution of Degraded and Nonconforming Conditions and on Operability," and Inspection Manual Part 9900, "Operability Determinations and Functionality Assessments for Resolution of Degraded or Nonconforming Conditions Adverse to Quality or Safety." In addition, where a component was inoperable, the inspectors verified the TS limiting condition for operation implications were properly addressed.

The inspectors performed field walkdowns, interviewed personnel, and reviewed the following items:

.

CR 2010-5103, Submerged Cables Found During Inspection of Manholes;

.

CR 2010-6857, Degraded Cable Supports Found in Off-Site Power Manhole;

.

CR 2010-3208, Boric Acid Residue and Corrosion Found in Containment Recirculation Fan Chiller Enclosures;

.

CR 2010-5660, Crack Discovered in Containment Concrete Exceeding Reporting Criteria; and

.

CR 2010-6141, Condensate Storage Tank (CST) Water Volume Contained in TS 3.7.6 May Be Non-Conservative.

b. Findinqs No findings were identified.

1R18 Plant Modifications

.1 Temporarv Modification

- (71111.18 - One sample)

a. Inspection Scope

The inspectors reviewed engineering change package (ECP) 10-000687, "Routing the Discharge Path from 'B' SFP Heat Exchanger (HX) Directly to the SFP." The ECP consisted of establishing a temporary path by cutting the piping on the discharge side of the 'B' SFP HX, welding a new flange to the pipe cut, and attaching a temporary hose section from the flange to the SFP. The inspectors reviewed the ECP to ensure that the replacement components were consistent with design basis and were compatible with installed SSCs. The inspectors observed actions taken by personnel to complete the modification and test the resultant configuration.

Findinqs No findings were identified.

Permanent Modifications (71111.18 - Two samples)

Inspection Scope The inspectors reviewed ECP 2009-0208, 'TDAFW Governor Control Valve (CV) 9519E Replacement with Enhanced Materials," Revision 0. The ECP consisted of replacing the TDAFW governor CV with a new valve assembly made of materials less susceptible to corrosion. The inspectors reviewed the ECP to determine whether the permanent change adversely affected system availability or a function important to plant safety. The inspectors reviewed the associated system design bases to ensure that the replacement components were consistent with design bases and were compatible with installed SSCs. The inspectors observed actions taken by personnel to complete the modification and test the resultant configuration.

The inspectors reviewed ECP 2009-0251, "lnstall New Circuit Breaker and Contactor for Control Room Emergency Air Treatment System (CREATS) 'A' Fan," Revision 1. The ECP consisted of replacing the CREATS 'A'fan supply breaker with a larger capacity breaker to increase the margin between the maximum motor starting current and the trip point of the circuit breaker. The inspectors reviewed the ECP to determine whether the permanent change adversely affected system availability or a function important to plant safety. The inspectors reviewed the associated system design bases to ensure that the replacement components were consistent with design bases and were compatible with installed SSCs. The inspectors observed actions taken by personnel to complete the modification and test the resultant configuration.

b. Findinqs No findings were identified.

1R19 Post-Maintenance Testinq (71111.19 - Six samples)

a. Inspection Scope

The inspectors observed portions of post-maintenance testing (PMT) activities in the field to determine whether the tests were performed in accordance with approved procedures. The inspectors assessed each test's adequacy by comparing the test methodology to the scope of maintenance performed. In addition, the inspectors evaluated the test acceptance criteria to verify that the tested components satisfied the applicable design and licensing bases and TS requirements. The inspectors reviewed the recorded test data to determine whether the acceptance criteria were satisfied.

The following PMT activities were reviewed:

.

STP-O-31A, "Charging Pump 'A' Inservice Test (lST)," Rev. 00401, STP-O-318, "Charging Pump 'B' lST," Rev. 00501, and STP-O-31C, "Charging Pump 'C' lST,"

Rev. 00301, to test the charging pumps following maintenance under WO C91019394, "Replace 'B' Charging Pump Discharge Relief Valve 284," (October 12, 2010);o STP-O-16QB,

.AFW Pump 'B'- Quarterly," Rev. 0, to test the'B' MDAFW pump recirculation air-operated valve 43108 following maintenance performed under WO C91056203, "Significant Air Leakage from Swage Lock Fitting Upstream Valve 43108," (November 5, 2010);r STP-O-12.1QC, "Safety Injection (Sl) Pump 'C' lST," Rev. 00300, to test the 'C' Sl pump supply breaker following maintenance performed under WO C90830160, .PM Inspection on Breaker 52lSlP1C2, Sl Pump 'C' Motor Supply from Bus 14,"

(November 5,2010);o STP-O-12.2, "EDG 'B'," Rev. 00800, following maintenance performed under WO C90866162, "Perform Routine PM and Inspection on D/G18," (November 12,2010);o STP-O-13, "Fire Pump Operation and System Alignment," Rev. 00005, to test the diesel fire pump after maintenance performed under WO C90818614, "Perform Inspection and Maintenance on the Diesel Fire Pump," (November 23,2010); and o STP-O-16-COMP-T, "AFW Turbine Pump - Comprehensive Test," Rev. 01400, to test the TDAFW system following maintenance performed under WO C90694245, "Replace TDAFW Governor CV 9519E Per ECP 2009-0208," (December 1, 2010).

b. Findinqs No findings were identified.

1R22 Surveillance Testinq (71111.22 - Five samples)

a. lnspection Scope The inspectors observed the performance and/or reviewed test data for the following surveillance tests that are associated with selected risk-significant SSCs to verify that TSs were followed and that acceptance criteria were properly specified. The inspectors also verified that proper test conditions were established as specified in the procedures, no equipment preconditioning activities occurred, and acceptance criteria were met.

.

STP-O-16-COMP-T, "AFW Turbine Pump - Comprehensive Test," Rev. 01300 (October 25,2010);

.

STP-O-2.8Q, "CCW Pump Quarterly Test," Rev. 00501 (October 25,2010);

.

S-12.4, "RCS Leakage Surveillance Record Instructions," Rev. 05401 (November 1, 2010);

.

STP-O-12.6A, "Diesel Generator Fuel OilTransfer Pump'A'Test," Rev. 0400 (November 6,2010); and

.

STP-O-16QA, "AFW Pump 'A'- Quarterly," Rev. 00500 (November 6, 2010).

b. Findinqs No findings were identified.

Cornerstone: Emergency Preparedness

lEPO Drill Evaluation (71114.06 - One sample)

a. Inspection Scope

On October 26,2010, the inspectors observed portions of a scheduled drill, number GIN-EP-ID-10-10, of Ginna's emergency preparedness organization. Following the drill, the inspectors observed the post-drill critique and assessment of the technical support center (TSC) performance during the drill. The drill scenario included an earthquake, flooding, loss of coolant accident, and containment failure. The inspectors verified that emergency classification declarations and notifications were completed in accordance with 10 CFR Part 50.72,10 CFR Part 50 Appendix E, and emergency plan implementing procedures. The inspectors verified that the TSC post-drill critique was thorough and drill enhancements were identified in Ginna's CAP.

b. Findinqs No findings were identified.

OTHER ACTIVITIES

4OA1 Performance lndicator Verification

Cornerstone: Mitiqatinq Svstems (71151- Two samples)

a. Inspection Scope

The inspectors completed a review of mitigating systems performance index (MSPI) data including a review of Ginna's train/system unavailability data, monitored component demands, and demand failure data. As part of this review, Ginna's MSPI basis document, "Ginna Nuclear Power Plant MSPI Basis Document," Revision 5, and Nuclear Energy Institute (NEl) 99-02, "Regulatory Assessment Performance lndicator (Pl)

Guideline," Revision 6, were examined. To verify the accuracy of the data, the inspectors reviewed monthly operating reports, NRC inspection reports, and Ginna event reports from August 2009 to December 2Q10. The inspectors also reviewed OOS logs, operating logs, and maintenance rule information to determine the accuracy and completeness of the reported unavailability data. For the selected systems, a review of maintenance and test history confirmed the accuracy of demand failure data for the identified active components for the most recent 12 quarters. The MSPIs reviewed included:

.

RHR System; and

.

Cooling Water Systems (CCW and service water (SW) systems).

b. Findinqs No findings were identified.

4c.A2 Problem ldentification and Resolution (7 1152)

.1 Continuous Review of ltems Entered into the Corrective Action Proqram

a. Inspection Scope

As specified by lP 71152, "ldentification and Resolution of Problems," and in order to help identify repetitive equipment failures or specific human performance issues for follow-up, the inspectors performed a daily screening of items entered into Ginna's CAP.

This review was accomplished by reviewing electronic copies of CRs, periodic attendance at daily screening meetings, and accessing Ginna's computerized database.

Findinqs No findings were identified.

.2 Semi-Annual Review (71152

- One sample)lnspection Scope The inspectors performed a semi-annual review of site issues to identify trends that might indicate the existence of more significant safety issues as required by lP 71152.

The inspectors included in this review repetitive or closely related issues that may have been documented by Ginna outside of the CAP such as trend reports, Pls, major equipment problem lists, system health reports, maintenance rule assessments, and maintenance or CAP backlogs. The inspectors also reviewed Ginna's CAP database for the period of June through December 2010 to assess CRs written in various subject areas (equipment problems, human performance issues, etc.) as well as individual issues identified during the NRC daily CR review. The inspectors reviewed Ginna's quality and performance assessment report for the period of May 1 through August 31, 2010, performed under CNG-QL-1

.01 -1008, "Quarterly Report Process," Revision

00200, to verify that Ginna personnel were appropriately evaluating and trending adverse conditions in accordance with applicable procedures.

b. Findinqs and Observations No findings were identified. No trends were noted that indicated a potential safety significant issue. The inspectors verified that Ginna appropriately identified trends and captured them in the CAP, performance monitoring program, system health reports, and quality assurance assessments. Examples of trends identified by Ginna were trends in the areas of configuration control, and procedure use and adherence. The inspectors also identified an increase in the number of CRs related to turbine generator vibrations, risk assessment, and emergency lighting. Ginna documented these apparent trends in their CAP under CRs 2010-0109, 2010-01 1 1 , and 2010-0114.

.3 Annual Sample: Increase in SFP Leak Rate (71152- One sample)

Inspection Scope Ginna has experienced relatively stable SFP leakage since 2006. The leakage rate has been partially mitigated by vacuum boxes that have been installed over known SFP liner cracks. CR 2010-5887, "SFP Leak-Off Rate Increased," identified that on September 26,2010, the SFP under liner leakage collection system leak rate increased from approximately 380 to 880 milliliters per minute. The inspectors assessed Ginna's problem identification threshold, cause analyses, functionality determination, and the prioritization and timeliness of corrective actions to determine whether Ginna was appropriately identifying, characterizing, and correcting problems associated with SFP liner leakage.

b. Findinqs and Observations No findings were identified. Ginna appropriately implemented their corrective action process regarding the increase noted in SFP liner leakage. Elements of the corrective actions were detailed and thorough. Interim corrective actions were appropriate to identify potential groundwater contamination. Long-term corrective actions include permanent liner repairs scheduled for 2011. The inspectors confirmed that Ginna was adequately monitoring and trending relevant parameters including calcium and iron concentration in the leakage so that worsening conditions could be evaluated.

.4 Annual Sample: Assessment of Corrective Actions Associated with Inadequate Water

Manaqement (71152 - One Sample)

a. Inspection Scope

The inspectors reviewed the corrective actions associated with CR 2010-3155, which described inadequate station water management and the use of a standby station water management (CNC - Chemical Nuclear Cleanup) system, to determine if the documentation was complete and accurate and entered in a timely manner. The corrective actions were reviewed for the evaluation and disposition of operability and reportability, consideration of extent of condition and cause, generic implications, common cause, and previous occurrences. The corrective actions were further reviewed to determine if the classification and prioritization of the problem's resolution was commensurate with its safety significance.

The inspectors reviewed various related documents and interviewed station personnel involved in station water management. The derived information was compared with the corrective actions' identification of root and contributing causes of the problem, The comparison focused on the identification of the significant condition adverse to quality, the cause of the condition, and the corrective actions taken. The inspectors verified that the documented information was reported to the appropriate level of management. The inspectors reviewed the corrective actions to verify the actions were appropriately focused, that the corrective actions taken would preclude repetition, and that corrective actions were completed in a timely manner commensurate with the safety significance of the issue. In addition, the inspectors compared the corrective actions against related negative trends associated with human or equipment performance to determine if the corrective actions could potentially impact nuclear safety. Finally, the inspector reviewed operating experience to verify that it was adequately evaluated for applicability, and applicable lessons learned were communicated to appropriate organizations and implemented.

b, Findinos and Observations No findings were identified. Ginna appropriately implemented their corrective action process. The cause and corrective actions that were developed were detailed and thorough.

40A6 Meetinos, Includinq Exit Exit Meetinq Summarv On January 18, 2011, the resident inspectors presented the inspection results to Mr. Eric Larson and other members of his staff, who acknowledged the findings. The inspectors verified that none of the material examined during the inspection is considered proprietary in nature.

ATTACHMENT:

SUPPLEMENTAL INFORMATION

SUPPLEMENTAL INFORMATION

KEY PO.INTS OF CONTACT

Licensee Personnel

J. Carlin Vice President, Ginna
J. Bowers General Supervisor, Radiation Protection
T. Hedges Director, Emergency Preparedness

E. Larson Plant General Manager

K. Mclaughlin General Supervisor, Shift Operations
T. Paglia Manager, Integrated Work Management
S. Snowden General Supervisor, Chemistry
J. Sullivan Manager, Operations
P. Swift Manager, Engineering Services

LIST OF ITEMS OPENED, CLOSED, AND DISCUSSED

None.

LIST OF DOCUMENTS REVIEWED

Section 1R01: Adverse Weather Protection

Document

UFSAR

Procedures

ER-SC.1, Adverse Weather Plan, Rev. 01700

O-22, Cold Weather Walkdown Procedure, Rev. 00601

Section 1R04: Equipment Aliqnment

Documents

Engineer Work Request 15948, SFP Cooling

UFSAR

Procedure

AR-K-29, SFP Hi Temp 115 Degrees Fahrenheit Hi-Lo Level, Rev. 013

Drawinqs

33013-1248, SFP Cooling, Rev. 036

33013-2539, Air Conditioning System Plant Load Distribution, Rev. 021

33013-1237, AFW P&lD, Rev.57

Condition Reports

2010-6775

2010-6722

Section 1R05: Fire Protection

Document

Ginna Fire Protection Plan, Rev. 5

Procedures

FRP-11.0, Intermediate Building Clean Side Basement, Rev. 00904

FRP-12.0, Intermediate Building Main Steam Header Floor, Rev. 00702

FRP-13.0, Intermediate Building Clean Side Fan Floor, Rev. 00802

FRP-14.0, Intermediate Building Clean Side Top Floor, Rev. 00802

FRP-21.0, Turbine Building Basement, Rev. 01100

Drawinos

33013-2545, Fire Response Plan Intermediate Building Operating Floor El. 253' 3", Rev. 9

33013-2551, Fire Response Plan Intermediate Building Operating Floor El. 278' 4" &274'6",

Rev.7

33013-2544, Fire Response Plan Turbine Building Basement Floor El. 253' 6", Rev. 11

Section 1R06: Flood Protection Measures

Documents

G1-1F-001, Ginna PRA Internal Flooding Analysis Notebook

Double Seal Cable Applications Catalog

Kerite Distribution Cable Catalog, Number Prefix 125C35

May 2010 Report on ECAD Testing at Ginna

NRC GL 2OO7-001, Inaccessible or Underground Power Cable Failures That Disable Accident

Mitigation Systems or Cause Plant Transients

Ginna Response to GL 2007-001, Dated May 7,2007

Procedure

CNG-AM-1 .01-1029, Medium Voltage Cable Program, Rev.0000

Drawinq

33013-1920, Chilled Water System P&lD, Rev. 012

Work Orders

c20807437

c91 028373

Section 1R11: Licensed Operator Requalification Prosram

Document

ZOtO giennial Exam (Cycle 10-7) Simulator vs. Plant Differences, Dated November 2,2010

Procedures

CNG-MD-1.01-3001, Physical Examination Process for NRC Licensed Operators and Licensed

Candidates, Rev. 0

ECA-0.0, Loss of All Air Conditioning Power, Rev. 03402

OTG-2.2, Simulator Examination lnstructions, Rev. 43

OTG-10.0, License Activation, Rev. 4

Simulator Discrepancv Reports

2007-132, TDAFW Pump Suction Break MALF has Little Effect

2008-128, Alarm G-8, 4 Kilovolt (kV) Motor Overload

2008-147, Nuclear Instrumentation System Service Range Failure - No Audio Count Rate

Change

2008-181, 'D' SW Pump Breaker Takes Approximately 6 Seconds to Close

2008-202, Boron Concentration Indicates High Following Loss-of-Coolant Accident (LOCA)

2008-207, RCS Boron Concentration Not Changing with Changes in Letdown Temp

2009-069, LT428 Deleted from Instrumentation and Control

20Q9-074, Reactor Coolant Drain Tank (RCDT) Level Lowers with no RCDT Pump Running and

Excess Letdown Aligned

2009-075, No NaOH Flow lndicated with LOCA in Progress and'B'Containment Spray Pump

Running

2009-086, RCDT Level Lowers with no RCDT Pumps Running

2009-098, CST Level Rate of Rise Not Reflecting Mass In-Out

2009-100, R-19 Does Not Respond to a Steam Generator Tube Leak

2009-149, On Rx Trip and Transfer of 4 kV Busses to Offsite Power D/Gs Started

2009-170, Reactor Coolant Pump (RCP) Coast-Down Time

2009-194, Could Not Cool Down Below 506 Degrees Fahrenheit on Core Exit Thermocouple with

Atmospheric Relief Valve

2009-224, TDAFW Pump Over Speed Malfunction

2009-230, Charging Line Leak CVC03

Simulator Testinq

2009 Core Test

2009 Normal Operations Test 14.4.2 - Normal Ops Acceptance Test

2010 Malfunction Test 14.4.7 .12.7 - RCP Locked Rotor

201 0 Malfunction Test 14.4.7.15.2 - Dropped Rod

2010 Malfunction Test 14.4.7.18.5 - Accumulator Leak

2010 Transient Test 14.4.8.8E3 - Simultaneous Closure of Both Main Steam lsolation Valves

2010 Transient Test 14.4.8.BE4 - Simultaneous Trip of Both RCPs

2010 Transient Test 14,4,8.8E0 - Main Turbine Trip

Section 1Rl2: Maintenance Effectiveness

Documents

DA-EE-92-091-21, Instrument Loop Performance Evaluation and Setpoint Verification, Rev. 6

DA-EE-92-092-21, Instrument Loop Performance Evaluation and Setpoint Verification, Rev. 5

RPS System Health Report, 3'o Quarter 2010

Condition Reports

201 0-6387

2010-1507

2010-6254

Section 1Rl3: Maintenance Risk Assessments and Emerqent Work Gontrol

Procedure

CNG-OP-4.01-1000, lntegrated Risk Management, Rev. 00601

Section 1R15: Operabilitv Evaluations

Procedure

STP-E-2.3.1Q, Containment Recirculation Fan Testing - Quarterly, Rev. 00001

Condition Reports

2010-3208

2010-5103

201 0-5660

2010-6857

Section 1R18: Plant Modifications

Documents

ECP 10-000687, Routing Discharge Path from 'B' SFP HX Directly to the SFP

ECP 2009-0251,Install New Circuit Breaker and Contactor for CREATS 'A' Fan, Rev. 1

ECP 2009-0208, TDAFW Governor CV 9519E Replacement with Enhanced Materials,

Rev.0

Procedure

CNG-OP-4.01-1000, Integrated Risk Management, Rev. 00601

Work Order

c91 00231 3

Section 1Rl9: Post-Maintenance Testinq

Document

DA-ME-2001-031 , Evaluation of Suppression System Flow and Pressure Requirements, Rev. 1

Procedures

STP-O-12.1QC, Sl Pump'C' lST, Rev. 00300

STP-O-12.2, EDG'B', Rev. 00800

STP-O-13, Fire Pump Operation and System Alignment, Rev. 00005

STP-O-16-COMP-T, AFW Turbine Pump - Comprehensive Test, Rev. 01400

STP-O-16-QB, AFW Pump'B'- Quarterly, Rev, 0

STP-O-31A, Charging Pump'A' lST, Rev.00401

STP-O-31B, Charging Pump 'B' lST, Rev. 00501

STP-O-31C, Charging Pump'C'lST, Rev. 00301

M-15.1P, 'A' or 'B' EDG Fuel Oil System Inspection and Maintenance, Rev. 0700

Drawinqs

33013-1265, Chemical Volume Control System P&lD, Rev.22, Sheet 2 of 2

33013-1989, Fire SW Plant Systems P&lD, Rev. 27

Condition Report

2010-7620

Work Orders

c91019394 c90866162

c90866520 c90818614

c91056203 c90694245

c908301 60

Section 1R22: Surveillance Testinq

Procedures

3-12.4, RCS Leakage Surveillance Record Instructions, Rev. 05401

STP-O-2.8Q, CCW Pump Quarterly Test, Rev. 00501

STP-O-12.64, Diesel Generator Fuel OilTransfer Pump'A'Test, Rev. 0400

STP-O-16-COMP-T, AFW Turbine Pump - Comprehensive Test, Rev. 01300

STP-O-16QA, AFW Pump 'A'- Quarterly, Rev. 00500

Drawinqs

33013-1237, AFW P&lD, Rev. 57

33013-1245, CCW P&lD, Rev. 31

33013-1265, Chemical Volume Control System P&lD, Rev.22, Sheet 2 of 2

Section 4OAl  : Performance Indicator Verification

Documents

NEI 99-02, Regulatory Assessment Pl Guideline, Rev. 6

Ginna Nuclear Power Plant MSPI Basis Document, Rev. 5

Section 4OM: Problem ldentification and Resolution

Documents

Apparent Cause Evaluation for CR 2006-1954, SFP Leakage

Ginna's Response to lndustry Groundwater Protection Initiative Voluntary Data Collection

Questionnaire, Dated JulY 2006

Operations Night Orders 07129110

Engineering Eva uatio n CA-21 01 -0021 84

I

Procedure

CNG-QL-1.01-1008, Quarterly Report Process, Rev. 00200

CNG-CA-1.01-1005, Attachment 1, Tier 1, Apparent Cause Evaluation Template, Rev. 00200

P-15.71, Service Water Processing Skid Operation, Rev. 00100

OPG- Water-Management, Water Management Guideline, Rev. 0

CNG-TR-1.01-1002, Training Analysis Phase Activities, Attachment 2, Performance/Needs

Analysis Worksheet, Rev. 00100

Condition Reports

2006-1 954 2010-6224 201 0-31 55 2009-8545

2009-941 3 2010-0109 2010-3876 2010-2178

2010-2280 2009-2928 2010-2181 2010-0114

201Q-3716 2010-0111 2010-2179 201 0-5887

2009-6289 2009-6998 2009-7640

2009-6358 2Q09-7057 2010-2381

LIST OF ACRONYMS

ADAMS Agencywide Documents Access and Management System

AFW auxiliary feedwater

CAP corrective action program

ccw component cooling water

CFR Code of Federal Regulations

CR condition report

CREATS control room emergency air treatment system

CST condensate storage tank

CV control valve

ECP engineering change package

EDG emergency diesel generator

Ginna R. E. Ginna Nuclear Power Plant

GL generic letter

HX heat exchanger

IP inspection procedure

IST inservice test

JPM Job Performance Measure

KV kilovolt

LOCA loss-of-coolant accident

MDAFW motor-driven auxiliary feedwater

MSPI mitigating systems performance index

NEI Nuclear Energy Institute

NRC U.S. Nuclear Regulatory Commission

oos out of service

P&ID piping and instrument drawing

PARS Publicly Available Records

PI performance indicator

PM preventive maintenance

PMT post-ma ntenance testing

i

PRA probabilistic risk assessment

RCDT reactor coolant drain tank

RCP reactor coolant pump

RCS reactor coolant system

RPS reactor protection system

SFP spent fuel pool

SI safety injection

SSC system, structure, and component

SW service water

TDAFW turbine-driven auxiliary feedwater

TS tech nical specification

TSC technical support center

UFSAR updated final safety analysis report

WO work order

Attachment