o-s SOUTH CAROLINA ELECTRIC & GAS COMPANY Post office 7s4 COLUMetA. SOUTH CAROUNA 29218

'Q o. W. DixoN, JR.

vice PaesioeNY rry

~3

- A December 2,1982 svetran onnanoNs O

C"'

'J v r.. n Mr. James P. O'Reilly, Director

((

U.S. Nuclear Regulatory Commission

>z Region II, Suite 3100 t. ;,

101 Marietta Street, N.W.

Atlanta, Georgia 30303

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Opera *,ing License No. NPF-12 Thirty Day Written Report LER 82-035

Dear Mr. O'Reilly:

Please find attached Licensee Event Report #82-035 for Virgil C.

Summer Nuclear Station.

This Thirty Day. Report is required by Technical Specification 6.9 1.13.(b) as a result of entry into Action Statement (a) of Technical Specification 3.3.3.5,

" Instrumentation, Remote Shutdown Instrumentation," on November 3, 1982.

Should there be any questions, please call us at your convenience.

Ver truly yours, O. W. Dixon, Jr.

ARK:0WD:dwr Attachment cc:

V.

C.

Summer A.

R. Koon T.

C. Nichols, Jr.

G.

D. Mof fatt G.

H. Fischer Site QA

0. W. Dixon, Jr.

C. L. Ligon (NSRC)

H. N. Cyrus G. J. Braddick H. T. Babb J. L.

Skolds D.

A.

Nauman J. B. Knotts, Jr.

M.

B. Whitaker, Jr.

B.

A.

Bursey W,

A. Williams, Jr.

I&E (Washington)

O.

S.

Bradham Document Management Branch R.

B.

Clary INPO Records Centergod i M. N. Browne NPCF File

%E 06 8212090449 821202 h

5-PDR ADOCK 05000395 S

PDR

Mr. James P. O'Reilly LER No.82-035 Page Two December 2, 1982 DETAILED DESCRIPTION OF EVENT On November 3,1982, the Plant entered Mode 3 with Boric Acid Tank B Level Instrument LI-163A out of service.

The instrument was declared inoperable as a result of failure to pass a channel check.

This instrument indication, which is located on the Control Room Evacuation Panel, is required to be operable per Technical Specification 3.3.3 5, " Remote Shutdown Instrumentation".

The provisions. of Specification 3.0.4 are not applicable.

PROBABLE CONSEQUENCES There were no adverse consequences because the remaining local level indication (LI-108) for Boric Acid Tank B was operable.

Also, level indication was available on the Control Room Evacuation Panel for Boric Acid Tank A (LI-161A).

CAUSE(S) 0F THE OCCURRENCE The cause of the occurrence was that LI-163A was out of calibration due to zero shif t of its transmitter (LT-163A).

IMMEDIATE CORRECTIVE ACTIONS TAKEN A Maintenance Work Request was immediately initiated to investigate and correct the problem.

LT-163A was discovered to be out of calibration.

The instrument was subsequently calibrated per applicable surveillance test procedures and returned to service on November 9, 1982.

ACTION TAKEN TO PREVENT RECURRENCE The Licensee plans no further action except for the normally required surveillance testing.