05000458/FIN-2013003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Adequately Evaluate and Correct Degraded 125 Vdc Fused Disconnect Switches |
| Description | The inspectors identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, for the failure to identify and take prompt and adequate corrective actions to address a condition adverse to quality specifically related to the 125 Vdc fused disconnect switches located in the diesel generator building electrical distribution panels. The licensee addressed the underlying safety concern by cycling the disconnect switch to clean the corroded contact surfaces and performing voltage and current checks to verify circuitry operability. The licensee entered the finding into the corrective action program as Condition Report CR-RBS-2013-04247
The inspectors determined that this finding is more than minor because it is associated with the equipment performance attribute of the mitigating systems cornerstone and affects the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, during a seismic event the partially seated, corroded knife blades could cause a loss of safety related 125 Vdc power to the Division 1 and 2 emergency diesel generators, reactor water recirculation pumps A and B, or Division 1 and 2 remote shutdown panels. In accordance with NRC Inspection Manual Chapter 0609, Attachment 4, Initial Characterization of Findings, and NRC Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process for Findings At-Power, Exhibit 2, this finding screened as very low safety significance (Green) because the degraded condition was not a design or qualification deficiency; did not represent an actual loss of function of a system; did not represent an actual loss of function of a single train or two separate trains for greater than its technical specification allowed outage time; did not represent an actual loss of function of one or more non-technical specification trains of equipment designated as high safety significant; and did not screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. Because the most significant causal factor of the performance deficiency was the licensees failure to use consistent key words in the corrective action program to characterize the disconnect switch failures, this finding has a cross-cutting aspect in the problem identification and resolution area associated with the corrective action program component because the licensee did not periodically trend and assesses information from the CAP and other assessments in the aggregate to identify programmatic and common cause problems. |
| Site: | River Bend |
|---|---|
| Report | IR 05000458/2013003 Section 4OA2 |
| Date counted | Jun 30, 2013 (2013Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | P Elkmann A Barrett J Laughlin G Larkin J Quichocho |
| Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
| CCA | P.4, Trending |
| INPO aspect | PI.4 |
| ' | |
Finding - River Bend - IR 05000458/2013003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (River Bend) @ 2013Q2
Self-Identified List (River Bend)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||